1 Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. UK. Ref: Rapidmain installation guide 4b
2 Index 1. Rapidmain fittings: Assembly and locking torque setting Calculating compressed air flow Design layout for thermal expansion Pipe work fall and further points to consider Pipe work bracket support. Bracket types and their use Take-offs lines (branch lines) and the use of flexible pipe. 11 Brief Specification Working Pressure to 13 bar (- 8 to 191 PSI) Media Compressed Air and other Neutral Gas Flow Range 20 to 63 mm 0.73 to 26.8 M/min (26 to 948 cfm) * Temperature Range -20 to +70 C * Flow rate calculated over 100 metres Single run line P1@ 8bar We suggest that both the installer and the user of the Rapidmain pipe installation carefully read this manual before its use and before carrying out any installation or modification work. Please also refer to the local health and safety guidelines and accident prevention rules and regulations. Page 2
3 Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Rapidmain fittings: Assembly and locking torque settings Tightening of locking collars on fittings Assemble by hand or use our spanner set the correct torque. Black for the body and blue for the nut: See table B below Table B O D Torque L = mm Use the depth gauge on the spanner to mark the outside of the pipe: See below. Push the fitting up to the mark on the pipe and then rotate the blue locknut to secure. Page 3
4 Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Rapidmain fittings: Assembly and locking torque settings Chamfer Pipe If you choose to use a vice to clamp the Aluminium pipe when cutting or chamfering leave clear at least 50mm of pipe to avoid damaging the radius diameter and pipe sealing surface. On larger pipe if required use a neutral lubricant or soap. Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. WA8 OSZ.UK. Page 4
5 Rapidmain fittings: Assembly and locking torque settings WARNING: to avoid O-Ring damage, the tube end must be chamfered before inserting the tube into the fittings. R-Range of Compressed Air distribution fittings Sizes DN 20 to 63 OD 1.1 Before use check that all the fitting connection parts are correctly assembled. Ensure you check the orientation of the locking clip; if this is incorrectly assembled the integrity of the connection cannot be guaranteed (See Table A). 1.2 Before inserting the tube into the fitting rotate the light-blue coupling ring until a slight mechanical stop is felt and no further. 1.3 The tube must be inserted into the fitting until the tube bottoms. This can be checked by previously marking on the tube the length L indicated in Table B. 1.4 Once the tube has been correctly inserted into the fitting, rotate the coupling ring completely over the first mechanical stop described in Section 1.2 above until fully tight. For best results it is advisable to use the C type spanners shown in the catalogue. 1.5 Table B shows the torque (N/m) required for each fitting size to provide the optimum mechanical operation and seal. 1.6 Table C illustrates the correct alignment for installation. Misalignment of more than 5 o from the horizontal could compromise the integrity of the fitting seal. 1.7 Please refer to the specifications shown in the present catalogue for pipe and fittings compatibility with chemical substances that could be present in the compressed air. 1.8 Rapidmain will not be held responsible for any damage caused by improper use of their products and/or non-compliance of the manufacturers assembly instructions here within. Table A How to calculate an air system pipe size 2.1 Pressure drop through fittings Although fittings are smooth inside and have the same tube internal diameter, they nonetheless cause a resistance to air flow, particularly when tubes change direction as in the case of elbows, tees, couplings and reduction fittings. Table E refers to pressure drops caused by fittings. Every fitting or change of direction has an equivalent pipe length of tube indicated in this table. 2.2 Air System pipe sizing Once the compressed air consumption (l/min) and the allowable pressure drop have been calculated, refer to Table D to select the correct tube dimension. After having examined the plant and considered the changes of direction as well as the pressure drop of fittings you can then refer to Table E to complete and correct previous calculations. Page 5
6 Calculating Compressed air flow Table C Table D Pressure drop for 100 m (in bars) Effective Absolute Pressure (in bars) Delivery SRA * (in l/min) Outside diameter of the tube (mm) Referential axis Delivery SRA * Actual delivery at the effective pressure (P) x absolute pressure (P+1) in bars Temperature Correction: 0 degrees Air delivery at 0 degrees C = delivery 15 degrees C x * SRA: Standard Reference Atmosphere 288 Using the Nomogram The tube diameter can be determined by first finding the flow rate in l/m and the allowable pressure drop. a. We have chosen the working pressure on the C axis. A straight red line has then been drawn connecting the working pressure to the pressure drop value on the A axis. b. Drawing this straight line allows us to locate a point on the R referential axis. c. A green line has then been drawn from the referential R axis to the value on the A axis which indicates plant delivery in l/min. d. This green line intersects on the B axis which shows the suitable tube diameter. Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. WA8 OSZ.UK. Page 6
7 Design layout for thermal expansion DL = DT x 0,02 x L A = DL x 23 B = 0.7 x A Variation due to thermal expansion Introduction The theoretical calculations and design criteria in this manual are only relevant where the installation ambient temperature is between 15 o C and 25 o C. Attention! Where the installation is outside of the recommended ambient temperatures indicated above, it may be necessary to take corrective action such as thermal insulation of the pipe or the inclusion of expansion/contraction loops. Calculating expansion loop dimensions On long straight runs of pipe it may be necessary to insert expansion loops in the line to prevent damage to the pipe, due to thermal movement (expansion or contraction) of the pipe. Example L1 = 40 mt L2 = 40 mt DT = 50 o C DL = DT x 0.02 x L = 50 x 0.02 x 40 = 40 mm A = DL x 23 = 40 x 23 = 920 mm B = 0.7 x A = 0.7 x 920 = 640 mm Legend A-B = Quote (mm) L-L1-L2 = Lengths (mt) DL = Expansions (mm) DT = Thermal range ( o C) M = Mobile bracket F = Fix bracket Examples of Expansion Loops Vertical layout (Upwards) Horizontal Vertical layout (Downwards) Fixed brackets hold the pipe firmly while sliding brackets allow axial movement. Page 7
8 Pipe work fall and further points to consider Fall of pipes Where possible horizontal runs should be designed to have a slight fall of (1-2%) in the direction of air flow to encourage drainage and collection of condensate at lower levels or at drop legs built within the air system, from which the condensate can be drained as required. Direction of air flow Install drains at low points where ever possible. Example Pipe Fall Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. WA8 OSZ. UK. Page 8
9 Pipe work fall and further points to consider To allow for system maintenance, install an adequate quantity of isolation valves in the pipe work. Valve Ball Valve Fixing of Pipes To allow for thermal movement of the pipe and to avoid stress points, the pipe should be installed and fixed to a secure surface of building, such as a wall, brickwork, roof support (direct or with hanging brackets) or the building framework using suitable fixed and sliding brackets as required. Fixed bracket Fixed bracket Sliding bracket Fixed bracket Page 9
10 Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Pipe work bracket support. Bracket types and there use Bracket and Pipe support centres It is important to install the pipe work brackets with correct spacing. Always try to support the pipe joint with a bracket located within 200 to 500 mm from the pipe joint. Please refer to the diagram below for examples of preferred installation Install brackets by each joint to support the pipe joint Suggested Maximum Support Centres) DN 20/ P (MT) Legend L = Length (mt) P = Brackets support centre (mt) M = Bracket G = Joint An alternative to the standard aluminium expansion loop, is to use suitable flexible hose assembly as shown below. DL = DT x 0,2 x L B = (2 x R) + DL 1 + DL 2 Legend L1-L2 = Lengths (mt) DL1-DL2 = Expansion (mm) DT = Thermal range ( o C) M = Bracket R = Radius (mm) A-B = Quotes (mm) Quote R A (mm) DN R (mm) A (mm) Attention! Tables are valid only for stainless steel flexible hoses type 1REX/INOX/N/321/DN. For other types refer to the manufacturer s technical documentation Page10
11 Take-off lines (branch lines) and the use of flexible pipe DL = DT x 0,2 x L A = DL x Y Legend A = Quote (mm) L1-L2 = Lengths (mt) DL = Expansion (mm) DT = Thermal range ( o C) F = Fixed bracket U = Use Y = Calculation factor Calculation Factor Y DN Y Bends using flexible hose. Using a flexible hose in corners is also acceptable. They can be used for the change of direction and at the same time to compensate for any thermal movement. L min = 1000 mm At the end of a pipe run always terminate the pipe and the fitting to an fixed anchored point eg: Wall Legend L1-L2 = Lengths (mt) DL1-DL2 = Expansion (mm) M = Bracket R = Radius (mm) L = Length of flexible pipe (mm) Pd 20od=0.2 b(3 psi) 6m/sec Pd 63od=2.5%(3 psi) 12m/sec Avoid installing flexible hoses with to tight a radius or where the hose is subject to, too much stretch Page 11
SIMPLAIR PIPING TOOL. JXT Company
SIMPLAIR PIPING INGERSOLL-RAND SIMPLAIR PIPING With push-in fittings and lightweight anodized aluminum pipe, a SimplAir system provides ideal connection throughout your entire air distribution system.
More informationINSTALLATION, OPERATION AND MAINTENANCE GUIDE
INSTALLATION, OPERATION AND Placement in Pipeline System When installing Process Development & Control s ElastoTITE Elastomer-Hinged Check Valves in a pipeline, a minimum of five pipe diameters should
More informationtubepress press procedure
tubepress press procedure tubepress 15mm up to 35mm tubepress 15 mm up to 35 mm 1. The tube ends must be clean with no scratches or grooves. Remove end caps. Cut tube to length. 2. Deburr tube inside and
More informationMaterials : Stainless steel ASTM A351 CF8M
Size : Ends : Min Temperature : Max Temperature : DN 1/2" to 3/4" Male, hose coupling - 10 C + 150 C Max Pressure : 16 Bars Specifications : Anti blow-out stem Locking device With hose coupling Materials
More informationS1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions
PREVIOUS REFERENCE NO. IMP02355 0231150/13 IMF0501ENISS2 CMGT S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions 1. Safety information 2. General product information
More informationk valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax
aylesbury k valve installation guide For valve sizes (DN): 2 (50)HF 2½ (65)SF 3 (80)RB IMPORTANT Please keep for future reference. PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER TO ANY DIAGRAMS BEFORE
More informationCOMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS
COMPACT TRIPLE WALL OUTLET STATION MODEL 6255-1 INSTALLATION AND OPERATING INSTRUCTIONS To assure safe operation and conformation to local fire codes, all Porter Outlet Stations are designed to be used
More informationPressure Dump Valve Service Kit for Series 3000 Units
Instruction Sheet Pressure Dump Valve Service Kit for Series 000 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00, 400, 500, and 700 applicator
More information// ADapters GUIDelines
// ADapters GUIDelines ADAPTER SELECTION Selection of an appropriate ALFAGOMMA adapter for a given application depends on the fluid system operating parameters listed below and the tube material and wall
More informationBSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions
1843950/3 IM-P184-03 ST Issue 3 BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation
More informationPressure Dump Valve Service Kit for Series 2300 Units
Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit
More informationInstrument Operating Manual
Instrument Operating Manual INDEX NO. SUBJECT PAGE 1 INFORMATION 3 2 SAFETY 4 3 INTENDED USE 4 4 COMMISSIONING & OPERATION 5 5 MAINTENANCE 6 2 INFORMATION The pressure gauges described in the operating
More informationCOMPRESSED AIR DISTRIBUTION SYSTEMS
Series COMPRESSED AIR DISTRIBUTION SYSTEMS 18 DESIGNING AN EFFICIENT COMPRESSED AIR DISTRIBUTION The main source of inefficiencies and problems affecting compressed air distribution systems is often the
More informationHM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions
0670350/4 IM-S03-11 ST Issue 4 HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information HM Series 3. Installation 4. Commissioning
More informationFT16 Ball Float Steam Trap Installation and Maintenance Instructions
1430050/1 IM-P143-04 ST Issue 1 FT16 Ball Float Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation ½" and ¾" shown 4 Commissioning
More informationDiscontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.
Powers Controls RV 201 Pressure Reducing Valves Description Features Product Numbers Dual Pressure PRV Technical Instructions Document No. 155-049P25 RV 201-1 Single Pressure PRV The RV 201 Pressure Reducing
More informationACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION
Application Note Doc. G8108-001 Rev. A - 23-Jul-02 ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION For more information regarding Digiquartz products contact: Paroscientific,
More informationTranslation of the original Operating Instructions for HKS rubber compensators
Because of their flexible elements and mechanisms, HKS rubber compensators are susceptible to damage of all types and adverse loads in operation. For reliable operation of a compensator and, thus, the
More informationSEries 29 Hydrant valves installation, operation & maintenance manual
Instruction for use Thank you for selecting an AVK product. With correct use, it will give long and reliable service. This manual has been prepared to assist you install, operate and maintain the valve
More informationMounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity
Type 4708-45 Supply Pressure Regulator with increased air capacity Translation of original instructions Mounting and Operating Instructions EB 8546-1 EN Edition March 2016 Note on these mounting and operating
More informationM45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions
BAC 13310 IM-P133-42 ST Issue 2 M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning 5.
More informationSERIES 500 VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTER
Man500e 09/2006 Installation Operation and Maintenance Instructions SERIES 500 VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTER INDEX 1. INSTALLATION 2. COMPRESSED AIR SUPPLY 3. FLOW MEASURE
More informationBTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions
1810050/4 IM-P181-03 ST Issue 4 BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation
More informationPRO SINK -R 1 and 2. Dilution system CONTENTS
PRO SINK -R 1 and 2 Dilution system CONTENTS 1.0 Product description 2 2.0 Warnings.. 3 3.0 Installation procedure 4 4.0 Plumbing connections 4 5.0 Technical features.. 5 6.0 Maintenance... 6 7.0 Troubleshooting......6
More informationInstallation, operation & maintenance manual - original version
Installation, operation & maintenance manual - original version AVK gate valves for water and wastewater Series 01, 02, 06, 12, 15, 18, 20, 26, 32, 33, 36, 38, 50, 55 and 636 COPYRIGHT AVK GROUP A/S 2018
More informationCA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions
1483250/3 IM-P148-10 ST Issue 3 CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions 1 General safety information CA16 and CA16S-14 ½" and ¾" 2 General product information 3 Installation
More informationPC3_ and PC4_ Pipeline Connectors
1283050/4 IM-P128-06 ST Issue 4 PC3_ and PC4_ Pipeline Connectors Installation and Maintenance Instructions 1. Safety information 2. Description PC30 shown 3. Installation 4. Welding of pipeline connector
More informationFILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS
FILTER REGULATORS MODEL NO: CAT155 & CAT156 PART NO: 3120169 & 3120170 FITTING & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS GC0117 INTRODUCTION Thank you for purchasing this CLARKE Filter/Regulator.
More informationCOMPRESSION TUBE FITTINGS
COMPRESSION TUBE FITTINGS 1/16 THROUGH 2 2 MM THROUGH 50 MM LET-LOK TUBE FITTINGS DESCRIPTION The HAM-LET GROUP has produced high quality tube and pipe LET-LOK HOW DOES IT WORK? A HAM-LET has gained an
More informationbook : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer
955751.book : t95575.fm Seite 1 Mittwoch, September 20, 2000 10:10 AM Avensys Exposed Single Lever Mixer 33 389 33 396 Installation Instructions and Operating Guide Please leave this document with the
More informationATS430 turbidity sensor Retractable insertion assembly
A MEASUREMENT & ANALYTICS INSTRUCTION ATS430 turbidity sensor Retractable insertion assembly Measurement made easy 1 Introduction This publication details installation procedures for the retractable insertion
More informationTD45 Thermodynamic Steam Trap Installation and Maintenance Instructions
0685255/1 IM-P068-47 ST Issue 1 TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation
More informationCRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES
CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES Sampling Valves Installation Commissioning and Operating Instructions SD IL 300 & SD IL 400 Inline Sampling Valve This
More informationThermocirc Installation and Maintenance Instructions
1570072/2 IM-P157-36 ST Issue 2 Thermocirc Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance
More informationCA10S, CA14 and CA14S Air and Gas Traps
1448150/9 IM-P148-13 ST Issue 9 CA10S, CA14 and CA14S Air and Gas Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5.
More informationInstallation and commissioning instructions 255 series and 256 series
Installation and commissioning instructions 255 series and 256 series Table of contents 1 General information... 3 1.1 About these instructions... 3 1.2 About this product... 3 1.3 Appropriate usage...
More informationCorrugated Hose Loop Calculations
Corrugated Hose Loop Calculations The loop installation is one of the most common application for metal hoses. It allows the flexible hose assembly to work properly. Care must always be exercised to ensure
More informationINFLATOR TDUX-IT-16 AND GAS CYLINDER E
INFLATOR TDUX-IT-16 AND GAS CYLINDER E7512-0160 Operating manual Inflator TDUX-IT-16 together with the special gas cylinder E7512-0160 is specifically designed for inflating TDUX duct seals. The inflator
More informationAir Operated Hydraulic Pumping Systems to 50,000 psi
High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air
More informationGLAUNACH THE SILENCER HANDBOOK INSTALLATION GLAUNACH GMBH ALL RIGHTS RESERVED -
GLAUNACH THE SILENCER HANDBOOK INSTALLATION GLAUNACH GMBH 2010 - ALL RIGHTS RESERVED - Part VII page 2 of 8 1. CHOOSING THE INSTALLATION LOCATION When selecting a suitable site for the installation of
More informationManual Actuated Boiler Blowdown Valves
Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety
More informationSpirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.
1849050/3 IM-P184-09 ST Issue 3 Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve Installation and Maintenance Instructions 1. Safety information 2. General product information 3.
More informationHYDRALECTRIC LIMITED,
Description:... 2 Applications:... 2 General Performance Data:... 2 Pressure Drop:... 3 General Construction Data:... 4 Dimensioning:... 4 Hose Data:... 5 Insulation:... 5 Ferrule Data:... 5 Installation:...
More informationHYDRALECTRIC LIMITED,
Description:...2 Applications:...2 General Performance Data:...2 Pressure:...3 General Construction Data:...4 Dimensioning:...4 Hose Data:...4 Ferrule Data:...5 Standards:...5 Installation:... Chemical
More informationUIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors
1130050/4 IM-P113-02 ST Issue 4 UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors Installation and Maintenance Instructions 1. Safety information 2. General product information
More informationINSTRUCTION MANUAL. January 23, 2003, Revision 0
INSTRUCTION MANUAL Model 810A In-Vitro Test Apparatus for 310B Muscle Lever January 23, 2003, Revision 0 Copyright 2003 Aurora Scientific Inc. Aurora Scientific Inc. 360 Industrial Parkway S., Unit 4 Aurora,
More informationML3M Monnier Miniature Compressed Air Lubricator
5041050/3 IM-P504-04 CH Issue 3 ML3M Monnier Miniature Compressed Air Lubricator Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation and commissioning
More informationBT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications
1800350/6 IM-P180-12 ST Issue 6 BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications Installation and Maintenance Instructions 1. Safety information 2. General
More informationPoollift Delphin. Version: February, 2015 MANUAL AND OPERATING INSTRUCTIONS
Poollift Delphin Version: February, 2015 MANUAL AND OPERATING INSTRUCTIONS Content 1. Introduction... 3 2. Technical Specifications... 3 Used materials... 3 3. Installation Instructions... 4 Fastening
More informationUser guide DIAPHRAGM SEALS. Industrial instrumentation for Pressure and Temperature
Industrial instrumentation for Pressure and Temperature ENG MI-SEP-ENG_0 10/2011 Copyright Nuova Fima S.p.A. All rights reserved. Any part of this publication should not be reproduced without a written
More informationLatvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.
Product Specification ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.0 bar Latvin Luxury Shower Panel ~ Fixing Centres 150mm +/- 10mm ~ Outlet size 1/2" Bottom Outlet Always maintain a
More informationAVK SERIES 601, 602, 603 & 605 UNIVERSAL COUPLINGS, ADAPTORS & END CAPS INSTALLATION, OPERATION & MAINTENANCE MANUAL
Instruction for use Thank you for selecting an AVK product. With correct use, the product is guaranteed to deliver a long and reliable service. This manual has been prepared to assist you with the installation,
More informationGeneral Performance Data Hose Ref Minimum Bend. Safety Pressure at 20 C (BAR) Working Pressure at. Flow Rate at 3 bar (lit/min) Working Pressure
The Classic range provides a safe and taint free conveyance of potable water supplies for Domestic and Commercial plumbing applications. The range is designed to achieve robust and flexible solutions with
More informationInstruction Manual. Standard Surge Eliminator. Standard X. Flushable X - X
Standard Surge Eliminator Standard 104052 - X Flushable 104053 - X - X Page 2 of 16 Issue: 2.3 Index Section 1.1 General Description 1.2 Operating Principle 1.3 Specification 1.4 Fitting Selection - Standard
More informationInstallation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series
Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator
More informationPANACEA P125 USER MANUAL
Basic Features Stainless steel body with 1.125 outside diameter. Will fit into wells down to 1-1/4 (schedule 80). Uses static water pressure to fill gas and sample return tubes. Maximum depth below ground
More informationM03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC
Before you start: Check the manifold box contents against the list below. Check the contents Flow gauges 1. Bar assembly with manual return valves 2. 2 x Auto air vent & drain hose attachments Optional
More informationMST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap
1250650/6 IM-P125-07 ST Issue 6 MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
More informationAquor House Hydrant V2
Aquor House Hydrant V2 IN-WALL OUTDOOR FAUCET SYSTEM FLUSH-MOUNT QUICK-CONNECT SELF-DRAINING ANTI-SIPHON NON-FREEZE VBH-SERIES AQUOR HOUSE HYDRANT V2: WALL HYDRANT / FREEZELESS SILLCOCK Freezeless sillcock
More informationdifferential pressure regulating valve - threaded
140-142 differential pressure regulating valve - threaded Introduction Differential pressure regulating valves (DPRV) maintain the differential pressure across a circuit or sub-branch at a set differential
More informationMaximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications
Outstanding performance in extremely low pressure and low pressure ranges from 0.003 to. Realizing high performance, energy saving, and compact size. Realize precise pressure control in a pressure range
More informationDN 1/2" to 2" Female BSP + 0 C C Max Pressure : 16 Bars Specifications : Stainless steel removable filter Female / Female With draining valve
Size : Ends : Min Temperature : Max Temperature : DN 1/2" to 2" Female BSP + 0 C + 120 C Max Pressure : 16 Bars Specifications : Stainless steel removable filter Female / Female With draining valve Materials
More informationCARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition
CARTRIDGE FILTERS TECHNICAL MANUAL MT 080 Installation, commissioning and maintenance instructions 08/02 Edition 1 2 CONTENTS 1.0 PAGE INTRODUCTION 1.1 MAIN FEATURES 1.2 OPERATION 1.3 CLOSING OF HEAD WITH
More informationMaterials : Dichromate zinc plated steel flanges or AISI 316
Size : Ends : Min Temperature : Max Temperature : DN 25 to 300 Flanges PN10/16-35 C + 90 C Max Pressure : 16 Bars (10 bars at 90 C) Specifications : Absorb vibrations and noise Linear and angular compansion
More informationSRI Jigger Tubes System
SRI Jigger Tubes System Design, Installation and Commissioning Manual (Abbreviated Version) INDEX This manual details how the SRI Jigger Tubes System can be tailored to suit the needs of a variety of vacuum
More informationSteam Trap BK 15 (DN40, DN 50) Original Installation Instructions English
Steam Trap BK 15 (DN40, DN 50) EN English Original Installation Instructions 810682-03 1 Contents Page Important Notes Usage for the intended purpose... 4 Safety note... 4 Danger... 4 Attention... 4 Application
More informationErection, maintenance and disposal Inverted installation. Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X
Erection, maintenance and disposal Inverted installation Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X 1 Important information The following instruction is valid for PEXLIM R-X, PEXLIM
More informationLEAK TROUBLESHOOTING
LEAK TROUBLESHOOTING If you suspect that your TMC isolation system is leaking (most often evidenced by going through air/nitrogen tanks too quickly), this guide will help you to find and fix the problem.
More informationIntroduction GUIDELINES FOR INSTALLATION PREINSULATED TUBE UNITHERM... Principal of Operation
GUIDELINES FOR INSTALLATION PREINSULATED TUBE UNITHERM... Introduction Principal of Operation The use of DEKORON/UNITHERM pre-insulated steam supply and condensate return lines offers cost savings features
More informationInstallation and Use Manual
Installation and Use Manual EMASMB & LMASMB Surface Mount Bottle Filling Stations Model EMASMB IMPORTANT THIS IS AN INDOOR APPLICATION ONLY! ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSONNEL.
More informationDN 3/8" to 4" Female BSP - 10 C C Max Pressure : 16 Bars up to DN 2 Specifications : Removable stainless steel filter Female / Female
Size : Ends : Min Temperature : Max Temperature : DN 3/8" to 4" Female BSP - 10 C + 120 C Max Pressure : 16 Bars up to DN 2 Specifications : Removable stainless steel filter Female / Female Materials :
More informationInstallation and Training Manual
AirForce1 Tower Kit Installation and Training Manual FuturEnergy Limited Ettington Park Business Centre Stratford upon Avon CV37 8BT +44 (0)1789 451070 Table of Contents Safety Notes... 3 Parts Supplied
More informationFIREFIGHTING EQUIPMENT
FIREFIGHTING EQUIPMENT User Manual ANTENOR 3000 Base or portable Trailer DOC 1974 En Rev.B - 22/10/13 Tel : 03 25 39 84 78 - Fax : 03 25 39 84 90 - Email : france@pok.fr - Web : www.pok.fr Identification
More informationDN 1/4" to 3" Female BSP - 10 C C Max Pressure : 25 Bars ( up to DN 1 ) Specifications : Anti blow-out stem With PTFE packing Full bore
Size : Ends : Min Temperature : Max Temperature : DN 1/4" to 3" Female BSP - 10 C + 120 C Max Pressure : 25 Bars ( up to DN 1 ) Specifications : Anti blow-out stem With PTFE packing Full bore Materials
More informationInstallation, Operation, and Maintenance Manual. Welker Constant Pressure Cylinder With Solid Indicator (Non-mixer) Model CP-30SI
Installation, Operation, and Maintenance Manual Welker Constant Pressure Cylinder With Solid Indicator (Non-mixer) Model The information in this manual has been carefully checked for accuracy and is intended
More informationRS Pro 300mm Long EPDM 15bar Braided Stainless Steel Hose RS Stock No
Datasheet RS Pro 300mm Long EPDM 15bar Braided Stainless Steel Hose RS Stock No.711-8476 Description: The Elite range provides robust and flexible solution for the safe conveyance and distribution of water
More informationTHE OWNER'S MANUAL IS IN TWO VOLUMES: VOLUME 2 TECHNICAL SPECIFICATIONS - ASSEMBLY PROCEDURE ZODIAC
CAUTION NOTICE: CAREFULLY READ THIS MANUAL BEFORE OPERATING YOUR BOAT. THIS OWNER S MANUAL IS IN TWO VOLUMES THAT MUST BE KEPT TOGETHER. THE OWNER'S MANUAL IS IN TWO VOLUMES: - VOLUME 1 DEALS WITH OPERATING
More informationSAILTEC, INC CONGER COURT, OSHKOSH, WI USA
OK to make this valve hand tight. Pin Mount Style Integral lies 4-5 Degrees above Horizontal. If you store your Hunter "bow down" you will get air-lock in the Integral. Slot Mount Style Pump Body "Down"
More informationDri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap
0509950/2 IM-P050-21 CH Issue 2 Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation and
More informationk valve ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF installation guide aylesbury For valve sizes (DN):
aylesbury k valve installation guide For valve sizes (DN): ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF IMPORTANT Please keep for future reference. PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER
More informationSeries SFD. Clean Air Filter. Variations. Made to Order. Type. Cartridge (replaceable element) Disposable (non-replaceable element) Up to 100
Clean Air Filter Variations SFD SFD SFD SFD Made to Order Type Disposable (non-replaceable element) Cartridge (replaceable element) Flow rate L/min (ANR) (at inlet pressure.7 MPa) Up to 6 Up to 8 Up to
More information09 - Choosing /sizing a cylinder and valve
- Choosing /sizing a cylinder and valve - Pipe flow resistence - Valve sizing - Cylinder sizing LII PIPE FLOW RESISTENCE Flow rate Qn Flow rate is calculated as the volume at normal conditions ( atmospheric
More informationAVM7 Stainless Steel Thermostatic Air Vent
1231850/4 IM-P123-23 ST Issue 4 AVM7 Stainless Steel Thermostatic Air Vent Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationKBV21i and KBV40i Air Actuated Boiler Blowdown Valves
4059051/1 IM-P405-48 AB Issue 1 KBV21i and KBV40i Air Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationData sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119
Pressure switch type CS December 2001 DKACT.PD.P10.A2.02 520B1119 Introduction Pressure switch type CS is part of the Danfoss pressure control range. All CS pressure switches have a built-in pressure-operated,
More informationBIMBAR INFLATABLE PACKERS AND ACCESSORIES
BIMBAR INFLATABLE PACKERS AND ACCESSORIES Geopro supplies a complete range of inflatable packers in nine different diameters from 28 up to 170mm. All our packers made of BIMBAR rubber technology are reinforced
More informationDri-Line Mk3 Monnier Compressed Air Drain Trap
5044050/2 IM-P504-24 CH Issue 2 Dri-Line Mk3 Monnier Compressed Air Drain Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation and Operation
More informationKAX VALVE ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF INSTALLATION GUIDE AYLESBURY FOR VALVE SIZES (DN):
AYLESBURY KAX VALVE INSTALLATION GUIDE FOR VALVE SIZES (DN): ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF IMPORTANT PLEASE KEEP FOR FUTURE REFERENCE. PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER TO ANY
More informationDISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING COMPRESSORS
DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING COMPRESSORS SA INTRODUCTION These instructions are for the maintenance personnel for maintenance and repair of compressors series SA. Disassembly and
More informationSCA Series Inverted Bucket Steam Traps
0770050/5 IM-P077-06 ST Issue 5 SCA Series Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning
More informationCalculation tables for thermal expansion.
Calculation tables for thermal expansion www.sanha.com 2 Contents Subject Page 1 THERMALLY INDUCED CHANGES IN LENGTH 5 1.1 Thermal expansion 6 1.1.1 NiroSan -, NiroSan -ECO system pipes and copper pipes
More informationPN LINE. Technical remarks PN 11 PN 13 PN 14 PN 15 PN 17 PN 18 PN 20 PN 23 PN 25 PN 26 PN 27 PN 28 PN 29 PN 37 PN 38 PN 39 PN 40 PN 43 PN 10 8_9 10_12
PN LINE PN 11 PN 13 PN 14 PN 15 PN 17 PN 18 PN 20 PN 23 PN 25 PN 26 PN 27 PN 28 PN 29 PN 37 PN 38 PN 39 PN 40 PN 43 PN 10 Technical remarks PN 11 PN 13 PN 14 PN 15 PN 17 PN 18 PN 20 PN 23 PN 25 PN 26 PN
More informationIMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION
IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION This Fitting Guide is designed to assist in the Installation of your Reverse Osmosis System. Some of the parts that are supplied with each system may
More informationCRANKSET 1 - TECHNICAL SPECIFICATIONS. 44,5 mm 8 mm
CRANKSET THIS TECHNICAL MANUAL IS INTENDED FOR USE BY PROFESSIONAL MECHANICS. Anyone who is not professionally qualified to assemble bicycles should not attempt to install and operate on the components
More informationPANACEA P100 LOW PRESSURE USER MANUAL
Basic Features Stainless steel body with 7/8 outside diameter. Will fit into wells down to 1 (schedule 80). Uses static water pressure to fill gas and sample return tubes. Maximum depth below ground surface
More informationS1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators
0231150/8 IM-P023-55 ST Issue 8 S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationAirmate TS1.5/6 Oil-less Air Compressor
Please dispose of packaging for the product in a responsible manner. It is suitable for recycling. Help to protect the environment, take the packaging to the local amenity tip and place into the appropriate
More informationKBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions
4059051/3 IM-P405-48 EMM Issue 3 KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4.
More information30T A/Manual Hydraulic Shop Press
30T A/Manual Hydraulic Shop Press Operation Manual 1 1. Important Information 1.1 Safety Information 1.1.1 Hazard Symbols Used in the Manuals This manual includes the hazard symbols defined below when
More informationInstallation Instructions for the AlphaDeck Staging System
Installation Instructions for the AlphaDeck Staging System Step 1 - Preparation A. Before setting up this system, determine the location of the stages and all the parts you will need. B. Read through the
More information