Erection, maintenance and disposal Inverted installation. Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X
|
|
- Primrose Scott
- 5 years ago
- Views:
Transcription
1 Erection, maintenance and disposal Inverted installation Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X 1
2 Important information The following instruction is valid for PEXLIM R-X, PEXLIM Q-X and PEXLIM P-X surge arresters for inverted mounting. For other installations, e.g. vertical upright mounted arresters, other instructions are valid. Serious material damage, severe personal injury and/or death can be the result of not following this instruction. Therefore, the personnel responsible for the installation of the equipment shall read and follow the instruction carefully. Handling and maintenance of all the surge arresters described in this instruction must be done by personnel trained for this type of work. WRNING! ll work related to the surge arresters shall be made with disconnected and earthed conductors. Follow all regulations and rules stated by international and national safety regulations. Normally, surge arresters operate at a high voltage. Therefore, they must be installed in such a way that only qualified personnel has access to it. 2
3 Table of contents hapter Page Important information General Unpacking and checking on arrival Lifting the surge arrester Line terminal Grading ring Insulating base, earth terminal and surge counter Mounting of arrester units Installation on structure onnection of conductors Maintenance and checking Disposal
4 1. General Surge arresters are dimensioned for a Maximum Permissible Service Loading of 2500 Nm (PEXLIM P-X and PEXLIM Q-X) and 1500 Nm (PEXLIM R-X) defined as: The bending moment (in Nm) acting at the base of a surge arrester resulting from the vector sum of all possible loads (eg. the line conductor load, the wind load, the arrester weight and earthquake) in the direction perpendicular to the arrester axis. Its design admits a visible deflection at normal load. It is recommended to connect the line conductor vertically to lower the mechanical stresses. Surge arresters are dimensioned for an operating voltage that is equal to or lower than the continuous operating voltage Uc (as per IE) or MOV (as per NSI). The Uc- or MOV-value is shown on the rating plate. To obtain the best protection performance, the surge arrester must be connected with as short leads as possible. However, the mechanical aspects must be taken into consideration! Special instruments or tools are not required for assembly and erection of the surge arrester. It is recommended to assemble all details of a complete arrester before mounting it on the structure. 2. Unpacking and checking on arrival packing list is attached to each package. When unpacking, the contents of the cases shall be checked against respective packing list. If there is any shortage or parts damaged during transport, the BB representative should be informed immediately. 4
5 3. Lifting the surge arrester Lift the surge arrester by the line terminal or the flange. Use of shackles or lifting eye bolts are recommended. See fig Range of weights of the surge arresters is kg. Do not lift the surge arrester by its insulator! Fig Line terminal djust the line terminal to desired position. Recommended tightening torque is 100 Nm. (M20). See fig Line terminal with clamp: when the line conductor is to be connected, assemble the clamp according to the assembly instruction delivered with it. 100 Nm M20 Fig 4.1 Fig 4.2 5
6 5. Grading ring When a grading ring is supplied, it must be fitted to the arrester, otherwise the correct performance is not guaranteed. If the surge arrester has a grading ring, assemble the stays with the ring/rings according to table 5.1. The recommended tightening torque for M10 bolts are 49 Nm. M6 screws are tightened with a screw driver. Table 5.1. Grading ring arrangement Type designation Mounted on the top flange of the top unit Type designation Mounted on the top flange of the top unit PEXLIM P132-XH170 P150-XH170 PEXLIM P132-XV170 P192-XV170 PEXLIM P192-XM245 PEXLIM Q180-XH245 Q210-XH245 PEXLIM Q216-XH245 Q228-XH245 PEXLIM Q180-XV245 Q228-XV245 B PEXLIM P180-XH245 P228-XH245 PEXLIM P210-XV245 P228-XV245 PEXLIM P180-XV245 P198-XV245 B PEXLIM Q216-XH300 Q276-XH300 PEXLIM Q216-XV300 Q276-XV300 PEXLIM Q258-XH362 Q288-XH362 PEXLIM P216-XH300 P276-XH300 PEXLIM P216-XV300 P276-XV300 PEXLIM P258-XH362 P288-XH362 B B PEXLIM Q258-XV362 Q288-XV362 PEXLIM Q330-XH420 Q360-XH420 PEXLIM P258-XV362 P288-XV362 PEXLIM P330-XH420 P360-XH420 PEXLIM R090-XV123 R102-XV123 PEXLIM R108-XH145 R120-XH145 PEXLIM R108-XV145 R120-XV145 PEXLIM Q090-XV123 Q096-XV123 PEXLIM Q108-XH145 Q120-XH145 PEXLIM Q108-XV145 Q120-XV145 PEXLIM R132-XH170 R150-XH170 PEXLIM R162-XV170 R192-XV170 BPEXLIM Q132-XH170 Q150-XH170 PEXLIM Q132-XV170 Q192-XV170 PEXLIM Q192-XM245 B 6
7 Grading ring according to table 5.1. (The numbered circles refer to the mounting alternatives in the right column) 1 M6x12 Mounting 2 B 49 Nm M10 M10x25 Washer 3 M6x Nm M10 M10x40 Washer 7
8 6. Insulating base, earth terminal and surge counter This instruction covers insulating bases 1HS and -B. 1HS B is identical to - except that the bolts used are of UN-type. If you have purchased -B, please use the bolts sizes indicated in brackets. In case where another insulating base is to be fitted, the installation instructions included with the delivery shall be followed. The bolt M12x45 (1/2 x 45) is only used to fix the earth terminal. If diagnostic indicator EXOUNT-II is to be mounted, the longer bolt M12x50 (1/2 x 51) shall be used instead. In this case the M12x45 (1/2 x 45) bolts is not required and can be discarded. Recommended tightening torque is 84 Nm. Fig 6.1 8
9 1) 1) 1) Requirements on M12 (1/2 ) bolts for anchoring to the structure: These bolts are not supplied with the arrester. Recommended tightening torque: ccording to strength class, however, max. 120 Nm. Strength class: 8.8 or higher. Material: Hot dip galvanized steel or waxed stainless steel. Required threaded grip length: 15 to 20 mm. washer shall be placed under the bolts head. Fig. 6.2 With earth terminal and/or surge counter EXOUNT- Fig. 6.3 With diagnostic indicator EXOUNT -II For installation of diagnostic monitor EXOUNT II, see assembly instruction included with it. For installation of a surge counter (EXOUNT ) ensure that: The arrester is insulated from the structure by an insulating base. The length of the conductor between the arrester and the surge counter shall not be less than 0.5 m and shall as a recommendation, not exceed 5 m, see figure 6.2. Longer lengths up to 10 m could be used, but please note that longer connection leads means a disadvantage from protection point of view since its inductance is added in series with that of the arrester. The conductor shall be insulated for 5xL kv (LIWL), where L is the conductor length in meter as shown in figure 6.2. (This could be achieved by using a bare conductor on insulators or a cable). The surge counter is installed according to the supplied assembly instruction. 9
10 7. Mounting of arrester units Multi-unit arresters must be erected with their units in the correct order as shown in fig ll units in an arrester have the same serial number with a consecutive suffix number to identify their position, i.e. top-unit = N.../1, next unit = N.../2, marked on the flanges. The position is always with respect to the high voltage connection i.e. high voltage connection is made to the top unit. Please note that arresters intended for inverted installation has an H at the end of the type designation. Main rating plate: 84 Nm M12 3 x M12x40 3 x M12 Nut 6 x Washer Engraved text on the flanges: Surge rrester PEXLIM (type designation) N. XXXXXXXX/2 TOP UNIT Surge rrester PEXLIM (type designation) N. XXXXXXXX/1 84 Nm M12 4 x M12x20 4 x washer Fig
11 8. Installation on structure Note the lifting instructions in paragraph 3. Fit the arrester to the structure according to fig. 8.1 if insulating base is not used. Otherwise se paragraph 6. Drilling plan is shown in fig nchoring bolts and nuts are not provided with the arrester. Ensure that the chosen bolts have sufficient mechanical strength, in order to handle the loads described in paragraph 1. Fig 8.1 Without insulating base Fig 8.2 Drilling plan 9. onnection of conductors ll earth terminals are compatible with both copper and aluminium conductors, as well as all line terminals except 1HS L and -N which cannot be combined with copper conductors. In these cases use stainless steel washers between the aluminium terminal and the copper conductor. 11
12 9.1. onnection of line conductor The line conductor should be as short as possible. onnect the line conductor to the line terminal in such a way that the possible bending moment under any circumstances does not exceed the maximum value! (See table 9.1) Maximum diameter of the conductor is 34 mm (for line terminal with clamp). The surge arrester design admits a visible deflection, which e.g. can appear due to the mechanical loading of the line conductor. This will not damage the arrester as long as the bending moment does not exceed the maximum usable load shown below in table 9.1. Warning! Faulty connection onnection of the conductor must be done correctly. For vertical mounting the conductor must be fixed edge to edge with the clamp Fig. 9.1 onnection of single line conductor can be done from top or side. Fig. 9.2 onnection of double line conductor can be done from top or side. Service loading Maximum Permissible Service Loading (MPSL) Definitions as per amendment (no 2) to IE Dynamic bending moment Table 9.1 PEXLIM R-X 1500 Nm 2500 Nm PEXLIM Q-X PEXLIM P-X 2500 Nm 4000 Nm 12
13 9.2. onnection of earth conductor onnect the earth terminal to the common earth system with as short conductor as possible. The earth conductor cross-section shall be chosen in accordance with local regulations and earth fault current requirements. The earth terminal (with clamp) accommodates conductor sizes from 8 mm to 34 mm diameter. For assembly of clamp see figure 9.3. Fig
14 10. Maintenance and checking properly chosen and installed PEXLIM surge arrester is maintenance-free, when operating under normal operating conditions, during its lifetime. However, the tightening torques on terminals shall be checked and if necessary adjusted to the right value at inspections of the plant. leaning PEXLIM arresters do not require any cleaning of the external surfaces for their lifetime. The surface may appear to be dirty, but this is of no significance. Should however for any reason the arresters be subjected to live washing observe the following in addition to normal precautions for live washing: rrester insulators usually have shorter flash-over distances than other insulators for the same system voltage, which means a higher risk for external flash-over during washing. rresters must be spray-washed evenly in order to avoid overheating. Do not use high pressure on the water. For extreme environments (e.g. high acidity, cement) please contact BB. General Should a routine check be desired, the only reliable method is to measure the resistive component of the leakage current periodically. For this purpose, use of BB Leakage urrent Monitor, LM, together with BBs clip-on current meter or BB diagnostic indicator EXOUNT-II is recommended. For description of the LM/EXOUNT-II and measurement procedures, please refer to relevant catalogues. 14
15 11. Disposal Surge arresters, type PEXLIM, consists of an outer insulator made of nonhalogenated silicon rubber with end fittings and terminals made of stainless steel alternatively aluminium or copper. The inside of the arrester consists of metal oxide varistors, steel spacers, aluminium components, glass fibre loops and aramide fibres. The metal-oxide varistors are sintered bodies composed mainly of ZnO (90 %), with the following other substances in more than 1 % weight (in accordance with the common market rules for hazardous components): Bi 2 O 3 Sb 2 O 3 Hazardous substances (according to the ouncil Directive 91/689/EE on hazardous waste), existing in more than 0,1 % weight but less than 1 % are NiO r 2 O 3 In addition the metal-oxide varistors are coated with a thin glass layer (<0,1 % weight) containing PbO. When the arrester is disposed of the silicone parts will eventually decompose into SiO 2 and O 2 and may in the long run expose the metal oxide part. s the substances of the sintered metal oxide varistors exists in an oxidized state, a leaching test according to EP-test (Federal Register /vol. 45, No 98 / Rules and Regulation), has shown that the sintered bodies may be disposed of without violating the EE Directive. 15
16 Producer: SWG/F MF NOTE! BB Power Technology Products B is working with continous improvements, therefore we reserve the right to change design and specifications without notice. BB Power Technology Products B High Voltage Products Surge rresters ssembly instruction: 2528en Edition 3, SE LUDVIK, SWEDEN Tel: +46 (0) Telefax: +46 (0) arresters.div@se.abb.com Internet:
S Surge Arresters
Surge Arresters UltraSIL Polymer-Housed VariSTAR Type US, UH, and UX Station-Class Surge Arresters Installation and Maintenance Instructions Service Information S235-88-1 Contents Product Information...........................1
More informationType POLIM -D..PI-2 Type POLIM -D..PI-3
Operating instructions Surge arrester Type POLIM -D..PI-2 Type POLIM -D..PI-3 Publication No. 1HC0019085 AH With ABB metal-oxide resistors Without gaps For medium voltage metal enclosed switchgear with
More informationOperating instructions. Surge arrester Type MVR
Operating instructions Surge arrester Type MVR Content 1 About this document...3 1.1 Validity...3 1.2 Target group...3 2 Safety...3 2.1 Symbols and advices...3 2.2 Basic safety precautions...4 2.2.1 Product
More informationOperating instruction
Operating instruction MV, XV, HG, HP, RKO, D2G, TV, BV, WB & SLV 1 Introduction 2 2 Stafsjö s knife gate valves 2 3 Technical information 2 3.1 Pressure test 2 3.2 Labelling 2 4 Storage 3 5 Transportation
More informationOperating instructions. Surge arrester Type POLIM -I, -S, -H
Operating instructions Surge arrester Type POLIM -I, -S, -H Content 1 About this document...3 1.1 Validity... 3 1.2 Target group... 3 2 Safety...3 2.1 Symbols and advices... 3 2.2 Basic safety precautions...
More informationManual for the. Installation. Use and Maintenance. "Söll-GlideLoc" fall arrest system. Ho-Ver turn table
Manual for the Installation Use and Maintenance "Söll-GlideLoc" fall arrest system of Ho-Ver turn table Part. No. 22322 in conjunction with Söll - ladders/vertical guide rails tested in accordance with
More informationOperating Instructions
Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table
More informationINSTRUCTION MANUAL Pressure Relief Device LPT
INSTRUCTION MANUAL Pressure Relief Device LPT 5COV475800 LPT REV00 CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment operation 2 2 PRESSURE RELIEF
More informationOperating Instructions
Operating Instructions Ex d Enclosures in Light Metal / Flameproof Encapsulation > 8265/0 Empty Enclosure > 8265/4 controller, installed in Ex e enclosure > 8265/5 controller Contents 1 Contents 1 Contents...2
More informationPULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING
PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING Please Note: Ranges above 500mbar are designed and manufactured in accordance with sound engineering
More informationCOOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions
Surge Arresters MN235005EN Lorem ipsum dolor sit Amat Effective February 2016 Supersedes IS235-35-1 June 2014 COOPER POWER SERIES UltraSIL polymer-housed VariSTAR surge arrester IEC 60099-4 for MV systems
More informationEffective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions
Surge Arresters MN235014EN Effective January 2017 Supersedes July 2011 (I235-84-1) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions COOPER POWER SERIES Olean, NY USA Va ristar
More informationFurther technical information is available on
1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,
More information2-1- Shipping Receiving Lifting Location on Site Installation Stages 6
NEUTRAL GROUNDING RESISTORS INSTALLATION, OPERATION & MAINTENANCE MANUAL Contents 1- SAFETY INSTRUCTIONS... 3 1-1- Compliance with Instructions in this Manual. 3 1-2- Guidance Notes Installation.... 3
More informationRapidmain Installation Guide
Rapidmain Installation Guide Aluminium Compressed Air Pipe Work Installation Guide Trafalgar Court, Waterloo Ind Estate, Widnes Cheshire. UK. Ref: Rapidmain installation guide 4b Index 1. Rapidmain fittings:
More informationInstallation and Operating Instructions Bypass Flow Meter DST
Installation and Operating Instructions Bypass Flow Meter DST DST_gb_A4_1.0.doc Version 1.0 1 von 10 Contents 1. Foreword... 3 2. Safety... 3 2.1. Symbol and meaning... 3 2.2. General safety directions
More informationBRAKE WINCH RUP 503-[T/BT] EQUIPMENT FOR LIFTING LOADS. AT 053-[T/BT] xx
Reference number: BRAKE WINCH RUP 503-[T/BT] EQUIPMENT FOR LIFTING LOADS DESIGNATED USE The brake winch RUP 503-[...]T series is a load lifting / lowering device. Device is equipped with safety brake for
More informationHoist Ring Forged Hoist Ring Machined Hoist Ring (Metric) Hoist Ring Swivel Shoulder Eyebolts JD Weld-On Alloy Lifting
Hoist Ring Forged........................... 94 Hoist Ring Machined........................ 95 Hoist Ring (Metric).......................... 96 Hoist Ring Swivel........................... 97 Shoulder
More informationSG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection
SG33KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG33KTL-M. In no case shall this guide substitute for the user manual or related notes on
More informationPressure relief valve
Pressure relief valve Operating manual Series DHV 712 R Version BA-2016.01.19 EN Print-No. 300 472 TR MA DE Rev001 ASV Stübbe GmbH & Co. KG Hollwieser Straße 5 32602 Vlotho Germany Phone: +49 (0) 5733-799-0
More informationSG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection
SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on
More informationType BBS-03, BBS-05, BBS-06, BBS-25
Type BBS-03, BBS-05, BBS-06, BBS-25 Sterile connection elements Sterile Verbindungselemente Raccords union stériles Operating Instructions Bedienungsanleitung Manuel d utilisation 1. THE OPERATING INSTRUCTIONS
More informationMagnetic level switch type MR783 Instruction Manual
Magnetic level switch Magnetic level switch type MR783 1. DESCRIPTION page 3 1.1 Operation page 3 1.2 Application page 3 1.3 Description page 3 2. SPECIFICATIONS page 3 2.1 Service Conditions page 4 2.2
More informationAgilent 1220 Infinity II LC Mobile Upgrade Kit
Agilent 1220 Infinity II LC Mobile Upgrade Kit Note 1220 Infinity II LC Mobile Upgrade Kit This note describes the procedures to install an Mobile Upgrade kit to an existing Agilent 1220 Infinity II LC.
More informationTranslation of the original Operating Instructions for HKS rubber compensators
Because of their flexible elements and mechanisms, HKS rubber compensators are susceptible to damage of all types and adverse loads in operation. For reliable operation of a compensator and, thus, the
More informationOperating instruction for the quick-change tap holders type:
type: HF 20 HF 30 Date of edition: 15.07.2008 Stage of alteration: 4 Please keep this for future use! Contents: 1 Application range, safety instructions and technical data... 3 1.1 Application range,
More informationPressure relief valve
Pressure relief valve Operating manual Series DHV 718 Version BA-2016.01.11 EN Print-No. 300 524 TR MA DE Rev001 ASV Stübbe GmbH & Co. KG Hollwieser Straße 5 32602 Vlotho Germany Phone: +49 (0) 5733-799-0
More informationManual winch MANISTOR 100 and 200
Manual wall winch Manual winch MANISTOR 100 and 200 Instruction manual UK 173-192.10-3 PRODUCT DEVELOPED AND MANUFACTURED ACCORDING TO NF EN 13157 STANDARD REGISTERED DESIGN To ensure the constant improvement
More informationFigure 1 - Parts Identification. Copyright 2002, DB Industries, Inc.
User Instruction Manual Zorbit Energy Absorber Kits for Horizontal Lifeline Systems This manual is provided as the Maunfacturer s Instructions, and should be used as part of an employee training program
More informationCOOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.
Surge Arresters MN235022EN Effective November 2016 Supersedes July 2011 (S235-87-1) COOPER POWER SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions 0.5 0.866
More informationS Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection
Surge Arresters VariSTAR Type AZF Intermediate lass Installation and Maintenance Instructions Service Information S235-70-1 ontents Product Information.......................... 1 General Application Recommendations..........
More informationDT400/436 Tee Connector Installation Instructions
Connectors Lorem ipsum and dolor Splices sit Amat Effective September 2014 Supersedes IS550-30-1 March 2011 MN650001EN DT400/436 Tee Connector Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION
More informationMANUAL. Sesame. Thermoplastic Tank Technologies
MANUAL Sesame Thermoplastic Tank Technologies INSTALLATION AND USER GUIDE CONTENT 1. GENERAL 3 2. IMPORTANT 3 3. INSTALLATION EXPANSION VESSEL 4 4. USE EXPANSION VESSEL 5 5. AIR CELL REPLACEMENT 5 5.1
More informationSIGNATURE DEF REELS Models: Bare Reel Reel Reel Reel
SERVICE BULLETIN SB2023 Rev C 7/11 SIGNATURE DEF REELS Models: 2400-006 Bare Reel 2400-007 16 Reel 2400-008 20 Reel 2400-009 30 Reel Thoroughly read and understand this manual before installing, operating
More informationINSTALLATION PROCEDURE FOR OPGW FIBER OPTIC CABLES
Page 1 of 15 INSTALLATION PROCEDURE FOR OPGW FIBER OPTIC CABLES Page 2 of 15 1. PURPOSE 2. SCOPE 3. REFERENCES 4. GENERAL INDEX 5. PROCEDURES 5.1 Line survey 5.2 Transport, loading, unloading and storage
More informationPRODUCT CARD WALL MOUNTED SIDE FOLDED BASKETBALL CONSTRUCTION PROJECTION: FROM 1,2 TO 2,45 M
PRODUCT CARD WALL MOUNTED SIDE FOLDED BASKETBALL CONSTRUCTION PROJECTION: FROM 1,2 TO 2,45 M I. List of components... 2 II. Complimentary products... 2 III. Product description... 3 IV. Product Purpose...
More informationMSA Latchways Ladder System
Systems overview 1 of 13 Important information Individuals or organisations carrying out the installation of a MSA Latchways ladder fall protection system shall read, understand and follow these instructions
More informationFloor Mount Socket. T: +44 (0) F: +44 (0)
G-Davit : Floor Mount Socket USER INSTRUCTION MANUAL A davit socket for installation bolted to a high strength flooring material. Suitable for both fall arrest use and lifting. EN795 Class B, PPE Anchor
More information// ADapters GUIDelines
// ADapters GUIDelines ADAPTER SELECTION Selection of an appropriate ALFAGOMMA adapter for a given application depends on the fluid system operating parameters listed below and the tube material and wall
More informationPRODUCT CARD WALL MOUNTED FIXED BASKETBALL CONSTRUCTION PROJECTION: FROM 1,00 TO 2,25 M
PRODUCT CARD WALL MOUNTED FIXED BASKETBALL CONSTRUCTION PROJECTION: FROM 1,00 TO 2,25 M I. List of components... 2 II. Complimentary products... 2 III. Product description... 3 IV. Product Purpose... 3
More informationOperating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073
Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4
More informationKTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS
Before installation these instructions must be fully read and understood SECTION 1 - STORAGE 1.1 Preparation and preservation for storage All valves should be properly packed in order to protect the parts
More informationRolled Rotary Ball Screw
51E Rolled Rotary Ball Screw Model BLR End cap Collar Seal Spacer Ball End cap Screw shaft Outer ring Ball screw nut Retainer Outer ring Ball Fig.1 Structure of Large Lead Rotary Nut Ball Screw Model BLR
More informationInstallation, Operating, Inspection and Maintenance Instructions Ladder Climber s Safety System. Warning
OWNER'S MANUAL Installation, Operating, Inspection and Maintenance Instructions Ladder Climber s Safety System Model # s: 6000, 6001, 6010 Warning You must read and fully understand all instructions, or
More informationAVK SERIES 601, 602, 603 & 605 UNIVERSAL COUPLINGS, ADAPTORS & END CAPS INSTALLATION, OPERATION & MAINTENANCE MANUAL
Instruction for use Thank you for selecting an AVK product. With correct use, the product is guaranteed to deliver a long and reliable service. This manual has been prepared to assist you with the installation,
More informationRepair instructions. Pivot bushing replacement. XL-AS10001RM-en-DE Rev B
Repair instructions Pivot bushing replacement XL-AS10001RM-en-DE Rev B Table of contents Table of contents 1 General information... 3 1.1 Safety information...3 1.2 Legal information...4 1.3 Order and
More informationContents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520
Operating instructions Contents EN Pressure switch, heavy-duty version Model PSM-520 1. General information 2. Design and function 3. Safety 4. Transport, packaging and storage 5. Commissioning, operation
More informationLow Wind High Yields Series
Low Wind High Yields Series Wind Turbines USER S MANUAL Introduction Low Wind High Yields Series rotor blades apply the latest advanced thermoplastic engineering and are manufactured by precision injection
More informationNeotecha SAPRO - Aseptic sampling valve SV Installation, operation and maintenance instructions
Before installation these instructions must be fully read and understood 2 Safety Please read these instructions carefully. 2.1 General danger potential Not paying attention to this instruction Incautious
More informationInstruction Manual. AlfaLavalSBAntiVacuumValve ESE02960-EN Original manual
Instruction Manual AlfaLavalSBAntiVacuumValve ESE02960-EN3 2017-11 Original manual Table of contents The information herein is correct at the time of issue but may be subject to change without prior notice
More informationTRAVSMART permanent single-cable horizontal lifeline system
The Travsmart single-line system provides a smooth travel. It allows the traveler to move freely over the intermediate anchors, minimizing wear and eliminating user assistance. The user s hands remain
More informationAllspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)
Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk SOFT LINE CUTTER SL55 PRODUCT CODE No. 980504 INSTRUCTIONS FOR INSTALLATION,
More informationInstallation & Operation Manual Proven Quality since 1892
Content 1. ERIKS operating companies 2. Product description 3. Requirements for maintenance staff 4. Transport and storage 5. Function 6. Application 7. Installation 8. Maintenance 9. Service and repair
More informationThe cost-efficient fixing for flexible use in non-cracked concrete VERSIONS. zinc-plated steel stainless steel hot-dip galvanised steel
The cost-efficient fixing for flexible use in non-cracked concrete VERSIONS APPROVALS zinc-plated steel stainless steel hot-dip galvanised steel BUILDING MATERIALS Approved for: Concrete C20/25 to C50/60,
More informationLoad Ring bolted > VWBG < in pink
RUD-Art.-Nr.: 8503693-EN / 03.014 Load Ring bolted > VWBG < in pink EN Safety instructions This safety instruction/declaration has to be kept on file for the whole lifetime of the product. Translation
More informationInstruction Manual Contact Pressure Vacuum Gauge
MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationInstallation, operation & maintenance manual - original version
Installation, operation & maintenance manual - original version AVK gate valves for water and wastewater Series 01, 02, 06, 12, 15, 18, 20, 26, 32, 33, 36, 38, 50, 55 and 636 COPYRIGHT AVK GROUP A/S 2018
More informationMSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection
1170850/1 IM-P117-36 ST Issue 1 MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection Installation and Maintenance Instructions 1. Safety information 2. General product information
More informationWellhead Mast. Installation and Operation Guide. Nanometrics Inc. Kanata, Ontario Canada
Installation and Operation Guide Nanometrics Inc. Kanata, Ontario Canada 2001 2005 Nanometrics Inc. All Rights Reserved. Installation and Operation Guide The information in this document has been carefully
More informationIt is essential that the maintenance staff is qualified for electrical works and follows safety procedures.
MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained
More informationVersie Date: USAGE AND SAFETY MANUAL SPREADERBEAMS
USAGE AND SAFETY MANUAL SPREADERBEAMS 1. INTRODUCTION: The spreader system exists of modular traverses with possibility of different spans. Each spreaderbeam exists of two head section complete with shackles
More informationMounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity
Type 4708-45 Supply Pressure Regulator with increased air capacity Translation of original instructions Mounting and Operating Instructions EB 8546-1 EN Edition March 2016 Note on these mounting and operating
More informationVertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment
3M Occupational Health and Environmental Safety Fall Protection Equipment Ladder Climb Vertical Lifeline User Instructions User Instructions for the 3M TM Ladder Climb Vertical Lifeline System. Important:
More informationHand winch MANIBOX GR
Hand spurgear winch Hand winch MANIBOX GR Instruction manual UK 34-331.09/9 PRODUCT DEVELOPED AND MANUFACTURED ACCORDING TO STANDARD NF EN 13157 In an endeavour to improve its products, HUCHEZ reserves
More informationCOOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN
Surge Arresters MN235006EN Effective August 2016 Supersedes June 2014 (S235-35-1) COOPER POWER SERIES UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions DISCLAIMER
More informationPLAQUE MFM0680 UNDERWATER LIGHT. Operating Instructions
PLAQUE MFM0680 UNDERWATER LIGHT Operating Instructions CONTENTS Preface... 3 Features... 3 Precautions... 3 Controls and Connectors... 4 Underwater Light PLAQUE MFM0680... 4 Power Supply Unit MPS021000
More informationParallel grippers HGPM, micro
Key features G6: G8: G9: stroke compensation clamping spigot flange mounting At a glance Compact, handy design With open or closed gripper jaws Versatility thanks to externally adaptable gripper fingers
More informationOFFICINE OROBICHE S.p.A. 1/9
OFFICINE OROBICHE S.p.A. 1/9 INSTRUCTIONS MANUAL FOR LEVEL SWITCHES SERIES 7000 mod. 7250 AND 7400 Electric 1. INSTRUMENT DESCRIPTION Series 7000 level switches have been designed for external lateral
More informationAir Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB
Air Sensor SAC Ex Manual AQ Elteknik AB ATEX Air Sensor SAC Ex ATEX Certified model Manual version 2.1 April 2014 AQ Elteknik AB 2 Table of contents 1. Manufacturer information... 4 Manufacture Declaration
More informationSempell High Pressure Forged Check Valves Forged steel, swing check and tilting disc configuration
Installation and Maintenance Instructions Handling requirements A - Packed valves Pallets: Lifting and handling of the packed valves in pallets will be carried out by a fork lift truck, by means of the
More informationPneumatic spool valve islands
Pneumatic spool valve islands P7.GB.R MEGA SPOOL VALVE ISLANDS MEGA pneumatic spool valve islands offer maximum performance along with flexibility, easy installation and simple operation. Due to their
More informationFigure 1 - Parts Identification
Instructions for the following series products: Zorbit Energy Absorber Kits (See back page for specific model numbers.) User Instruction Manual Zorbit Energy Absorber Kits for Horizontal Lifeline Systems
More informationUser Manual 1792 Standing Seam Metal Roof Retractable Swivel Anchor
1 User Manual 1792 Standing Seam Metal Roof Retractable Swivel Anchor This manual is intended to meet the Manufacturer Instructions as required by ANSI Z359.1 and should be used as part of an employee
More informationInstallation and Operation Instruction Manual
Installation and Operation Instruction Manual Toggle Lok Anchor - Model #7442 Portable Concrete Anchorage Connector ANSI Z359.1 5,000 lbs / 22.24 kn FallTech, Inc 1306 Alameda Street Compton, CA 90221
More informationLTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.
LTB013EN Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. to IECEx scheme Subject to technical modification Bachofen AG Ackerstrasse 42
More informationOPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: SWY100N
OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: SWY100N IMPORTANT!!! ALL PERSONS USING THIS EQUIPMENT MUST READ AND UNDERSTAND ALL INSTRUCTIONS. FAILURE TO DO SO MAY RESULT IN SERIOUS INJURY OR DEATH.
More informationTypes and approvals. Page 1/6. Data Sheet
Page 1/6 Panel-mounting Thermostats EM Series as: Protection temperature monitor STW (STB) Protection temperature limiter STB tested to DIN 3440 and Pressure Equipment Directive 97/23/EC Brief description
More informationGEMS SENSORS & CONTROLS
GEMS SENSORS & CONTROLS OPERATING & INSTALLATION INSTRUCTIONS 31XX / 32XX SERIES PLEASE READ CAREFULLY BEFORE INSTALLING Part Number: 560550-0076 Issue: E INTRODUCTION Series 3100/3200 high output pressure
More informationABTQ-110 rev 00 (Last review: 28 Aug 12) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR ABTECH S RANGE ENCLOSURES IECEx SIR U SERIAL No
ABTQ-110 rev 00 (Last review: 28 Aug 12) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR ABTECH S RANGE ENCLOSURES IECEx SIR 05.0046U SERIAL No 20 TYPE SX Ex e II C Gb Ex tb IIIC Db IP6* IECEx SIR
More informationTECHNICAL MANUAL DHR60 LED. Den Haan Rotterdam MED96/98/EC
TECHNICAL MANUAL DHR60 LED MED96/98/EC SINCE 1922 Den Haan Rotterdam DISCLAIMER Despite constant care and attention DHR puts in its manuals it is still possible that information in this manual is incomplete
More informationPRESSURE TEST PUMP OPERATING & MAINTENANCE INSTRUCTIONS. Model No: PTP100. Part No: GC01/09
PRESSURE TEST PUMP Model No: PTP00 Part No: 06020 OPERATING & MAINTENANCE INSTRUCTIONS GC0/09 INTRODUCTION Thank you for purchasing this CLARKE Pressure Testing Pump. Before attempting to use the product,
More informationATS430 turbidity sensor Retractable insertion assembly
A MEASUREMENT & ANALYTICS INSTRUCTION ATS430 turbidity sensor Retractable insertion assembly Measurement made easy 1 Introduction This publication details installation procedures for the retractable insertion
More informationInstallation, Operation and Maintenance Manual for Back Pressure Regulator
Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN
More informationTarget disk flowmeter Series DP. Instructions manual DP65 DP500. R-MI-DP Rev.: 4 English version
Target disk flowmeter Series DP Instructions manual DP65 DP500 R-MI-DP Rev.: 4 English version PREFACE Thank you for choosing the flowmeter series DP from Tecfluid S.A. This instruction manual allows the
More informationMAINTENANCE AND OPERATING MANUAL
MAINTENANCE AND OPERATING MANUAL Cyclone condensate separator Type ASA EN EN Maintenance and operating manual Purpose and appropriate use Dear Customer, thank you for choosing our product. In order to
More informationPlummer Block Housings
Plummer Block Housings TECHNICAL INFORMATION Feature The majority of SLB Plummer Block Housing is made of Gray Cast Iron and is of the models of 'SN', 'SNU' and 'SAF'. Its basic size conforms with 'ISO'
More informationMounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2
Self-operated Pressure Regulator Pressure Reducing Valve Type M 44-2 Type M 44-2, connection G 1 4, K VS = 0.15 Type M 44-2, connection G 1, K VS = 6 Fig. 1 Type M 44-2 Pressure Reducing Valve Mounting
More informationCOOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013
Switches MN008005EN Effective April 2016 Supersedes S328-120-1 June 2013 D-73P3 bypass switches installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationNEW TYPE M PRESSURE RELIEF DEVICE
NEW TYPE M PRESSURE RELIEF DEVICE M PRESSURE RELIEF DEVICE ACCORDING TO EN 50216-5/A2 PATENTED 2 PRESSURE RELIEF DEVICE TYPE 50 M Section A-A 170 139 Transformer tank F 41.5 3 ø48.3 ø166 A P.R.D. TAG A
More informationSIROCCO. Robust high-pressure diecast aluminium housing. Computer aided design reflector. Graduated scale for accurate aiming.
SIROCCO is a family of floodlight, surface washer and area lighting. Three (3) types of light distribution, asymmetric, bi-symmetric, and road optic. Available in 2 sizes with a range of mounting accessories
More informationFoundation Products. Poured In Ground Anchor Bolts E1 - E4. Structural Foundations E5 - E12. Copyright 2016 s Industry Inc. SIE-RA-CMP EN
Foundation Products Poured In Ground Anchor Bolts E1 - E4 Structural Foundations E5 - E12 EA EB Poured in Ground Anchor Bolts Layout SIEMENS Anchor Bolts 131702-4X shown for reference purposes only! Actual
More informationOWNER'S MANUAL. Turnbuckle. Stanchions. Warning
GEMTOR, INC....when your life is on the line One Johnson Avenue Matawan, NJ 07747 732-583-6200 800-405-9048 Fax 732-290-9391 OWNER'S MANUAL Installation, Operating, Inspection and Maintenance Instructions
More informationSEries 29 Hydrant valves installation, operation & maintenance manual
Instruction for use Thank you for selecting an AVK product. With correct use, it will give long and reliable service. This manual has been prepared to assist you install, operate and maintain the valve
More informationDescription Supply pressure Pressure range Connection Device Page max. bar bar thread
Pressure Regulators Supply pressure Pressure range onnection Device Page max. bar bar thread Maxi -Series, robust, interlockable 1 0. 1.8 / 17 G¼ - G1 R0, R1.0 made of plastic, also for liquids 1,5 0 4
More informationPFC Lightweight Composite Push Up Mast. Operating Manual
PFC Lightweight Composite Push Up Mast Operating Manual South Midlands Communications Ltd SM House, School Close Chandlers Ford Industrial Estate Eastleigh, Hampshire SO53 4BY United Kingdom Tel: +44 (0)23
More informationFlange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing
Flange Bolt Torquing for Resistoflex Plastic-Lined Piping Products Torquing When assembling flange connections, always use a full complement of clean, new high strength A193-B7 bolting. If using stainless
More informationFRONT DERAILLEUR - CURRENT RANGE
FRONT DERAILLEUR - CURRENT RANGE (since 2015) (since 2018) (since 2017) (since 2018) WARNING! This technical manual is intended for use by professional mechanics. Anyone who is not a qualified professional
More informationElectro-Pneumatic Converter YT-940 SERIES
Electro-Pneumatic Converter YT-940 SERIES PRODUCT MANUAL VERSION 1.00 Contents 1. Introduction 3 1.1 General information for the users. 3 1.2 Manufacturer Warranty 3 1.3 Explosion Proof Warning. 4 2. Product
More informationIMPORTANT: If you have questions on the use, care, or suitability of this equipment for your application, contact DBI/SALA.
User Instruction Manual Precast Concrete Beam Horizontal Lifeline System This manual is provided as the Manufacturer s Instructions, and should be used as part of an employee training program as required
More informationPHOENIX, ARIZONA USA
NEW PRODUCTS MODEL: US-AASS-80 DESCRIPTION: Cantilever Arm 80 MEETS OSHA & ANSI Z359.14 CLASS B 1-800-850-5914 PHOENIX, ARIZONA USA WWW.ULTRASAFEUSA.COM CANTILEVER ARM The Ultra-Safe cantilever arm has
More information