Hazardous (Classified) Locations

Size: px
Start display at page:

Download "Hazardous (Classified) Locations"

Transcription

1 Hazardous (Classified) Locations Presented by: John Chambers UL HazLoc operations Presented at: Safety & You in Safety Conference Flexible Packaging Association (FPA) 1

2 AREA CLASSIFICATIONS Class I Flammable, gases, vapors or liquids Class II Combustible dusts Class III Ignitable fibers and flyings 2

3 WHO CLASSIFIES AREAS? WHO ACCEPTS EQUIPMENT? ARE THEY THE SAME PERSON? Area Classification Vs. Authority Having Jurisdiction (AHJ) Approved vs. Listed vs. Identified 3

4 CLASS I, DIVISION 1 A Class I, Division 1 location is a location where ignitable concentrations of flammable gases, vapors or liquids: can exist under normal operating conditions; may exist frequently because of repair or maintenance operations or leakage; or may exist because of equipment breakdown that simultaneously causes the equipment to become a source of release 4

5 CLASS I, DIVISION 2 A Class I, Division 2 location is a location where: volatile flammable liquids or flammable gases or vapors exist, but are normally confined within closed containers; ignitable concentrations of gases, vapors or liquids are normally prevented by positive mechanical ventilation; or adjacent to a Class I, Division 1 location where ignitable concentrations might be occasionally communicated 5

6 CLASS I, ZONE 0 A Class I, Zone 0 location is a location where ignitable concentrations of flammable gases, vapors or liquids: are present continuously; or are present for long periods or time 6

7 CLASS I, ZONE 1 A Class I, Zone 1 location is a location where ignitable concentrations of flammable gases, vapors or liquids: are likely to exist under normal operating conditions; may exist frequently because of repair or maintenance operations or leakage; may exist because of equipment breakdown that simultaneously causes the equipment to become a source of ignition; or adjacent to a Class I, Zone 0 location from which ignitable concentrations could be communicated ignitable concentrations could be communicated 7

8 CLASS I, ZONE 2 A Class I, Zone 2 location is a location where: ignitable concentrations of flammable gases, vapors or liquids are not likely to occur in normal operation or, if they do occur, will exist only for a short period; volatile flammable liquids or flammable gases or vapors exist, but are normally confined within closed containers; ignitable concentrations of gases, vapors or liquids are normally prevented by positive mechanical ventilation; or adjacent to a Class I, Zone 1 location from which 8 ignitable concentrations could be communicated

9 Definition: MESG MESG (Maximum Experimental Safe Gap) - The maximum clearance between two parallel metal surfaces that has been found, under specified test conditions, to prevent an explosion in a test chamber from being propagated to a secondary chamber containing the same gas or vapor at the same concentration. 9

10 Definition: MIC Ratio MIC (Minimum Igniting Current) Ratio - The ratio of the minimum current required from an inductive spark discharge to ignite the most easily ignitable mixture of a gas or vapor, divided by the minimum current required from an inductive spark discharge to ignite methane under the same test conditions. 10

11 CLASS I, DIVISION 1 & 2 Group A Acetylene Group B GROUPS Gases or vapors having: MESG < 0.45 mm or MIC Ratio < 0.40 Examples are: hydrogen, fuel and combustible process gases containing more than 30 percent hydrogen by volume, butadiene, ethylene oxide, propylene oxide, and acrolein. 11

12 CLASS I, DIVISION 1 & 2 GROUPS (cont.) Group C Gases or vapors having: 0.45 mm < MESG < 0.75 mm or 0.40 < MIC Ratio < 0.80 Examples are: ethyl ether and ethylene. Group D Gases or vapors having: 0.75 mm < MESG 0.80 < MIC Ratio Examples are: acetone, ammonia, benzene, butane, cyclopropane, ethanol, gasoline, hexane, methanol, methane, naphtha, and propane. 12

13 CLASS I, ZONE 0, 1 AND 2 Group IIC GROUPS Atmospheres containing acetylene, hydrogen, or gases or vapors having: MESG < 0.50 mm MIC Ratio <

14 CLASS I, ZONE 0, 1 AND 2 GROUPS (cont.) Group IIB Atmospheres containing ethylene or acetaldehyde, or gases or vapors having: 0.50 mm < MESG < 0.90 mm 0.45 < MIC Ratio < 0.80 Group IIA Atmospheres containing acetone, ammonia, ethyl, alcohol, gasoline, methane, propane, or gases or vapors having: 0.90 mm < MESG 0.80 < MIC Ratio 14

15 CLASS II, DIVISION 1 A Class II, Division 1 location is a location where: Ignitable concentrations of combustible dust can exist in the air under normal operating conditions; Ignitable concentrations of combustible dust may exist because of equipment breakdown that simultaneously causes the equipment to become a source of ignition; or Electrically conductive combustible dusts may be present in hazardous quantities 15

16 CLASS II, DIVISION 2 A Class II, Division 2 location is a location where: combustible dust is not normally in the air in ignitable concentrations; dust accumulations are normally insufficient to interfere with normal operation of electrical equipment; Dust may be in suspension in the air as the result of infrequent malfunction of equipment; or Dust accumulation may be sufficient to interfere with safe dissipation of heat or may be ignitable by abnormal operation 16

17 CLASS II, DIVISION 1 ONLY GROUP Group E Atmospheres containing combustible metal dusts including aluminum, magnesium and their commercial alloys, or other combustible dusts whose particle size, abrasiveness, and conductivity present similar hazards in the use of electrical equipment 17

18 CLASS II, DIVISION 1 AND 2 GROUPS Group F Atmospheres containing combustible carbonaceous dusts, including carbon black, charcoal, coal or dusts that have been sensitized by other materials so that they present an explosion hazard Group G Atmospheres containing combustible dusts not included in Group E or F, including flour, grain, wood, plastic, and chemicals 18

19 CLASS I, DIVISION 1 AND 2 and CLASS II TEMPERATURE CLASSES T1 (<450º C) T2 (< 300º C) T2A, B, C, D (< 280º C, < 260ºC, < 230ºC, < 215º C) T3 (< 200º C) T3A, B, C, (< 180º C, < 165º C, < 160º C) T4 (< 135º C) T4A (< 120º C) T5 (< 100º C) T6 (< 85º C) 19

20 CLASS I, ZONE 0, 1 AND 2 TEMPERATURE CLASSES T1 (< 450 C) T2 (< 300 C) T3 (< 200 C) T4 (< 135 C) T5 (< 100 C) T6 (< 85 C) 20

21 CLASS III, DIVISION 1 A location in which easily ignitable fibers or materials producing combustible flyings are handled, manufactured or used 21

22 CLASS III, DIVISION 2 A location in which easily ignitable fibers are stored or handled 22

23 CLASS III, DIVISION 1 AND 2 GROUPS Not divided into groups 23

24 CLASS III, DIVISION 1 AND 2 TEMPERATURE LIMITS Article 503 of the NEC limits maximum temperatures for Class III equipment 165 C for equipment not subject to overloading 120 C for equipment that may be overloaded 24

25 CLASS I DIVISION /ZONE AREA CLASSIFICATION COMPARISON Division 1: Where ignitable concentrations of flammable gases, vapors or liquids can exist all of the time or some of the time under normal operating conditions Zone 0: Where ignitable concentrations of flammable gases, vapors or liquids can exist all of the time or for long periods of time under normal operating conditions Division 2: Where ignitable concentrations of flammable gases, vapors or liquids are not likely to exist under normal operating conditions Zone 1: Where ignitable concentrations of flammable gases, vapors or liquids can exist some of the time under normal operating conditions Zone 2: Where ignitable concentrations of flammable gases, vapors or liquids are not likely to exist under normal operating conditions 25

26 Division 1 and 2 Zone 0, 1 and 2 A (acetylene) B (hydrogen) C (ethylene) D (propane) IIC (acetylene & hydrogen) IIB (ethylene) IIA (propane) 26

27 CLASS I DIVISION/ZONE TEMPERATURE CLASS COMPARISON Division 1 and 2 Zone 0, 1 and 2 T1 (<450º C) T1 (<450º C) T2 (<300º C) T2 (<300º C) T2A,B,C,D (<280º C, <260º C, <230º C, <215º C) T3 (<200º C) T3 (<200º C) T3A,B,C, (<180º C, <65º C, <160º C) T4 (<135º C) T4 (<135º C) T4A (<120º C) T5 (<100º C) T5 (<100º C) T6 (<85º C) T6 (<85º C) 27

28 COMPARISON OF PRODUCT MARKINGS U.S. CANADA EUROPE IEC Class I, Div. 1, Group C,D Class I, Div. 1, Group C,D EEx de IIB T5 Certificate No. Ex de IIB T5 Cert. Number Class I, Zone 1 AEx de IIB T5 Ex de IIB T5 Additional for ATEX: 0539 II 2 G

29 CLASS I, DIVISION 1 AND 2 PROTECTION TECHNIQUES Area Division 1 Division 2 Protection Techniques Explosionproof Intrinsically Safe (2 fault) Purged/Pressurized (Type X or Y) Hermetically Sealed Nonincendive Circuits Nonincendive Components Nonincendive Equipment Non-Sparking Oil Immersion Purged/Pressurized (Type Z) Sealed Devices Any Class I, Division 1 technique Any Cl. I, Zn. 0, 1, or 2 technique 29

30 CLASS II, DIVISION 1 AND 2 PROTECTION TECHNIQUES Area Division 1 Protection Techniques Dust-Ignitionproof Intrinsically Safe Pressurized (Type X or Y) Division 2 Dusttight Nonincendive Circuits Nonincendive Components Nonincendive Equipment Pressurized (Type Z) Any Class II, Division 1 technique 30

31 CLASS III, DIVISION 1 AND 2 PROTECTION TECHNIQUES Area Protection Techniques Division 1 & 2 Dusttight Intrinsically Safe 31

32 CLASS I, ZONE 0 AND 1 PROTECTION TECHNIQUES Area Zone 0 Zone 1 Protection Techniques Intrinsically Safe (2 fault), ia Class I, Division 1 Intrinsically Safe (2 fault) Encapsulated, m Flameproof, d Increased Safety, e Intrinsically Safe (1 fault), ib Oil Immersed, o Powder Filled, q Purged/Pressurized, p Any Class I, Zone 0 technique Any Class I, Division 1 technique 32

33 CLASS I, ZONE 2 PROTECTION TECHNIQUES Area Protection Techniques Zone 2 Energy Limited nc ( nl in EN50021) Hermetically Sealed, nc Nonincendive, nc Non-Sparking, na Pressurization nz ( np in EN50021) Restricted Breathing, nr Sealed Device, nc Any Class I, Zone 0 or 1 technique Any Class I, Division 1 or 2 technique 33

34 ORDINARY LOCATIONS REQUIREMENTS For all equipment: Risk of Fire Risk of Electric Shock Special Applications: Environmental Ratings Marine Ratings Signaling/Fire Alarm 34

35 OTHER HAZARDOUS LOCATIONS REQUIREMENTS Some examples of requirements that may apply to multiple protection techniques include: Marking/Labeling Static Electricity Thermal Shock on glass parts Vibration Test 35

36 EXPLOSIONPROOF EQUIPMENT Equipment that has an enclosure capable of: withstanding an explosion of a specified gas or vapor that is expected to occur within the enclosure, preventing the ignition of a specified gas or vapor surrounding the enclosure due to sparks, flashes or explosion of the gas or vapor within the enclosure, and operating at an external temperature that will not ignite a specified gas or vapor surrounding the enclosure 36

37 Enclosure with enlarged gap, ready for an explosion test

38 4 5 Each frame = 1/2000 seconds 6 38

39 WITHSTANDING THE PRESSURE OF AN EXPLOSION The ability of an enclosure to withstand an explosion without rupture or permanent distortion is dependent upon: the strength of the enclosure material, and securement means, such as bolts 39

40 WITHSTANDING THE PRESSURE OF AN EXPLOSION (CON T) The strength of the enclosure material and securement means is determined by the following requirements: type of metal or metal alloy (zinc & magnesium are not allowed) type of plastic (including resistance to chemical atmospheres) casting/molding design minimum thickness hydrostatic pressure testing 40

41 PREVENTING THE IGNITION OF SURROUNDING ATMOSPHERE DUE TO PROPAGATION The ability of an enclosure to prevent ignition of a specified gas or vapor surrounding the enclosure is dependent upon the ability of any path from the interior to the exterior of the enclosure (or flame paths) to: prevent the escape of any flames, sparks or hot particles capable of ignition, and sufficiently cool the vented material 41

42 PREVENTING THE IGNITION OF SURROUNDING ATMOSPHERE DUE TO PROPAGATION (CON T) The suitability of these flame paths to prevent ignition is determined by the following requirements: Joint widths and clearances Shaft lengths and clearances Thread engagement Explosion testing 42

43 EXPLOSIONPROOF JOINT REQUIREMENTS More Restrictive than Flameproof May be: Flat Threaded Rabbet (Spigot) Labyrinth Cylindrical 43

44 JOINT COMPARISON EXAMPLE Group C (IIB) Enclosure Volume 2000 cm³ (122 in³) Explosionproof Flameproof Width 19.1 mm (3/4 in) 12.5 mm Clearance 0.05 mm (0.002 in) 0.2 mm 44

45 EXPLOSION TESTS: Minimum 10 Tests Covers the Explosive Range Covers both Reference Pressure and Non-transmission 45

46 TEST GAS MIXTURES Group A Acetylene 5-20% Group B Hydrogen 15-35% Group C Ethylene 4-9 % Group D Propane 3-7 % 46

47 Explosion Testing The custom built, Process Control and Gas Monitoring Panel enables the technician to fully control tests from outside the test room. Remote video cameras connected to monitors on top of the control panel, allow the technician to view the device under test. The entire test area is also monitored (video & audio) to ensure that nobody is in the room before conducting a test. With these features in place, personnel safety is maximized. The test area has been accident free in its four decades of operation. 47

48 48

49 The device under test is placed inside a wood chamber and is set-up with inlet & outlet connections to introduce explosive gas-air mixtures through the device and the wood chamber. Pneumatically actuated valves are used to isolate the explosive gas-air mixture in the device from the explosive gas-air mixture in the wood chamber. 49

50 A thin sheet of clear plastic is installed over the wood chamber and provides a seal to maintain an explosive atmosphere within the chamber, and also enables the device to be viewed during the testing process. If the explosive atmosphere within the wood chamber ignites, the pressure from the explosion will vent out through the clear plastic cover which will prevent the explosion from destroying the wood chamber. A spark plug is used to ignite the explosive mixture within the device. The spark plug is placed at a location in the device where an arc may occur from electrical components or wiring that would normally be present in the device. 50

51 Quartz Piezoelectric pressure transducers are installed into the device under test and connected to an oscilloscope for the purpose of measuring the internal explosion pressure developed during the explosion test series. The maximum pressure obtained from the test series will be used to further test the strength of the device after the explosion test series. 51

52 HYDROSTATIC PRESSURE TEST The device must withstand a hydrostatic test based on the maximum explosion pressure No rupture or permanent distortion For example: maximum explosion pressure of 100 PSI = 400 PSI hydrostatic test for 10 seconds 52

53 PREVENTING THE IGNITION OF SURROUNDING ATMOSPHERE DUE TO TEMPERATURE The ability of an enclosure to prevent ignition of a specified gas or vapor surrounding the enclosure is also dependent upon how heat- producing components within the enclosure affect the temperature on the external surface of the enclosure. 53

54 PREVENTING THE IGNITION OF SURROUNDING ATMOSPHERE BY TEMPERATURE (CON T) The affect of these internal heat-producing components is determined by the following requirements: temperature testing (determines Temperature Class) marking of Temperature Class (T-Code) restriction that T-Code must be less than the autoignition temperature of surrounding atmosphere 54

55 55

56 56

57 57

58 58

59 59

60 Explosionproof Pushbutton Switch Cylindrical Joint ---> <---Threaded Joint Flat Joint---> Threaded Conduit Entries 60

61 61

62 62

63 63

64 64

65 65

66 66

67 67

68 68

69 69

70 70

The Omron STI Hazardous Location

The Omron STI Hazardous Location Hazardous Location Rating Systems for Interlock Switches The Omron STI Hazardous Location Rated Safety Interlock Switches presented in this catalog are classified by the European standard as Ex, ExdIIc

More information

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus Hazardous Location Equipment - United States Equipment listed in this category for Hazardous (Classified) Locations is also suitable for installations in areas that are unclassified locations and, unless

More information

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof Hazardous Location Equipment - Canada Equipment listed in this category for Hazardous Locations is also suitable for installations in areas that are non-hazardous locations and, unless referenced in the

More information

Session #: Selection of Explosion Protected Equipment for Hazardous Locations

Session #: Selection of Explosion Protected Equipment for Hazardous Locations Abstract Session #: (Arial 16) Selection of Explosion Protected Equipment for Hazardous Locations Pieter Coetzee Explosion Prevention Consultant Registered person How can we mitigate the risks of explosions

More information

Explosive Environment Review

Explosive Environment Review Explosive Environment Review Version 3.0 A Comprehensive Guide to Electronic Weighing Equipment and Hazardous Environments PN 16985 Contents 1.0 Introduction... 1 2.0 Standards... 2 2.1 NFPA 70, National

More information

TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION

TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION Equipment listed in this guide for Hazardous (Classified) Locations is also suitable for installations in areas that are unclassified locations

More information

General information on explosion protection

General information on explosion protection 427 Why explosion protection? Explosion protection for electrical and mechanical machinery is an important precautionary measure to ensure the safety of persons and all kinds of production, storage and

More information

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS 1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS EXPLOSION PROTECTION In addition to the type approval and certification of industrial weighing systems concerned with accuracy, equipment that is also

More information

CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS IN GAS UTILITY AREAS. Gerry Pickens

CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS IN GAS UTILITY AREAS. Gerry Pickens CLASSIFICATION OF LOCATIONS FOR ELECTRICAL INSTALLATIONS IN GAS UTILITY AREAS Gerry Pickens Atmos Energy 810 Crescent Centre Drive Franklin, TN 37067 The National Electrical Code (NEC) defines hazardous

More information

BASIC NATIONAL ELECTRIC CODE APPLICABLE TO MEASUREMENT. Gerry Pickens. Atmos Energy 810 Crescent Centre Drive Franklin, TN 37067

BASIC NATIONAL ELECTRIC CODE APPLICABLE TO MEASUREMENT. Gerry Pickens. Atmos Energy 810 Crescent Centre Drive Franklin, TN 37067 BASIC NATIONAL ELECTRIC CODE APPLICABLE TO MEASUREMENT The National Electrical Code (NEC) defines hazardous locations as those areas "where fire or explosion hazards may exist due to flammable gases or

More information

The evolution of the Ex-proof flame path

The evolution of the Ex-proof flame path April 2017 The evolution of the Ex-proof flame path As written in previous dissertation, the most critical part of a flameproof enclosure 'Ex d' is the flame path. Although the Standards are divided into

More information

Pioneers. Ex-ENGINEERING. Quality

Pioneers. Ex-ENGINEERING. Quality Pioneers The increasing demands of industry for dependable explosionproof lighting, motivated Baliga to pioneer the design and manufacture of a quality line way back in 1962, when the first Indian Standards

More information

Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments

Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments Gas Well Deliquification Workshop Sheraton Hotel, February 19 22, 2012 Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments Glenn Longley, Sr. Product Manager FreeWave Technologies Agenda

More information

Hafner-Pneumatik presents: General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range

Hafner-Pneumatik presents: General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range Hafner-Pneumatik presents: Including Pneumatic Valves General information on ATEX 95 & Products for explosion hazardous environment from the Hafner range General information - 1 A product that is supposed

More information

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres Page 1 of 7 Title Plan electrical installations for explosive atmospheres Level 5 Credits 8 Purpose This unit standard is intended for use in the training and assessment of people who work with electrical

More information

NZQA registered unit standard version 1 Page 1 of 8. Conduct detailed inspection of electrical installations for explosive atmospheres

NZQA registered unit standard version 1 Page 1 of 8. Conduct detailed inspection of electrical installations for explosive atmospheres Page 1 of 8 Title Conduct detailed inspection of electrical installations for explosive atmospheres Level 5 Credits 5 Purpose This unit standard is intended for use in the training and assessment of people

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

Intrinsic safety 101 hazardous locations

Intrinsic safety 101 hazardous locations Intrinsic safety 101 hazardous locations Protection methods, containment, segregation, and prevention By Robert Schosker This article answers the question, Why worry about hazardous locations? The area

More information

PRINCIPLES OF EXPLOSION PROTECTION

PRINCIPLES OF EXPLOSION PROTECTION PRINCIPLES OF EXPLOSION PROTECTION Contact Details... 19 Definitions... 1 Explosion proof apparatus... 14 Hazard zone classifications... 4 Installations... 15 Introduction... 1 Maintenance... 17 Primary

More information

General information on explosion protection

General information on explosion protection 427 Why explosion protection? Explosion protection for electrical and mechanical machinery is an important precautionary measure to ensure the safety of persons and all kinds of production, storage and

More information

Process Instrumentation. Product Guide. Registered Quality System to ISO 9001

Process Instrumentation. Product Guide. Registered Quality System to ISO 9001 Process Instrumentation Product Guide Registered Quality System to ISO 9001 SORis committed to and understands the demanding requirements of the process industry. We design, develop and manufacture the

More information

WHITE PAPER on Explosion Proof and Intrinsic Safety Solutions. Oct. 2013

WHITE PAPER on Explosion Proof and Intrinsic Safety Solutions. Oct. 2013 WHITE PAPER on Explosion Proof and Intrinsic Safety Solutions Oct. 2013 TABLE OF CONTENTS Abstract... 3 Abbreviations... 4 Introduction to Standards... 5 Protection Layers... 7 Simple Devices... 7 Mechanical

More information

Explosive Environment Review

Explosive Environment Review Explosive Environment Review Version 3.0 A Comprehensive Guide to Electronic Weighing Equipment and Hazardous Environments PN 16985 Contents 1.0 Introduction... 1 2.0 Standards... 2 2.1 NFPA 70, National

More information

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS SECTION 7 ELECTRICITY CHAPTERS A APPROACH B DOCUMENTS, REGULATIONS AND

More information

The Proper Procedure

The Proper Procedure The Proper Procedure Lockout Lockout is used to prevent the release of hazardous energy or equipment from starting by applying a lockout device and lock A padlock is placed on the appropriate energy isolating

More information

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany EXPLOSION PROTECTION USING THE DATABASE Maria Molnarne formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany Department - Chemical Safety Engineering Outline Database CHEMSAFE

More information

RTD temperature probes

RTD temperature probes RTD temperature probes Ex i for use in areas with an explosion hazard (Ex areas) Persons concerned: Experienced professional electricians as per EU Directive 1999/92/EC and trained personnel Operating

More information

HAZARDOUS AREA CLASSIFICATION & SELECTION OF ELECTRICAL EQUIPMENT FOR FLAMMABLE ATMOSPHERES

HAZARDOUS AREA CLASSIFICATION & SELECTION OF ELECTRICAL EQUIPMENT FOR FLAMMABLE ATMOSPHERES HAZARDOUS AREA CLASSIFICATION & SELECTION OF ELECTRICAL EQUIPMENT FOR FLAMMABLE ATMOSPHERES Hydrocarbon Risks OISD Accident compilation (1996-1999): Out of the total 71 accidents (5 lakh property loss/fatality/loss

More information

Hot Work Program. University of Wisconsin-Platteville Reviewed 4/2016

Hot Work Program. University of Wisconsin-Platteville Reviewed 4/2016 Hot Work Program University of Wisconsin-Platteville Reviewed 4/2016 The purpose of the Hot Work Program is to establish safety procedures for employees, contractors, and subcontractors engaging in any

More information

WHAT IS GAS TANK/CYLINDER?

WHAT IS GAS TANK/CYLINDER? Introduction To use compressed gas cylinders safely, it is important that they are stored properly, handled correctly, used with the correct equipment, and that the properties of the gases they contain

More information

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display.

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display. Display Thermo, Inc. Instruction Manual English TP-5 Display TP-7 Display TP-8 1-1 Thermo, Inc. Instructions for use- Models TP-5, TP-7, and TP-8 The manual describes basic function and use of Thermo instruments

More information

OIL+GAS PRODUCTS AND THEIR APPLICATIONS

OIL+GAS PRODUCTS AND THEIR APPLICATIONS OIL+GAS PRODUCTS AND THEIR APPLICATIONS FIELDS OF APPLICATIONS AND REQUIREMENTS OIL RIGS SHIP AND SHIP EQUIPMENT Oil rigs have extremely high requirements for the technology used. Even the smallest spark

More information

M.A. Rezaei. TEHRAN, IRAN

M.A. Rezaei. TEHRAN, IRAN () */! "#$ %& M.A. Rezaei rezaeima@nigc.org TEHRAN, IRAN http://igs.nigc.ir !! / # $% &'() *) ".3% %*)(ZONE=0).3% %*) (ZONE=1) (.3% %*) (ZONE=2) 6.3=( ;?= > 8(9: ;

More information

II 2G EEx ia IIC T6. Ignition protection class

II 2G EEx ia IIC T6. Ignition protection class ATEX General information According to 94/9/EC, a device that is to be used in an environment at risk of explosion may only be brought into the market if it satisfies the standards specified in the norm.

More information

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide

OSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide OSAT Series Intrinsically Safe Infrared Temperature Sensor Operator's Guide Issue L Jan 2017 Introduction OSAT Series intrinsically safe non-contact infrared temperature sensors measure the temperature

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 12 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

HAZARDOUS APPLICATIONS

HAZARDOUS APPLICATIONS HAZARDOUS APPLICATIONS I. WHAT CONSTITUTES A HAZARDOUS CLASSIFIED AREA? Any area inside or outdoor that has explosive gas, vapor, dust or flyings mixed with air in ignitable concentrations. II. WHAT TYPES

More information

NATURAL GAS MAINTENANCE. Part 192 Subpart "M"

NATURAL GAS MAINTENANCE. Part 192 Subpart M NATURAL GAS MAINTENANCE Part 192 Subpart "M" CONTACT INFORMATION Pamela West Pipeline Safety Specialist U.S. Department of Transportation PHMSA Inspector Training and Qualifications Main: (405) 686-2310

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 2419437 Master Contract: 203012 Issued to: ABB Automation Products GmbH 72 Schillerstrasse Minden, 32425 Germany Attention: Ralf Schaffer The products listed below

More information

NFPA 496. Standard for. Purged and Pressurized Enclosures for Electrical Equipment Edition

NFPA 496. Standard for. Purged and Pressurized Enclosures for Electrical Equipment Edition NFPA 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment 2003 Edition Copyright 2003, National Fire Protection Association, All Rights Reserved This edition of NFPA 496, Standard

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Application Single-acting positioner for attachment to pneumatic control valves. Supplied with either an electric input signal from

More information

Certificate of Compliance

Certificate of Compliance FF0002 Certificate of Compliance Certificate: 70024080 Date Issued: 2017-07-04 Issued to: ecom instruments GmbH Industriestrasse 2 Assamstadt, Baden Wurttemburg 97959 GERMANY Attention: Kevin Spence The

More information

IECEx certification of Non-Electrical Ex Equipment

IECEx certification of Non-Electrical Ex Equipment IECEx certification of Non-Electrical Ex Equipment Thierry Houeix Ex Certification Officer Brief history of Non Electrical Ex Equipment standards In 2008, during the SC31M Plenary meeting it was decided

More information

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E DSEAR Regulations 2002 Sets minimum requirements for the protection

More information

Intrinsically explosion-proof and safety barrier introduction

Intrinsically explosion-proof and safety barrier introduction Intrinsically explosion-proof and safety barrier introduction Summary of Topics Page 1. Explosion basic knowledge 1 2. Explosion groups 1 3. Zone classification 2 4. Explosion-proof electrical apparatus

More information

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus Page 1 of 7 Title Conduct a conformity assessment of explosion-protected apparatus Level 6 Credits 9 Purpose This unit standard covers the assessment and certification of explosion-protected apparatus

More information

Pressure Switches Application Guideline

Pressure Switches Application Guideline Pressure Switches Application Guideline Product Overview The Fema Pressure Switch product portfolio provides devices suitable for many applications. The portfolio contains Special functions and equipment

More information

A Unified Marking System for Ex Equipment

A Unified Marking System for Ex Equipment CERTEX Appointed Ex Laboratory Reg No: 1999/027771/07 (Pty) Ltd Government Approved Inspection Authority T0104 PO Box 467 Tel: +27 (11) 316 4601 Olifantsfontein Fax: +27 (11) 316 5670 1665 E- mail: info@explolabs.co.za

More information

NZQA registered unit standard version 3 Page 1 of 6

NZQA registered unit standard version 3 Page 1 of 6 Page 1 of 6 Title Report on the integrity of explosion-protected electrical apparatus in explosive atmospheres Level 3 Credits 3 Purpose This unit standard covers the explosion-protection aspects of plant

More information

Approval Standard. for

Approval Standard. for Approval Standard for Nonincendive Electrical Equipment for Use in Class I and II, Division 2, and Class III, Divisions 1 and 2, Hazardous (Classified) Locations Class Number 3611 December 2004 2004 FM

More information

6-5 Maintenance Manual

6-5 Maintenance Manual Non Return Valve 6-5 Maintenance Manual Contents 1. PRODUCT DESCRIPTION... 1 1.1 How it works... 1 1.2 Overall dimensions... 3 1.3 Technical datasheet... 4 1.3.1 Push flow situation... 4 1.3.2 Pull flow

More information

USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases)

USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases) (June 27, 2002) USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases) 1. General Being designed for light industrial applications, NAP-100A series also available

More information

FLAMMABLE GAS SENSOR/TRANSMITTER

FLAMMABLE GAS SENSOR/TRANSMITTER FLAMMABLE GAS SENSOR/TRANSMITTER Plant safety protection for flammable gases. F E A T U R E S Fixed gas monitoring for point source hazards and perimeter protection in arduous duty and exposed locations.

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard CITY AND COUNTY OF DENVER CR&CF RISK UNIT 65.5.11 Compressed Gas Safety Standard 1.0 Introduction 2.0 Scope This standard has been developed to protect all City and County of Denver employees and contractors

More information

INSTRUCTION MANUAL. Gas Salamander

INSTRUCTION MANUAL. Gas Salamander INSTRUCTION MANUAL Gas Salamander This manual contains important information regarding your unit. Please read this manual thoroughly prior to equipment set-up, operation and maintenance. Failure to comply

More information

9700 Transmitter Submersible hydrostatic level transmitter

9700 Transmitter Submersible hydrostatic level transmitter Specification sheet IP0078 October 2007 Level 9700 Transmitter Submersible hydrostatic level transmitter Description The 9700 series hydrostatic level transmitter is designed to perform in the most arduous

More information

SECTION 2 APPLICATION OF FUNDAMENTALS

SECTION 2 APPLICATION OF FUNDAMENTALS SECTION 2 APPLICATION FUNDAMENTALS ENVIRONMENTAL CONDITIONS IN NEC CLASS I HAZARDOUS LOCATIONS Section II covers a great number of illustrations which can be applied directly to a hazardous area under

More information

Basics of Fire and Explosion: Risk Assessment

Basics of Fire and Explosion: Risk Assessment 1 1 Basics of Fire and Explosion: Risk Assessment If static electricity was really static, as one may assume by its name, then it could be ignored. Only when it becomes more dynamic does it appear to be

More information

CERTIFICATE OF COMPLIANCE

CERTIFICATE OF COMPLIANCE FM Approvals 1151 Boston Providence Turnpike P.O. Box 9102 Norwood, MA 02062 USA T: 781 762 4300 F: 781-762-9375 www.fmapprovals.com CERTIFICATE OF COMPLIANCE HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL

More information

User Manual. GPL 3000 e. gas detector

User Manual. GPL 3000 e. gas detector User Manual GPL 3000 e gas detector Table of contents Application...4 Unit ppm, Vol.%...5 Operation elements GPL 3000 e...6 Gas Sensor...7 Measurement range...8 LED allocation...8 Turning on the GPL 3000

More information

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,

More information

Operating Instructions

Operating Instructions Operating Instructions Before operating the thin film evaporator, please be aware of all safety concerns associated with this experiment: Burn hazard from the column and steam lines, Chemical hazards associated

More information

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Installation Instructions BGA Series Issue Date October 3, 2017 BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Applications The BGA Series shutoff gas valve is an electrically operated gas valve that

More information

Electrical Equipment and Installations in Hazardous Areas. Univerza v Ljubljani Fakulteta za elektrotehniko

Electrical Equipment and Installations in Hazardous Areas. Univerza v Ljubljani Fakulteta za elektrotehniko Univerza v Ljubljani Fakulteta za elektrotehniko Electrical Equipment and Installations in Hazardous Areas Student: Tiago da Silva Oliveira; Student Number: 70080035; Subject: Electrical Installations

More information

Safety Manual HAL Extraction Technology Ltd. Extraction Booth Systems

Safety Manual HAL Extraction Technology Ltd. Extraction Booth Systems Safety Manual HAL Extraction Technology Ltd. Extraction Booth Systems CAUTION: READ AND UNDERSTAND THIS BEFORE USE www.extractionbooth.com (720) 504-4726 info@extractionbooth.com 12/06/2016 HAL Extraction

More information

Flammability Chart. Gas Formula Ignition

Flammability Chart. Gas Formula Ignition Leak Detection 101 Investigating a leak is simplified if you know the basics. By J. Scott Kleppe Sensit (J and N Enterprises, Inc.) Every day new gas services are added to provide economical energy to

More information

BGA158 Series CE Approved Class B Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve

More information

TECHNOLOGY GUIDE NO. 12

TECHNOLOGY GUIDE NO. 12 SSPC: The Society for Protective Coatings TECHNOLOGY GUIDE NO. 12 Guide for Illumination of Industrial Painting Projects SSPC-Guide 12 1. Scope 1.1 This guide provides information on the quantity and quality

More information

Compressed Gases Storage and Handling Safety Policy. Individual Unit Function: Safety Procedure No.: SOP-0103 Page: 1 of 6

Compressed Gases Storage and Handling Safety Policy. Individual Unit Function: Safety Procedure No.: SOP-0103 Page: 1 of 6 Procedure No.: SOP-0103 Page: 1 of 6 MIDGA Reviewed: 07/09/18 Effective: 1/14/98 Supersedes: Original Preparer: Owner: Approver: Safety Safety Safety 1. PURPOSE The purpose of this procedure is to establish

More information

Fires and Explosions: What You Need to Know to Prevent Them

Fires and Explosions: What You Need to Know to Prevent Them Fires and Explosions: What You Need to Know to Prevent Them CSChE PSM Symposium Edmonton, Alberta 2007 Gerry Phillips, GC Phillips Consulting Ltd. Norman Nibber, Independent Risk Control Objectives Understand

More information

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee Page: Page 1 of 5 1 Introduction Compressed gas cylinders can present a variety of hazards due to their pressure and/or contents. One of the contributing factor to these hazards is gas leak due to malfunction

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Vision Painting Inc Safety Management System

Vision Painting Inc Safety Management System Abrasive Blasting 1. PURPOSE The purpose of this program is to provide training and qualification guidelines for the safe operation of Abrasive Blasting. The Safety Officer is responsible for facilitating

More information

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124 Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124 13.7 Pressure Equipment Directive (PED) 97/23/EC 1 The Pressure Equipment Directive (PED) 97/23/EC applies to the design, manufacturing and conformity

More information

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL 00, 0, 000 00, 000, 00 A. TECHNICAL INFORMATION Model 00 Inlet/Outlet " Air Inlet /" 0 / 000 /" /" 00 /" /" 000 /" /" 00 /" /" Flow Rate GPM/ 0LPM GPM/ 0LPM GPM/ LPM GPM/ LPM GPM/ 0LPM GPM/ 0LPM Maximum

More information

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm Dimensions M30x1,5 5 40 37 0102 Model Number 36 LED Features Comfort series 10 mm embeddable Connection BN BU Accessories BF 30 Mounting flange, 30 mm L+ L- Technical Data specifications Switching element

More information

Rotary air valves used for material feed and explosion protection are required to meet the criteria of NFPA 69 (2014)

Rotary air valves used for material feed and explosion protection are required to meet the criteria of NFPA 69 (2014) Rotary air valves used for material feed and explosion protection are required to meet the criteria of NFPA 69 (2014) 12.2.4.2. 12.2.4.2 rotary valve design criteria (close clearance) 12.2.4.3 THE DESIGN

More information

Fan and air movement essentials

Fan and air movement essentials 1 Properties of air For the purposes of this section we will assume that it is air that will be moved by the various types of fans. The air we breathe is made up of a mixture of gasses - nitrogen 78%,

More information

Pressure Piping Code-Industrial Piping. Part 6: Safeguarding

Pressure Piping Code-Industrial Piping. Part 6: Safeguarding ICS 23.040 J74 National Standard of the People's Republic of China GB/T 20801.6-2006 Pressure Piping Code-Industrial Piping Part 6: Safeguarding ffi1jtfil~ju1t1 I~tfil ~6$?t: ~~~1? Issued on: December

More information

GUIDELINES FOR HAZARDOUS AREA CLASSIFICATION AND ELECTRICAL INSTALLATIONS OF TANKERS

GUIDELINES FOR HAZARDOUS AREA CLASSIFICATION AND ELECTRICAL INSTALLATIONS OF TANKERS GUIDANCE NOTES GD 01-2010 CHINA CLASSIFICATION SOCIETY GUIDELINES FOR HAZARDOUS AREA CLASSIFICATION AND ELECTRICAL INSTALLATIONS OF TANKERS 2010 Beijing Contents Chapter 1 General...1 1.1 General...1 1.2

More information

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. Supplied with an electric input signal of 4 to 20

More information

Mechanical pressure switches

Mechanical pressure switches 18 Technical features / Advantages Diecast aluminium housing IP 54 or IP 65 version also available Wall mounting or directly on the pressure line Switching element (microswitch) Lead sealable setpoint

More information

GUIDELINES FOR HAZARDOUS AREA CLASSIFICATION AND ELECTRICAL INSTALLATIONS OF TANKERS

GUIDELINES FOR HAZARDOUS AREA CLASSIFICATION AND ELECTRICAL INSTALLATIONS OF TANKERS GUIDANCE NOTES GD 01-2010 CHINA CLASSIFICATION SOCIETY GUIDELINES FOR HAZARDOUS AREA CLASSIFICATION AND ELECTRICAL INSTALLATIONS OF TANKERS 2010 -------------------------------------- China Communications

More information

APG. Intrinsically Safe, Heavy Duty Pressure Transducer Series: PT-400

APG. Intrinsically Safe, Heavy Duty Pressure Transducer Series: PT-400 Intrinsically Safe, Heavy Duty Pressure Transducer Series: PT-400 C US The PT-400 offers high accuracy and reliability over a wide range of pressures. The small size, integrated electronics, wide operating

More information

ATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE

ATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE ATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE ATEX CHEMISTRY DIAPHRAGM PUMPS. ATEX VARIO CHEMISTRY DIAPHRAGM PUMPS. Chemistry diaphragm pumps, vacuum systems and gauges for use in

More information

ENGINEERING STANDARD FOR HAZARDOUS AREA SECOND EDITION JANUARY 2016

ENGINEERING STANDARD FOR HAZARDOUS AREA SECOND EDITION JANUARY 2016 IPS-E-EL-110(2) ENGINEERING STANDARD FOR HAZARDOUS AREA SECOND EDITION JANUARY 2016 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor

More information

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ?

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ? IEP Technologies 417-1 South Street, Marlborough, MA, 01752 ph 855.793.8407 fax 508.485.3115 www.ieptechnologies.com IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA 69-2014? Introduction Dust explosions can

More information

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848 Cal/OSHA Gas Systems for Welding GAS WELDING Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848 When performing gas welding, the following precautions, work procedures,

More information

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15)

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15) 1. PURPOSE: This SPI has been developed to ensure compliance to government regulations and to provide clear standards for storage of compressed gases. 2. CONTEXT The storage of compressed gases is legislated

More information

Title: Pressure Relieving and Venting Devices Function: Ecology & Safety No.: BC Page: 1 of 7 Reviewed: 6/30/12 Effective: 7/1/12 (Rev.

Title: Pressure Relieving and Venting Devices Function: Ecology & Safety No.: BC Page: 1 of 7 Reviewed: 6/30/12 Effective: 7/1/12 (Rev. Preparer: Team Member, North America, Process Safety Center of Expertise No.: BC032.020 Page: 1 of 7 Owner: Manager, North America Process Safety Center of Expertise Approver: Sr. Vice President, Ecology

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised Truck Module Page 1 of 5 GAS EMERGENCIES Introduction Natural gas and Liquid Propane Gas (LPG) are flammable gases. Many households and commercial buildings utilize these gases for everything from heating

More information

Packaging HM for shipment:

Packaging HM for shipment: Packaging HM for shipment: Considerations for Selection and Filling under the HMR Dangerous Goods Instructors Symposium, 2015 Process flow for the HMR: Person who offers Identify Is this material hazardous

More information

There are three fuelling systems which use LNG/CNG and which may be found in vehicles today:

There are three fuelling systems which use LNG/CNG and which may be found in vehicles today: UKRO Humberside Education Workshop 2017 NATURAL GAS POWERED VEHICLES Some LGV manufacturers (currently IVECO and SCANIA) are able to offer and Alternative Fueled vehicles that use Compresses Natural Gas

More information

Explosion Protection Technology Pty Ltd

Explosion Protection Technology Pty Ltd How to Apply Hazardous Area Australian Standards (Group II) 3-Day On-Site Workshop * 2018 This workshop provides a sound understanding of electrical compliance and your responsibilities in Group II hazardous

More information

Operating Instructions

Operating Instructions LPL Series LED Pendant Lighting Operating Instructions IM0102 COOPER Electronic Technologies (Shanghai) Co., Ltd. No. 955 Shengli Road, East Area of Zhangjiang High-Tech Park, Shanghai 201201 China 1.

More information