The Omron STI Hazardous Location

Size: px
Start display at page:

Download "The Omron STI Hazardous Location"

Transcription

1 Hazardous Location Rating Systems for Interlock Switches The Omron STI Hazardous Location Rated Safety Interlock Switches presented in this catalog are classified by the European standard as Ex, ExdIIc T6. A sealed contact block makes these interlock switches suitable for use in Zone 1 and Zone 2 environments, which are typical of those found in the chemical and petrochemical industries. The tables that follow explain and compare the European method with the U.S. method of classification of Explosion Proof products. The European classification of E ExdIIc T6 is explained as follows: Explanation of Marking of EX Equipment for European Market Ex = equipment corresponds to a type of protection covered by British or Baseefa Standards (e.g. BS 4683, SFA 3009) EEx = equipment corresponds to a type of protection covered by specific European Standards (e.g. EN ) E Ex indicates they meet the European safety standards of EN and EN and BS5501 parts I-V. d suffix indicates that the explosion proof enclosure of the contact block is designed to contain an internal explosion and will not ignite a surrounding flammable atmosphere. llc refers to the group of gases for which the switches are suitable. Group II gases are sub-divided into three categories by the suffix a, b, or c. Suffix c gases are the most flammable within Group II and include gases such as hydrogen. Special precautions may be required to protect the vulnerable parts Type of protection used Covered by Standard o = oil immersion EN p = pressurized apparatus EN q = powder filing EN d = flameproof enclosure EN e = increased safety EN i = intrinsic safety (ia or ib) EN m = encapsulation EN s = special protection BASEEFA SFA 3009 of the switch from corrosion, such as PVC covered cables against attack by certain corrosive elements and physical damage. The T designation represents the surface temperature classification of the switch and is divided into categories with the suffix 1 to 6. T6 is the lowest temperature and thus the safest classification with a maximum permitted surface temperature of 85 C (providing that the electric loading of the switch does not exceed its stated current rating). These switches have been tested with an ambient temperature of 60 C as opposed to the normal test limit of only 40 C, allowing them to be used in gases having a low flash point. Switches classified as E Exdllc T6 (All Omron STI Ex switches) are not suitable for use in atmospheres containing Group I gases, e.g. methane (firedamp). Please note that these switches DO NOT meet all conditions of the US classification of Class I, Div 1 due to the differences between European and US classification methods. See the table on the following page, (Figure 7.2). example EExd IIC T6 Subdivisions A, B & C are based on classification of Maximum Experimental Safe Gap (MESG) and Minimum Ignition Currents (MIC) - For more information refer to EN 50014: 1992 Annex A. Usage / gas group Group Usage place Representative gas I = Mines Methane IIA = Surface Propane IIB = Surface Ethylene, Propane IIC = Surface Hydrogen, Ethylene,Propane Fig. 7.1 Classification of maximum surface temperature T1 = 450 C T2 = 300 C The maximum surface temperature must be less than the lowest ignition T3 = 200 C temperature of the explosive atmosphere. T4 = 135 C T5 = 100 C T6 = 85 C 1

2 hazardous location Rating Systems For Interlock Switches Classifications of Hazardous Locations Explosive Continuous Intermittent Occasional Atmosphere Presence Presence Presence (normal operating (abnormal operating conditions) conditions) IEC Zone 0 (gas) Zone 1 (gas) Zone 2 (gas) (International) Zone 20 (dust) Zone 21 (dust) Zone 22 (dust) France ( ) Zone 0 (gas) Zone 1 (gas) Zone 2 (gas) and Europe Canada (CEC) CI. I Div. 1 (gas) CI. I Div. 1 (gas) CI. I Div. 2 (gas) and USA (NEC) CI. II Div. 1 (dust) CI. II Div. 1 (dust) CI. II Div. 2 (dust) CI. III Div. 1 (fibers) CI. III Div. 1 (fibers) CI. III Div. 2 (fibers) Gas Groups Place of Use Group Class & Group Representative CENELEC/IEC Canada & USA Gas Mines with firedamp l Gaseous Mines Methane Surface industries IIA I-D Propane IIB I-C Ethylene IIC I-B Hydrogen IIC I-A Acetylene Marking Temperatures Temperature Class (CENELEC/IEC) T1 T2 T3 T4 T5 T6 Group ll Maximum Surface 450 C 300 C 200 C 135 C 100 C 85 C Temperature The maximum surface temperature of equipment must always be lower than the ignition temperature of the gas present in the hazardous area. Fig

3 Hazardous (Classified) Locations NEC Article 500 Class I Combustible material in the form of gas or vapor Division 1 (1) in which hazardous concentrations of flammable gases or vapors exist continuously, intermittently, or periodically under normal operating conditions. (2) in which ignitable concentrations of such gases or vapors may exist frequently because of repair or maintenance operations or because of leakage. (3) in which breakdown or faulty operation of flammable gases or vapors, might also cause simultaneous failure of electrical equipment (A) Division 2 (1) in which volatile flammable liquids or flammable gases are handled, processed, or used, but in which the hazardous liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems, or in the case of abnormal operation of equipment. (2) in which ignitable concentrations of gases or vapors are normally prevented by positive mechanical ventilation, but which might become hazardous through failure or abnormal operation of the ventilating equipment (3) that are adjacent to Class I, Division 1 locations, and to which ignitable concentrations of gases or vapors might occasionally be communicated unless such communication is prevented by adequate positive-pressure ventilation safeguards against ventilation failure are provided (B) Group A Atmospheres containing acetylene FPN #5 Group B Atmospheres containing hydrogen, gases or vapors of equivalent hazard, such as manufactured gas FPN #6 Group C Atmospheres containing ethyl ether vapors, ethylene, or cyclopropane FPN #7 Group D Atmospheres containing gasoline, hexane, naphtha, benzine, butane, propane, alcohol, acetone, benzol, lacquer, solvent vapors, or natural gas FPN #8 Group E Atmospheres containing metal dust, including aluminum, magnesium, and their commercial alloys, and other metals of similar hazardous characteristics FPN #17 Group F Atmospheres containing carbon black, coal, or coke dust FPN #14 Group G Atmospheres containing flour starch or grain dusts FPN #15 Fig

4 Hazardous (Classified) Locations european STAndard Gases Combustible material in the form of gas or vapor. US Class I Zone O of flammable gases or vapors are present continuously or present for long periods of time. US Div. 1 Zone 1 of flammable gases or vapors are likely to exist under normal operating conditions, or because of leakage. US Div. 1 Zone 2 of flammable gases or vapors are not likely to occur in normal operation; but if they do, only for short periods. US Div. 2 Group IIC Atmospheres containing acetylene US Group A Group IIC Atmospheres containing hydrogen, gases or vapors of equivalent hazard, such as manufactured gas. US Group B Group IIB Atmospheres containing ethyl ether vapors, ethylene, or cyclopropane. US Group C Group IIA Atmospheres containing gasoline, hexane, naphtha, benzine, butane, propane, alcohol, acetone, benzol, lacquer, solvent vapors, or natural gas. US Group D In Prep Atmospheres containing metal dust, including aluminum, magnesium, and their commercial alloys, and other metals of similar hazardous characteristics. US Group E In Prep Atmospheres containing carbon black, coal, or coke dust. US Group F In Prep Atmospheres containing flour starch or grain dusts. US Group G Fig

5 OMRON AUTOMATION AND SAFETY THE AMERICAS HEADQUARTERS Chicago, IL USA OMRON CANADA, INC. HEAD OFFICE Toronto, ON, Canada OMRON ELECTRONICS DE MEXICO HEAD OFFICE México DF OMRON ELECTRONICS DE MEXICO SALES OFFICE Apodaca, N.L OMRON ARGENTINA SALES OFFICE Cono Sur OMRON CHILE SALES OFFICE Santiago OTHER OMRON LATIN AMERICA SALES OMRON ELETRÔNICA DO BRASIL LTDA HEAD OFFICE São Paulo, SP, Brasil OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. +31 (0) Authorized Distributor: Automation Control Systems Machine Automation Controllers (MAC) Programmable Controllers (PLC) Operator interfaces (HMI) Distributed I/O Software Drives & Motion Controls Servo & AC Drives Motion Controllers & Encoders Temperature & Process Controllers Single and Multi-loop Controllers Sensors & Vision Proximity Sensors Photoelectric Sensors Fiber-Optic Sensors Amplified Photomicrosensors Measurement Sensors Ultrasonic Sensors Vision Sensors Industrial Components RFID/Code Readers Relays Pushbuttons & Indicators Limit and Basic Switches Timers Counters Metering Devices Power Supplies Safety Laser Scanners Safety Mats Edges and Bumpers Programmable Safety Controllers Light Curtains Safety Relays Safety Interlock Switches C332I-E-01 08/14 Note: Specifications are subject to change Omron Electronics LLC Printed in U.S.A. Printed on recycled paper.

Hazardous (Classified) Locations

Hazardous (Classified) Locations Hazardous (Classified) Locations Presented by: John Chambers UL HazLoc operations Presented at: Safety & You in 2002 2002 Safety Conference Flexible Packaging Association (FPA) 1 AREA CLASSIFICATIONS Class

More information

Session #: Selection of Explosion Protected Equipment for Hazardous Locations

Session #: Selection of Explosion Protected Equipment for Hazardous Locations Abstract Session #: (Arial 16) Selection of Explosion Protected Equipment for Hazardous Locations Pieter Coetzee Explosion Prevention Consultant Registered person How can we mitigate the risks of explosions

More information

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof Hazardous Location Equipment - Canada Equipment listed in this category for Hazardous Locations is also suitable for installations in areas that are non-hazardous locations and, unless referenced in the

More information

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus Hazardous Location Equipment - United States Equipment listed in this category for Hazardous (Classified) Locations is also suitable for installations in areas that are unclassified locations and, unless

More information

General information on explosion protection

General information on explosion protection 427 Why explosion protection? Explosion protection for electrical and mechanical machinery is an important precautionary measure to ensure the safety of persons and all kinds of production, storage and

More information

TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION

TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION Equipment listed in this guide for Hazardous (Classified) Locations is also suitable for installations in areas that are unclassified locations

More information

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS 1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS EXPLOSION PROTECTION In addition to the type approval and certification of industrial weighing systems concerned with accuracy, equipment that is also

More information

Process Instrumentation. Product Guide. Registered Quality System to ISO 9001

Process Instrumentation. Product Guide. Registered Quality System to ISO 9001 Process Instrumentation Product Guide Registered Quality System to ISO 9001 SORis committed to and understands the demanding requirements of the process industry. We design, develop and manufacture the

More information

The evolution of the Ex-proof flame path

The evolution of the Ex-proof flame path April 2017 The evolution of the Ex-proof flame path As written in previous dissertation, the most critical part of a flameproof enclosure 'Ex d' is the flame path. Although the Standards are divided into

More information

CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS IN GAS UTILITY AREAS. Gerry Pickens

CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS IN GAS UTILITY AREAS. Gerry Pickens CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS IN GAS UTILITY AREAS Gerry Pickens Atmos Energy 810 Crescent Centre Drive Franklin, TN 37067 The National Electrical Code (NEC) defines hazardous

More information

BASIC NATIONAL ELECTRIC CODE APPLICABLE TO MEASUREMENT. Gerry Pickens. Atmos Energy 810 Crescent Centre Drive Franklin, TN 37067

BASIC NATIONAL ELECTRIC CODE APPLICABLE TO MEASUREMENT. Gerry Pickens. Atmos Energy 810 Crescent Centre Drive Franklin, TN 37067 BASIC NATIONAL ELECTRIC CODE APPLICABLE TO MEASUREMENT The National Electrical Code (NEC) defines hazardous locations as those areas "where fire or explosion hazards may exist due to flammable gases or

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 12 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

General-purpose Relays and Power Relays Sockets

General-purpose Relays and Power Relays Sockets General-purpose Relays and Power Relays Sockets Relay Type Track Mount Sockets Back Connecting Sockets Solder terminals PCB terminals G2R-1-S P2RF-05 P2RF-05-E P2RF-05-S P2R-05A P2R-05P G2R-2-S P2RF-08

More information

II 2G EEx ia IIC T6. Ignition protection class

II 2G EEx ia IIC T6. Ignition protection class ATEX General information According to 94/9/EC, a device that is to be used in an environment at risk of explosion may only be brought into the market if it satisfies the standards specified in the norm.

More information

Pioneers. Ex-ENGINEERING. Quality

Pioneers. Ex-ENGINEERING. Quality Pioneers The increasing demands of industry for dependable explosionproof lighting, motivated Baliga to pioneer the design and manufacture of a quality line way back in 1962, when the first Indian Standards

More information

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres Page 1 of 7 Title Plan electrical installations for explosive atmospheres Level 5 Credits 8 Purpose This unit standard is intended for use in the training and assessment of people who work with electrical

More information

Intrinsically explosion-proof and safety barrier introduction

Intrinsically explosion-proof and safety barrier introduction Intrinsically explosion-proof and safety barrier introduction Summary of Topics Page 1. Explosion basic knowledge 1 2. Explosion groups 1 3. Zone classification 2 4. Explosion-proof electrical apparatus

More information

General information on explosion protection

General information on explosion protection 427 Why explosion protection? Explosion protection for electrical and mechanical machinery is an important precautionary measure to ensure the safety of persons and all kinds of production, storage and

More information

NZQA registered unit standard version 1 Page 1 of 8. Conduct detailed inspection of electrical installations for explosive atmospheres

NZQA registered unit standard version 1 Page 1 of 8. Conduct detailed inspection of electrical installations for explosive atmospheres Page 1 of 8 Title Conduct detailed inspection of electrical installations for explosive atmospheres Level 5 Credits 5 Purpose This unit standard is intended for use in the training and assessment of people

More information

Explosive Environment Review

Explosive Environment Review Explosive Environment Review Version 3.0 A Comprehensive Guide to Electronic Weighing Equipment and Hazardous Environments PN 16985 Contents 1.0 Introduction... 1 2.0 Standards... 2 2.1 NFPA 70, National

More information

Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments

Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments Gas Well Deliquification Workshop Sheraton Hotel, February 19 22, 2012 Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments Glenn Longley, Sr. Product Manager FreeWave Technologies Agenda

More information

EBARA PUMPS EUROPE S.p.A. ATMOSPHERES EXPLOSIBLES ATEX CONTENTS 100. Page INTRODUCTION 101

EBARA PUMPS EUROPE S.p.A. ATMOSPHERES EXPLOSIBLES ATEX CONTENTS 100. Page INTRODUCTION 101 CONTENTS Page CONTENTS 100 INTRODUCTION 101 GENERAL CONCEPTS 200 MACHINE NOT INCLUDED IN THE 94/9/CE DIRECTIVE 200 PRODUCTS WHICH ARE INCLUDED IN THE 94/9/CE DIRECTIVE 200 ELECTRICAL SET 201 INSTALLATIONS

More information

OIL+GAS PRODUCTS AND THEIR APPLICATIONS

OIL+GAS PRODUCTS AND THEIR APPLICATIONS OIL+GAS PRODUCTS AND THEIR APPLICATIONS FIELDS OF APPLICATIONS AND REQUIREMENTS OIL RIGS SHIP AND SHIP EQUIPMENT Oil rigs have extremely high requirements for the technology used. Even the smallest spark

More information

Hafner-Pneumatik presents: General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range

Hafner-Pneumatik presents: General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range Hafner-Pneumatik presents: Including Pneumatic Valves General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range General information - 1 A product that is supposed

More information

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide OSAT Series Intrinsically Safe Infrared Temperature Sensor Operator's Guide Issue L Jan 2017 Introduction OSAT Series intrinsically safe non-contact infrared temperature sensors measure the temperature

More information

Intrinsic safety 101 hazardous locations

Intrinsic safety 101 hazardous locations Intrinsic safety 101 hazardous locations Protection methods, containment, segregation, and prevention By Robert Schosker This article answers the question, Why worry about hazardous locations? The area

More information

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS SECTION 7 ELECTRICITY CHAPTERS A APPROACH B DOCUMENTS, REGULATIONS AND

More information

PRINCIPLES OF EXPLOSION PROTECTION

PRINCIPLES OF EXPLOSION PROTECTION PRINCIPLES OF EXPLOSION PROTECTION Contact Details... 19 Definitions... 1 Explosion proof apparatus... 14 Hazard zone classifications... 4 Installations... 15 Introduction... 1 Maintenance... 17 Primary

More information

A Unified Marking System for Ex Equipment

A Unified Marking System for Ex Equipment CERTEX Appointed Ex Laboratory Reg No: 1999/027771/07 (Pty) Ltd Government Approved Inspection Authority T0104 PO Box 467 Tel: +27 (11) 316 4601 Olifantsfontein Fax: +27 (11) 316 5670 1665 E- mail: info@explolabs.co.za

More information

Gas Fired Residential Heating Boilers

Gas Fired Residential Heating Boilers USER S INFORMATION MANUAL Gas Fired Residential Heating Boilers Models 0042B, 0066B, 0090B, 0135B, 0180B Type H WARNING: If the information in this manual is not followed exactly, a fire or explosion may

More information

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus Page 1 of 7 Title Conduct a conformity assessment of explosion-protected apparatus Level 6 Credits 9 Purpose This unit standard covers the assessment and certification of explosion-protected apparatus

More information

Electrical Equipment and Installations in Hazardous Areas. Univerza v Ljubljani Fakulteta za elektrotehniko

Electrical Equipment and Installations in Hazardous Areas. Univerza v Ljubljani Fakulteta za elektrotehniko Univerza v Ljubljani Fakulteta za elektrotehniko Electrical Equipment and Installations in Hazardous Areas Student: Tiago da Silva Oliveira; Student Number: 70080035; Subject: Electrical Installations

More information

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee Page: Page 1 of 5 1 Introduction Compressed gas cylinders can present a variety of hazards due to their pressure and/or contents. One of the contributing factor to these hazards is gas leak due to malfunction

More information

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm Dimensions M30x1,5 5 40 37 0102 Model Number 36 LED Features Comfort series 10 mm embeddable Connection BN BU Accessories BF 30 Mounting flange, 30 mm L+ L- Technical Data specifications Switching element

More information

E2B PROXIMITY SENSORS

E2B PROXIMITY SENSORS E2B PROXIMITY SENSORS Enjoy innovation and reliability today» Time and cost savings» Perfect fit for standard environments» New LITE inductive sensor 2 3 Quality, reliability and value-for-money We asked

More information

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display.

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display. Display Thermo, Inc. Instruction Manual English TP-5 Display TP-7 Display TP-8 1-1 Thermo, Inc. Instructions for use- Models TP-5, TP-7, and TP-8 The manual describes basic function and use of Thermo instruments

More information

USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases)

USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases) (June 27, 2002) USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases) 1. General Being designed for light industrial applications, NAP-100A series also available

More information

IA CERTIFICATE (Annual review required by MASC covered by an additional letter) (Revision 2- Review & Review)

IA CERTIFICATE (Annual review required by MASC covered by an additional letter) (Revision 2- Review & Review) Certificate Number: MASC MS/11-127X Issue: 09 October 2017 Expire: 09 October 2020 Page: 1 of 5 IA CERTIFICATE (Annual review required by MASC covered by an additional letter) (Revision 2- Review & Review)

More information

NZQA registered unit standard version 3 Page 1 of 6

NZQA registered unit standard version 3 Page 1 of 6 Page 1 of 6 Title Report on the integrity of explosion-protected electrical apparatus in explosive atmospheres Level 3 Credits 3 Purpose This unit standard covers the explosion-protection aspects of plant

More information

FLAMMABLE GAS SENSOR/TRANSMITTER

FLAMMABLE GAS SENSOR/TRANSMITTER FLAMMABLE GAS SENSOR/TRANSMITTER Plant safety protection for flammable gases. F E A T U R E S Fixed gas monitoring for point source hazards and perimeter protection in arduous duty and exposed locations.

More information

FLAMMABLE MIXTURE ANALYSIS FOR HAZARDOUS AREA CLASSIFICATION

FLAMMABLE MIXTURE ANALYSIS FOR HAZARDOUS AREA CLASSIFICATION FLAMMABLE MIXTURE ANALYSIS FOR HAZARDOUS AREA CLASSIFICATION Allan Bozek P.Eng, MBA Member IEEE EngWorks Inc. 1620, 49 th Avenue SW Calgary, Canada T2T2T7 Vince Rowe, P.Eng Member IEEE Marex Canada Ltd.

More information

WHITE PAPER on Explosion Proof and Intrinsic Safety Solutions. Oct. 2013

WHITE PAPER on Explosion Proof and Intrinsic Safety Solutions. Oct. 2013 WHITE PAPER on Explosion Proof and Intrinsic Safety Solutions Oct. 2013 TABLE OF CONTENTS Abstract... 3 Abbreviations... 4 Introduction to Standards... 5 Protection Layers... 7 Simple Devices... 7 Mechanical

More information

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm Dimensions M18x1 37 40 4 0102 24 LED Model Number Features 5 mm embeddable Usable up to SIL2 acc. to IEC 61508 Connection BN BU Accessories L+ L- EXG-18 Quick mounting bracket with dead stop BF 18 Mounting

More information

Explosive Environment Review

Explosive Environment Review Explosive Environment Review Version 3.0 A Comprehensive Guide to Electronic Weighing Equipment and Hazardous Environments PN 16985 Contents 1.0 Introduction... 1 2.0 Standards... 2 2.1 NFPA 70, National

More information

HAZARDOUS APPLICATIONS

HAZARDOUS APPLICATIONS HAZARDOUS APPLICATIONS I. WHAT CONSTITUTES A HAZARDOUS CLASSIFIED AREA? Any area inside or outdoor that has explosive gas, vapor, dust or flyings mixed with air in ignitable concentrations. II. WHAT TYPES

More information

Technical Data Sheet. OPTIMASS 7000 Custody Transfer Mass Flowmeter

Technical Data Sheet. OPTIMASS 7000 Custody Transfer Mass Flowmeter Technical Data Sheet KROHNE 12/2004 7.02516.21.00 CH/GR OPTIMASS 7000 Custody Transfer Mass Flowmeter with single straight measuring tube OIML R117 Pattern Approval Accuracy classes 0.3 / 0.5 / 1.0 / 1.5

More information

Describe Flammable Gas Measurement

Describe Flammable Gas Measurement Training Module Describe Flammable 100% 90% C 80% No Combustion 70% 60% 50% 40% 30% 20% UEL B Combustion No Combustion 10% 0% LEL A Human Development HDC Human Development All rights reserved. No part

More information

HAZARDOUS AREA CLASSIFICATION & SELECTION OF ELECTRICAL EQUIPMENT FOR FLAMMABLE ATMOSPHERES

HAZARDOUS AREA CLASSIFICATION & SELECTION OF ELECTRICAL EQUIPMENT FOR FLAMMABLE ATMOSPHERES HAZARDOUS AREA CLASSIFICATION & SELECTION OF ELECTRICAL EQUIPMENT FOR FLAMMABLE ATMOSPHERES Hydrocarbon Risks OISD Accident compilation (1996-1999): Out of the total 71 accidents (5 lakh property loss/fatality/loss

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

Explosion Protection Technology Pty Ltd

Explosion Protection Technology Pty Ltd How to Apply Hazardous Area Australian Standards (Group II) 3-Day On-Site Workshop * 2018 This workshop provides a sound understanding of electrical compliance and your responsibilities in Group II hazardous

More information

TECHNOLOGY GUIDE NO. 12

TECHNOLOGY GUIDE NO. 12 SSPC: The Society for Protective Coatings TECHNOLOGY GUIDE NO. 12 Guide for Illumination of Industrial Painting Projects SSPC-Guide 12 1. Scope 1.1 This guide provides information on the quantity and quality

More information

M.A. Rezaei. TEHRAN, IRAN

M.A. Rezaei. TEHRAN, IRAN () */! "#$ %& M.A. Rezaei rezaeima@nigc.org TEHRAN, IRAN http://igs.nigc.ir !! / # $% &'() *) ".3% %*)(ZONE=0).3% %*) (ZONE=1) (.3% %*) (ZONE=2) 6.3=( ;?= > 8(9: ;

More information

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS Government Approved Test Laboratory (Previously AIA) Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS ZEST

More information

SECTION 2 APPLICATION OF FUNDAMENTALS

SECTION 2 APPLICATION OF FUNDAMENTALS SECTION 2 APPLICATION FUNDAMENTALS ENVIRONMENTAL CONDITIONS IN NEC CLASS I HAZARDOUS LOCATIONS Section II covers a great number of illustrations which can be applied directly to a hazardous area under

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 2419437 Master Contract: 203012 Issued to: ABB Automation Products GmbH 72 Schillerstrasse Minden, 32425 Germany Attention: Ralf Schaffer The products listed below

More information

Technical Manual. Sensepoint XCD Gas Detector

Technical Manual. Sensepoint XCD Gas Detector Technical Manual Sensepoint XCD Gas Detector 19 Cross Interference and Cross Calibration 19.1 Cross Interference Table for Toxic and Oxygen This table shows the relative cross sensitivity of the Sensepoint

More information

Certificate of Compliance

Certificate of Compliance FF0002 Certificate of Compliance Certificate: 70024080 Date Issued: 2017-07-04 Issued to: ecom instruments GmbH Industriestrasse 2 Assamstadt, Baden Wurttemburg 97959 GERMANY Attention: Kevin Spence The

More information

Rules for Classification and Construction Ship Technology

Rules for Classification and Construction Ship Technology I Rules for Classification and Construction Ship Technology 1 Seagoing Ships 9 Oil Recovery Vessels Edition 1993 The following Rules come into force on 1st September, 1993. The respective latest edition

More information

Mechanical pressure switches

Mechanical pressure switches 18 Technical features / Advantages Diecast aluminium housing IP 54 or IP 65 version also available Wall mounting or directly on the pressure line Switching element (microswitch) Lead sealable setpoint

More information

CERTIFICATE OF COMPLIANCE

CERTIFICATE OF COMPLIANCE FM Approvals 1151 Boston Providence Turnpike P.O. Box 9102 Norwood, MA 02062 USA T: 781 762 4300 F: 781-762-9375 www.fmapprovals.com CERTIFICATE OF COMPLIANCE HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL

More information

Two-Wire In Situ Oxygen Analyzer (550 to 1400 C)

Two-Wire In Situ Oxygen Analyzer (550 to 1400 C) Product Data Sheet PDS 106-581.A01 March, 2004 Model 5081FG Two-Wire In Situ Oxygen Analyzer (550 to 1400 C) Intrinsically safe: - CENELEC EEx ia IIC - Class I Div. I Gr. B, C, D (pending) Operates at

More information

Technical Data. General specifications. Rated operating distance s n 2 mm

Technical Data. General specifications. Rated operating distance s n 2 mm 0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Rated operating distance s n 2 mm Installation

More information

ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994

ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994 ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor any part of this

More information

Ultima. XI Infrared Gas Monitor

Ultima. XI Infrared Gas Monitor Ultima XI Infrared Gas Monitor Instruction Manual "! WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING OR SERVICING THE PRODUCT. Like any

More information

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany EXPLOSION PROTECTION USING THE DATABASE Maria Molnarne formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany Department - Chemical Safety Engineering Outline Database CHEMSAFE

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity Certificate No.: IECEx KEM 09.0016 IECEx Certificate of Conformity Date of Issue: 2013-02-22 Issue No.: 3 Page 2 of 4 Manufacturer: Endress+Hauser GmbH+Co. KG Hauptstraße 1 79689 Maulburg Germany Additional

More information

Inductive slot sensor

Inductive slot sensor 0102 Model Number Features 3.5 mm slot width Usable up to SIL 3 acc. to IEC 61508 Nonferrous targets Application Danger! In safety-related applications the sensor must be operated with a qualified fail

More information

INDICATIONS FOR CHOICE OF ATEX FANS

INDICATIONS FOR CHOICE OF ATEX FANS INDICATIONS FOR CHOICE OF ATEX FANS CAUTION! ATEX marking is possible only if the fan is assembled by Ferrari or one of its qualified "OBT ATEX" dealers. 1. ATEX SERIES FANS Fan type Category 2 Category

More information

RTD temperature probes

RTD temperature probes RTD temperature probes Ex i for use in areas with an explosion hazard (Ex areas) Persons concerned: Experienced professional electricians as per EU Directive 1999/92/EC and trained personnel Operating

More information

Torque Tube TB300 Digital Transmitters

Torque Tube TB300 Digital Transmitters Page 1 of 7 7E.300-E Issue 4-2009 Description Series TB300 torque tube liquid level instruments utilize the buoyancy exerted on a displacer when immersed in a liquid. The buoyancy on the displacer is proportional

More information

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION Jeff Strath Principal Engineer Paterson Flood Engineers Pty Ltd www.pfe.com.au INTRODUCTION This presentation provides an overview

More information

Applications Note: Use of "pentane equivalent" calibration gas mixtures

Applications Note: Use of pentane equivalent calibration gas mixtures Introduction The gas that is used to verify accuracy is every bit as important as the detector itself when it comes to worker safety. Choosing (and using) the right mixture is critical to the success of

More information

An Introduction To Gas Detection

An Introduction To Gas Detection An Introduction To Gas Detection Supplied & serviced by : Q Instrument Services Limited, Cork. Phone : 086-8129925 Fax : 021-4341218 Email : info@qlimited.com www.qlimited.com Introduction Gas monitoring

More information

Calibration Requirements for Direct Reading Confined Space Gas Detectors

Calibration Requirements for Direct Reading Confined Space Gas Detectors : Calibration Requirements for Direct Reading Confined Space Gas Detectors However, the definition of bump test has always been a little slippery. Some manufacturers differentiate between a bump test that

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features Comfort series 15 mm non-flush Stainless steel housing Accessories BF 30 Mounting flange, 30 mm Technical Data specifications Switching element function NAMUR, NC Rated operating

More information

Two-Wire In Situ Oxygen Analyzer (550 to 1400 C)

Two-Wire In Situ Oxygen Analyzer (550 to 1400 C) Product Data Sheet PDS 106-581.A01 September, 2007 Model 5081FG Two-Wire In Situ Oxygen Analyzer (550 to 1400 C) Intrinsically safe: ATEX, Zone 1, EEx ia IIC T4 Class I, Div. I, Gr. A, B, C, D T4 Operates

More information

Supplementary Operator s Manual 42/24-14 EN Rev. 3

Supplementary Operator s Manual 42/24-14 EN Rev. 3 Advance Optima Continuous Gas Analyzers AO2000 Series with Uras26, Magnos206, Caldos25, Caldos27 Designed per Category 3G for Measurement of Flammable Gases ( Safety Concept ) and Non-flammable Gases Supplementary

More information

Approval Standard. for

Approval Standard. for Approval Standard for Nonincendive Electrical Equipment for Use in Class I and II, Division 2, and Class III, Divisions 1 and 2, Hazardous (Classified) Locations Class Number 3611 December 2004 2004 FM

More information

Rosemount 2120 Full-featured Vibrating Fork Liquid Level Switch. Quick Start Guide , Rev BA August 2012

Rosemount 2120 Full-featured Vibrating Fork Liquid Level Switch. Quick Start Guide , Rev BA August 2012 Rosemount 220 Full-featured Vibrating Fork Liquid Level Switch Quick Start Guide 00825-000-40, Rev BA August 202 Quick Start Guide August 202 NOTICE This installation guide provides basic guidelines for

More information

Technical Data. General specifications. Rated operating distance s n 5 mm

Technical Data. General specifications. Rated operating distance s n 5 mm 0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching

More information

Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure

Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material: Copper, brass, stainless

More information

COMPARISON OF NATIONAL REQUIREMENTS FOR ELECTRICAL APPARATUS FOR USE IN HAZARDOUS ATMOSPHERES

COMPARISON OF NATIONAL REQUIREMENTS FOR ELECTRICAL APPARATUS FOR USE IN HAZARDOUS ATMOSPHERES 55 COMPARISON OF NATIONAL REQUIREMENTS FOR ELECTRICAL APPARATUS FOR USE IN HAZARDOUS ATMOSPHERES By H. G. RIDDLESTONE, B.Sc.(Eng.), C.Eng., M.I.E.E.* SYNOPSIS International standardisation of the methods

More information

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] 12th Edition 1 1. Introduction Thank you for purchasing the DPharp electronic pressure transmitter. This manual

More information

HAZARDOUS AREAS. Calibration in WEIGHING SCALE CALIBRATION HOW TO CALIBRATE PRESSURE GAUGES CUSTOMER SUCCESS STORIES

HAZARDOUS AREAS. Calibration in WEIGHING SCALE CALIBRATION HOW TO CALIBRATE PRESSURE GAUGES CUSTOMER SUCCESS STORIES BEAMEX CORPORATE MAGAZINE 2018 Calibration in HAZARDOUS AREAS WEIGHING SCALE CALIBRATION How to calibrate weighing instruments HOW TO CALIBRATE PRESSURE GAUGES 20 things you should consider CUSTOMER SUCCESS

More information

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC Mechatronic pressure measurement Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC WIKA data sheet PV 35.41 Process Compact Series Applications Differential pressure monitoring

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

PROCEDURE FOR INITIAL AND PERIODIC INSPECTION POTENTIALLY EXPLOSIVE ATMOSPHERES (HAZARDOUS AREA) ORIGINAL EDITION

PROCEDURE FOR INITIAL AND PERIODIC INSPECTION POTENTIALLY EXPLOSIVE ATMOSPHERES (HAZARDOUS AREA) ORIGINAL EDITION PROCEDURE FOR INITIL ND PERIODIC INSPECTION IN POTENTILLY EXPLOSIVE TMOSPHERES (HZRDOUS RE) ORIGINL EDITION DEC. 1997 This Standard is the property of Iranian Ministry of Petroleum. ll rights are reserved

More information

Title: Classification of South African Hard Rock Mines Establishing a sound basis for classification

Title: Classification of South African Hard Rock Mines Establishing a sound basis for classification 1 First Edition 20 July 2006 Second Edition 10 September 2009 Title: Classification of South African Hard Rock Mines Establishing a sound basis for classification Author: Johannes G Auret PhD Engineering

More information

Non-electrical equipment for use in potentially explosive atmospheres

Non-electrical equipment for use in potentially explosive atmospheres BRITISH STANDARD BS EN 13463-1:2009 Non-electrical equipment for use in potentially explosive atmospheres Part 1: Basic method and requirements ICS 13.230 NO COPYING WITHOUT BSI PERMISSION ECEPT AS PERMITTED

More information

Pressure switch, Differential pressure switch and Thermostat RT-E

Pressure switch, Differential pressure switch and Thermostat RT-E Data sheet Pressure switch, Differential pressure switch and Thermostat RT-E The RT-E series consist of pressure and differential pressure switches as well as thermostats. The units are designed for industrial

More information

INDICATIONS FOR CHOICE OF ATEX FANS

INDICATIONS FOR CHOICE OF ATEX FANS INDICATIONS FOR CHOICE OF ATEX FANS CAUTION! ATEX marking is possible only if the fan is assembled by Ferrari or one of its qualified "OBT ATEX" dealers. For the machine technical specifications, refer

More information

WHAT IS GAS TANK/CYLINDER?

WHAT IS GAS TANK/CYLINDER? Introduction To use compressed gas cylinders safely, it is important that they are stored properly, handled correctly, used with the correct equipment, and that the properties of the gases they contain

More information

2018 STATEMENTS OF FACT MINE RESCUE. 1. To test for methane, use a methane detector or chemical analysis.

2018 STATEMENTS OF FACT MINE RESCUE. 1. To test for methane, use a methane detector or chemical analysis. 2018 STATEMENTS OF FACT MINE RESCUE 1. To test for methane, use a methane detector or chemical analysis. 2. Carbon monoxide can be detected by means of carbon monoxide detectors, multigas detectors, or

More information

Implementation of Electrical and Instrument Installation in Hazardous Area Classification

Implementation of Electrical and Instrument Installation in Hazardous Area Classification Implementation of Electrical and Instrument Installation in Hazardous Area Classification Rosihan Anwar - Pertamina Hulu Energi ONWJ Phe.pertamina.com IECEx Conference, Jakarta 8-9 August 2018 PERTAMINA,

More information

Basics of Fire and Explosion: Risk Assessment

Basics of Fire and Explosion: Risk Assessment 1 1 Basics of Fire and Explosion: Risk Assessment If static electricity was really static, as one may assume by its name, then it could be ignored. Only when it becomes more dynamic does it appear to be

More information

Operating Instructions

Operating Instructions LPL Series LED Pendant Lighting Operating Instructions IM0102 COOPER Electronic Technologies (Shanghai) Co., Ltd. No. 955 Shengli Road, East Area of Zhangjiang High-Tech Park, Shanghai 201201 China 1.

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable

More information

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC Supplementary Installation and Operating Instructions Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex Category: II 2G Ex IIC II 3G Ex IIC Contents 1 General safety directions...3 2 Main safety features...4

More information

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E DSEAR Regulations 2002 Sets minimum requirements for the protection

More information

Paint Spraying and Other Painting Processes Fire Safety

Paint Spraying and Other Painting Processes Fire Safety April 2011 Country of Origin: United Kingdom Paint Spraying and Other Painting Processes Fire Safety Introduction... 1 Risk Assessment... 2 Recommendations... 2 Location... 2 Heating... 3 Electrical Equipment...

More information