1 pco Electronic Control CHILLERS ARIES FREE-COOLING Original instructions in Italian language SERVICE

2

3 Index 1 INDEX INDEX... 1 Chapter 1 TECHNICAL CHARACTERISTICS Structure of units Components of pco network pco inlet and outlet connections Layout of module network How to use the programmed Smart-Key How to address pco board Terminal unit Hardware addressing of the local/remote terminal How to set the software address between the terminal and the board How to address the electronic thermostatic valves How to wire the terminal How to wire the remote terminal (optional)... 9 Chapter 2 GLISH PRESSURE AND TEMPERATURE TRANSDUCERS Pressure transducers Inspection of the pressure transducer (only 4 20mA) Temperature probes Function of transducers and of probes Location of transducers Chapter 3 UTILISATION OF THE TERMINAL Display of pco terminal Displaying/signalling masks Terminal buttons Function of combined buttons Chapter 4 UNIT STARTING AND STOPPING Unit start-up Automatic restart Unit switching off Chapter 5 ACCESS TO THE PROGRAMMING How to modify a parameter in Free Menu How to modify a parameter of Password Menu How to modify the language Chapter 6 MAIN SETTINGS How to modify the setpoint value How to modify the differential value How to modify the Free-Cooling Delta activation Chapter 7 TEMPERATURE REGULATION MANAGEMT Water temperature regulation for conditioning use in chiller modality NEUTRAL ZONE temperature regulation Water temperature regulation in FREE-COOLING modus Anti-freeze control... 26

4 2 Index Chapter 8 GLISH SETPOINT MANAGEMT Fixed setpoint Compensated setpoint Double setpoint Adjustable setpoint by daily bands...28 Chapter 9 FREE-COOLING SYSTEM MANAGEMT Operating logic Free-Cooling three-way-valve...30 Chapter 10 MANAGEMT OF COMPRESSORS OPERATION Unit type and compressor number Working hours and startings of compressors and of the unit Compressors sequencing procedure Compressor sequencing procedure disabled Sequencing procedure per compressor Compressors Pump-Down procedure (only AS FC units) Compressors Unloading procedure Unloading procedure by high pressure probes...37 Chapter 11 FANS OPERATION MANAGEMT Condensing Fans Management by step Management by variable speed Management by variable speed on the medium value Speed-Up time logic Nightly operation Free Cooling fans FC fans regulated by variable speed...42 Chapter 12 SINGLE OR DOUBLE PUMP OPERATION MANAGEMT Operating hours and number of startings of the pump Pump management and operation Automatic rotation Manual rotation...46 Chapter 13 MANUAL PROCEDURE...47 Chapter 14 ELECTRONIC THERMOSTATIC VALVE Operation Driver of the thermostatic valve...48 Chapter 15 SUPERVISION SYSTEM Carel Modbus Gsm Direct Modem (Rs232) LonWorks Variables managed by the electronic control Digital variables Analogue variables Entire variables...56

5 Index Chapter 16 3 MASKS NO PASSWORD REQUIRED Menu Free Menu Chapter 17 MASKS REQUIRING A PASSWORD Menu with password Chapter 18 GLISH ALARM MANAGEMT Alarm signals Alarm displaying Alarm resetting Alarms masks Chapter 19 HISTORY Chapter 20 SETTING TABLES Settings without password Settings with password Chapter 21 PARAMETERS WITH SETTINGS RELATED TO THE TYPE OF UNIT Settings related to the alphanumeric string-code Settings related to the unit model... 92

6 4 Technical characteristics CHAPTER 1 GLISH 1.1 Structure of units All units have one circuit and are equipped with two SCROLL compressors. These units are furnished with a pco net. T ECHNICAL CHARACTERISTICS 1.2 Components of pco network pco network practically constitutes the unit electronic control and is similar to a little hardware net (plan) formed of: 1. Terminal unit 2. Main control board 3. Telephone cable for connecting the terminal and the board The Fig.1 shows the connections of the plan (Local Area Network) which forms the classic hardware architecture of a pco network with the local/remote terminal (1) Fig.1 COMPONTS OF A PCO MODULE 1.3 pco inlet and outlet connections The Fig.2 shows the planimetry of the pco board. Here are marked the connectors of all available inlets and outlets (J1 J18). Some inlets are used to receive signals of analogue type, others to receive signals of digital type. The outlets are used to send signals of digital type. Particulars of the board: 1. Power supply connector 24 Vac 2. Telephone connector to terminal or to download/upgrade the software using the Smart-Key. 3. RS485/Modem optoisolated board for serial line connection to supervisory/telemaintenance systems (optional) 4. Collector for the connection of pco boards to plan network 5. Outlet relay 6. Digital inlets; Analogue inlets; Analogue outlets. Fig.2 BOARD OF PCO ATTTION The planimetry which marks the utilisation of inlets and outlets of the board is shown in the wiring diagram annexed to each unit.

7 Technical characteristics Layout of module network On each unit is installed a board which, together with the terminal, constitutes pco network. The unit can operate in an independently way (LOCAL operation) or can operate connected to other units (until four units max., MODULAR operation). ATTTION The ARIES freecooling units can by utilized in the MODULAR operation. In the event of modular operation, pco hardware allows to manage a network of two until four modules. Modular operation is used if you want to co-ordinate the operation of more machines. The connected modules constitute the module network. It is important to define the module 1, that is the main module or Master module. This is the module which co-ordinates the main functions of the unit group. The other modules are defined secondary modules or Slave modules. The definition of the modules is done software addressing the board. The wiring diagram, annexed to the unit, explains the connection layout of the module network. GLISH 1.5 How to use the programmed Smart-Key The Smart-Key allows to download the programmes in pco boards and to upload them from pco boards. LED of the Smart-Key: LED on LED status Description flashing The Key is connected to the pco, during this phase, even some seconds, the start button is disabled. start flashing The Key is checking the accesses start + start + start + on on on pressing start button download the data into the pco pressing start button the pco begins to read the data in the pco and download them in the key pressing start button you begins to read the alarm historic of the pco mode on pressed for 1 second you enter the write modality (IF ABKLED) ATTTION start + you record from the key to the pco; start + you record from the pco to the key; Each recording deletes the previous Smart-Key buttons: The Key has two buttons which have the following functions: mode button is used to change from read to write modality. (pco write modality) (pco read modality). start button allows to begin the read or write modality, that will be indicate by the relative symbols ( or ). When the operation will be complete the buzzer will ring for 20 seconds. If there is an error the symbol will switch on with the LED. The table below shows the cause of the problems: Led on Led status Description mode + mode flashing on flashing Communication error: no answer from the pco or the firmware version of the key is not compatible Password error or the key is not compatible The key is not compatible

8 6 Technical characteristics Led on Led status Description GLISH + start + +buzzer + start + flashing and the buzzer is intemittent flashing and the buzzer is intemittent The write command is failed The read command is failed +buzzer + start + + flashing and the buzzer is intemittent The command to read the hysterics is failed. buzzer + on The key has not one or more compulsory files. + +start on + start flashing The bios and the pco hardware are not compatible + +mode on + mode flashing The software and the pco hardware are not compatible + + on + flashing The historic configuration and the pco hardware are not compatible on on on The memory is not enough to read the hysterics Historical data not present in the pco. The key is not programmed. The following procedure describes what to do to download the program from the Smart-Key to the pco card: 1. cut the power supply from the pco turning off the machine main switch; 2. Disconnect the phone connector of the terminal from the pco card. 3. Connect the key to the phone connector of the pco as showed in the picture;. 4. Restore the power supply of the pco card. 5. The symbols will light on and the buzzer will play. 6. Wait for some seconds till the key will become effective. During this period the symbol will flash. 7. At the end the control will enter the program modality and the start button can be pressed to start the data transfer. 8. Before pressing the start button be sure that the symbol has been selected (pco write mode). Otherwise press the mode button to start the write modality; the symbol must be on (pco write mode). (pco write mode) (pco read mode). 1.6 How to address pco board pco controller needs to be addressed to operate in plan network. The address modification is carried out using pgd terminal or a REMOTE terminal. To modify the address by local/remote pgd terminal: 1. Switch off pco; 2. Use a standard pgd terminal with the address as 0 (see paragraph 1.8 Hardware addressing of the local/remote terminal ); 3. Disconnect pco from eventual plan connections of other controllers (j11 terminal); 4. Switch on pco pressing at the same time g and j buttons; 5. The following mask will appear after a few seconds: PLAN ADRESS: 0 UP: INCREASE DOWN: DECREASE TER: SAVE & EXIT

9 6. To modify the address operate on g and f buttons, then press h button to confirm the new value. 1.7 Terminal unit Technical characteristics 7 Each unit is furnished with a terminal for controlling the programming (see Fig.3). The terminal unit, connected to the board of each module, is necessary to program the unit and to display its working parameters. It enables you to perform the following operations: programming via password; programming without password; display of all inlets/outlets; possibility to modify run-time the operating setpoint value; display of all measured values; display of any alarm condition; display of alarm historic. Fig.3 PGD TERMINAL GLISH The unit has 6 buttons. Furthermore, the terminal is equipped with: 1. a LCD display for the displaying and programming; 2. LED indicators associated to buttons. Furthermore, if requested each unit can be supplied with a REMOTE terminal for remote controlling and programming (see Fig.3). 1.8 Hardware addressing of the local/remote terminal pgd remote terminal needs to be addressed to operate in plan network. The address modification is possible only after switching off the terminal by the telephone connector, see chapter 1.2 Components of pco network. How to address pgd remote terminal: 1. at the same time press g, f, h buttons for 5 seconds, 2. the mask on the side will appear, the cursor will start to flash on the top left corner Display address setting...:nn I/O Board address:xx 3. To modify the remote terminal address, press h button; the cursor will move on address field (nn) 4. Press g and f buttons to modify the address and h button to store the new value. 5. If the setting is different from the one stored before, the mask on the side will appear and the new value will be stored in the permanent memory of the display. Display address changed ATTTION If the event of MODULAR operation, fix the board address of each module as indicated below. 1.9 How to set the software address between the terminal and the board ATTTION Before carrying out the following operations be sure that all the wiring of the board and of the terminal have been correctly carried out (see paragraphs "1.2 Components of pco network" and "1.3 pco inlet and outlet connections"). Be sure that all the indication about the hardware addressing have been followed (see paragraphs "1.6 How to address pco board" and "1.8 Hardware addressing of the local/remote terminal"). 1. If the unit is off, switch it on operating on the breaker on the electrical panel, then wait for one minute at least to allow to pco net to stabilize; 2. Assure that the unit is in STAND-BY; A mask similar to the following one will appear; The indication Unit Off must appear in the last row of the display: 12/11/02 03:00 Temp.IN : C Temp.OUT: C Unit Off 3. At the same time keep pressed the buttons: g, f and h;

10 8 Technical characteristics GLISH 4. After a few seconds the following mask will appear; Terminal Adr: 3 I/O board Adr: 1 Terminal Adr:3 (used for local terminal address) Terminal Adr:13 (used for remote terminal address) Release the three buttons: means that the terminal, connected to the boards which are in use, has the address Nr. 3 (see paragraph "1.8 Hardware addressing of the local/remote terminal"); means that the board which will be used for software address is the one with address nr. 1 (see paragraph "1.6 How to address pco board"). If the message appears, press g or f button to set it as Press h button, the following mask will appear: Terminal config Press TER to continue 6. Press h button again; the following mask will appear: P:01 Adr Priv/Shared Trm1 3 Pr Trm2 None Trm3 None Ok/No The indication P:01 on the top left corner of the mask corresponds to the address of the board which is used to set the software address already selected in point 4. with the parameter I/O board Adr:1 (see paragraph "1.6 How to address pco board"). 7. If the mask is not the same of the one shown above, set the address of LOCAL terminal () to by means of g button (see also paragraph 1.8 Hardware addressing of the local/remote terminal ); 8. Confirm the modification of the parameter by means of h button; 9. By means of g button, set the operating modality of LOCAL terminal to and the operating modality of REMOTE terminal to (in units with one module) or to (in units with more than one module); 10. Confirm the modification of the parameter by pressing h button; the following mask will appear: ATTTION 12/11/02 03:00 Temp.IN : C Temp.OUT: C Unit Off If the display doesn t show anything, repeat all the procedure keeping attention to switch off the unit and wait any second before switching it on again How to address the electronic thermostatic valves The electronic thermostatic valves, positioned inside the refrigerant circuit, must be addressed by means of their dip-switches of the Driver positioned in the electrical panel (see Fig.4) in order to operate correctly Fig.4 EVD DRIVER

11 Technical characteristics The addressing is carried out with not powered boards, opportunely moving the dip-switches by means of a pointed object (see Fig.5). 9 GLISH Fig.5 ADDRESS How to wire the terminal It is possible to install a terminal following the instruction indicated below in the manual and in the electrical diagram annexed to the unit: 3 50m 4 1 Fig.6 WIRING OF THE LOCAL TERMINAL IN ONE PCO MODULE UNTIL 50M 1.12 How to wire the remote terminal (optional) LOCAL Adr: REMOTE Adr: 13 Fig.7 WIRING OF THE REMOTE TERMINAL IN ONE PCO MODULE UNTIL 200M 1. Terminal unit (address Nr.3 - see paragraph "1.6 How to address pco board"); 2. Telephone connector for connecting the connecting board to the PCO board; 3. Telephone connector for connecting the terminals to the board; 4. REMOTE terminal unit (address Nr.13 - see paragraph "1.8 Hardware addressing of the local/remote terminal"); 5. Connecting board for the connection to the REMOTE terminal;

12 10 Technical characteristics 6. Screened cable for the wiring of the connecting boards (see Fig.8). GLISH Fig.8 PARTICULAR OF THE SCREED CABLE

13 Pressure and temperature transducers 11 CHAPTER 2 P RESSURE AND TEMPERATURE TRANSDUCERS 2.1 Pressure transducers They are pressure transmitters which are directly powered by pco (5 Vdc); they have the following specifications: working range: for high pressure transducers 0 34 barg (relative pressure measurement); polarised wiring; output signal ( V) or (4 20mA); linear function in output signal. GLISH Tension/Current 4,5 V / 20 ma 0,5 V / 4 ma 0 max Pressure Range Fig.9 OPERATING LOGIC OF TRANSDUCERS Inspection of the pressure transducer (only 4 20mA) DANGER The operations indicated below can seriously damage the unit electronic control, therefore they must be carried out by specialized personnel only. In the event of any wrong measurement by pressure sensors, before replace them, it is recommended to carry out the following inspections: Verify if analogue inputs are suitable to receive signals of 4 20mA; Verify the full scales set by software. These full scales must correspond to the values of transducers, generally 0 30 barg. Verify that the capillary of the transducer is not obstructed; With direct current, measuring by a voltmeter the tension on the heads of the connectors Bn and GND you can indirectly obtain the current of the probe signal, as the analogue input has an impedance of 50Ω, by applying the formula I=V/R. The pressure value PS sent by the probe can be obtained in the following way: PS=(Vmis/ )*(FSmax-FSmin)/0.016+FSmin where: Vmis= tension measured in Vcc; FSmin= min. full scale of the transducer; FSmax= max. full scale of the transducer. NOTE If carried out by a manometer in parallel, this last inspection can indicate if the transducer is sending a wrong pressure or if pco board is reading wrong values. 2.2 Temperature probes They are NTC resistive probes (Negative Temperature Coefficient) that permit nonpolarised wiring. According to the temperature, their electrical resistance changes as described in Table 1: Temperature 0 C / +32 F kω Resistance values +20 C / +68 F kω +25 C / +77 F kω +30 C / +86 F 8.31 kω Table 1 CHARACTERISTICS OF TEMPERATURE TRANSDUCERS

14 12 Pressure and temperature transducers GLISH 2.3 Function of transducers and of probes Pressure transducers (P) and temperature probes (T) are connected to the appropriate inlets of pco board. Each transducer has its own function and is identified by a B associated to a number. The table below shows the types of transducers and probes and their use. pco analogue input Connector Name Probe-Transducer Name Description Function B1 (-BHP1) High press. transm. circuit 1 P B B3 (-BFCIT) Free Cooling water inlet temperature T B4 (-BEWIT) Evaporator water inlet temperature T B5 (-BEWOT) Evaporator water outlet temperature T B6 (-BLP1) Low pressure transducer 1 P B B8 (-BAT1) Ambient temperature 1 T B9 (-BAT2) Ambient temperature 2 T B10 (-BTOWT) Tank water outlet temperature T ATTTION The number of transducers or probes connected to the board depends on the type of unit and is fixed during design phase. 2.4 Location of transducers To identify the temperature and pressure transducers and verify their location, please consult the refrigerant drawing annexed to the manual. The presence of absence of any transducer depends on the unit type.

15 Utilisation of the terminal 13 CHAPTER 3 U TILISATION OF THE TERMINAL 3.1 Display of pco terminal The display of pco terminal is used to show the information about the unit status and to change the values of programmable parameters. The top left corner on the display represents the HOME position of cursor. At the first start up of the electronic control it is displayed the MAIN mask (see Ref. A1). However, if during the programming of pco it is necessary to return to the main mask, it is sufficient to press once or more times k button. GLISH NOTE If no operation is carried out within 5 minutes the unit will automatically return to the MAIN mask. The contents of the display are depicted in Fig.10: HOME Position Pre-fixed date and hour (if clock board is present) ON, it indicates the FREE COOLING operation Indicator for unit status Temperature measured by inlet and outlet probe. Temperature measured by outlet probe. Fig.10 MAIN MASK The display shows many types of masks, distinguished as follows: R - Read-only masks: used to show the unit status (temperatures, pressures, alarms, etc.). W - Read-write masks: used to show the values set by programmable parameters and/or to allow their modification. In read only masks (R) it is only possible to display the parameter values, while in read-write masks (W) it is also possible to modify them (For further information see manual ahead). The last row of the MAIN mask informs the user about the status of the unit using one of the messages shown in Table 2: MESSAGE UNIT STATUS ACTION OBTAINED WITH CONDITION ON Terminal Unit ON/OFF button The action is not possible if the unit was OFF by digital input ID1 or if the unit was OFF by supervisor. ON Digital input ID1 powered The action is not possible if the unit was OFF by terminal. ON By supervisor / By digital input The action is not possible if the unit was OFF by terminal. OFF Terminal Unit ON/OFF button The action is always possible: this action has priority over any other. OFF Digital input ID1 not powered The action is possible only if the unit was ON by terminal. If ID1 is activated with unit already OFF, the message will change but LED will remain OFF. OFF By Supervisor The action is possible only if the unit was ON by terminal. OFF By daily bands The action is possible only if the daily and weekly bands have been enabled. OFF Alarm condition The message appears only when it trips an alarm which stops the unit. OFF By manual procedure The message appears only when the manual procedure has been enabled. Table 2 MESSAGES ABOUT THE UNIT STATUS

16 14 Utilisation of the terminal GLISH Displaying/signalling masks In the electronic control are available other displaying and signalling masks. These masks are displayed after a period of transition during which no button of pgd is pressed. This mask appears if no button of pgd is pressed for 10 minutes. In the top left part of the display is shows the temperature regulation value and the unit ON status; the bottom left part shows the temperature regulation setpoint and the current time. This mask is similar to the previous one, it shows the unit OFF status. This mask is similar to the previous one, it is displayed only when an alarm trips (the bell flashes). To display the appropriate alarm press j button (see Chapter 18 Alarm management ) When no button of pgd is pressed for 20 minutes it appears the screen saver mask. Signalling mask: it indicates that unloading procedure is enabled (see Chapter 10 Compressors Unloading procedure ). NOTE To return to display the main mask press a button of pgd terminal.

17 Utilisation of the terminal Terminal buttons The functions of pgd terminal buttons are explained here below: k l Utilized to return from the various menus to the main displaying mask. If pressed once it allows to enter DIRECT loop. If pressed for more than 5" it allows to enter the configuration modality (password needed). GLISH j If pressed once it is utilized to check if in the pco there is any alarm on. After removing the alarm cause, a second pressure of this button resets the signalling. Used to scroll the various masks of a loop when the cursor is in HOME position. Used to increase or decrease the value of a numeric field (configuration). or Used to scroll the various sub-sections of a mask. g It allows to scroll the list of sub-sections of a loop. If pressed during unit normal operation or when unit is in stand-by, it shows the programme version, the status of compressors, the type of board and the BIOS and BOOT versions. f Used to move the cursor on the various adjustable fields of a mask. It allows the access to the selected programming sub-section. Sometimes it is used to confirm the operation. h Function of combined buttons pgd g + h k + f l + j + g l + j + f g + f + h Description When the unit is on, if pressed together they switch on and off the unit. When the unit is on, if pressed together they are used to change the module. When the unit is on, keeping pressed l + j buttons, press many times g button to increase the contrast. When the unit is on, keeping pressed l + j buttons, press many times f button to decrease the contrast. When the unit is on, if pressed together they are used to address the pgd/network.

18 16 Unit starting and stopping CHAPTER 4 GLISH U NIT STARTING AND STOPPING 4.1 Unit start-up When the installation and electrical connections have been made, operate on the unit general switch-breaker (on the electrical panel) putting it in ON position. The terminal unit is correctly connected to the power supply line when the leds of f, g, h and k buttons lights up and the following mask appears on the display: After the network has stabilized, the main mask will be displayed (see Ref. A1). In these conditions the unit is in STAND-BY. NOTE Every time the unit is switched on by means of the main switch-breaker, it is recommended to leave the unit in STAND-BY for a few seconds to allow the pco net to stabilize. Press h+g buttons of pgd to switch on the unit and consequently start the setting procedure. When the unit is switched on the message will appear on the display. If the unit doesn t start, follow the indications below: if the remote control is enabled, assure that the digital input 1 of the board is closed (see Ref. E9); assure that the unit has not been switched OFF by a Supervisor system (if installed); assure that the board is correctly connected and addressed; the unit must not be in manual operating mode (see Ref. K1); there must be no alarm condition. If the problem persists contact the nearest service centre. 4.2 Automatic restart The electronic control allows to restart automatically the unit after a blackout or after a power failure. To do this, it is necessary to enter the mask Ref. D3 in USER loop and enable the parameter. The automatic restart is possible only if, at power failure, the unit was already ON. Used Masks: Ref. D3 4.3 Unit switching off To switch OFF the unit press h+g buttons of pgd terminal. The unit will stop and the message will appear on the display. In these conditions the unit is in STAND-BY. The antifreeze functions will remain enabled (if they are present). If necessary, operate on the main breaker-switch of the unit (positioned on the electrical panel) turning it in OFF position. In these conditions the unit is OFF and not connected to the power supply line.

19 Access to the programming 17 CHAPTER 5 A CCESS TO THE PROGRAMMING The electronic control is furnished with two main menus: 1. FREE menu (PASSWORD NOT needed) see "5.1 How to modify a parameter in Free Menu " It can be accessed by pressing and releasing l button. 2. PASSWORD menu (PASSWORD needed) see "5.2 How to modify a parameter of Password Menu " It can be accessed by pressing and releasing for 5 sec. l button. According to the password inserted, PASSWORD menu is divided in USER, SERVICE and MANUFACTURER. 5.1 How to modify a parameter in Free Menu GLISH 1. Press and release l button on the terminal (see paragraph "3.2 Terminal buttons") to access the loop mask (free menu) (Ref. B1). 2. It is possible to scroll the various loops (see " Ref. B1") using g or f button on the terminal. Ref. B1 3. After selecting the desired loop (e.g. User loop), to access the mask of this loop (HOME position) press h button. It will be possible to scroll the masks using g or f button. Ref. B1 ATTTION The selection of the loop or of the parameter happens when the indication becomes negative. 4. After the individuation of the parameter to be modified, press h button to move the cursor on the first parameter of the displayed mask. If in the mask there is more than one parameter, each time h button is pressed the cursor will move to the next field of the same mask. 5. Modify the value using g or f buttons. 6. Press h button again to confirm the modifying. If in the mask there is more than one parameter the cursor will move to the following one and, when the last one is reached, the cursor will return to HOME position. 7. To move to another mask of the loop press g or f button when the cursor is in HOME position. To access a new loop it is first necessary to return to the loop mask pressing once k button (Ref. B1). 8. To return to MAIN mask (Ref. A2) press twice k button on the terminal.

20 18 Access to the programming GLISH 5.2 How to modify a parameter of Password Menu 1. Enable the password menu pressing for 5 sec. l button on the terminal (see paragraph "3.2 Terminal buttons"); 2. The password is requested; 3. Insert the password using g or f button on the terminal; Ref. F1 4. Press h button again to confirm the password. 5. If the password is wrong, the message will appear, it will be necessary to insert it again. If the password is right, the various scrolling loops will be accessed (Ref. F2); It is possible to scroll the loops using g or f button on the terminal. The loops will be displayed in groups of three. 6. After having selected the desired loop (e.g. Modularity ), to access the mask of this loop (HOME position) press h button. To scroll the masks use g or f button. Ref. F2 Ref. F2 ATTTION The selection of the loop happens when the indication becomes negative. The access to the loops depends on the password. 7. After the individuation of the parameter to be modified, press h button to move the cursor on the first parameter of the displayed mask. If in the mask there is more than one parameter, each time h button is pressed the cursor will move to the next field of the same mask. 8. Modify the value using g or f button. 9. Press h button again to confirm the modification. If in the mask there is more than one parameter the cursor will move to the following one and, when the last one is reached, the cursor will return to HOME position. 10. To move to another mask of the loop press g or f button when the cursor is in HOME position. To access a new loop it is first necessary to return to the loop mask pressing once k button (Ref. E2). 11. To return to MAIN mask (Ref. A2) press twice k button on the terminal. ATTTION All the parameter masks are listed in Chapter 16 or Chapter 17, grouped by LOOP they belong to. They are joined to an alpha-numeric reference, this same number will be used in the rest of this manual to easily individuate the corresponding mask.

21 Access to the programming How to modify the language The pco allows to choose the language of the masks. The available languages are: Italian, English, German, French and Spanish. 1. To access User loop follow the same procedure described in chapter "5.1 How to modify a parameter in Free Menu ". Ref. B1 GLISH 2. Reach the mask of languages (Ref. D5) using g or f button; Ref. D5 3. Press h: the cursor starts flashing under the indication of the current language; Ref. D5 4. Select the desired language using g or f button; 5. Press h to confirm the selected language; The display automatically displays the main mask translated on the language selected and, consequently, also all the other masks. Ref. D5

22 20 Main settings CHAPTER 6 GLISH ATTTION M AIN SETTINGS Each unit is delivered ready to work, therefore all the control parameters have been already set during the testing operation and it isn t necessary to modify them. On particular cases it is possible to modify the set point and differential values by following the instruction indicated below: 6.1 How to modify the setpoint value 1. If the unit is off, switch it on by means of the main breaker of the electrical panel and wait at least one minute to allow pco net to stabilize; 2. The main mask must be displayed (Ref. A1), it will be similar to the one shown on the side; 3. Press l button on the terminal: Free menu will be displayed (Ref. B1); 4. Select Setpoint loop and press h button on the terminal. 5. The first mask of Setpoint loop will be displayed, scroll the mask using g or f button until reaching the mask shown on the side (Ref. C2); 6. Press h button on the terminal: the cursor will move on field. NOTE The second setpoint is displayed only if enabled. Ref. A1 Ref. B1 Ref. C2 Ref. C2 7. Use g or f buttons to change the value; 8. Press h to store the new value; 9. Press twice k button on the terminal to return to the Main mask.

23 6.2 How to modify the differential value Main settings If the unit is off, switch it on by means of the main breaker of the electrical panel and wait at least one minute to allow pco net to stabilize; GLISH 2. The main mask must be displayed (Ref. A1), it will be similar to the one shown on the side; 3. Press l button on the terminal: Free menu will be displayed (Ref. B1); 4. Select User loop and press h button on the terminal. 5. The first mask of User loop will be displayed, scroll the mask using g or f button until reaching the mask shown on the side (Ref. D1); 6. Press h button on the terminal: the cursor will move on field. Ref. A1 Ref. B1 Ref. D1 Ref. D1 7. Use g or f buttons to change the value; 8. Press h to store the new value; 9. Press twice k button on the terminal to return to the Main mask. ATTTION Modify the SETPOINT or the DIFFERTIAL only if necessary, making sure that they are neither too low nor too high. DANGER A Summer Setpoint which is too low may cause ice formation so that antifreeze must be added. Generally the differential values must not be too low. If the differential value must be modified, consider also the delays for compressor starts and stops.

24 22 Main settings 6.3 How to modify the Free-Cooling Delta activation GLISH 1. If the unit is OFF, switch it ON by means of the main breaker of the electrical panel and wait at least one minute to allow pco net to stabilize; 2. The main mask will be displayed, it will be similar to the one shown on the side (Ref. A1); On the terminal press l for 5 sec. at least then release it; Insert the password using f or g buttons and confirm it using h. The SERVICE password is If the procedure is right the mask Ref. F2 will appear; Ref. A1 Ref. F2 3. Select the Free Cooling loop and press h to access it. 4. The first mask of Free Cooling loop will be displayed. Scroll the masks using g or f button until reaching the mask shown on the side (Ref. W2); 5. Press h button on the terminal: the cursor will position on the field. Ref. W2 Ref. W2 6. Use g or f buttons to change the value; 7. Press h to store the new value; 8. Press twice k button on the terminal to return to the Main mask.

25 Temperature regulation management 23 CHAPTER 7 T EMPERATURE REGULATION MANAGEMT The electronic control of the ARIES FREE-COOLING units can manage the temperature regulation of the process water: chiller modality free-cooling system GLISH The unit normally allows to obtain: the cooling of a water volume for a conditioning plant (CHILLER units only); the heating (by means of a heat recuperator) of a water volume for the sanitary use (CHILLER units only). As it could happen the contemporary request of heated water by the sanitary plant and of the water (cold) by the conditioning plant, the pco electronic control has been designed to satisfy in the best way both the requests. NOTE For the Free Cooling system logic consult Chapter 9 Free-Cooling system management 7.1 Water temperature regulation for conditioning use in chiller modality The pco allows to set three different ways of temperature regulation (see Ref. V1): 1. the proportional way (P); (NOT UTILIZED) 2. the integral-proportional way (P+I); (NOT UTILIZED) 3. the Neutral Zone way (N.Z.) NEUTRAL ZONE temperature regulation The pco allows to manage the temperature regulation following the Neutral Zone logic. The Neutral Zone temperature regulation can use the following probes: -BEWIT (inlet) or -BEWOT (evaporator outlet) or -BTOWT (tank outlet). The temperature interval, included between the setpoint value an the setpoint plus the differential value, (see Ref. C2-Ref. D1) establishes the Neutral Zone. To set the Neutral Zone temperature regulation it is sufficient to be sure that is displayed in the mask (see Ref. V1). Set the regulation probe -BEWIT, -BEWOT or -BTOWT (if present) by operating on the mask (see Ref. G3). When the unit is in LOCAL operation modality, it is possible to set which probe will be used for the regulation by operating on the mask (see Ref. G3). The temperature regulation will be considered at evaporator outlet, at evaporator inlet or at tank outlet, according to the selected probe, following Table 3. REGULATION PROBE -BEWIT -BEWOT -BTOWT TEMPERATURE REGULATION EVAPORATOR INLET EVAPORATOR OUTLET TANK OUTLET Table 3 PROBES UTILIZED FOR THE NEUTRAL ZONE TEMPERATURE REGULATION When the temperature measured by the probe will be lower than the setpoint value (so under the Neutral Zone) it will be required the stopping of one or more compressors (the compressors consecutive stopping will be done with a delay time fixed by the parameter see Ref. L2) until the temperature measured will return within the limits of the Neutral Zone. When the temperature measured by the probe will be higher than the setpoint + differential value (so above the Neutral Zone), it will be required the starting of one or more compressors (the compressors consecutive starting will be done with a delay time fixed by the parameter see Ref. L1) until the temperature measured will return within the limits of the Neutral Zone.

26 24 Temperature regulation management The graphic of Fig.11 explains how the increasing or decreasing requirement of cold fixes the compressors starting or stopping, following the logic of the Neutral Zone. GLISH WATER TEMPERATURE SET+DIFF. NEUTRAL ZONE (see Ref. C2-Ref. D1) SET COMPRESSORS STATUS TIME Compr. 2 ON Compr. 1 ON Compr. OFF Ref. L1 Ref. L1 TIME Fig.11 CHILLER NEUTRAL ZONE LOGIC For setpoint and differential setting enter parameters Ref. C2-Ref. D1. To set the delay time between the compressors staring or stopping enter parameters Ref. L1, Ref. L2. It is also possible to set the parameter (see Ref. L3) which allows to start a compressor when the water temperature value remains within the neutral zone for a time longer than the preset one. This allows to obtain an homogeneous compressor starting distribution, avoiding situations during which only some compressors remain in operation for a long time and others will be started only for short periods and, consequently, to force the system when the setpoint temperature is reached. Used masks: Ref. L1 Ref. L2 Ref. L3 Ref. D1 Ref. G3 BEWIT Ref. H1 Ref. C2 Ref. V1

27 Temperature regulation management Water temperature regulation in FREE-COOLING modus The Free-Cooling system can be utilized only if the ambient temperature is lower than the temperature of the inlet process water. In this way the process water can be cooled, partially or completely, by the ambient air in order to allow an important energy saving (the refrigerant compressors and the condensing fans stop). The Free-Cooling system is enabled when: Tamb BFICT- where: Tamb is the medium temperature measured by BAT probe; BFICT is the temperature measured by the probe at Free-Cooling inlet is the Free-Cooling activation delta GLISH The Free-Cooling temperature regulation with the Neutral Zone follows the same logic of the chiller modus (see paragraph above). When the process water temperature is lower than the setpoint value (under the Neutral Zone), the Free-Cooling system will gradually stop, until the temperature will reach again the Neutral Zone. When the process water temperature is higher than setpoint+differential (over the Neutral Zone), the Free-Cooling system will be increased, until the temperature value will reach again the Neutral Zone. The following graphic Fig.12 shows the Free-Cooling Neutral Zone logic. WATER TEMPERATURE SET+DIFF. SET NEUTRAL ZONE (see Ref. C2, Ref. D1) FREE-COOLING STATUS TIME Free-cooling ON FREE-COOLLING ON Free-cooling OFF TIME FREE-COOLING INCREASE FREE-COOLING PERFORMANCE UPKEEP FREE-COOLING INCREASE FREE-COOLING PERFORMANCE UPKEEP FREE-COOLING DECREASE Fig.12 FREE-COOLING NEUTRAL ZONE LOGIC To set the setpoint and the differential see the parameter Ref. C2, Ref. D1. NOTE If the Free-Cooling system is working at 100% of its capacity (three-way-valve open and free-cooling fans on), and this will not be enough to satisfy the cool request, the chiller (fans and compressors start up) modus will start operating as explained in paragraph "7.1 Water temperature regulation for conditioning use in chiller modality". For further information about the Free-Cooling system see Capitolo 9 Gestione del funzionamento del sistema Free-Cooling. TIME

28 26 Temperature regulation management GLISH 7.3 Anti-freeze control The anti-freeze control depends on the temperature measured at the evaporator outlet (-BEWOT probe). When the temperature decreases below the preset antifreeze threshold (see Ref. Q3) the pco will produce an alarm which will block the unit (see Ref. AM19). It will persist until the temperature increases and reaches a value higher than setpoint + differential (see Fig.13). The differential value cannot be changed and it is of 4 C. The anti-freeze alarm stops all the connected devices except for the pump. ALARM STATUS LOW TEMPERATURE OF WATER AT EVAPORATOR OUTLET ON OFF DIFFERTIAL TEMPERATURE MEASURED BY B2 Fig.13 ANTIFREEZE CONTROL LOGIC NOTE To lower the freeze protection setpoint, modify mask Q3 and add a suitable amount of antifreeze solutions to the system. If in doubt, contact the MTA after-sales service. Used masks: ALARM SETPOINT Ref. G6 Ref. Q3

29 Setpoint management 27 CHAPTER 8 S ETPOINT MANAGEMT NOTE This chapter explains the setpoint management logic for chiller units only. For Free-Cooling operating logic please consult Chapter 9 Free-Cooling system management. GLISH Modifying the mask (see Ref. V1) pco electronic control can manage the setpoint in five different ways: Used masks: fixed setpoint; compensated setpoint; double setpoint; adjustable setpoint by daily bands; setpoint by analogue input. Ref. V1 8.1 Fixed setpoint pco electronic control manages the water temperature regulation according to a setpoint (Ref. C2) and to a fixed differential (Ref. D1), which can not be modified by external causes. Used masks: Ref. C2 Ref. D1 8.2 Compensated setpoint The compensated setpoint is calculated according to the external temperature measured by -BAT1 probe and according to the values of parameters (Ref. C3) and (Ref. C4). The graphic below shows the setpoint state according to the settings of the parameters: Graphic with positive value;

30 28 Setpoint management GLISH Graphic with negative value; Used masks: Ref. C3 Ref. C4 8.3 Double setpoint It is possible to fix a second operating setpoint. Commute the digital input on the electronic board (see wiring diagram) to choose the setpoint. Used masks: Ref. C2 8.4 Adjustable setpoint by daily bands During the operation with adjustable setpoint by daily bands it is possible to programme four daily bands with their different setpoints. At preset time, the electronic control will change the unit setpoint according to the preset settings. Used masks: Ref. C5 Ref. C6 Ref. C7 Ref. C8

31 Free-Cooling system management 29 CHAPTER 9 F REE-COOLING SYSTEM MANAGEMT The pco control manages the Free-Cooling system. It activates or deactivates the Free-Cooling system according to the medium ambient temperature Tamb, which is checked by the BAT1 and BAT2 probes and the unit inlet water temperature Tin FC, which is checked by the BFCIT probe. With the Free-Cooling it is possible to pre-cool the water by fins coils. If the ambient conditions are not available to active the Free-Cooling system, the chiller will work normally. Here below you can see the hydraulic circuit of the unit: GLISH EVAPORATOR 9.1 Operating logic The pco is enabled to manage the Free-Cooling system by the mask Ref. W1. The electronic control will active the Free-Cooling system when: Tamb BFCIT - where: Tamb = is the medium ambient temperature detected by the probes (BAT1- BAT2) BFCIT = is the water inlet temperature detected by the BFCIT probe. = temperature difference to enable the Free-Cooling system, its value is set in the parameter Ref. W2. The Free-Cooling activation condition must persist for the time set in the parameter Ref. W3. When all conditions are respected, the pco turns off the compressors and starts modulating the three-way-valve following the Neutral Zone temperature regulation, see paragraph "7.2 Water temperature regulation in FREE-COOLING modus". If the three-way-valve is completely open, and this will not be enough to bring the temperature back within the neutral zone, the fans will start up according to the logic explained in the paragraph "11.3 Free Cooling fans". When the fans reach the maximum speed, the electronic control will start up the compressor/s and/or the capacity control according to the logic explained in paragraph "7.1 Water temperature regulation for conditioning use in chiller modality". The Free-Cooling system will stop operating when Tamb BFCIT - and this condition is detected for the time set in the parameter Ref. W3.

32 30 Free-Cooling system management Used Masks: GLISH Ref. W2 Ref. W3 9.2 Free-Cooling three-way-valve The three-way-valve is managed by the pco according to the Neutral Zone logic. The Fig.14 describes the management of the three-way-valve logic. WATER TEMPERATURE SET+DIFF. SET NEUTRAL ZONE (see Ref. C2-Ref. D1) OPING/ CLOSING % OF THE THREE-WAY VALVE TIME A A A A A A A A A A A B B B B B B B B B B B B B TEMPO A= opening and closing percentage of the three-way-valve, Ref. W10; B= steps activation/deactivation time, Ref. W9 Used Masks: Fig.14 REGULATED FREE-COOLING FANS LOGIC Ref. C2 Ref. D1 Ref. W9 Ref. W10

33 Free-Cooling system management 31 When the temperature detected by the probe is lower than the setpoint value (under the Neutral Zone), the pco start closing the three-way-valve ( A corresponds to the decrees value Ref. W10 B is the time value Ref. W9) until the valve will be completely closed, or the temperature will go back within the Neutral Zone. When the temperature detected by the probe is higher than the setpoint value + differential (over the Neutral Zone), the pco start opening the three-way-valve ( A corresponds to the decrees value Ref. W10 B is the time value Ref. W9) until the three-way-valve will be completely open, or the detected temperature will go back within the Neutral Zone. GLISH

34 32 Management of compressors operation CHAPTER 10 GLISH M ANAGEMT OF COMPRESSORS OPERATION 10.1 Unit type and compressor number ATTTION The unit type and compressor number exclusively depend on the unit manufacturing characteristics. The parameters which configure the unit type and the compressor number are directly set by the manufacturer and absolutely must not be modified. Their modification, carried out by not qualified personnel, could seriously damage the unit operation. Each pco module is programmed setting both the type of unit and the global number of compressors. The type of unit can be selected by the mask, accessible into (see Ref. G1). The type of unit can be: Single-circuit N 2 Scroll Comp.: if the unit is single-circuit with two SCROLL compressors Single-circuit N 3 Scroll Comp.: if the unit is single-circuit with three SCROLL compressors Single-circuit N 1 Semi hermetic + Part. Comp.: if the unit is single-circuit with a Semi hermetic and chocked compressor (ONLY SPECIAL UNITS) Single-circuit N 1 SCREW Compressor: if the unit is single-circuit with a SCREW compressor (ONLY SPECIAL UNITS) 10.2 Working hours and startings of compressors and of the unit pco stores the working hours and the number of startings of each compressor and of the unit (see Ref. J1, Ref. J4, Ref. J5, Ref. J6, Ref. J7, Ref. J8, Ref. J9). Furthermore, in the appropriate mask it is possible to set a working threshold (see Ref. J6). When the compressors and the unit reach a number of working hours higher than the preset threshold, an alarm message will be displayed to indicate that prompt maintenance is needed (see Ref. AM27, Ref. AM30). The alarm message doesn t block the unit. ATTTION After the maintenance, the operator must reset the timer and the contactors by means of the appropriate masks of WORKED HOURS loop (see Ref. J7, Ref. J10, Ref. J11, Ref. J16, Ref. J17, Ref. J18, Ref. J19). The reset procedure (consult the appropriate masks of paragraph " Masks requiring a password") is necessary to avoid that the pco terminal continues to signal the maintenance alarm. After resetting the timer and the contactors, reset the alarm as indicated in paragraph "18.2 Alarm resetting". Used masks: Ref. J1 Ref. J7 Ref. J4 Ref. J10 Ref. J5 Ref. J11 Ref. J6 Ref. J16

35 Management of compressors operation Compressors sequencing procedure The sequencing procedure consists on the starting/stopping of compressors following a logic which allows all compressors to operate at the same number of hours. The compressors sequencing procedure is enabled when the parameter (see Ref. G3) is set as, and is disabled when this parameter is set as. The compressors sequencing procedure will help to guarantee all compressors long life. Used masks: GLISH Ref. G3 BEWIT Compressor sequencing procedure disabled DANGER The sequencing procedure of compressors must NEVER be disabled. However, pco allows to set the parameter as. This setting can be used only in some particular situations, referred to special units, and must not be used in standard units because it could cause the unit to malfunction. On the graphic of Fig.15 is explained an example of starting and stopping logic during the first start-up of a two compressors unit with sequencing procedure disabled. The following graphic shows the insertion of compressors, according to the water inlet temperature, starting from a situation of unit completely stopped. Water Temperature SET: see Ref. C2 DIF: see Ref. D1 SET+DIFF DIFF/2 SET Time CIRCUIT 1 compr.1 compr.2 Unit stopped First start-up SINGLE-CIRCUIT UNIT WITH TWO COMPRESSORS Not capacity controlled compr. OFF ON Fig.15 GRAPHIC OF THE COMPRESSORS SEQUCING PROCEDURE DISABLED

36 34 Management of compressors operation GLISH Sequencing procedure per compressor This procedure manages all compressors starting and stopping following the FIFO logic: that is, in the event of cold request the first compressor started, when this request decreases, will be the first stopped. At the following request the compressor that has been idle for more time, will start. On the graphic of Fig.16 is explained an example of starting and stopping during the first start-up of a two compressors unit without capacity control. The following graphic explains the compressors sequencing logic, according to the water inlet temperature, starting from a situation of completely stopped unit. Water Temperature SET: see Ref. C2 DIF: see Ref. D1 SET+DIFF DIFF/2 SET Time Unit stopped First start-up CIRCUIT 1 compr.1 compr.2 SINGLE-CIRCUIT UNIT WITH TWO COMPRESSORS Not capacity controlled compr. OFF ON Fig.16 GRAPHIC OF THE COMPRESSORS SEQUCING PROCEDURE ABLED 10.4 Compressors Pump-Down procedure (only AS FC units) If Pump-Down procedure is enabled (see Ref. G13), the last operating compressor will be stopped following the modality described below. This procedure is used to avoid that compressors suck refrigerant at liquid state, during the successive unit starting. When the last compressor stopping is requested, the Pump-Down procedure starts by switching on a solenoid-valve which closes the refrigerant circuit just after the condenser. When the preset low pressure threshold will be reached (see Ref. G14) the compressor will be stopped. After a delay time set by a certain parameter (see Ref. G14), the low pressure threshold could not be reached. In this case, the compressor will stop and will cause a Wrong Pump-Down alarm tripping (see Ref. AM14, Ref. AM28) which stops the interested circuit. The pump-down, if enabled, is carried out even if the unit is in OFF status, by pressing h + g buttons of pco terminal.

37 Management of compressors operation 35 The following graphics explain Pump-Down procedure logic: Warm Request SI NO GLISH Time Refrigerant Solenoid Valve ON OFF Time Refrigerant Pressure PRESSURE AT THE D OF PUMP-DOWN A B Compressor Time case A ON OFF compressor stopping for low pressure level reached Compressor Time case B ON OFF compressor stopping for max. time reached with the tripping of Wrong Pump-Down Alarm Time Fig.17 PUMP-DOWN LOGIC

38 36 Management of compressors operation Used masks: GLISH Ref. G13 Ref. G14 Ref. G Compressors Unloading procedure This procedure is needed during peak periods of cooling requirements, for example when the unit has not been started for a long period of time. In these conditions, the water temperature at evaporator inlet could be excessively high to request a refrigerant rating higher than the one designed for the unit. The unit overload could cause the tripping of all compressors which must work at extreme conditions. The overloaded compressors could overheat and cause the tripping of thermal protections, or the refrigerant gas pressure could reach alarm levels which will block the unit. pco will allow to avoid these problems by unloading procedure. This procedure will cause the forced exclusion of one compressor for each circuit, until the alarm condition stops. The unloading is carried out without considering the temperature regulation, the sequencing procedure and the min. time for the capacity control of the compressors. The unit will slowly return to normal operating conditions, without exceeding its capacities. Table 4 indicates the outlets interested by unloading for all the unit configurations. If the unloading is requested, the interested compressor is immediately disabled, without considering the sequencing procedure, the temperature regulation and the min. time for compressor starting. UNIT TYPE UNLOADING OF CIRCUIT 1 2 Scroll compressors the compressor 2 is put in OFF 3 Scroll compressors the compressor 3 is put in OFF Table 4 COMPRESSORS INTERESTED BY UNLOADING NOTE At the following starting of the compressors, stopped for unloading, the delays related with the compressors or the delay of the capacity control enabling will be always respected. The compressors exclusion by unloading procedure can be established by temperature values measured by -BEWIT probe (see Ref. E1) or by pressure values measured by -BHP1 and -BHP2 high transducers (see Ref. E3).

39 Management of compressors operation Unloading procedure by high pressure probes It is possible by setting a pressure setpoint, a differential and an Unloading time (see Ref. O2 and Ref. O3). The Unloading procedure, which follows the logic explained on the graphic of Fig.18, starts when the pressure measured by high pressure transducers is higher than or equal to the prefixed setpoint. The procedures stops if: A the pressure, measured during Unloading time, decreases under the Set - Differential value. B after Unloading time, the pressure is lower than the prefixed setpoint. High pressure probes GLISH SET B SET-DIFF A Unloading Procedure Time case A case B OFF ON OFF ON Unloading time Unloading time Fig.18 OPERATING LOGIC OF UNLOADING BY HIGH PRESSURE PROBES Time Used masks: Ref. O2 Ref. O3 Ref. G7

40 38 Fans operation management CHAPTER 11 GLISH FANS OPERATION MANAGEMT There are always two independent and separate groups of fans, one is connected to the refrigerant circuit and the other one to the Free Cooling circuit (see figure below). The condensing fans are activated according to the pressure detected by the high pressure transducers (-BHP1). The Free Cooling fans are activated according to the cool request (Neutral Zone temperature regulation) detected by the probe (-BTOWT if the tank is present, - BEWOT or -BEWIT). For further information see Chapter 9 Free-Cooling system management. ELECTRIC BOARD FREE COOLING CONDSING FANS FANS 11.1 Condensing Fans High pressure transducers connected to pco board (see paragraph "2.1 Pressure transducers") can be used to manage the fans in three ways The enabling of fans is fixed according to the pressures measured by high pressure transducers of the circuit Management by step During step regulation, the unit fans are divided in two subgroups composed of one or more fans. This subdivision is fixed during design phase and depends on the way the electrical connections of fans have been carried out (consult the wiring diagram of the unit). The activation of one fans step corresponds to the starting of one fans subgroup. The Fig.19 describes the two fans step management logic (see Ref. N3-Ref. N4Ref. N5, Ref. N6, Ref. N9). For each of the two steps can be set a proper setpoint value (Set 1, Set2); the differential (Diff) can be set for the first step, for the second step it is calculated by the electronic control (Diff 1 ). FAN STATUS STEP 2 STEP 1 OFF OFF 2nd fans subgroup ON ON OFF 1st fans subgroup } } 1 VALUE MEASURED BY HIGH PRESSURE TRANSDUCERS Used masks: Fig.19 FANS ABLING LOGIC BY STEP Ref. N3 Ref. N4 Ref. N1

41 Fans operation management Management by variable speed The speed of the fans can be modified (see Ref. N1) using a phase-cutting regulator managed by pco. To determine the min. and max. speed of fans, pco uses the parameters of mask Ref. N7, the pressure setpoint and the differential (see Ref. N7-Ref. N9, Ref. N10). The fans speed regulation is carried out only if the following conditions are respected, otherwise the fans will remain off: The unit is in ON status and at least one compressor is in ON. No alarm condition referred to the fan is present: Fan overload / Anomaly on the speed regulator. During normal operation the fans are stopped when the pressure measured by the high pressure transducer (-BHP1) is lower than Set or when the last operating compressor of the unit is stopped. Furthermore, it is possible to fix two differentials (Diff and Diff 1 ) where Diff is used for daily operation and Diff1 for nightly operation. Fig.20 describes the operating logic of fans speed regulation. GLISH FANS SPEED % of the max. speed fans ON % of the min. speed fans OFF Set } } Diff Diff 1 Set+Diff Set+Diff 1 VALUE MEASURED BY HIGH PRESSURE TRANSDUCERS Fig.20 FANS ABLING LOGIC BY SPEED REGULATOR The starting of fans by variable speed regulation is influenced also by the settings described in the paragraph " Speed-Up time logic". Used masks: Ref. N1 Ref. N7 Ref. N9 Ref. N Management by variable speed on the medium value The fan speed can be adjusted on the pressure medium value (see Ref. N1). To fix the min. and max. speed of fans, pco uses the parameters of mask Ref. N7, the pressure setpoint and the differential (see Ref. N12). pco stores immediately the pressure values measured by the transducer(-bhp1) creating a value storing loop. The medium value among these stored values will give the pressure value used to calculate the fans speed. At compressor starting, this regulation can be carried out after an adjustable delay time (Ref. N11). It will continue until the medium pressure reaches the regulation threshold on the actual value. When the variable speed regulation on the pressure medium value is not enabled, pco regulates the fans following the variable speed regulation logic (see paragraph " Management by variable speed").

42 40 Fans operation management Used masks: GLISH Ref. N1 Ref. N7 Ref. N11 Ref. N Speed-Up time logic The Speed-Up time logic can be used only if the fan operation is set as or (see Ref. N1). The characteristics of the normally used fans don t allow their starting when the parameter is set to a too low value. The problem depends on the initial current reduction to start-up fans which, in these conditions, is too low. The problem has been solved using the parameters and, used when the starting of fans is requested. These parameters allow to fix a period of time during which the fan rotation speed is forced to the value set (see Ref. N8). After the speed will be reduced according to the setting of parameter. Fig.21 shows the Speed-Up time logic. FAN SPEED fans ON per cent speed in speed-up fans ON min. speed fans OFF TIME Fig.21 SPEED-UP TIME LOGIC Therefore, if is set as zero, it will not be possible to start the fans with a value set to a value lower than 30% for SSN versions and under 50% for N versions. Used masks: Ref. N1 Ref. N8

43 Fans operation management Nightly operation pco control can manage the fans in nightly modality by enabling the parameter Low Noise (see Ref. N2). This modality allows, at a certain adjustable hour (see Ref. R2), to decrease the max. number of fan turning in order to reduce the noise level. Used masks: Ref. N1 Ref. N2 GLISH Ref. N5 Ref. N6 Ref. N10 Ref. N21 Ref. R Free Cooling fans The Free-Cooling fans activation/disactivation depends on the Neutral Zone temperature regulation. The probes -BTOWT, -BEWOT or -BEWIT are connected to the pco board (see paragraph "2.1 Trasduttori di pressione"), and can be utilized to manage the Free-Cooling coils fans in two different ways : by steps by variable speed (regulated) ATTTION The fans can be activated only if the Free-cooling system is on and the three-ways-valve in completely open. During the normal operation the fans work according to the Neutral Zone temperature regulation. In the graphic of Fig.22 and Fig.23 it is possible to see the fans operation with neutral zone. If the temperature checked by the regulation probe (BEWOT, BEWIT or BEWOT see Ref. G3) is lower than the setpoint value (Ref. C2) (under the Neutral Zone) the free-cooling fans stop, while if the temperature is higher than the setpoint value (Ref. C2) + differential (Ref. D1) (over the Neutral Zone), the free-cooling fans start up. The fans operation depends on their management modus (by steps, regulated Ref. W4) as explained below. Used Masks: Ref. C2 Ref. D1 Ref. G3 BEWIT The fans speed regulation is carried out only if the following conditions are respected, otherwise the fans will remain off: The unit and the free-cooling coil are ON fans start up depends on the free-cooling coils Any alarm condition referred to the free-cooling circuit fan: - Fan overload - Anomaly on the speed regulator (regulated only)

44 42 Fans operation management GLISH During step regulation, the unit fans are divided in three subgroups composed of one or more fans. This subdivision is fixed during design phase and depends on the way the electrical connections of fans have been carried out (consult the wiring diagram of the unit). The activation of one fans step corresponds to the starting of one fans subgroup. The Fig.22 describes the three fans step management logic. The parameter Ref. W5 set a delay time between two steps. WATER TEMPERATURE SET+DIFF. NEUTRAL ZONE (see Ref. C2-Ref. D1) SET FANS STATUS TIME Fan ON Group 2 Fan ON Group 1 Fan OFF Group 1 Used Masks: Ref. W5 Fig.22 FREE-COOLING FANS GROUP ACTIVATION LOGIC Ref. W5 TIME Ref. W FC fans regulated by variable speed The speed of the fans can be modified using a phase-cutting regulator managed pco. The pco utilizes the following parameters to: set the min. and max. fans speed, mask Ref. W7; set the fans speed increase or decrease, mask Ref. W6; set the steps activation time (% of increase), mask Ref. W5. During normal operation the fans are managed according to the Neutral Zone temperature regulation.

45 Fans operation management 43 WATER TEMPERATURE SET+DIFF. NEUTRAL ZONE (see Ref. C2-Ref. D1) GLISH SET TIME FANS % INCREASE A A A A A A A A A A A A A B B B B B B B B B B B B B TIME A= speed increase or decrease percentage, Ref. W6; B= activation/disactivation time between steps, Ref. W5 Fig.23 FREE-COOLING REGULATED FANS LOGIC When the temperature checked by the probe is lower than the setpoint (under the Neutral Zone), the pco decreases the fans rotation speed ( A is the speed value Ref. W6 and B is the time value Ref. W5) until the free-cooling fans stop, or until the temperature reaches the Neutral Zone. If the temperature is higher than the setpoint + differential (over the Neutral Zone), the pco increases the fans speed ( A is the speed value Ref. W6 and B is the time value Ref. W5) until the fans reach the maximum speed or the temperature goes back into the Neutral Zone. The graphic in Fig.20 explains the Free-Cooling fans operation according to the Neutral Zone logic. ATTTION The management of the fans by regulation logic depend even on the parameters described in paragraph " Speed-Up time logic".

46 44 Fans operation management Used Masks: GLISH Ref. W5 Ref. W6 Ref. W7

47 Single or double pump operation management 45 CHAPTER 12 S INGLE OR DOUBLE PUMP OPERATION MANAGEMT 12.1 Operating hours and number of startings of the pump pco stores the operating hours and the number of startings of each pump (see Ref. J2, Ref. J3). Furthermore, in the appropriate mask it is possible to set a operating threshold (see Ref. J6). When the operating hour threshold is exceeded, an alarm message will be displayed to indicate that prompt maintenance is needed (see Ref. AM27, Ref. AM28). The alarm message doesn t block the unit. GLISH ATTTION After the maintenance, the operator must reset the timer and the contactors by means of the appropriate masks of WORKED HOURS loop (see Ref. J8, Ref. J9). The reset procedure (consult the appropriate masks of paragraph " Masks requiring a password") is necessary to avoid that the pco terminal continues to signal the maintenance alarm. After resetting the timer and the contactors, reset the alarm as indicated in paragraph "18.2 Alarm resetting". Used masks: Ref. J2 Ref. J3 Ref. J Pump management and operation pco allows to manage either one single pump or two pumps. In the event of double pump it is managed one pump at a time while the other one remains in stand-by. And in the event of anomaly on the operating pump, there is the instantaneous automatic commutation to the other pump. Furthermore, always in the event of double pump, it can be automatically managed by pco enabling the parameter (see Ref. M2)or manually by parameter (see Ref. M5). The pump outlet is enabled when all the following conditions are respected: The unit is in ON status; No alarm of the followings is present: Pump overload Water differential pressure switch alarm Phase sequence alarm Level indicator alarm Clock board damaged or disconnected Eeprom damaged When the unit is put in STAND-BY by pressing g + h buttons, the operating pump will be disabled at the end of the time set by the parameter (see Ref. M4)The graphic of Fig.24 explains the pump operating logic, already described: ON OFF ON OFF Unit operation Pump operation Pump stopping delay Fig.24 PUMP OPERATION LOGIC

48 46 Single or double pump operation management GLISH In the event of alarm tripping which stops the pump, the pump stops instantaneously, independently from the parameter (see Ref. M4). Used masks: Ref. M Automatic rotation pco allows to select an adjustable parameter which manages the automatic rotation of pumps (see Ref. M2) in order to equalize the number of operating hours (see Ref. J2, Ref. J3). When the automatic rotation is enabled, at each restart of the unit and when the threshold is reached (see Ref. M3) the pump which was stopped starts. Used masks: Ref. M2 Ref. M Manual rotation When the pump automatic rotation is disabled (see Ref. M2), pco allows to manually manage the pump by enabling the single pump using the mask (see Ref. M5). Used masks: Ref. M2 Ref. M5

49 Manual procedure 47 CHAPTER 13 M ANUAL PROCEDURE The manual procedure is used only to verify the correct operation of electrical components during eventual testing or assistance testing, only in presence of the min. working conditions (without any alarm which stops the unit). During manual operation, the unit switches on but it can not normally operate. However, all the safety devices connected to the alarms will remain enabled. Particular attention must be done when the manual procedure is enabled because the (ON/OFF) status of the unit electrical components doesn t change automatically, but it should be set by the operator. To start, enter the menu with password (see Chapter 17 Masks requiring a password ), go to menu loop and enter the menu (see Ref. K1); then change to the field. If the unit was on ( indication displayed), after enabling the manual procedure the unit is automatically put in STAND-BY ( indication displayed - see Ref. A1). In the same menu it is possible to manually start of stop the pump operation. In the other masks, marked by indication, it will be possible to start manually the compressors (the pump must be on and the circuits must not be shut down - Ref. K2 -) and fans. If during the operation in manual procedure the unit is switched off for a power failure or switching off the unit by the breaker, at the following starting the manual procedure is automatically disabled. GLISH Used masks: Ref. K1 Ref. K2 Ref. K3 Ref. K4 Ref. K5 Ref. K9 Ref. K10 Ref. K7 Ref. K8

50 48 Electronic thermostatic valve CHAPTER 14 GLISH 14.1 Operation E LECTRONIC THERMOSTATIC VALVE The electronic thermostatic valve regulates the refrigerant fluid flow at evaporator inlet, according to the superheating value measured by the evaporation pressure and the temperature value at compressor suction. They are installed only if requested. The use of the electronic lamination device instead of the traditional one: allows the operation with sensibly lower condensation values (night hours, areas with a cool climate, winter seasons); allows to use capacity controls until the 20% of the total power without the risk of liquid returning or instability of the evaporator; avoids dangerous fluctuations of the evaporation pressures, typical of the mechanical regulation. NOTE The valve will try to maintain the superheating within the preset value Driver of the thermostatic valve To operate, each electronic thermostatic valve is controlled by an electronic device, called Driver. It is furnished with a pressure probe and a temperature probe positioned at evaporator outlet. Each Driver is electronically connected to pco board and receives from it the settings inserted by means of Driver parameters. Furthermore, it receives and translates the measurement values by the two connected probes. It elaborates the data and controls the thermostatic valve, assuring an exact and a continuous regulation. Furthermore, it allows pco to display the data about the thermostatic valve status. ATTTION In the event of damage, it is recommended to replace the electronic thermostatic valve with original spare parts only. Used masks: Ref. E14 DANGER Absolutely avoid to modify the parameters about the management of the electronic thermostatic valves. They are set by the manufacturer and depends on the unit design characteristics, therefore they don t need to be modified. NOTE To access the enabled inlets/outlets of Driver, enter mask Ref. E14 (see chapter "16.2 Free Menu") and press twice h button to access this mask.

51 Supervision system 49 CHAPTER 15 pco can manage various supervision protocols. They can be: CAREL MODBUS GSM DIRECT MODEM LONWORKS 15.1 Carel S UPERVISION SYSTEM GLISH Setting CAREL protocol in mask Ref. U2 pco can communicate with all CAREL protocols Modbus Setting Modbus protocol in mask Ref. U2 pco allows to use the supervision system. Modbus protocol allows pco to be managed by a remote supervisor only when a traditional telephone line is available. The communication between pco and the Modbus protocol is carried out following the RS485 standard, for this reason it is necessary to install an appropriate interface Gsm pco allows, by a GSM modem, to send SMS messages (to minimum 1 to maximum 3 numbers) for alarm signalling even if a traditional telephone line is not available. The control is furnished with a book with 3 telephone numbers for message sending. Furthermore, it is possible to select, for each single number, the type of alarm to be sent: all alarms only manual reset alarms only automatic reset alarms At alarm sending, pco will send an appropriate alarm message to the first available number and, if it will not receive an answering message within a pre-set time, the control will send the same alarm message to the second number and then to the third (if they are available). The communication between pco and the GSM modem is carried out following the RS232 standard, for this reason it is necessary to install an appropriate interface. Before using a GSM modem, it is important to assure that: The SIM card of the modem has the PIN code disabled. pco, during the initialisation of the modem, checks if the PIN code has been disabled. In the contrary case, it signals by a message that the PIN is enabled and that it must be disabled. Generally, this control can be done by checking if the red LED of the device is not lit when the modem is powered. If this LED doesn t unlit it is necessary to disable the PIN. The number of the service centre has been already inserted in the SIM card. To receive or send SMS messages it is necessary to insert in the card the number of the Service Centre of the telephone company you want to use. To do this it is necessary to insert the SIM of the modem into a cellular-telephone and use the functions of this telephone. The memory for the SMS of the SIM card is free. Before connecting the modem to the pco, especially it the SIM card is used also for cellular-telephones, it is recommended to cancel all the received messages in order to free the SMS memory. It is possible to set pco for sending SMS alarm messages to any cellular-telephone. 1. Enable the supervision by protocol (see Ref. U1 and Ref. U2); 2. Set the address of pco network and the speed for data communication (see Ref. U2); 3. Enable SMS sending (see Ref. U4), then set a number of cellular-telephone for sending SMS messages and a password for protecting the memory data (see Ref. U3). NOTE It is possible to store until 3 telephone numbers max. It is necessary to insert these numbers slowly in order to give pco the time to store the numbers. The sending of SMS can have the following results: If the modem doesn t answer correctly to the sending request, the application program stores the message, re-initialises the modem and tries the sending again after 18 seconds from the modem initialisation. If the modem accepts the sending request, the message is sent and cancelled from the memory. If the service centre doesn t receive the message or there is an error, the application program cancels the message but signals the error. If, during the sending, there is an input by remote before having obtained the result of the sending from the service centre, pco manages the restarting of the sending process of the SMS message at the end of the connection to the supervisor Direct Modem (Rs232) Setting Direct Modem protocol in mask Ref. U2 pco allows to use the supervision system. Direct Modem protocol allows pco to be managed by a remote supervisor only when a traditional telephone line is available. The communication between pco and the Direct Modem protocol is carried out following the RS232 standard, for this reason it is necessary to install an appropriate interface.

52 50 Supervision system GLISH 15.5 LonWorks Setting LonWorks protocol in mask Ref. U2 pco allows to use the supervision system. LonWorks protocol allows pco to be managed by a remote supervisor by connecting it directly to a LonWorks network. The communication between pco and the LonWorks protocol is carried out following the RS485 standard, for this reason it is necessary to install an appropriate interface. Used masks: Ref. U1 Ref. U Variables managed by the electronic control pco communicates with supervision systems using a serial connection, used to receive or send variables which manage the system operation. In the following paragraphs are listed all the variables managed by pco application program, with their descriptions, the indication of the data flow at pco outlet (Out), at pco inlet or both at pco inlet and outlet (In/Out) Digital variables Variable address Variable name Description Flow 1 QAL_SONDA_BFC Alarm temperature probe BFCIT damaged or disconnected Out 95 2 QAL_SONDA_AMB1 Alarm temperature probe BAT1 damaged or disconnected Out 95 3 QAL_SONDA_AMB2 Alarm temperature probe BAT2 damaged or disconnected Out 95 4 QAL_VT_FC Fans overload / Freecooling circuit regulator anomaly Out 95 5 _FREECOOL Freecooling enabling Out 95 6 VT_FC_GRADINI Freecooling Ventilation type (0= Regulated - 1= A Steps) Out 95 7 _SONDA_BFC BFCIT probe enabling Out 95 8 _SONDA_AMB1 BAT1 probe enabling Out 95 9 _SONDA_AMB2 Bat2 probe enabling Out TIPO_SONDE_HP2 Circuit 2 high pressure probe type (0= 4-20 ma - 1= 0-5 Vdc) Out TIPO_SONDE_LP2 Circuit 2 low pressure probe type (0= 4-20 ma - 1= 0-5 Vdc) Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out 95 Variable type for LonWorks network

53 Supervision system 51 Variable address Variable name Description Flow Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out Not utilized Out QEPROMNOOK Flash memory malfunction alarm Out QAL_CLOCK Clock damaged alarm Out QAL_FLUS_ACQ Water differential pressure switch alarm Out QAL_LIV_SERB Tank level alarm Out QAL_POMPA1 Pump 1 overload alarm Out QAL_POMPA2 Pump 2 overload alarm Out QAL_TV_ALREG_1 Fan overload alarm/ Anomaly alarm of the speed regulator group 1 Out QAL_TV_ALREG_2 Fan overload alarm/ Anomaly alarm of the speed regulator group 2 Out QAL_HP_CIRC1 High pressure alarm circuit 1 Out QAL_HP_CIRC2 High pressure alarm circuit 2 Out QAL_LP_CIRC1 Low pressure alarm circuit 1 Out QAL_LP_CIRC2 Low pressure alarm circuit 2 Out QAL_P_HP_CIRC1 High pressure alarm circuit 1 Out QAL_P_HP_CIRC2 High pressure alarm circuit 2 Out QAL_PHP1_TC13 High pressure switch alarm / Overload of compressor 3 circuit 1 Out QAL_PHP2_TC23 High pressure switch alarm / Overload of compressor 3 circuit 2 Out QAL_TERM_C_1_1 Overload of compressor 1 circuit 1 Out QAL_TERM_C_1_2 Overload of compressor 2 circuit 1 Out QAL_TERM_C_2_1 Overload of compressor 1 circuit 2 Out QAL_TERM_C_2_2 Overload of compressor 2 circuit 2 Out QAL_PROT_INT_C1 Integral protection alarm of compressor 1 Out QAL_PARTW_COMP1 Wrong partwinding alarm of compressor 1 Out QAL_LIV_OLIO1 Oil level alarm of compressor 1 Out QAL_OLIO_COMP1 Oil pressure switch alarm of compressor 1 Out QAL_OLIO_COMP2 Oil pressure switch alarm of compressor 2 Out QAL_PD_CIRC1 Wrong pump-down procedure alarm circuit 1 Out QAL_PD_CIRC2 Wrong pump-down procedure alarm circuit 2 Out QAL_ALIMT Three-phase supply anomaly alarm Out QAL_HT_IN_ACQ High evaporator water inlet temperature alarm Out QAL_LT_IN_ACQ Low evaporator water inlet temperature alarm Out QAL_HT_OUT_ACQ High evaporator water outlet temperature alarm Out QAL_LT_OUT_ACQ Low evaporator water outlet temperature alarm Out QAL_HT_SERB High tank water outlet temperature alarm Out QAL_LT_SERB Low tank water outlet temperature alarm Out QAL_SONDA_B5 Alarm pressure transducer -BHP1 damaged or disconnected Out QAL_SONDA_B13 Alarm pressure transducer -BHP2 damaged or disconnected Out QAL_SONDA_B7 Alarm pressure transducer -BLP1 damaged or disconnected Out QAL_SONDA_B15 Alarm pressure transducer -BLP2 damaged or disconnected Out QAL_SONDA_B1 Alarm temperature probe -BEWIT damaged or disconnected Out QAL_SONDA_B2 Alarm temperature probe -BEWOT damaged or disconnected Out QAL_SONDA_B23 Alarm temperature probe -BTOWT damaged or disconnected Out QAL_SONDA_B3 Alarm temperature probe -BD1 damaged or disconnected Out QAL_SONDA_B11 Alarm temperature probe -BD2 damaged or disconnected Out QAL_SONDA_B9 Alarm temperature probe -BAT1 damaged or disconnected Out QAL_ORE_UNITA Unit maintenance alarm Out QAL_ORE_POMPA1 Pump 1 maintenance alarm Out QAL_ORE_POMPA2 Pump 2 maintenance alarm Out QAL_ORE_C_1_1 Compressor 1 of circuit 1 maintenance alarm Out QAL_ORE_C_1_2 Compressor 2 of circuit 1 maintenance alarm Out 95 Variable type for LonWorks network GLISH

54 52 Supervision system GLISH Variable address Variable name Description Flow 88 QAL_ORE_C_1_3 Compressor 3 of circuit 1 maintenance alarm Out QAL_ORE_C_2_1 Compressor 1 of circuit 2 maintenance alarm Out QAL_ORE_C_2_2 Compressor 2 of circuit 2 maintenance alarm Out QAL_ORE_C_2_3 Compressor 3 of circuit 2 maintenance alarm Out QAL_N_SBRIN_1 Alarm max. number of defrostings per hour circuit 1 Out QAL_N_SBRIN_2 Alarm max. number of defrostings per hour circuit 2 Out QAL_NO_MODUL1 Alarm Master module disconnected Out QAL_NO_MODUL2 Alarm module 2 disconnected Out QAL_NO_MODUL3 Alarm module 3 disconnected Out QAL_NO_MODUL4 Alarm module 4 disconnected Out QAL_PROBE_D1 Alarm driver 1 probe error Out QAL_EEPROM_D1 Alarm driver 1 eeprom error Out QAL_STEP_MOT_D1 Alarm driver 1 motor step error Out QAL_BATTERY_D1 Alarm driver 1 coil error Out QAL_MOP_DEL_D1 Alarm driver 1 high pressure Out QAL_LOP_DEL_D1 Alarm driver 1 low pressure Out QAL_LOW_SH_D1 Alarm driver 1 low superheat Out QAL_VLV_NCL_D1 Alarm driver 1 valve not closed (at unit switching off) Out QAL_HIGH_SH_D1 Alarm driver 1 timeout max. suction in MOP Out QAL_PROBE_D2 Alarm driver 2 probe error Out QAL_EEPROM_D2 Alarm driver 2 eeprom error Out QAL_STEP_MOT_D2 Alarm driver 2 motor step error Out QAL_BATTERY_D2 Alarm driver 2 coil error Out QAL_MOP_DEL_D2 Alarm driver 2 high pressure Out QAL_LOP_DEL_D2 Alarm driver 2 low pressure Out QAL_LOW_SH_D2 Alarm driver 2 low superheat Out QAL_VLV_NCL_D2 Alarm driver 2 valve not closed (at unit switching off) Out QAL_HIGH_SH_D2 Alarm driver 2 timeout max. suction in MOP Out QAL_DRIVER1 Alarm driver 1 disconnected Out QAL_DRIVER2 Alarm driver 2 disconnected Out _ON_OFF_EXT Remote on/off inlet enable In/Out _EST_INV_REM Summer/Winter inlet enable In/Out AUTOSTART Automatic restart after blackout In/Out FORZ_FUNZ_LOC Module forced to local operation In/Out VTIL_DUE_FILE Ventilation type (0=Single-Row - 1=Double-Row) Out ABIL_LOW_NOISE Low Noise function enable In/Out ABIL_RECUPERO Heat recovery enable Out _FORZ_V_SBR Fans forcing in dripping In/Out _ALARM_SERB Tank level alarm enable Out ABIL_AL_ALIMT Supply alarm enable In/Out RIPR_AL_ALIMT Supply alarm restoring (0=Manual - 1=Auto) In/Out _FASCIA_S Unit on/off weekly band enable In/Out _FASCIA_G Unit on/off daily band enable In/Out TIPO_UNITA Unit type (0=CH - 1=CH+HP) Out TIPO_CONDS Condensation type (0=Air -1=Water) Out LOGIC_PARZ Capacity control operating logic (0=Normal Close - 1=Normal Open) Out TIPO_COMP Compressor type (0=BITZER - 1=COMER-FU SHG) Out ABIL_SERBATOIO Tank presence enable Out ABIL_RES_SERB Tank resistance presence enable Out UNIT_CELS_FAR Temperature unit of measurement (0= C - 1= F) In/Out UNIT_BAR_PSI Pressure unit of measurement (0=Bar - 1=PSI) In/Out _SONDA_B1 Water inlet temperature probe -BEWIT enable In/Out _SONDA_B2 Water outlet temperature probe -BEWOT enable In/Out _SONDA_B3 Coil 1 temperature probe -BD1 enable In/Out _SONDA_B11 Coil 2 temperature probe -BD2 enable In/Out 95 Variable type for LonWorks network

55 Supervision system 53 Variable address Variable name Description Flow 143 _SONDA_B5 High pressure probe -BHP1 of circuit 1 enable In/Out _SONDA_B13 High pressure probe -BHP2 of circuit 2 enable In/Out TIPO_SONDE_HP High pressure probe type (0=4-20 ma - 1=0-5 Vdc) Out _SONDA_B7 Low pressure probe -BLP1 of circuit 1 enable In/Out _SONDA_B15 Low pressure probe -BLP2 of circuit 2 enable In/Out TIPO_SONDE_LP Low pressure probe type (0=4-20 ma - 1=0-5 Vdc) Out _SONDA_B9 Ambient temperature probe -BAT1 enable In/Out _SONDA_B23 Tank temperature probe -BTOWT enable In/Out ABIL_PUMPDOWN1 Pumpdown circuit 1 enable In/Out ABIL_PUMPDOWN2 Pumpdown circuit 2 enable In/Out ABIL_RES_ANTIG Antifreeze resistance enable Out CLOCK_PRESTE Clock present Out DISABIL_CIRC1 Exclusion operation of circuit 1 In/Out DISABIL_CIRC2 Exclusion operation of circuit 2 In/Out ABIL_DUE_POMPE Double pump enable Out ABIL_ROT_POMPE Pump automatic rotation In/Out SI_ON_POMPA1 Pump 1 starting enable In/Out ABIL_POMP_ANTIG Pump enable as antifreeze In/Out _DRIVER_VLV Electronic thermostatic valve driver enable Out _ON_OFF_SUP On/Off by supervisor enable In/Out ON_OFF_SUP On/Off by supervisore In/Out ABIL_MODULI Modular operation enable Out MOD_MASTER_ON The unit is Master module Out MOD_SLAVE_ON The unit is Slave module Out NO_MODULARE Unit in local operation Out ABIL_COMP_1_1 Compressor 1 circuit 1 present Out ABIL_COMP_1_2 Compressor 2 circuit 1 present Out ABIL_COMP_1_3 Compressor 3 circuit 1 present Out ABIL_COMP_2_1 Compressor 1 circuit 2 present Out ABIL_COMP_2_2 Compressor 2 circuit 2 present Out ABIL_COMP_2_3 Compressor 3 circuit 2 present Out ABIL_CIRCUITO2 Circuit 2 present Out ABIL_PARZ_G Semi-hermetic compressor capacity control enable Out ABIL_PARZ_C Screw compressor capacity control enable Out ABIL_PIU_COMP Unit with a number of compressors higher than 1 Out OK_MACCH2_MONOV Double-circuit unit Out MACCHINA_P57 Unit Out ESTIN_ONOFF_LOC Summer/Winter and local On/Off enable Out INVERNO Unit in heat pump operation Out _SONDE_HP Presence of a high pressure probe Out _SONDE_LP Presence of a low pressure probe Out _SONDE_BAT Presence of a coil temperature probe Out GLB_ALARMS Presence of at least one alarm Out SETPOINT_FISSO Fixed setpoint enable Out ABIL_SET_COMP Compensated setpoint enable Out ABIL_DOPPIO_SET Double setpoint enable Out ABIL_SET_FASCE Setpoint by bands enable Out ABIL_SET_EXT External setpoint enable Out SBRIN_CONTEMP Contemporaneous defrost enable Out SBRIN_SEPARATO Separated defrost enable Out SBRIN_INDIPD Independent defrost enable Out ABIL_SBR_DT Defrost for dt enable Out ABIL_SBR_TEMP Defrost in temperature enable Out FINE_SBR_TEMP End of defrost in temperature enable Out AB_SBR_SINGOLO Single defrost enable Out 95 Variable type for LonWorks network GLISH

56 54 Supervision system GLISH Variable address Variable name Description Flow 198 AB_BI_SBR Defrost on double-circuits enable Out Analogue variables Variable type for LonWorks network Variable address Variable name Description Flow 1 TEMP_IN_ACQ Evaporator water inlet temperature Out TEMP_OUT_ACQ Evaporator water outlet temperature Out TEMP_OUT_SERB Tank water outlet temperature Out TEMP_BATTERIA1 Coil temperature circuit 1 Out TEMP_BATTERIA2 Coil temperature circuit 2 Out PRESS_COND1 High pressure circuit 1 Out 30 7 PRESS_COND2 High pressure circuit 2 Out 30 8 TEMP_CONV_COND1 High pressure temperature circuit 1 Out TEMP_CONV_COND2 High pressure temperature circuit 2 Out PRESS_EVAP1 Low pressure circuit 1 Out PRESS_ EVAP2 Low pressure circuit 2 Out TEMP_CONV_ EVAP1 Low pressure temperature circuit 1 Out TEMP_CONV_ EVAP2 Low pressure temperature circuit 2 Out TEMP_AMBITE Ambient temperature Out ACTUAL_SHEAT_D1 Driver 1: overheating value Out SUCTION_TEMP_D1 Driver 1: suction temperature Out SUCTION_PRESS_D1 Driver 1: evaporator pressure Out SATURATION_TEMP_D 1 Driver 1: evaporator pressure temperature Out ACTUAL_SHEAT_D2 Driver 2: overheating value Out SUCTION_TEMP_D2 Driver 2: suction temperature Out SUCTION_PRESS_D2 Driver 2: evaporator pressure Out SATURATION_TEMP_D 2 Driver 2: evaporator pressure temperature Out SET_TEMP_CALC Actual temperature setpoint Out MIN_SET_T_EST Min. value of summer temperature setpoint In/Out MAX_SET_T_EST Max. value of summer temperature setpoint In/Out MIN_SET_T_INV Min. value of winter temperature setpoint In/Out MAX_SET_T_INV Max. value of winter temperature setpoint In/Out SET_TEMP_EST Summer temperature setpoint In/Out SEC_SETT_EST Second summer temperature setpoint In/Out SET_TEMP_INV Winter temperature setpoint In/Out SEC_SETT_INV Second winter temperature setpoint In/Out SET_EXT_COMP_E Ambient temperature setpoint for summer compensation In/Out DIFF_COMPSA_E Ambient temperature differential for summer compensation In/Out SET_EXT_COMP_I Ambient temperature setpoint for winter compensation In/Out DIFF_COMPSA_I Ambient temperature differential for winter compensation In/Out MAX_COMPSA Max. compensation value In/Out SET_FASCIA1_EST Second summer temperature setpoint hourly band 1 In/Out SET_FASCIA1_INV Winter temperature setpoint hourly band 1 In/Out SET_FASCIA2_EST Second summer temperature setpoint hourly band 2 In/Out SET_FASCIA2_INV Winter temperature setpoint hourly band 2 In/Out SET_FASCIA3_EST Second summer temperature setpoint hourly band 3 In/Out SET_FASCIA3_INV Winter temperature setpoint hourly band 3 In/Out SET_FASCIA4_EST Second summer temperature setpoint hourly band 4 In/Out SET_FASCIA4_INV Winter temperature setpoint hourly band 4 In/Out MAX_SET_EXT Max. value of setpoint by analogue input In/Out DIFF_TEMP_EST Summer regulation band In/Out DIFF_TEMP_INV Winter regulation band In/Out 105 Variable type for LonWorks network

57 Supervision system 55 Variable address Variable name Description Flow 48 SET_VT_1_1 Setpoint step 1 fans group 1 In/Out SET_VT_1_2 Setpoint step 2 fans group 1 In/Out DIFF_VT_1 Differential to disable fans group 1 In/Out SET_VT_2_1 Setpoint step 1 fans group 2 In/Out SET_VT_2_2 Setpoint step 2 fans group 2 In/Out DIFF_VT_2 Differential to disable fans group 2 In/Out SET_VT_LN_1_1 Second setpoint step 1 fans group 1 In/Out SET_VT_LN_1_2 Second setpoint step 2 fans group 1 In/Out DIFF_VT_LN_1 Second differential to disable fans group 1 In/Out SET_VT_LN_2_1 Second setpoint step 1 fans group 2 In/Out SET_VT_LN_2_2 Second setpoint step 2 fans group 2 In/Out DIFF_VT_LN_2 Second differential to disable fans group 2 In/Out SET_REG_GIRI_1 Setpoint speed control group 1 In/Out DIFF_GIRI_1 Differential speed control group 1 In/Out SET_REG_GIRI_2 Setpoint speed control group 2 In/Out DIFF_GIRI_2 Differential speed control group 2 In/Out DIFF_GIRI_LN_1 Second differential speed control group 1 In/Out DIFF_GIRI_LN_2 Second differential speed control group 2 In/Out SET_NO_MEDIA Setpoint by-pass speed medium control In/Out DIFF_NO_MEDIA Differential by-pass speed medium control In/Out SET_TEMP_UNLOAD Enable threshold of unloading in temperature In/Out DIF_TEMP_UNLOAD Differential unloading in temperature In/Out SET_PRES_UNL_E Enable threshold of unloading with high pressure probes In/Out DIF_PRES_UNL_E Differential unloading with high pressure probes In/Out SET_PRES_UNL_I Enable threshold of unloading with low pressure probes In/Out DIF_PRES_UNL_I Differential unloading with low pressure probes In/Out SET_MAAX_ON_REC Max. pressure of On recovery In/Out SET_ON_SBR Defrost start setpoint In/Out SET_OFF_SBR Defrost end setpoint In/Out SET_MIN_IN_EV_E Setpoint min. summer temperature of evaporator inlet Out SET_MAX_IN_EV_E Setpoint max. summer temperature of evaporator inlet Out SET_MIN_IN_EV_I Setpoint min. winter temperature of evaporator inlet Out SET_MAX_IN_EV_I Setpoint max. winter temperature of evaporator inlet Out SET_MIN_OUT_EV Setpoint min. temperature of evaporator outlet Out SET_MAX_OUT_EV Setpoint max. temperature of evaporator outlet Out SET_LT_SERB Setpoint min. temperature of tank outlet Out SET_HT_SERB Setpoint max. temperature of tank outlet Out SET_AL_LP Low pressure alarm threshold Out DIFF_AL_LP Low pressure alarm differential Out SET_HP_EST Summer high pressure alarm threshold Out DIFF_HP_EST Summer high pressure alarm differential Out SET_HP_INV Winter high pressure alarm threshold Out DIFF_HP_INV Winter high pressure alarm differential Out FSC_MIN_HP Min. full scale for high pressure probes Out FSC_MAX_HP Max. full scale for high pressure probes Out FSC_MIN_LP Min. full scale for low pressure probes Out FSC_MAX_LP Max. full scale for low pressure probes Out SET_FIME_PDOWN Pumpdown end pressure setpoint In/Out SET_POMP_ANTIG Setpoint enable pump as antifreeze In/Out DIFF_POMP_ANTIG Differential pump as antifreeze In/Out SUPER_HEAT_SET_CH Overheating regulation setpoint in CH In/Out SUPER_HEAT_SET_HP Overheating regulation setpoint in HP In/Out SUPER_HEAT_SET_DF Overheating regulation setpoint in DF In/Out THRESHOLD_MOP Protection threshold MOP In/Out SET_RES_ANTIG Antifreeze resistance setpoint In/Out 105 Variable type for LonWorks network GLISH

58 56 Supervision system GLISH Variable address Variable name Description Flow 103 DIFF_RES_ANTIG Antifreeze resistance differential In/Out SET_RES_SERB Tank resistance setpoint In/Out DIFF_RES_SERB Tank resistance differential In/Out TEMP_OUT_MU Temperature displayed in the third row of menu mask Out FSC_MIN_HP2 Circuit 2 high pressure probe minimum value Out FSC_MAX_HP2 Circuit 2 high pressure probe maximum value Out FSC_MIN_LP2 Circuit 2 low pressure probe minimum value Out FSC_MAX_LP2 Circuit 2 low pressure probe maximum value Out TEMP_AMB_1 Ambient Temperature 1 Out TEMP_AMB_2 Ambient Temperature 2 Out TEMP_IN_BATT_FC Freecooling Coils Inlet Water Temperature Out LIM_MIN_DELTAFC Freecooling Delta Minimum Limit Out LIM_MAX_DELTAFC Freecooling Delta Maximum Limit Out DELTA_FC Freecooling Delta activation In/Out 105 Variable type for LonWorks network Entire variables Variable address Variable name Description Flow 1 VIS_REG_GIRI1 Fan 1 speed regulator outlet per cent Out 8 2 VIS_REG_GIRI2 Fan 2 speed regulator outlet per cent Out 8 3 VIS_VALV_COND1 Condenser 1 opening valve per cent Out 8 4 VIS_VALV_COND2 Condenser 2 opening valve per cent Out 8 5 POSITION_VALVE_D1 Thermostatic valve opening circuit 1 Out 8 6 POSITION_VALVE_D2 Thermostatic valve opening circuit 2 Out 8 7 ORA_ON_SET1 Start hour hourly band 1 for setpoint changing In/Out MIN_ON_SET1 Start minutes hourly band 1 for setpoint changing In/Out ORA_ON_SET2 Start hour hourly band 2 for setpoint changing In/Out MIN_ON_SET2 Start minutes hourly band 2 for setpoint changing In/Out ORA_ON_SET3 Start hour hourly band 3 for setpoint changing In/Out MIN_ON_SET3 Start minutes hourly band 3 for setpoint changing In/Out ORA_ON_SET4 Start hour hourly band 4 for setpoint changing In/Out MIN_ON_SET4 Start minutes hourly band 4 for setpoint changing In/Out TIPO_REG_VT Fan regulation type (0=Step Control - 1=Speed Control - 2=Speed Medium Control) Out 8 16 MIN_REG_GIRI Min. speed control Out 8 17 MAX_REG_GIRI Max. speed control Out 8 18 TIME_SPEED_UP Speed-up time Out GIRI_SPEED_UP Fan speed in speed-up Out 8 20 TIME_BY_P_MEDIA By-pass time speed medium control In/Out MIN_REG_VALVC Min. opening of condensation valves Out 8 22 MAX_REG_VALVC Max. opening of condensation valves Out 8 23 RIT_PRES_UNL_E Max. duration for high pressure probe unloading In/Out 8 24 RIT_PRES_UNL_I Max. duration for low pressure probe unloading In/Out 8 25 TIPO_RECUPERO Recovery modality (0=TOTAL - 1=PARTIAL-SEPARATED - 2=PARTIAL-SOLE) In/Out 8 26 TIME_TRA_RECUP Min. time between two recoveries In/Out TIME_MINON_REC Min. time of on recovery In/Out TIME_MINOFF_REC Min. time of off recovery In/Out TIME_RECUP_T1 Delay on outlet recovery enable In/Out TIME_RECUP_T2 Min. time of off recovery In/Out TIPO_SBRINAM Defrost control type (0=Start: DT-End: Timed - 1=Start: Temperature- End: Timed - 2=Start: Temperature-End: Temperature) Out 8 32 MODO_SBRINAM Defrost modality (0=CONTEMPORARY - 1=SEPARATED - 2=INDIPDT) Out 8 33 SBR_MAX_TIME Defrost time In/Out 123 Variable type for LonWorks network

59 Supervision system 57 Variable address Variable name Description Flow 34 SBR_DELAY_TIME Defrost control exclusion time In/Out SBR_CHECK_TIME Defrost control time In/Out SBR_ADD_TIME Defrost additional time In/Out TIME_SBR_T1 Compressor off time before defrost In/Out TIME_SBR_T2 Compressor off time after defrost In/Out VEL_VT_SBR Fan speed in dripping In/Out 8 40 N_ALL_SBR Max. number defrost per hour In/Out 8 41 RIT_AL_IN_ACQ Delay high/low temperature alarms of evaporator water inlet Out RIT_AL_T_SERB Delay high/low temperature alarms of tank water outlet Out RIT_LP_PAR Low pressure alarm delay when compressor starts Out RIT_LP_REG Low pressure alarm delay with operating compressor Out RIT_AL_OLIO Oil level alarm delay Out RIT_AL_FLUS_PAR Flow meter alarm when pump starts Out RIT_AL_FLUS_REG Flow meter alarm with operating pump Out RIT_AL_LIV_SERB Oil level alarm delay Out RIT_AL_ALIMT Supply alarm delay In/Out ORA_ON_LOW_N Starting hour of low noise function band In/Out MIN_ON_LOW_N Starting minutes of low noise function band In/Out ORA_OFF_LOW_N Stopping hour of low noise function band In/Out MIN_OFF_LOW_N Stopping minutes of low noise function band In/Out ACC_DAY_WEEK Starting day of weekly band (1=Sun - 2=Mon - 3=Tue - 4=Wed - 5=Thu - 6=Fry - 7=Sat) In/Out 8 55 SPEGN_DAY_WEEK Stopping day of weekly band (1=Sun - 2=Mon - 3=Tue - 4=Wed - 5=Thu - 6=Fry - 7=Sat) In/Out 8 56 ACC_HOUR Starting hour of daily band In/Out ACC_MINUTE Starting minutes of daily band In/Out SPEGN_HOUR Stopping hour of daily band In/Out SPEGN_MINUTE Stopping minutes of daily band In/Out TIPO_MACCHINA Unit type (1=Single-circuit-N 2 Scroll Comp. - 2=Double-circuit-N 4 Scroll Comp. - 3= Double-circuit-N 5 Scroll Comp. - 4= Double-circuit- N 6 Scroll Comp. - 5=Double-circuit-N 2 Semihermetic+Cap.Cont.Comp. - 6=Single-circuit-N 1 Screw Compressor) Out 8 61 RIT_PARZ Disabling delay on compressor capacity control Out SONDA_REGOLAZ Regulation probe (0=-BEWIT - 1=-BEWOT - 2=-BTOWT) In/Out 8 63 TIPO_ROTAZ Compressor rotation type (0=None - 1=Circuit - 2=Compressor) In/Out 8 64 TIPO_GAS Gas type for pressure/temperature conversion (0=R22-1=R134C - 2=R404A - 3=R407C - 4=R410A - 5=R507C - 6=R209-7=R600-8=R600A - 9=R717-10=R744) In/Out 8 65 TIME_MAX_PDOWN Max. pump-down time In/Out NUM_MODULI Number of modules for modular operation Out 8 67 SONDA_REG_MOD Regulation probe for modular operation (0=-BEWIT - 1=-BEWOT - 2=- BTOWT) Out 8 68 PESO_MODULO1 Weight module 1 for the calculation of temperature regulation Out 8 69 PESO_MODULO2 Weight module 2 for the calculation of temperature regulation Out 8 70 PESO_MODULO3 Weight module 3 for the calculation of temperature regulation Out 8 71 PESO_MODULO4 Weight module 4 for the calculation of temperature regulation Out 8 72 RIT_ATTIV_GRAD Delay between starts out of neutral zone In/Out RIT_DISAT_GRAD Delay between stops out of neutral zone In/Out RIT_AT_INT_GRAD Delay between starts in of neutral zone In/Out TEMPO_INTEGRA PI control integration time In/Out RIT_ON_COMP Delay on compressor start at unit start In/Out T_MIN_OFF Min. time for compressor stop Out T_MIN_ON Min. time for compressor start Out T_STESS_COMP Time between starts of the same compressor Out T_TRA_COMP Time between starts of different compressors Out TIME_PARTW Partwinding time Out 8 82 RIT_AL_PARTW Partwinding alarm delay Out TIME_VALV_INT Intermittent valve time Out 107 Variable type for LonWorks network GLISH

60 58 Supervision system GLISH Variable address Variable name Description Flow 84 TIME_MAX_START Max. start time Out TIME_ROT_POMPE Pump rotation interval In/Out RIT_OFF_ROTP Contemporaneous operation interval In/Out RIT_SPEGN_POMPE Delay on pump stop at unit stop In/Out TIPO_REGOLAZ Regulation type (0=P - 1=P+I - 2=N.Z.) In/Out 8 89 TIPO_SETPOINT Setpoint management modality (0=FIXED - 1=COMPSATED - 2=DOUBLE SETP. - 3=BY BANDS - 4=BY ANALOGUE INPUT) In/Out 8 90 STATO_MACCHINA Unit status (0=Unit Off - 1=Unit On - 2=Unit Off by Bands - 3=Unit Off by Superv. 4=Unit Off by Remote - 5=Unit Off by Alarm -6=Manual Procedure) 91 TXT_T_OUT_MU Temperature display on menu mask (0=Outlet Temp. - 1=Tank Temp. - 2=Regul.Temp.) Out 8 Out Program Version for the variables list sent to the Supervisor Out 8 93 VIS_VALV_FC 3-way-valve opening % Out 8 94 VIS_VT_FC_MOD Freecooling fans working % (with continuous regulation) Out 8 95 RIT_ATT_FC Freecooling activation/disactivation time In/Out RIT_ATT_VT_FC Freecooling fans steps activation control time In/Out RIT_ATT_VALV_FC 3-ways-valve steps activation control time In/Out PERC_VT_FC Fans regulation % (with continuous regulation) In/Out 8 99 PERC_VALV_FC 3-way-valve regulation % In/Out WORD_IN_OUT_1 Inlets status/digital variable 1 outlets (see " NOTE A: Digital Variables") Out WORD_IN_OUT_2 Inlets status/digital variables 2 outlets (see " NOTE A: Digital Variables") 102 WORD_IN_OUT_3 Inlets status/digital variables 3 outlets (see " NOTE A: Digital Variables") Out 8 Out MIN_VEL_FC Freecooling regulated fans minimum speed In/Out MAX_VEL_FC Freecooling regulated fans maximum speed In/Out GIRI_SPEEDUP_FC Freecooling regulated fans Speed-up In/Out TIME_SPEEDUP_FC Freecooling regulated fans speed percentage In/Out 107 Variable type for LonWorks network NOTE A: Digital Variables Variable name Bit Nr. Single bit description WORD_IN_OUT_1 0 Status of digital inlet 1 (0=Closed - 1=Opened) WORD_IN_OUT_1 1 Status of digital inlet 2 (0=Closed - 1=Opened) WORD_IN_OUT_1 2 Status of digital inlet 3 (0=Closed - 1=Opened) WORD_IN_OUT_1 3 Status of digital inlet 4 (0=Closed - 1=Opened) WORD_IN_OUT_1 4 Status of digital inlet 5 (0=Closed - 1=Opened) WORD_IN_OUT_1 5 Status of digital inlet 6 (0=Closed - 1=Opened) WORD_IN_OUT_1 6 Status of digital inlet 7 (0=Closed - 1=Opened) WORD_IN_OUT_1 7 Status of digital inlet 8 (0=Closed - 1=Opened) WORD_IN_OUT_1 8 Status of digital inlet 9 (0=Closed - 1=Opened) WORD_IN_OUT_1 9 Status of digital inlet 10 (0=Closed - 1=Opened) WORD_IN_OUT_1 10 Status of digital inlet 11 (0=Closed - 1=Opened) WORD_IN_OUT_1 11 Status of digital inlet 12 (0=Closed - 1=Opened) WORD_IN_OUT_1 12 Status of digital inlet 13 (0=Closed - 1=Opened) WORD_IN_OUT_1 13 Status of digital inlet 14 (0=Closed - 1=Opened) WORD_IN_OUT_1 14 Status of digital inlet 15 (0=Closed - 1=Opened) WORD_IN_OUT_1 15 Status of digital inlet 16 (0=Closed - 1=Opened) WORD_IN_OUT_2 0 Status of digital inlet 17 (0=Closed - 1=Opened) WORD_IN_OUT_2 1 Status of digital inlet 18 (0=Closed - 1=Opened) WORD_IN_OUT_2 2 Status of digital outlet 1 (0=Opened - 1=Closed) WORD_IN_OUT_2 3 Status of digital outlet 2 (0=Opened - 1=Closed) WORD_IN_OUT_2 4 Status of digital outlet 3 (0=Opened - 1=Closed) WORD_IN_OUT_2 5 Status of digital outlet 4 (0=Opened - 1=Closed) WORD_IN_OUT_2 6 Status of digital outlet 5 (0=Opened - 1=Closed) WORD_IN_OUT_2 7 Status of digital outlet 6 (0=Opened - 1=Closed)

61 Supervision system 59 Variable name Bit Nr. Single bit description WORD_IN_OUT_2 8 Status of digital outlet 7 (0=Opened - 1=Closed) WORD_IN_OUT_2 9 Status of digital outlet 8 (0=Opened - 1=Closed) WORD_IN_OUT_2 10 Status of digital outlet 9 (0=Opened - 1=Closed) WORD_IN_OUT_2 11 Status of digital outlet 10 (0=Opened - 1=Closed) WORD_IN_OUT_2 12 Status of digital outlet 11 (0=Opened - 1=Closed) WORD_IN_OUT_2 13 Status of digital outlet 12 (0=Opened - 1=Closed) WORD_IN_OUT_2 14 Status of digital outlet 13 (0=Opened - 1=Closed) WORD_IN_OUT_2 15 Status of digital outlet 14 (0=Opened - 1=Closed) WORD_IN_OUT_3 0 Status of digital outlet 15 (0=Opened - 1=Closed) WORD_IN_OUT_3 1 Status of digital outlet 16 (0=Opened - 1=Closed) WORD_IN_OUT_3 2 Status of digital outlet 17 (0=Opened - 1=Closed) WORD_IN_OUT_3 3 Status of digital outlet 18 (0=Opened - 1=Closed) WORD_IN_OUT_3 4 Status of recovery 1 outlet (0=Opened - 1=Closed) WORD_IN_OUT_3 5 Status of recovery 2 outlet (0=Opened - 1=Closed) WORD_IN_OUT_3 6 Not utilized WORD_IN_OUT_3 7 Not utilized WORD_IN_OUT_3 8 Not utilized WORD_IN_OUT_3 9 Not utilized WORD_IN_OUT_3 10 Not utilized WORD_IN_OUT_3 11 Not utilized WORD_IN_OUT_3 12 Not utilized WORD_IN_OUT_3 13 Not utilized WORD_IN_OUT_3 14 Not utilized WORD_IN_OUT_3 15 Not utilized GLISH

62 60 Masks no password required CHAPTER 16 GLISH DANGER M ASKS NO PASSWORD REQUIRED The wrong pco programming can cause big damages to the unit; if there is any doubt please call an authorised service centre. NOTE For information about the parameter setting please consult Chapter 20 Setting Tables. ATTTION The displaying of some masks depends on the settings of other masks and also on the unit configuration, decided during design phase Menu During normal operation, press f or g button on the terminals Ref. Mask (*) Range A1 R Notes This is the main mask, which displays, in the second row, the values measured by the temperature probe of evaporator water inlet (-BEWIT probe) and, in the third row, of evaporator water outlet (-BEWOT probe). The first row of the display will show the current time and date. The last row will show the unit status (on, off, manual mode, off by remote control, off by time bands control). In the event of abnormal operation, the flashing message will be displayed in the last row. A2 R Unit specifications, program version. Bios and Boot versions. A3 R Modem status. * R: Read only mask W: Read and write mask.

63 Masks no password required Free Menu Press and release l button on the terminal to access the loop mask (Free Menu); to modify a parameter see Chapter 5 How to modify a parameter in Free Menu Ref. Mask (*) Range B1 R When this mask has been reached, to enter the parameters follow the indications of the following diagram: D1 h f Notes h f h f C1 E1 GLISH * R: Read only mask W: Read and write mask. Inside the masks of a loop (see mask from Ref. C1 to Ref. C8) it is possible to return to Free Menu (see Ref. B1), simply pressing once k button; press it twice to return to the main mask (Ref. A1 - see paragraph "16.1 Menu"). SETPOINT Ref. Mask (*) Range Notes C1 R Identifies the actual unit operation setpoint. C2 W see Ref. V2 step: 00.1 C3 W step: 00.1 C4 W step: 00.1 Use this mask to fix the setpoint and the second setpoint, if enabled. For further information see Chapter 8 Fixed setpoint and Chapter 8 Double setpoint. Use this mask to fix the setpoint of external temperature used to calculate the compensated setpoint. For further information see Chapter 8 Compensated setpoint. Use this mask to fix the max. compensation value. For further information see Chapter 8 Compensated setpoint. C5 W see Ref. V2 step: 00.1 C6 W see Ref. V2 step: 00.1 Use this mask to set the starting hour and the setpoint of the first band. For further information see Chapter 8 Adjustable setpoint by daily bands. Use this mask to set the starting hour and the setpoint of the second band. For further information see Chapter 8 Adjustable setpoint by daily bands.

64 62 Masks no password required GLISH Ref. Mask (*) Range Notes C7 W see Ref. V2 step: 00.1 C8 W see Ref. V2 step: 00.1 Use this mask to set the starting hour and the setpoint of the third band. For further information see Chapter 8 Adjustable setpoint by daily bands. Use this mask to set the starting hour and the setpoint of the fourth band. For further information see Chapter 8 Adjustable setpoint by daily bands. * R: Read only mask W: Read and write mask. USER Ref. Mask (*) Range D1 W step: 00.1 D2 W Notes Use this mask to set the regulation temperature band (Differential). Use this mask to enable the remote ON/OFF of pco (digital input Nr. 1). D3 W An option of the electronic control allows to restart automatically the unit after a blackout or after any power failure. The automatic restart is possible only if the unit, at the power failure, was already ON. For further information consult paragraph "4.2 Automatic restart" D4 W It allows to select the desired language for the masks. For further information consult paragraph "5.3 How to modify the language" * R: Read only mask W: Read and write mask. I/O Ref. Mask (*) Range Notes E1 R Values measured by temperature probes of evaporator water inlet and outlet and tank water outlet. This mask will be displayed only if -BEWIT, -BEWOT and -BTOWT probes have been previously enabled. For further information see Chapter 2 Pressure and temperature transducers E2 R Value measured by temperature probe of condensing coil of circuit 1. This mask will be displayed only if -BD1 and -BD2 probes have been previously enabled. For further information see Chapter 2 Pressure and temperature transducers E3 R Value measured by high pressure transducer of circuit 1. This mask will be displayed only if -BHP1 probe has been previously enabled. For further information see Chapter 2 Pressure and temperature transducers

65 Masks no password required 63 Ref. Mask (*) Range Notes E4 R Values measured by high pressure transducers of circuits 1, expressed in C. This mask will be displayed only if -BHP1 probe has been previously enabled. For further information see Chapter 2 Pressure and temperature transducers E5 R Values measured by low pressure transducers of circuits 1, expressed in bar. This mask will be displayed only if -BLP1 probe has been previously enabled. For further information see Chapter 2 Pressure and temperature transducers GLISH E6 R Values measured by low pressure transducers of circuits 1, expressed in C. This mask will be displayed only if -BLP1 probe has been previously enabled. For further information see Chapter 2 Pressure and temperature transducers E7 R The values detected by the ambient probe 1 and 2 are measured in C. This mask will be displayed only if -BAT1 and -BAT2 probes have been previously enabled. For further information see Capitolo 2 Trasduttori e Sonde. E8 The values detected by the free-cooling temperature probe are measured in C. This mask will be displayed only if -BFCIT probe has been previously enabled. For further information see Capitolo 2 Trasduttori e Sonde. E9 R This mask shows the status of digital inputs of the board: = close: connected to 24 Vac (normal status); = open: not connected to 24 Vac (alarm status). E10 R This mask shows the status of digital outputs of the board: = de-energized outlet; = energized outlet. E11 R This mask shows the status of heat recovery valves of circuit 1. E12 R This mask shows the percentage of fan speed if they are controlled by a speed regulator. For further information see Chapter 11 Fans operation management. E13 R This mask displays the free-cooling fans speed if they are managed by the speed regulator. For further information see Capitolo 11 Ventilatori Free Cooling. E14 R This mask allows to enter the loop about the Driver status of electronic thermostatic valves. It is sufficient to press twice h button to display the following masks. * R: Read only mask W: Read and write mask.

66 64 Masks requiring a password CHAPTER 17 GLISH M ASKS REQUIRING A PASSWORD 17.1 Menu with password DANGER The wrong pco programming can cause big damages to the unit; if there is any doubt please call an authorised service centre. NOTE For information about the parameter setting please consult Chapter 20 Setting Tables. Inside this Loop are the masks which permit to set the fundamental parameters for the correct unit operation. The modification of these parameters is necessary only in the following cases: When a new pco board is installed. When for any reason, as fluctuations on the electrical power supply, any parameter has incorrect values. ATTTION The modifying of these parameters must be carried out by specialized personnel only, therefore it is necessary to call an authorized service centre. The access to this menu can be carried out following the procedure here indicated; to modify the parameters follow the indication of Chapter 5 How to modify a parameter of Password Menu. keep l button pressed for 5 seconds at least, then release it; insert the password using f or g buttons, then confirm it pressing h button. ATTTION The number of mask which is possible to access depends on the password (user, maintenance or manufacturer). USER password is: SERVICE password is: ATTTION The displaying of some masks depends on the settings of other masks and also on the unit configuration, decided during design phase. Ref. Mask (*) Range Notes F1 W After inserting the password press h button. If the password is not correct will appear, it is necessary to insert the password again. If the password is correct, it is possible to access the following mask Password Menu (Ref. F2).

67 Masks requiring a password 65 Ref. Mask (*) Range Notes F2 R When this mask has been reached, to enter the parameters follow the indications of the diagram here below: G1 H1 J1 L1 N1 h f h f h f h f h f h f f I1 h K1 h M1 f GLISH P1 h f h O1 f Q1 S1 V1 h f h f h f h f h R1 f f Q1 h U1 h W1 f * R: Read only mask W: Read and write mask.

68 66 Masks requiring a password GLISH Inside the masks of a loop (see masks UNIT CONFIGURATION ) it is possible to return to Password Menu (see Ref. F2), simply pressing once k button; press it twice to return to the main mask (Ref. A1 - see paragraph "16.1 Menu"). UNIT CONFIGURATION Ref. Mask (*) Range Notes G3 W - - BEWIT G5 W G6 W This mask is used to set the regulation probe for water temperature regulation during LOCAL modality operation. For further information consult Chapter 7 Temperature regulation management. Furthermore, it is possible to enable the compressor rotation. For further information consult Chapter 10 Compressors sequencing procedure. The software can convert the default unit of measurement to the Anglo- Saxon unit of measurement ( C, F, bar, PSI). The unit of measurement could be set (as bar or as psi) only if the pressure probes have been previously enabled. After modifying the unit of measurement, the default values for temperature and/or pressure settings will be installed again. This operation must be carried out before modifying eventual settings which could be lost. It allows to enable the probes which measure the evaporator water inlet temperature (-BEWIT) and the evaporator water outlet temperature (- BEWOT). For further information consult Chapter 2 Function of transducers and of probes. G7 W It allows to enable the high pressure transducer of circuit 1 (-BHP1). For further information consult Chapter 2 Function of transducers and of probes. G8 W step:000.1 G9 W Use this mask to fix the operating range of high pressure transducers. Furthermore, it is possible to fix the type of return signal of the transducer. It allows to enable the low pressure transducer of circuit 1 (-BLP1). For further information consult Chapter 2 Function of transducers and of probes. G10 W It allows to enable the tank water outlet temperature probe (-BTOWT). For further information consult Capitolo 2 La funzione dei trasduttori e delle sonde. G11 W G12 W It allows to enable the ambient temperature probes (-BAT1) and (- BAT2). For further information consult Capitolo 2 La funzione dei trasduttori e delle sonde. It allows to enable the free-cooling coils inlet temperature probes (- BFCIT). For further information consult Capitolo 2 La funzione dei trasduttori e delle sonde.

69 Masks requiring a password 67 Ref. Mask (*) Range Notes G13 W G14 W step: Use this mask to enable the pumpdown procedure for circuit 1. For further information consult Chapter 10 Compressors Pump-Down procedure (only AS FC units). Use this mask to set the max. time for pump-down and the low pressure threshold which fixes the pump-down end. If after max. time the low pressure threshold is not reached, the compressor stops and an alarm which blocks the circuit is activated (see Ref. AM20). This mask will be displayed only when the pump-down procedure has been enabled (see Ref. G13) and if the low pressure probes have been previously enabled (see Ref. G9). For further information consult Chapter 10 Compressors Pump-Down procedure (only AS FC units) GLISH * R: Read only mask W: Read and write mask. MODULARITY DRIVER Ref. Mask (*) Range I5 W step: 0.1 I6 W step: 0.1 step: 1 step: 0.1 I7 W step: 0.1 step: 0.1 I8 W step: 0.1 step: 0.1 I12 W step: 0.1 Notes Use this mask to set the min. and max. value of evaporator pressure probe. In this mask it is possible to insert the proportional, integral and derivative values of PID. Use this mask to fix the setpoint for overheating regulation and the temperature interval during which this regulation is not considered (Dead Area). Use this parameter to fix the tripping threshold of low pressure protection. Under this value it starts the integral type regulation with an adjustable constant, in order to restore and maintain the temperature over the preset value. Furthermore, it is possible to fix the integration time. Use this mask to fix the value used to enable the suction high pressure alarm (MOP). I13 W step: 0.1 Use this mask to fix the delay in low and high overheating alarms. * R: Read only mask W: Read and write mask.

70 68 Masks requiring a password GLISH HOURS WORKED Ref. Mask (*) Range Notes J1 R Unit working hours (time during which the board is activated). J2 R Total number of working hours and number of startings of pump 1. J3 R Total number of working hours and number of startings of pump 2. J4 R Total number of working hours and number of startings of compressor 1 of the first circuit. For further information consult paragraph "10.2 Working hours and startings of compressors and of the unit". J5 R Total number of working hours and number of startings of compressor 2 of the first circuit. For further information consult paragraph "10.2 Working hours and startings of compressors and of the unit". J6 W step: 1 Use this mask to select the working hour thresholds for unit, pump and compressors. When this threshold is exceeded, the appropriate maintenance alarm will appear. For further information consult paragraph "10.2 Working hours and startings of compressors and of the unit" and paragraph "18.3 Alarms masks". J7 W Use this mask to reset the contactors of working hours. To reset, set the interested parameter to and confirm by pressing g button. For further information consult paragraph "10.2 Working hours and startings of compressors and of the unit" and paragraph "18.3 Alarms masks". J8 W J9 W J10 W J11 W Use this mask to reset the contactors of working hours and of startings of pump 1. To reset, set the interested parameter to and confirm by pressing g button. Use this mask to reset the contactors of working hours and of startings of pump 2. To reset, set the interested parameter to and confirm by pressing g button. Use this mask to reset the contactors of working hours and of startings of compressor 1 of circuit 1. To reset, set the interested parameter to and confirm by pressing g button. Use this mask to reset the contactors of working hours and of startings of compressor 2 of circuit 1. To reset, set the interested parameter to and confirm by pressing g button.

71 Masks requiring a password 69 * R: Read only mask W: Read and write mask. MANUAL OPERATION Ref. Mask (*) Range Notes K1 W Use this mask to enable the manual procedure. The selection of the manual procedure forces the OFF status of the unit. After enabling the manual procedure the masks from Ref. K2 to Ref. K6 will appear. For further information consult Chapter 13 Manual procedure. GLISH K2 W This mask allows to start manually pump 1 or pump 2. K3 W K4 W K5 W K6 W Use this mask to manually start the compressor 1-2 or 3 of the first circuit when the manual procedure is enabled (Ref. K1) in order to verify its operation. It is first necessary to turn ON the pump (Ref. K2). This mask will be displayed only after the manual procedure has been enabled (Ref. K1). Use this mask to verify the fan two-step operation of group 1, when manual mode is enabled. This mask will be displayed only after the manual procedure has been enabled (Ref. K1) Use this mask to regulate the fan speed when the unit is in manual mode. This mask will be displayed only after the manual procedure has been enabled (Ref. K1). Use this mask to verify the operation of antifreeze resistance or tank resistance. K7 W+ R K8 R Not used mask. This mask will be displayed only after the manual procedure has been enabled (Ref. K1). Use this mask to manually regulate the opening of the electronic thermostatic valve of circuit 1. The parameter is read only and displays the actual opening step of the valve. K9 W K10 W This mask will be displayed only if the manual procedure has been previously enabled Ref. K1. Use this mask to check the operation of the fans two steps, if the manual procedure has been enabled. This mask will be displayed only if the manual procedure has been previously enabled Ref. K1.. In the upper part of the display: it is utilized to manage the opening percentage of the Free-Cooling fans 3-way-valve, if the manual procedure has been previously enabled. In the lower part: it is utilized to regulate the Free-Cooling fans speed, if the manual procedure has been previously enabled. * R: Read only mask W: Read and write mask.

72 70 Masks requiring a password GLISH Ref. Mask (*) COMPRESSORS Range L1 W step: 1 Notes This mask will be displayed only if the temperature regulation is set to Neutral Zone (Ref. V1). It allows to set the compressor starting delays when the temperature measured by temperature regulation probe is out of the Neutral Zone limits (see "7.1 Water temperature regulation for conditioning use in chiller modality"). L2 W step: 1 L3 W 1 step: 1 L4 W step: 1 This mask will be displayed only if the temperature regulation is set to Neutral Zone (Ref. V1). It allows to set the compressor stopping delays when the temperature measured by temperature regulation probe is out of the Neutral Zone limits (see "7.1 Water temperature regulation for conditioning use in chiller modality"). This mask will be displayed only if the temperature regulation is set to Neutral Zone (Ref. V1). It allows to set the compressors starting delays when the temperature measured by temperature regulation probe is within the Neutral Zone limits (see "7.1 Water temperature regulation for conditioning use in chiller modality"). This mask will be displayed only if the temperature regulation is set to P+I (Ref. V1). It allows to fix the integration time. L4 W step: 1 When pco is switched on or commuted from OFF to ON, the compressors are started after the delay time here set. * R: Read only mask W: Read and write mask. PUMPS Ref. Mask (*) Range Notes M2 W This mask is displayed only if the double pump is enabled. Use this mask to enable the automatic rotation of pumps. M3 W step: 1 M4 W step: 1 M5 W This mask is displayed only if the double pump is enabled and if the automatic rotation of pumps is enabled (Ref. M2). It allows to fix the rotation interval time, after this time a pump stops and the other pump starts. Furthermore, it is possible to fix an interval time, before the rotation, during which both the pumps operate. This mask is displayed only if the double pump is enabled and if the automatic rotation of pumps is enabled (Ref. M2). It allows to fix a delay time on pump stopping from unit stopping. For further information consult Chapter 12 Single or double pump operation management This mask is displayed only if the double pump is enabled and if the automatic rotation of pumps is enabled (Ref. M2). Use this mask to enable the start of pump 1 or 2.

73 Masks requiring a password 71 Ref. Mask (*) Range Notes M6 W step: 1 M7 W step: 00.1 Use this mask to fix the time for the contemporaneous operation of both the pumps from pump operation changing. Use this mask to enable the pump in antifreeze function. The pump starts under the setpoint value and stops (if necessary) when setpoint + differential is exceeded. GLISH * R: Read only mask W: Read and write mask. FANS Ref. Mask (*) Range Notes N2 W This mask allows to enable Low Noise function (see paragraph "11.2 Nightly operation") N3 W step: N4 W step: N5 W step: N6 W step: It allows to fix the setpoint for each step of fan tripping of group 1. For further information consult Chapter 11 Fans operation management. It allows to fix the differential of fans of group 1. For further information consult Chapter 11 Fans operation management. This mask will be displayed only if function (Ref. N2) has been enabled. It allows to fix the second setpoint for each step of fan tripping of group 1. This mask will be displayed only if function (Ref. N2) has been enabled. It allows to fix the second differential of fans of group 1. N9 W step: N10 W step: Use this mask to set the setpoint and the differential for fan speed regulation of group 1. For further information consult Chapter 11 Fans operation management. This mask will be displayed only if function (Ref. N2) has been enableduse this mask to set the second differential for fan speed regulation. N11 W step: 1 Use this mask to fix the time for operation in, then it will pass to.

74 72 Masks requiring a password GLISH Ref. Mask (*) Range Notes N12 W step: Use this mask to set the setpoint and the differential for fan speed regulation. For further information consult Chapter 11 Fans operation management. * R: Read only mask W: Read and write mask. UNLOADING Ref. Mask (*) Range O1 W step: O2 W step: O3 W step: 1 Notes Use this mask to set the unloading temperature (setpoint/differential) for the temperature probe. This mask will be displayed only if the temperature probe has been previously enabled (Ref. G6, Ref. G9). For further information consult paragraph "10.5 Compressors Unloading procedure". Use this mask to set the unloading pressure (setpoint/differential) for the pressure probe. This mask will be displayed only if the pressure probe has been previously enabled (Ref. G7). For further information consult paragraph " Unloading procedure by high pressure probes" Use this mask to set the max. duration time for high pressure unloading. This mask will be displayed only if high pressure probes have been previously enabled (Ref. G7). For further information consult paragraph " Unloading procedure by high pressure probes" * R: Read only mask W: Read and write mask. RECOVERY DEFROSTING ALARMS Ref. Mask (*) Range Q10 W step: 001 Notes This mask allows to enable the electrical feed alarm. Furthermore, it allows to fix a delay time on alarm tripping (Ref. AM15) * R: Read only mask W: Read and write mask.

75 Masks requiring a password 73 CLOCK Ref. Mask (*) Range R1 W / step: 1 R2 W / / step: 1 Notes This mask will be displayed only if the clock board has been previously enabled (Ref. G6). Used to set the date, current day and hour. This mask will be displayed only if the clock board has been previously enabled (Ref. G6). Use this mask to fix the hour for silenced function enabling and disabling (see Chapter 11 Nightly operation ) GLISH R3 W R4 W This mask will be displayed only if the clock board has been previously enabled (Ref. G6). Use this mask to enable the weekly and daily time-zone (weekly and daily time-zones allow the automatic ON/OFF of the unit at preset times and days). This mask will be displayed only if the clock board has been previously enabled (Ref. G6). Use this mask to set the ON/OFF day. R5 W / / step: 1 This mask will be displayed only if the clock board has been previously enabled (Ref. G6). Use this mask to set the ON/OFF time. * R: Read only mask W: Read and write mask.

76 74 Masks requiring a password GLISH HISTORY Ref. Mask (*) Range Notes S1 R When this mask has been reached, to enter the parameter list follow the indications of the diagram here below: f h Resets the alarms history Ref. S4 h f Displays the alarms history The alarm sequence or the alarms history is displayed by a series of masks where it is indicated the date, the hour and the alarm description; until 50 alarm signals are stored. ATTTION Pressing more times h button inside any mask of alarms history, it is possible to display the pressure values, the temperature values and the status of inlets and outlets measured by pco sensors, when that alarm has occurred. See masks from Ref. T1 to S4 W It allows to cancel all the alarms history. Press k to return to mask Ref. S1. It is recommended to reset the alarms history every time the initialisation of the electronic control is carried out (see Ref. G16). * R: Read only mask W: Read and write mask. At each alarm tripping pco automatically stores in some masks the operating conditions (pressure, temperature, status of inlets, etc...). These masks are listed here below. The displaying of some masks depends on unit configuration. ALARMS HISTORY Ref. Mask (*) Range Notes T1 R Evaporator water inlet/outlet temperatures (-BEWIT, -BEWOT), tank water outlet temperatures (-BTOWT). T2 R Coil temperature (-BD1). T3 R High pressure (-BHP1).

77 Masks requiring a password 75 Ref. Mask (*) Range Notes T4 R Low pressure (-BLP1). T6 R BFCIT, BAT1 and BAT2 probes temperature. T7 R Status of digital inputs. GLISH T8 R Status of digital outputs. T9 R Status of recovery valve. T10 R Status of speed regulator. T11 R Status of Driver 1. T12 R Free-Cooling 3-way-valve and speed regulator staus * R: Read only mask W: Read and write mask. SUPERVISOR Ref. Mask (*) Range Notes U1 W This mask allows pco to be managed by a supervision system.

78 76 Masks requiring a password GLISH Ref. Mask (*) Range Notes U2 W step: 1 U3 W Step: 1 This mask will be displayed only if the supervision is enabled (Ref. U1). Use this mask to give the unit a specific address when it is networkconnected into a supervisory system. In the second row it is possible to fix the speed for data communication. Furthermore, it is possible to set the type of supervision protocol. For further information consult Chapter 15 Supervision system This mask will be displayed only if the supervision is enabled (Ref. U1). Use this mask to fix the max. value of telephone numbers which can be stored and the telephone numbers used for SMS sending. ATTTION Before inserting the telephone numbers it is necessary to enable the SMS sending (Ref. U4) U4 W Furthermore, it is possible to set a password to protect the stored data. This mask will be displayed only if the supervision by GSM Protocol is enabled (Ref. U2). It allows to fix the max. number of rings which the modem receives before the answer and the type of modem. Furthermore, it is possible to enable the sending SMS messages. For further information consult Chapter 15 Supervision system. U5 W This mask will be displayed only if the supervision is enabled (Ref. U1). Use this mask to enable or disable the possibility to switch on or off the unit by the supervision system. * R: Read only mask W: Read and write mask. OTHER SETTINGS Ref. Mask (*) Range Notes V1 W V2 W Step:000.1 Use this mask to set the type of temperature regulation (seechapter 7 Temperature regulation management ) P= PROPORTIONAL P+I= PROPORTIONAL + INTEGRAL N.Z.= NEUTRAL ZONE Furthermore, it is possible to select the type of setpoint management (see Chapter 8 Setpoint management ). Use this mask to set the min. and max. limits for SUMMER setpoint (Ref. C2). V3 W Step:000.1 V4 W Step:000.1 Use this mask to fix the setpoint and differential values of antifreeze resistance (see Chapter Antifreeze resistance and tank resistance in unit manual). Use this mask to fix the setpoint and differential values of tank antifreeze resistance (see Chapter Antifreeze resistance and tank resistance in unit manual).

79 Masks requiring a password 77 V8 Ref. Mask (*) Range Notes Step:00.1 V9 W Step:1 Use this mask to calibrate the probes -BAT1 -BAT2 -BFCIT. For further information see Capitolo 2 Trasduttori e Sonde. If one or more probes are not enabled this mask will be dispalyed, but the modification of the parameter will not change the unit operation. This mask allows to change USER password. GLISH V10 W Step:1 This mask allows to change SERVICE password. * R: Read only mask W: Read and write mask. FREECOOLING Ref. Mask (*) Range Notes W2 W Step:00.1 W3 W Step:1 W5 W Step:1 W6 W Step:1 W7 W Step:1 W8 W X Step:1 X=minimum speed W7 This mask will be dispalyed only if the Free-cooling system has been previously enabled. It allows to set the Free-Cooling activation delta. For further information see Chapter 9 Free-Cooling system management This mask will be dispalyed only if the Free-cooling system has been previously enabled. Use this mask to set the Free-Cooling activation/disactivation delay time. For further information see Chapter 9 Free-Cooling system management This mask will be dispalyed only if the Free-cooling system has been previously enabled: - Steps : it visualizes the activation/disactivation time between two steps; - Regulated : visualizes the time between two speed increses/ decreases. This mask will be dispalyed only if the Free-cooling system has been previously enabled. It allows to set the fans speed increase/deacrese percentage. This mask will be dispalyed only if the Free-cooling system has been previously enabled. Use this mask to set the range (percentage) on the Free-cooling speed control. This mask will be dispalyed only if the Free-cooling system has been previously enabled. This mask allows to set the time (Speed-Up Time) during which the fans speed rotation, at fans start-up, is forced to the value set in parameter. After Speed-Up Time the speed will decrease according to the setting of parameter Min. Speed.

80 78 Masks requiring a password GLISH Ref. Mask (*) Range Notes W9 W Step:1 W10 W Step:1 * R: Read only mask W: Read and write mask. This mask will be dispalyed only if the Free-cooling system has been previously enabled. It dispalys the time between two increses and/or decreases of the 3-wayvalve opening. For further information see Chapter 9 Free-Cooling system management. This mask will be dispalyed only if the Free-cooling system has been previously enabled. It allows to set the opening increse/decrese percentage of the 3-wayvalve. For further information see Chapter 9 Free-Cooling system management.

81 Alarm management 79 CHAPTER Alarm signals A LARM MANAGEMT Alarm displaying During the unit working, some alarm conditions could happen. Depending on their danger they could be controlled by pco by means of a simple signal or by means of the partial / complete block of the unit. When an alarm occurs, on pco display appears the indication and the red led of j button lights up. GLISH Press j button on the terminal to display the first alarm mask. In the top right corner it will appear the number of enabled alarms. Use g or f button on the terminal to scroll the other eventual alarm messages. After reading the alarm message on the display, use the alarms list (see paragraph "18.3 Alarms masks") to identify the displayed alarm and to have further information Alarm resetting When the alarm cause has been resolved, if it was of automatic reset type the unit will automatically return to normal operation. If the alarm was of manual reset type, press j button on the terminal more times until reaching the reset. The message will appear on the display if j button is pressed without any alarm. To return to the main mask press k button Alarms masks Ref. Mask Reset Controller action Input Notes AM1 No active alarm masks. AM2 aut. Complete stop of the unit and of the pump --- The memory of pco is irreparably damaged. Try to restart the unit. If the alarm repeats, call an authorised service centre. AM3 aut. Complete stop of the unit and of the pump --- The Clock board of pco is irreparably damaged. Try to restart the unit. If the alarm repeats, call an authorised service centre. AM4 manual Complete stop of the unit and of the pump ID3 Insufficient water flow throughout the evaporator (differential pressure switch). AM5 aut. Complete stop of the unit and of the pump ID4 Insufficient water level in the tank. When the water level in the tank is restored, the alarm is automatically reset. Table 5 ALARMS MASKS

Standard Chiller 1/4 compressors Manual version: /10/96

Standard Chiller 1/4 compressors Manual version: /10/96 Application program for Macroplus II Standard Chiller 1/4 compressors Manual version: 1.4-18/10/96 Program code: EP000ECH02 Rif.: 68EM Contents 0$,1)($785(6 HARDWARE...2 FUNCTIONS OF THE SYSTEM...3 PROTECTIONS...3

More information

Standard 1/4 compressor chiller/heat pump with heating recovery Manual version: /02/97

Standard 1/4 compressor chiller/heat pump with heating recovery Manual version: /02/97 Application program for Macroplus II Standard 1/4 compressor chiller/heat pump with heating recovery Manual version: 2.2-06/02/97 Program code: EP000EPDC0 Rif.: 17EM INDEX MAIN FEATURES...2 Hardware Description...2

More information

1 STARTUP Overview Buttons Basics of Control Resetting Faults and Alarms OPERATION...

1 STARTUP Overview Buttons Basics of Control Resetting Faults and Alarms OPERATION... Operation & Service Manual 940126-0002 pco 3 Programmable Logic Controller Contents 1 STARTUP...1 1.1 Overview... 1 1.1.1 Buttons... 1 1.1.2 Basics of Control... 1 1.2 Resetting Faults and Alarms... 2

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

CONTROL PANEL OPERATING MANUAL. AIR COOLED SCREW CHILLER GLOBAL DESIGN Software version ASDU01C and later D-EOMCP EN

CONTROL PANEL OPERATING MANUAL. AIR COOLED SCREW CHILLER GLOBAL DESIGN Software version ASDU01C and later D-EOMCP EN CONTROL PANEL OPERATING MANUAL AIR COOLED SCREW CHILLER GLOBAL DESIGN Software version ASDU01C and later D-EOMCP00104-14EN TABLE OF CONTENTS 1 CONTENTS... 5 1.1. Installation Precautions... 5 1.2. Temperature

More information

Touch Screen Guide. OG-1500 and OG Part # T011

Touch Screen Guide. OG-1500 and OG Part # T011 Touch Screen Guide OG-1500 and OG-2000 Part # 9000000.T011 Effective 11/2010 External View Internal View 1. Transducer Banks 2. Oxygen Sensor 3. PLC These are the two manifolds with three (3) transducers

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

A TECHNICAL REFERENCE

A TECHNICAL REFERENCE A TECHNICAL REFERENCE FOR CAREL DCM CONTROLLERS DIGITAL COMPRESSOR MODULE CANADIAN HEAD OFFICE AND FACTORY USA HEAD OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

REASONS FOR THE DEVELOPMENT

REASONS FOR THE DEVELOPMENT 7 Series 7 Series +24VDC VDC OUTPUT MICROPROCESS. E P IN EXH OUT 7 Series 7 ø,8 8 7 Series 9 5 8 9 7 Series Display features The proportional regulator has a 3 /2 digit display and a three-pushbutton

More information

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x Electrical Installation Requirements Care should be taken to separate the power and signal cables to prevent electrical interference and possible damage due to inadvertent connection. SUPPLY E L N LN2

More information

ECL Comfort 110, application 131 (valid as of software version 2.00)

ECL Comfort 110, application 131 (valid as of software version 2.00) Operating Guide ECL Comfort 110, application 131 (valid as of software version 2.00) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Operating instructions Electrical switching facility pco

Operating instructions Electrical switching facility pco Operating instructions Electrical switching facility pco from software version V1.33 on TABLE OF CONTENTS 1. Before you start... 4 1.1 Brief description... 4 1.2 Using this manual... 4 2. pco integrated

More information

User Manual. asense VAV. CO 2 / temperature sensor with built-in general purpose controller

User Manual. asense VAV. CO 2 / temperature sensor with built-in general purpose controller Gas and Air Sensors User Manual asense VAV CO / temperature sensor with built-in general purpose controller General The IAQ-sensor product asense VAV is used to measure indoor air carbon dioxide concentration

More information

SR-242 USER S GUIDE. Table of Contents

SR-242 USER S GUIDE. Table of Contents User s Guide gfhf Table of Contents 1. Introduction...3 2. Faceplate...3 2.1 Parameter List...3 2.2 Parameter Buttons ( and )...4 2.3 Function Buttons ( and )...4 2.4 LED Status Window...4 2.5 Value Setting

More information

Guida parametri EVD 200. Manuale d'uso User manual

Guida parametri EVD 200. Manuale d'uso User manual Guida parametri EVD 200 Manuale d'uso User manual Contents 1. EVD200 parameter guide... 15 1.1 Driver configuration... 15 1.2 Parameter configuration... 15 1.3 Alarms enable/delay (COMM)... 17 1. EVD200

More information

Design Envelope Booster. Sequence of operation

Design Envelope Booster. Sequence of operation Design Envelope Booster Sequence of operation File No: 62.835 Date: february 11, 2015 Supersedes: 62.835 Date: july 11, 2014 sequence of operation Design Envelope Booster 2 general The packaged domestic

More information

Built-in Purge Control Functions

Built-in Purge Control Functions Built-in Purge Control Functions Why clean a sensor? As the velocity sensor was calibrated clean, operating it clean also preserves the best calibration. Any build up of material on a thermal sensor tends

More information

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION 1 INFORMATION and TECNICAL DESCRIPTION 14 2 AIRLEADER Professional Compressor Management + Compressed Air Visualisation + Alarm Service Management + AIRLEADER - has been the effective answer for compressed

More information

USER MANUAL. Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * 1/73

USER MANUAL. Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * 1/73 USER MANUAL Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * *) Require software ID: DID-SW-001 1/73 Table of contents 1 General... 3 1.1

More information

IPR208D - IPR215D IPR208D - IPR215D GB r docx IPR208D -IPR215D 1/99

IPR208D - IPR215D IPR208D - IPR215D GB r docx IPR208D -IPR215D 1/99 IPR208D - IPR215D 1592025760 IPR208D - IPR215D GB r.1.4 24.03.2017.docx IPR208D -IPR215D 1/99 INDEX 1. GENERAL SPECIFICATIONS 4 1.1 APPLICATIONS 4 1.2 HARDWARE ARCHITECTURE 4 1.3 IPR215D 5 1.4 DESCRIPTION

More information

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND Configuration # : 41G20F0 CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND Input/output table: Inputs Qty Outputs Qty Inside Temperature Probe 3 Inflatable Balloon 8 Chimney Temperature Probe 1 Chimney Activator

More information

MACON R70 FOR 1 OR 2 COMPRESSORS

MACON R70 FOR 1 OR 2 COMPRESSORS MACON R70 FOR 1 OR 2 COMPRESSORS GENERAL CHARACTERISTICS Application to chiller and heat pumps. INPUTS 5 Analogical inputs for temperature measuring in range - 50 +99 C. 3 for the first circuit Nο1. Water

More information

Operating instructions. FOCUS compressor control for screw compressors

Operating instructions. FOCUS compressor control for screw compressors Operating instructions compressor control for screw compressors Table of contents Operating instructions compressor control for screw compressors BOGE KOMPRESSOREN Postfach 10 07 13 D-33507 Bielefeld Germany

More information

User s manual VCI07. For variable speed compressors ed00. Applicable as of Version 12. Bar PSI C F

User s manual VCI07. For variable speed compressors ed00. Applicable as of Version 12. Bar PSI C F User s manual EN VCI07 For variable speed compressors 62 205 930 11 ed00 Applicable as of Version 12 Bar PSI C F Table of contains 1 - GENERAL INFORMATION...3 2 - USER INTERFACE...3 2.1 DISPLAYS...3 2.2

More information

CONSOLE-320 ENGLISH. 230A: CONSOLE-320 with cable data output Item 230B: CONSOLE-320 with cable + wireless radio data output

CONSOLE-320 ENGLISH. 230A: CONSOLE-320 with cable data output Item 230B: CONSOLE-320 with cable + wireless radio data output CONSOLE-320 Item 230A: CONSOLE-320 with cable data output Item 230B: CONSOLE-320 with cable + wireless radio data output Table of contents 1. INTRODUCTION...2 1.1 Power supply...2 1.2 Connections...2 1.3

More information

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) ENGLISH ENGLISH ENGLISH ENGLISH Installation user s manual Warning! electrical scheme modified JANUARY 2005 version 3.3 JOLLY2 DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) 6 different operating modes

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

Sequence of Operations

Sequence of Operations MAGNUM Condensing Unit Software 5580 Enterprise Pkwy. Fort Myers, FL 33905 Office: 239-694-0089 Fax: 239-694-0031 Sequence of Operations MAGNUM Chiller V8 software www.mcscontrols.com MCS Total Solution

More information

Temperature Controller CC24-7 ULTRA USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

Temperature Controller CC24-7 ULTRA USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517) Temperature Controller USER S MANUAL Aerotech, Inc. FORM: QM1387 4215 Legion Dr. Mason, MI 48854-1036 USA October 2010 Ph. (517) 676-7070 Fax (517) 676-7078 FOR CUSTOMER USE Enter the serial number located

More information

Revision 1 AIR & WATER COOLED LIQUID CHILLERS MICRO BASED CONTROL SYSTEM WITH IPUII

Revision 1 AIR & WATER COOLED LIQUID CHILLERS MICRO BASED CONTROL SYSTEM WITH IPUII YLAA0189SE-YLAA0485SE YLAA0195HE-YLAA0515HE YLAE0195SE-YLAE0490SE YLAE0195HE-YLAA0510HE YLAE0195LT-YLAE0490LT YCWL0240SE - YCWL0395SE YCWL/YCRL0200HE - YCWL/YCRL0610HE OPERATING INSTRUCTION Revision 1

More information

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity

More information

A4s Operation Manual

A4s Operation Manual A4s Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and

More information

MAESTRO USER S MANUAL TIP00G-105 AIR COMPRESSORS

MAESTRO USER S MANUAL TIP00G-105 AIR COMPRESSORS AIR COMPRESSORS MAESTRO USER S MANUAL TIP00G-105 ING. ENEA MATTEI SpA Strada Padana Superiore 307 20090 VIMODORONE (MI) Tel +39 02253051 (16 lines) Fax +39 0225305243 E-mail: info@mattei.it - www.matteiaircompressors.com

More information

CF8-W-Disp-CO. User manual. CO 2 / CO sensor with built-in general purpose controller

CF8-W-Disp-CO. User manual. CO 2 / CO sensor with built-in general purpose controller User manual CF8-W-Disp-CO CO 2 / CO sensor with built-in general purpose controller General The IAQ-sensor product CF8-W-Disp-CO is used to measure indoor air carbon dioxide and carbon monoxide concentrations.

More information

Specifications and information are subject to change without notice. Up-to-date address information is available on our website.

Specifications and information are subject to change without notice. Up-to-date address information is available on our website. www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp LD302 - AssetView HMI LD302

More information

Technical Data Sheet MF010-O-LC

Technical Data Sheet MF010-O-LC Technical Data Sheet MF010-O-LC - 1 - 1. Properties The oxygen measuring system MF010-O-LC determines the oxygen content in gas mixtures up to a temperature of 250 C. It is particularly suitable for the

More information

Manual Oxygen Analyzer A4009T

Manual Oxygen Analyzer A4009T Manual Oxygen Analyzer A4009T Revision 01-EN DIVIZE B.V.- info@divize.com November 25, 2014 Contents 1 Measuring principle 3 2 Safety 4 3 Installation 5 3.1 Mounting................................................

More information

A4 Operation Manual. Fig.1-1 Controller Socket Diagram

A4 Operation Manual. Fig.1-1 Controller Socket Diagram A4 Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and

More information

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. .

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. . User Manual Capacitance Continuous Level Indicator Comprehensive User s Manual. Introduction. General Description. Principle of Operation. Specifications. Connection Diagrams. Quick Calibration Chart.

More information

Instructions and Advices to use the electronic controller Logik 31-S

Instructions and Advices to use the electronic controller Logik 31-S Instructions and Advices to use the electronic controller Logik 31-S ORIGINAL INSTRUCTIONS 01/08/12 Rev. 0 1 LOGIKA CONTROL s.r.l. Via Garibaldi, 83/a 20054 NOVA MILANESE MI ITALY Tel.: +39 0362 37001

More information

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES I N S T R U C T I O N - M A N U A L CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES FUNCTION: Conductivity level limit switches are based on the principle of measuring level through the electrical

More information

MICRO BASED CONTROL SYSTEM YLCS-SA/HA/AA YAES-SA 2 System YAES-SA 3 System YAES-DSA 4 System

MICRO BASED CONTROL SYSTEM YLCS-SA/HA/AA YAES-SA 2 System YAES-SA 3 System YAES-DSA 4 System MICRO BASED CONTROL SYSTEM YLCS-SA/HA/AA YAES-SA 2 System YAES-SA 3 System YAES-DSA 4 System OPERATION INSTRUCTION YLCS-SA/HA/AA: R134a - Software Version B.A05.01.01 and higher version levels YAES-SA

More information

MONSOON 6V Pump Control System

MONSOON 6V Pump Control System MONSOON 6V Pump Control System Installation and Operating Instructions Please pass these instructions on to the operator of this equipment. INTRODUCTION MONSOON 6V Pump Controller The MONSOON 6V pump control

More information

Speed Controller ADR 40 Condensing pressure controller SPEED REGULATORS FOR ASYNCHRONOUS SINGLE PHASE MOTORS SERIES ADR 40 ADR 40 ADR 40 PP

Speed Controller ADR 40 Condensing pressure controller SPEED REGULATORS FOR ASYNCHRONOUS SINGLE PHASE MOTORS SERIES ADR 40 ADR 40 ADR 40 PP SPEED REGULATORS FOR ASYNCHRONOUS SINGLE PHASE MOTORS SERIES ADR 40 ADR 40 ADR 40 PP Control by pressure or temperature Pressure control 0-50 bar for all refrigerants Temperature control -20 to +100 C

More information

Roller AC Servo System

Roller AC Servo System Safely Instruction Roller AC Servo System HMI-15 User Manual Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller

More information

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1*

Safety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1* Safety Manual Process pressure transmitter IPT-1* 4 20 ma/hart Process pressure transmitter IPT-1* Contents Contents 1 Functional safety 1.1 General information... 3 1.2 Planning... 4 1.3 Instrument parameter

More information

In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure

In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure PPMS Service Note 1099-412 In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure Introduction: Loss of electricity to the PPMS EverCool II should not cause damage to

More information

Reverse Osmosis System Installation Guide and Operation Manual.

Reverse Osmosis System Installation Guide and Operation Manual. Reverse Osmosis System Installation Guide and Operation Manual. Table of Contents 1 Introduction...2 2 Installation...3 2.1 Feed water connection...3 2.2 Permeate and concentrate plumbing...3 2.3 Electrical

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

Stand-Alone Bubble Detection System

Stand-Alone Bubble Detection System Instruction Sheet P/N Stand-Alone Bubble Detection System 1. Introduction The Bubble Detection system is designed to detect air-bubble induced gaps in a bead of material as it is being dispensed. When

More information

USER MANUAL OPERATION AND THE USE OF A CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM

USER MANUAL OPERATION AND THE USE OF A CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM USER MANUAL OPERATION AND THE USE OF A CAR WITH Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM Page 2 / 8 Table of csontents 1. STARTING THE ENGINE... 3 2. CONTROL PANEL... 3 2.1 Indication of the current

More information

Race Screen: Figure 2: Race Screen. Figure 3: Race Screen with Top Bulb Lock

Race Screen: Figure 2: Race Screen. Figure 3: Race Screen with Top Bulb Lock Eliminator Competition Stand Alone Mode - Instruction Manual Main Menu: After startup, the Eliminator Competition will enter the Main Menu. Press the right/left arrow buttons to move through the menu.

More information

CPF 270, CPF 340. Instruction book

CPF 270, CPF 340. Instruction book CPF 270, CPF 340 Instruction book Chicago Pneumatic CPF 270, CPF 340 Instruction book Original instructions Copyright Notice Any unauthorized use or copying of the contents or any part thereof is prohibited.

More information

Description. Measuring Device 3760XBI USP. Balancing

Description. Measuring Device 3760XBI USP. Balancing Measuring Device 3760XBI Description 3760XBI comprises from a differential pressure unit with an integrated true differential pressure sensor for the exact measuring of both differential and static pressures

More information

Domino DUEMMEGI. Domino. Communication Interface DFTS User s Manual. Release September 2007

Domino DUEMMEGI. Domino. Communication Interface DFTS User s Manual. Release September 2007 Domino Domino Communication Interface DFTS User s Manual Release 2.3 - September 2007 srl Via Longhena 4-20139 MILANO Tel. 02/57300377 - FAX 02/55213686 Domino - DFTS: User s Manual R.2.3 Index 1- INTRODUCTION...3

More information

WMC Magnetic Bearing Compressor Chillers

WMC Magnetic Bearing Compressor Chillers Operating and Maintenance Manual OMM WMC-2 OITS Group: Chiller Part Number: 331374701 Effective: March 2005 Supersedes: OM WMC-1 WMC Magnetic Bearing Compressor Chillers Model WMC 035T 50/60 Hertz OITS

More information

660 Multipoint Electronic Level Switch

660 Multipoint Electronic Level Switch 660 Multipoint Electronic Level Switch General Instructions The Multipoint Electronic Level Switch is a level sensing device which reads process level by capacitance measurement. Capacitance varies according

More information

HyperSecureLink V6.0x User Guide

HyperSecureLink V6.0x User Guide HyperSecureLink V6.0x User Guide Note: This software works with the LS-30 Version (06.0x or later) 1, Hardware Installation: 1-1, Connection Diagram for USB or RS-232 Computer Interface To LS-30 CM1 To

More information

FLSTDmSCHE Software for the management of chiller screw Code: FLSTDmSCHE

FLSTDmSCHE Software for the management of chiller screw Code: FLSTDmSCHE FLSTDmSCHE Software for the management of chiller screw Code: FLSTDmSCHE User manual H i g h E f f i c i e n c y S o l u t i o n s IMPORTANT CAREL bases the development of its products on decades of experience

More information

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM

More information

RAM Operation Manual

RAM Operation Manual RAM 4021-1 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-1 For Your Safety... 2 Description... 2 Setup Mode... 3 Lights/Alarms... 3 Operation... 4 Calibration...

More information

FAULT CODE TROUBLESHOOTING INDEX

FAULT CODE TROUBLESHOOTING INDEX FAULT CODE TROUBLESHOOTING INDEX 1. Display indicates Change Filters 2. Display indicates Drip Tray Full Continuous Alarm will Sound 3. Display indicates Cold Fault 4. Display indicates Hot Fault 5. Display

More information

CHILLER CONTROL PANEL PROGRAMMING AND DATA ACCESS

CHILLER CONTROL PANEL PROGRAMMING AND DATA ACCESS Micropanel CHILLER CONTROL PANEL PROGRAMMING AND DATA ACCESS STATUS DISPLAY SETPOINTS CLOCK DISPLAY INFORMATION KEYS 00407VIP PRINT ON / OFF PROGRAM & SETUP KEY DISPLAY AND STATUS INFORMATION KEYS Status

More information

CONTROL PANEL OPERATING MANUAL

CONTROL PANEL OPERATING MANUAL MICROTECH III CONTROLLER MICROTECH III CONTRO CONTROL PANEL OPERATING MANUAL EWWD~FZXS WATER COOLED MAGNETIC BEARINGS CHILLERS OITS Software Version: 2.01.01 Control Software Version: EWWDU3UU02B Table

More information

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

Electronic Commissioning Unit. Instructions

Electronic Commissioning Unit. Instructions Electronic Commissioning Unit Instructions 1. The Comdronic AC6 Electronic Commissioning Unit 2. Health and Safety 3. Description of Unit 4. Connection and Set-up Procedure 5. Menu System a. Main Menu

More information

CONTROL and INSTRUMENTATION

CONTROL and INSTRUMENTATION CONTROL and INSTRUMENTATION COURSE 500: 5 DAYS: Max 8 Candidates This course covers the key aspects of current instrumentation and process control technology and is designed to enable maintenance personnel

More information

SCIENTIFIC DATA SYSTEMS, INC. Depth Tension Line Speed Panel. DTLS Manual

SCIENTIFIC DATA SYSTEMS, INC. Depth Tension Line Speed Panel. DTLS Manual SCIENTIFIC DATA SYSTEMS, INC. Depth Tension Line Speed Panel DTLS Manual This document contains proprietary information. Copyright 2015 Scientific Data Systems, Inc. All rights reserved. 1 Depth Tension

More information

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021-PR Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-PR For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

Monsoon3V+ Multiple Pump VFD Control System. Please pass these instructions on to the operator of this equipment.

Monsoon3V+ Multiple Pump VFD Control System. Please pass these instructions on to the operator of this equipment. Monsoon3V+ Multiple Pump VFD Control System Please pass these instructions on to the operator of this equipment. INTRODUCTION MONSOON 3V+ Pump Controller The MONSOON 3V+ pump control system is a fully

More information

User Manual. asense miii. / CO sensor with built-in general purpose controller

User Manual. asense miii. / CO sensor with built-in general purpose controller Gas and Air Sensors User Manual asense miii CO 2 / CO sensor with built-in general purpose controller General The IAQ-sensor product asense miii is used to measure indoor air carbon dioxide and carbon

More information

Special Documentation Proline Promass 80, 83

Special Documentation Proline Promass 80, 83 SD00077D/06/EN/14.14 71272498 Products Solutions Services Special Documentation Proline Promass 80, 83 Functional safety manual Coriolis mass flow measuring system with 4 20 ma output signal Application

More information

HumiSys HF High Flow RH Generator

HumiSys HF High Flow RH Generator HumiSys HF High Flow RH Generator Designed, built, and supported by InstruQuest Inc. Versatile Relative Humidity Generation and Multi-Sensor System The HumiSys HF is a high flow version of the previously

More information

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments Pegas 4000 MF Gas Mixer InstructionManual Contents I Table of Contents Foreword Part I Introduction 1 2 1 System overview... 2 2 Specifications... 3 Part II Installation 4 1 Rear panel connections...

More information

Hydro-Control V User Guide

Hydro-Control V User Guide Hydro-Control V User Guide Hydronix Part no: HD0193 Version 2.3.0 Revision date: July 2006 1 COPYRIGHT Neither the whole or any part of the information contained in nor the product described in this documentation

More information

New product release. Universal Rebreather Monitor (URBM) Three cell / Independent backup

New product release. Universal Rebreather Monitor (URBM) Three cell / Independent backup New product release Closed Circuit Research is pleased to announce the launch of our range of Universal Rebreather Monitors Universal Rebreather Monitor (URBM) Three cell / Independent backup Key features

More information

Helium Level Measurement Unit

Helium Level Measurement Unit Helium Level Measurement Unit HLMU User Manual Version 002 The information in this manual may be altered without notice. BRUKER BIOSPIN accepts no responsibility for actions taken as a result of use of

More information

Operating instructions. FOCUS compressor control for piston compressors

Operating instructions. FOCUS compressor control for piston compressors Operating instructions FOCUS compressor control for piston compressors Operating instructions FOCUS compressor control for piston compressors BOGE KOMPRESSOREN Postfach 10 07 13 33507 Bielefeld Otto-Boge-Straße

More information

LENNOX SLP98UHV DIAGNOSTIC CODES

LENNOX SLP98UHV DIAGNOSTIC CODES Code Status of Equipment Action required to clear and recover - Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF) A Cubic feet per minute (cfm) setting for indoor blower (1 second

More information

Connect with Confidence NO POWER NO PROBLEM

Connect with Confidence NO POWER NO PROBLEM Connect with Confidence NO POWER NO PROBLEM The ideal solution to implement wireless sensor monitoring in IoT applications where power is not available. At last, there s a roll-out ready way to implement

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

KEM Scientific, Inc. Instruments for Science from Scientists

KEM Scientific, Inc. Instruments for Science from Scientists KEM Scientific, Inc. Instruments for Science from Scientists J-KEM Scientific, Inc. 6970 Olive Blvd. St. Louis, MO 63130 (314) 863-5536 Fax (314) 863-6070 E-Mail: jkem911@jkem.com Precision Vacuum Controller,

More information

BI-680 Online Dissolved Oxygen Controller Instruction Manual

BI-680 Online Dissolved Oxygen Controller Instruction Manual BI-680 Online Dissolved Oxygen Controller Instruction Manual BANTE INSTRUMENTS CO., LTD BI-680 Online Dissolved Oxygen Controller 1 Introduction Thank you for selecting the BI-680 online dissolved oxygen

More information

RAM 4021-DPX Operation Manual

RAM 4021-DPX Operation Manual RAM 4021-DPX Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS ABL 4021-DPX / RAM 4021-DPX For Your Safety... 3 Description... 3 Setup Mode... 4 Lights/Alarms... 4 Operation...

More information

Manual Weighingblock VB2 series and Uniscale

Manual Weighingblock VB2 series and Uniscale Manual Weighingblock VB2 series and Uniscale Note: At page 8 in this manual you will find a short form instruction. Normally the only instruction shipped together with the Scale. Overview different ranges.

More information

EasySas. The most advanced airlock electronics on the market. Recyclable product. Eco-design. Energy savings

EasySas. The most advanced airlock electronics on the market. Recyclable product. Eco-design. Energy savings EasySas The most advanced airlock electronics on the market Eco-design Energy savings Recyclable product ELECTRONIC AIRLOCK MANAGEMENT SkySas range UniSas range CompacSas range An electronic management

More information

Code Basic module and level control complete with optionals code

Code Basic module and level control complete with optionals code AUTOMATION AND PROCESS CONTROL MPCT - Modular Process Control Trainer Code 916960 Basic module and level control complete with optionals code 916961-916962-916963-916964-916965 1. General Didacta proposes

More information

Valve Communication Solutions Axiom

Valve Communication Solutions Axiom Axiom Detect automated valve problems... before they shut down your process Reasons for Automated On/Off Valve Failures Monitor Fail Solenoid Fail Actuator Fail Coupling Break Too Slow Leaking Sticking

More information

TH-1800-T TRX-700-CNG Converter

TH-1800-T TRX-700-CNG Converter TH-1800-T TRX-700-CNG Converter low detector The CNG fuel gas flowmeter is so accurate as to meet a demand of measuring the CNG directly by making the most use of our well-established mini-thermal flowmeter

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Automotive and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

CMC Peer-to-Peer Control System Software. User s Manual Version 1.0

CMC Peer-to-Peer Control System Software. User s Manual Version 1.0 CMC Peer-to-Peer Control System Software User s Manual Version 1.0 2 22562920 Rev. 03 Date of Issue: 6/12/07 PREFACE Information and Illustrations Information and illustrations are not binding. Ingersoll-Rand

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

DGBOX rev Inverter electronic control panels for single pumps or pumping units OPERATOR S AND MAINTENANCE MANUAL

DGBOX rev Inverter electronic control panels for single pumps or pumping units OPERATOR S AND MAINTENANCE MANUAL DGBOX rev. 60 EN Inverter electronic control panels for single pumps or pumping units OPERATOR S AND MAINTENANCE MANUAL Model V in V out A P (kw) P (HP) DGB MV 30 3 ~ 400V 3 ~ 400V 8 3 4 DGB MV 55 3 ~

More information

APPLICATION NOTE. OJ-DV Modbus protocol. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS E 03/18 (PDJ) 2018 OJ Electronics A/S

APPLICATION NOTE. OJ-DV Modbus protocol. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS E 03/18 (PDJ) 2018 OJ Electronics A/S APPLICATION NOTE 67467E 03/18 (PDJ) 2018 OJ Electronics A/S OJ-DV Modbus protocol OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS Introduction This protocol contains the Modbus addresses

More information

Instruction Manual Dräger MSI P7 and MSI P7 plus

Instruction Manual Dräger MSI P7 and MSI P7 plus Dräger MSI GmbH Rohrstraße 32 58093 Hagen Tel.: +49-2331 / 9584-0 Fax: +49-2331 / 9584-29 e-mail: info@draeger-msi.de D 923; Edition 2011-01-01 Content 1. General Hints Page 4 2. The Instrument 2.1 Front

More information

Napa Technology Trouble Shooting. For Premier & Premier PLUS Models

Napa Technology Trouble Shooting. For Premier & Premier PLUS Models Napa Technology Trouble Shooting For Premier & Premier PLUS Models Before contacting Napa Technology for support, please check if the problem and solution are found below: Machine Is Off & All LCD s are

More information

The CWE / HWE-R Series: Overview. Frame and cabinet covering

The CWE / HWE-R Series: Overview. Frame and cabinet covering Table Of Contents The CWE / HWE-R Series: Overview...... 1 Frame and cabinet covering... 1 Refrigerant gas...... 2 Compressors...... 2 Condensers...... 2 Fans... 3 Evaporator...... 3 Refrigerant circuit......

More information

Multifunction Altimeter/Variometer AV1

Multifunction Altimeter/Variometer AV1 Multifunction Altimeter/Variometer AV1 Revision#3.0, 21/11/2014 For firmware version 2.2 Page intentionally left blank SECTIONS MECHANICAL INSTALLATION ELECTRICAL INSTALLATION USE OF THE INSTRUMENT INSTRUMENT

More information