AQUASONIC WATER-ATOMIZING FIRE SUPPRESSION SYSTEM Design, Installation, Recharge, and Maintenance Manual. (Order No. PN437205)

Size: px
Start display at page:

Download "AQUASONIC WATER-ATOMIZING FIRE SUPPRESSION SYSTEM Design, Installation, Recharge, and Maintenance Manual. (Order No. PN437205)"

Transcription

1 AQUASONIC WATER-ATOMIZING FIRE SUPPRESSION SYSTEM Design, Installation, Recharge, and Maintenance Manual (Order No. PN437205)

2 ANSUL AQUASONIC WATER-ATOMIZING ENGINEERED FIRE SUPPRESSION SYSTEM DESIGN, INSTALLATION, RECHARGE AND MAINTENANCE MANUAL ANSUL PART NO MARCH 1, 2010 Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

3 Table of Contents Page 1 Form No. Pages I. COMPONENTS US Gallon (189.3 L) Water Tank Assembly F CV-98 Valve/Cylinder Shipping Assembly F Cylinder Bracketing F AUTOPULSE Control System F ANSUL AUTOMAN II-C Releasing Device F Remote Actuator (Optional) F Booster Actuator F HF Electric Actuator F Lever Release Actuator F Flexible Discharge Bend F Water Tank Pressurization Hose and Fitting F Header Vent Plug F Header Safety Burst Disc F Actuation Components F Check Valves F Relief Valve F Vent Poppet F Pressure Switch DPST F Pressure Switch DPDT Explosion-Proof F Pressure Switch 3PST F Pressure Trip F Water Tank Relief Valve F System Shut-Off Valves F Nitrogen Discharge Regulators F Water Pressure Regulator F Atomizer F Pneumatic Selector Valve F Electric Selector Valves F Nameplate AQUASONIC SYSTEM (US) F Nameplate AQUASONIC SYSTEM (EMEA) F Nameplate Main F Nameplate RESERVE F Warning Plate Inside Room With Alarm F Warning Plate Outside Room Without Alarm F Pressure Test Assembly F Check Valves F

4 Table of Contents Page Form No. Pages II. GENERAL INFORMATION Spray Characteristics 2-1 Approvals 2-2 Pendent Mounting of Atomizer 2-2 Sidewall Mounting of Atomizer 2-2 Typical Operation Sequence 2-2 Types of Actuation 2-2 Electrical 2-2 Mechanical 2-2 Pneumatic 2-2 Types of Detection 2-3 Electronic Control Panel 2-3 Electric Releasing Device 2-3 System Limitations AQUASONIC Atomizer 2-3 AQUASONIC Atomizer Placement and Obstructions Usage 2-3 Discharge Path 2-4 Obstruction Allowances Sample Calculation Procedure 2-6 AQUASONIC Atomizer Parameters Pendent (Downward) Position 2-6 Sidewall Position Application of Pendent Constraints Rectangular Array 2-7 Triangular Array Application of Sidewall Constraints Sidewall Mounted Atomizers 2-9 Control of Run-Off 2-9 Ventilation and Leakage 2-9 Relief Venting 2-10 III. PLANNING Initial General Information 3-1 Hazard Information 3-1 Supply Requirements Atomizer Placement Requirements 3-2 Actuation and Alarm Requirements 3-2 Planning for Regulator Setting Procedure 3-2

5 Table of Contents Page 3 Form No. Pages IV. DESIGN Step No. 1 Determine the Floor Area and Gross Volume of the Room 4-1 Step No. 2 Determine the Minimum Number of Atomizers Required 4-1 Step No. 3 Verify Atomizer Array Placement 4-2 Step No. 4 Determine Location of System Supply 4-2 Step No. 5 Sketch Pipe Routing 4-2 Water Calculation Procedure Piping and Fitting Notes 4-3 Step No. 6 Determine Total Atomizer Pressure (TAP) Step No. 7 Select Appropriate Atomizer Assembly 4-8 Step No. 8 Determine Volume of Water Supply Required 4-8 Step No. 9 Determine Number of Water Tanks Required 4-9 Step No. 10 Determine Atomizer Pressure Loss Step No. 11 Determine Regulator Flowing Set Pressure 4-13 Step No. 12 Select the Appropriate Regulator 4-13 Step No. 13 Determine the Number of Nitrogen Cylinders 4-13 Step No. 14 Complete Layout of the System 4-13 Step No. 15 Create a Bill of Materials 4-13 Step No. 16 Create Installation Drawings 4-14 V. INSTALLATION General Information 5-1 Nitrogen Cylinder Installation Bracketing Without Uprights Double Row 5-2 Bracketing With Uprights Back-To-Back 5-2 Bracket With Uprights Double Row Back-To-Back 5-3 Water Tank Installation 5-4 Atomizer Installation 5-4 Releasing Devices 5-5 General Piping Requirements 5-5 Pipe Assembly 5-5 Hanger Requirements 5-5 Actuation Piping Actuation Pipe, Tubing, and Fitting Requirements 5-5 Installation of Actuation Piping 5-6 High Pressure Manifold and Regulator High Pressure Pipe and Fitting Requirements 5-6 Installation of High Pressure Manifold and Regulators Discharge Piping (After Regulators) System Piping, Tubing, and Fitting Requirements 5-7 Installation of Water Tank Pressurization Piping 5-8 Installation of Water Discharge Piping 5-8 Installation of Nitrogen Discharge Piping 5-9 Setting the Regulator

6 Table of Contents Page Form No. Pages V. INSTALLATION (Continued) Installing Detection/Actuation System 5-10 AUTOPULSE with Electric Actuator 5-10 AUTOPULSE with ANSUL AUTOMAN II-C with Pneumatic Actuation 5-10 Installing Actuator Pneumatic Actuation for CV-98 Valve 5-11 Electric Actuator 5-11 Installing the Booster Actuator 5-11 Installing the HF Actuator 5-11 Wiring for HF Actuator to AUTOPULSE Control Panel 5-11 Stacking Actuator 5-12 Installing Remote Pneumatic Actuators 5-12 Electric Pull Station to AUTOPULSE Control Panel 5-12 Installing Accessories Alarms 5-12 Pressure Trip 5-13 Pressure Switch 5-13 Ventilation 5-13 Fill Water Tanks 5-13 VI. TESTING AND PLACING IN SERVICE Testing 6-1 Testing Electric Detection/Actuation System AUTOPULSE Control System CV-98 Valve/HF Actuator/Booster Actuator 6-1 Testing Electric Detection System ANSUL AUTOMAN II-C Release 6-1 Placing In Service Step No. 1 Prepare System Actuation Devices ANSUL AUTOMAN II-C 6-1 Remote Pneumatic Actuator 6-2 Step No. 2 Open Valves 6-2 Step No. 3 Nitrogen Cylinder Pressure 6-2 Step No. 4 Inform Personnel 6-2 Discharge Test 6-2 VII. INSPECTION VIII. MAINTENANCE

7 Table of Contents Page 5 Form No. Pages IX. RESETTING AND RECHARGE Clear Electrical Equipment 9-1 Check Electrical and Mechanical Equipment Piping and Atomizers 9-1 Selector Valves 9-1 Electric Detection System Pressure Switch 9-2 Place System Back in Service Recharge Water Tank 9-2 Recharge Nitrogen Cylinders Remote Pneumatic Actuation 9-3 Lever Actuator 9-3 Electric Manual Pull Station 9-4 Replace ANSUL AUTOMAN II-C Cartridge 9-4 Resetting the HF Actuator 9-4 Resetting the Booster Actuator 9-4 X. APPENDIX Appendix A Selector Valves Appendix B European Cylinder, Bracketing, and Manifold Installation Appendix C Main and Reserve Systems Appendix D Typical Examples A1 A12 B1 B4 C1 C2 D1 D25

8 System Components Page US Gallon (189.3 L) Water Tank Assembly The AQUASONIC System agent tank is a 50 US gal (189 L) capacity water tank featuring a 0.17 in. (4.3 mm) thick ASME pressure vessel that is certified to 150 psi (14.8 bar). This vessel is both ASME and 97/23/EC (PED) CE marked. The tank features a 2 in. (5.1 cm) fill opening; the tank also has an outlet that is positioned for optimal flow, containing a Y strainer which will reduce the number of foreign particles in the water stream reaching the atomizers. The tank is constructed from 304L stainless material to help ensure rust-free performance. Note: Mounting feet will accept up to a 1/2 in. (12 mm) diameter bolt. Part No Y STRAINER DISCHARGE PORT FILL/ PRESSURIZATION PORT HEIGHT TO CENTER OF PIPE CONNECTION 63.5 IN. (1.61 m) WATER LINE SHUT-OFF VALVE (BLACK) IN. (0.37 m) SQUARE PATTERN FOR MOUNTING FEET TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

9 System Components Page 1-2 CV-98 Valve / Cylinder Shipping Assembly Description The cylinder is factory filled with nitrogen to a nominal pressure of 2900 psi (200 bar). Multiple cylinders can be manifolded together to obtain the required quantity of nitrogen. The cylinder valve can be actuated electrically, pneumatically, and/or manually with approved valve actuation components. All valves are equipped with an anti-recoil feature. The cylinders are shipped with a maintenance record card and protective shipping cap attached to the threaded neck of each cylinder. This cap entirely encloses and protects the valve while in shipment. Component Material Approvals Cylinder Steel Meets DOT 3AA3000 or EN Valve Brass Safety Relief Valve Brass Valve/Cylinder FM Approved Assembly Shipping Cap Steel Shipping Standardized Approximate Amount Dimension Dimension Assembly Cylinder N 2 Capacity Weight of N 2 A B Part No. ft 3 (m 3 ) lb (kg) lb (kg) in. (cm) in. (cm) DOT (16.3) 322 (146) 41.1 (18.6) 68.5 (174.0) 11.0 (27.9) TPED (16.0) 229 (104) 40.0 (18.2) 68.0 (172.7) 10.5 (26.7) CYLINDER SHIPPING CAP PRESSURE GAUGE VALVE SHIPPING CAP RECORD TAG VALVE PRESSURE GAUGE SAFETY RELIEF VALVE HEIGHT TO OUTLET CENTER A B CV-98 INERGEN Valve The CV-98 valve has a ten (10) year warranty. The valve requires no internal maintenance. The valve is sealed closed and must not be disassembled. If there is ever a malfunction of the CV-98 valve, the complete valve must be sent back to ANSUL for warranty replacement. If the external seal is broken, the warranty is voided. Note: Use Flexible Discharge Bend, Part No , when attaching valve to supply pipe or manifold. TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

10 System Components Page 1-3 Cylinder Bracketing Description The cylinder bracketing is designed to rigidly support the installed nitrogen agent cylinders. The bracketing components are constructed of heavy structural steel. Bracket assemblies are available in modules for two to six cylinders and can also be connected together for any combination over six. Bracketing can be assembled to support single row, double row or back-to-back rows of cylinders. Bracketing components are painted with a red enamel coating. Uprights and back frame assemblies can be bolted or welded together, whichever makes the installation more convenient. Component Material Approvals Bracketing Steel FM Approved Shipping Assembly Part No. Description ft3 (16.3 m 3 ) cylinder strap (single cylinder) ft 3 (16.3 m 3 ) cylinder channel with nuts and bolts (single cylinder) Back frame assembly (2 cylinder) Back frame assembly (3 cylinder) Back frame assembly (4 cylinder) Back frame assembly (5 cylinder) Back frame assembly (6 cylinder) Upright, for 575 ft 3 (16.3 m 3 ) cylinders (used either for right side, left side or center (center upright required when connecting seven or more cylinders in a row)) Single row or back-to-back row bracket foot (left side) Single row or back-to-back row bracket foot (right side) Double row bracket foot (left side) Double row bracket foot (right side) Center upright foot Connector (required to hook together back frames for seven or more cylinders) in. (33.0 cm) carriage bolt with nut (for single row 575 ft 3 (16.3 m 3 ) cylinders) in. (68.6 cm) carriage bolt with nut (for double row 575 ft 3 (16.3 m 3 ) cylinders) Cylinder clamp (2 cylinders) Cylinder clamp (3 cylinders) Weigh rail support single row Weigh rail support double row Weigh rail support back-to-back rows Weigh rail support back-to-back double row

11 Multi-Cylinder Single Cylinder UPRIGHT WEIGH RAIL SUPPORT BACK FRAME CYLINDER CLAMP CARRIAGE BOLT WITH NUT RIGHT BRACKET FOOT CHANNEL CLAMP LEFT BRACKET FOOT TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

12 System Components Page 1-4 AUTOPULSE Control System Description The AUTOPULSE Control System provides a range of features and benefits, ranging from simple detection through counting circuits. Several models of the AUTOPULSE Control System are available depending on the type of hazard being protected. Refer to the ANSUL Detection and Control Application Manual for detailed information concerning all AUTOPULSE Control Systems TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

13 System Components Page 1-5 ANSUL AUTOMAN II-C Releasing Device The ANSUL AUTOMAN II-C Releasing Device consists of a metal enclosure which contains a spring-loaded puncture pin release mechanism, actuation cartridge, electrical circuitry, and an input/output terminal strip for making electrical connections. The ANSUL AUTOMAN II-C Releasing Device provides automatic pneumatic actuation of the AQUASONIC System. When wired to an AUTOPULSE Control System, it will provide supervised electric detection and release. The ANSUL AUTOMAN II-C Releasing Device also provides manual actuation using the strike button on the release enclosure or with the optional remote manual cable pull station. When an AUTOPULSE Control System is used, manual actuation is accomplished using an electric manual pull station. The ANSUL AUTOMAN II-C Releasing Device requires an LT-10-R nitrogen cartridge for system actuation. Cartridge must be ordered separately LT-10-R CARTRIDGE Part No. Description ANSUL AUTOMAN II-C Releasing Device Shipping Assembly ANSUL AUTOMAN II-C Explosion/Weather- Proof Releasing Device Shipping Assembly (24 VDC) ANSUL AUTOMAN II-C Explosion/ Weather-Proof Releasing Device Shipping Assembly (120 VAC) ANSUL AUTOMAN II-C Explosion/ Weather-Proof Releasing Device Shipping Assembly (240 VAC) LT-10-R Nitrogen Cartridge Shipping Assembly (order separately) TPED Approved LT-10-R Nitrogen Cartridge Shipping Assembly (order separately) LT-30-R Nitrogen Cartridge Shipping Assembly (order separately) TPED Approved LT-30-R Nitrogen Cartridge Shipping Assembly (order separately) Cocking Lever (order separately) ANSUL AUTOMAN II-C Releasing Device Mounting Bracket ANSUL AUTOMAN II-C Explosion/Weather- Proof Releasing Device Mounting Bracket TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

14 System Components Page 1-6 Remote Actuator (Optional) The remote actuator is a device that allows for system actuation from a location either near or far from the AQUASONIC System Supply. Two types of actuators are offered. One requires an LT-10-R nitrogen cartridge, and the other requires an LT-30-R nitrogen cartridge. When actuated, the cartridges will supply pressure to the CV-98 valve pilot actuation port on the pilot cylinder, allowing nitrogen to flow. Cartridge must be ordered separately. Part No. Description Remote Actuator Shipping Assembly LT-10-R Remote Actuator Shipping Assembly LT-30-R LT-10-R Nitrogen Cartridge Shipping Assembly (order separately) TPED Approved LT-10-R Nitrogen Cartridge Shipping Asembly (order separately) LT-30-R Nitrogen Cartridge Shipping Assembly (order separately) TPED Approved LT-30-R Nitrogen Cartridge Shipping Assembly (order separately) Maximum Combined Length of Actuation Piping 1/4 in. 1/4 in. Stainless Steel Cartridge Schedule 40 Piping Tubing (0.028 in. wall) LT-10-R 50 ft (15 m) 150 ft (46 m) LT-30-R 150 ft (46 m) 450 ft (137 m) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

15 System Components Page 1-7 Booster Actuator Description The Booster Actuator, Part No , is used when electric actuation is required on the 1 in. selector valve, 2 in. selector valve, or the CV-98 cylinder valve. The actuator mounts directly to the component and then an HF electric actuator mounts to the top of the booster actuator. The Booster Actuator requires resetting after actuation. A Reset Tool, Part No , is available for this use. Component Material Approvals Booster Stainless Steel FM Approved Actuator and Brass 1 1/4 18 UNEF Ø /8 18 UNEF TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

16 System Components Page 1-8 HF Electric Actuator Description Electrical actuation is accomplished by an HF electric Actuator, Part No , interfaced through an AUTOPULSE Control System. This actuator can be used in hazardous, indoor environments where the ambient temperature range is between 0 F to 130 F ( 18 C to 54 C). The HF electric actuator meets the requirements of N.E.C. Class I, Div. 1, Groups B, C, D and Class II, Div. 1, Groups E, F, G. A maximum of two HF electric actuators can be used on a single AUTOPULSE release circuit. When utilizing only one HF electric actuator, an in-line resistor, Part No , is required in the supervised release circuit. In auxiliary or override applications, a manual-local override valve actuator or a manual cable pull actuator can be installed on top of the HF electric actuator by removing the safety cap. An arming tool, Part No , is required to reset the actuator after operation. The actuator contains a standard 1/2 in. threaded female straight connector for electrical conduit hookup. Technical Information Nominal Voltage: amps Rated Voltage: Minimum: VDC Maximum: VDC Thread Size/Type: /2 in. straight female for electrical conduit hookup Material: Body: Brass Plunger: Stainless Steel FM Approved 2 1/4 IN. (57 mm) 1 1/ / /2 IN. (114 mm) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

17 System Components Page 1-9 Lever Release Actuator Description The manual lever release actuator provides a manual means of actuating cylinder valves and selector valves. This can be accomplished by direct manual actuation of its pull lever or cable actuation when used in conjunction with a remote manual pull station. When used with a remote manual pull station, the pull station must contain the components necessary to meet the actuator lever traveling requirements of 7 in. (178 mm). The actuator is shipped with ring pin and chain attached. If the ring pin is not required, it must be removed. Failure to remove the ring pin/chain assembly will prevent system actuation if a remote cable pull actuation system is employed and the ring pin is accidentally installed in the actuator. Four actuators are available. Each is designed for a specific component. Note: For use with systems without selector valves. Component Material Approvals All Manual Brass with UL Listed Cable-pull Stainless Steel Pin FM Approved Actuators Shipping Assembly Part No. Description Lever Release (1 1/8-18 mounting thread) Mounts directly to a CV-98 cylinder valve for service and installation only. Do not use for actuation in final system configuration Lever Release (1 1/4-18 mounting thread) Mounts directly to an HF electric actuator. PIN 3 7/8 IN.* (9.8 cm) 3 7/8 IN. (9.8 cm) DEPTH: 3 7/8 IN. (7.6 cm) * Add 1 9/16 in. (3.9 cm) to height when lever is in the straight up position. TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

18 System Components Page 1-10 Flexible Discharge Bend Description The valve Flexible Discharge Bend (Part No ) is a 5/8 in. (1.59 cm) ID extra-heavy flexible hose which connects the valve discharge outlet to the fixed piping or header manifold. The discharge bend has a special female thread for connecting to the valve outlet and a male 1/2 in. NPT thread for connecting to the fixed piping or manifold. The discharge bend will withstand a pressure of 9000 psi (621 bar). Its flexible connection allows for easy alignment of multiple cylinder banks to fixed piping. Each bend has a built-in check valve that prevents loss of agent should the system discharge while any cylinder is removed. Shipping Assembly Part No. Description Flexible discharge bend Washer The equivalent length of this hose is equal to 18 ft (5.5 m) of 1/2 in. Sch. 40 pipe. Thread Size/Type Component Material Valve End Manifold End Approvals 5/8 in. Flexible SAE 100 R2 Special to 1/2 in. NPT Male UL Listed (EX-4510) Discharge Bend Type AT mate with FM Approved CV-98 Valve FEMALE ADAPTOR (BRASS) WASHER CHECK 18 7/8 IN. (47.9 cm) SWAGE ON 1/2 IN. NPT MALE COUPLING VALVE END MANIFOLD/END TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

19 System Components Page 1-11 Water Tank Pressurization Hose and Fitting The water tank pressurization hose (Part No ) is a 1/2 in. diameter flexible hose which connects the water tank to the regulated water tank pressurization piping. This allows for easy removal of the water tank fill connection for tank inspection and filling. The swivel adaptor (Part No ) provides a swivel connection which allows installation of the hose without twisting the hose. Part No Hose Assembly IN. (74.1 cm) Part No Swivel Adapter Union TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

20 System Components Page 1-12 Header Vent Plug Description The header vent plug is used to release low pressure buildup that may occur in a closed system. The header vent plug must be installed on every high pressure manifold where cylinders are connected. The header vent plug must be installed on the cylinder sides of the check valves on both main and reserve systems to relieve any pressure that may leak past the check valve and accidentally actuate the reserve system while the main system is discharging. Shipping Assembly Part No. Description Header vent plug Component Material Thread Size/Type Approvals Vent Plug Body: 1/4 in. NPT Male FM Approved Brass Spring: Bronze Seal: Neoprene 1.69 IN. (43 mm) 1.50 IN. (38 mm) 0.71 IN. (18 mm) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

21 System Components Page 1-13 Header Safety Burst Disc Description The manifold relief valve is used to release high pressure build-up that may occur in a closed system. A manifold relief valve must be installed on every high pressure manifold where cylinders are connected and on every manifold isolated by a selector valve or check valve. Internal safety disc will rupture between psi ( bar). Shipping Assembly Part No. Description Manifold Relief Valve Component Material Thread Size/Type Approvals Manifold Relief Valve Body: 1/2 in. NPT Male FM Approved Brass CE Approved SAFETY NUT SAFETY DISC BODY TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

22 System Components Page 1-14 Actuation Components Description The Stainless Steel Actuation Hose is used to connect the actuation line flared tees between each agent tank. The hose has the same thread, 7/16-20, as the flared tees. The actuation hose allows flexibility between the rigid actuation piping and the tank valve. 7/16 20 J.I.C. 1/4 IN. NPT MALE Shipping Assembly Part No. Description Stainless Steel Braided Hose, 16 in. (40.6 cm) Female-to-Female 7/ / Stainless Steel Braided Hose, 20 in. (50.8 cm) Female-to-Female Stainless Steel Braided Hose, 24 in. (60.9 cm) Female-to-Female Stainless Steel Braided Hose, 12 in. (30.5 cm) Male-to-Female Stainless Steel Braided Hose, 16 in. (40.6 cm) Male-to-Female Stainless Steel Braided Hose, 20 in. (60.9 cm) Male-to-Female Stainless Steel Braided Hose, 32 in. (81.3 cm) Male-to-Female Stainless Steel Braided Hose, 42 in. (107cm) Male-to-Female Additional Actuation Fittings Part No. Description CV-98 Actuation Adapter Male Straight Connector (7/16-20 JIC x 1/4 in. NPT) Male Elbow (7/16-20 JIC x 1/8 in. NPT) Male Elbow (7/16-20 JIC x 1/4 in. NPT) Male Branch Tee (7/16-20 JIC x 1/8 in. NPT) Male Branch Tee (7/16-20 JIC x 1/4 in. NPT) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

23 System Components Page 1-15 Check Valves Description Actuation line check valves are used to prevent actuation line pressure from unnecessarily pressurizing sections of actuation piping and preventing cylinder pressure from escaping through the actuation line relief valve. Part No Shipping Assembly Part No. Description /4 in. Check Valve (Female-to-Female) /4 in. Check Valve (Male-to-Male) Part No TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

24 System Components Page 1-16 Relief Valve Description The actuation line relief valve allows excess actuation line pressure to be vented from the actuation piping. Part No Shipping Assembly Part No. Description Safety Relief Valve 275 psi (18.9 bar), 1/4 18 NPT TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

25 System Components Page 1-17 Vent Poppet Description The 2-Way Poppet Valve (Part No. 1732) allows the remaining actuation line pressure to be manually vented from the actuation line prior to resetting and recharge of the system. Part No Shipping Assembly Part No. Description 1732 Two-Way Poppet Valve 1/8 in. 27 Male NPT TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

26 System Components Page 1-18 Pressure Switch DPST Description The pressure switch is operated by the nitrogen agent pressure when the system is discharged. The pressure switch can be used to open or close electrical circuits to either shut down equipment or turn on lights or alarms. The double pole, single throw (DPST) pressure switch is constructed with a gasketed, water tight housing. The housing is constructed of malleable iron, painted red. A 1/4 in. NPT pressure inlet is used to connect the 1/4 in. pipe from the AQUASONIC system. The pressure switch can be installed either before or after the pressure reducer in the distribution piping. Minimum operating pressure is 50 psi (3.5 bar). Shipping Assembly Part No. Description Pressure switch DPST Component Material Thread Size/Type Electrical Rating Approvals Pressure Switch Switch: Conduit Inlet: 3/4 in. NPT Female 2 HP 240 VAC/ FM Approved DPST BAKELITE Pressure Inlet: 1/4 in. NPT Female 480 VAC Housing: 2 HP 250 VDC, Malleable 30A 250V AC/DC Iron 5A 480V AC/DC Piston: Brass Cover: Brass 3 5/8 IN. (9.2 cm) TO ELECTRICAL EQUIPMENT TO BE CONTROLLED MALLEABLE IRON FINISH RED PAINT BRASS RESET PLUNGER MOISTURE-PROOF JOINT 2 7/8 IN. (7.3 cm) GASKET NUT O RING GASKET NAMEPLATE DOUBLE POLE HEAVY DUTY TOGGLE SWITCH WITH FULLY ENCLOSED BAKELITE BASE 4 9/16 IN. (11.5 cm) BRASS PISTON PISTON O RING GASKET TO POWER 3/4 IN. ELECTRICAL CONDUIT OUTLETS 1/4 IN. UNION /64 IN. (7.5 mm) MOUNTING HOLE TYP. 2 PLACES 1/4 IN. PIPE FROM CYLINDERS BAKELITE is a trademark of Union Carbide Corp. TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

27 System Components Page 1-19 Pressure Switch DPDT Explosion-Proof Description The pressure switch is operated by the nitrogen agent pressure when the system is discharged. The pressure switch can be used to open or close electrical circuits to either shut down equipment or turn on lights or alarms. The double pole, single throw (DPST) pressure switch is constructed with a gasketed, water tight housing. The housing is constructed of malleable iron, painted red. A 1/4 in. NPT pressure inlet is used to connect the 1/4 in. pipe from the AQUASONIC system. The pressure switch can be installed either before or after the pressure reducer in the distribution piping. Minimum operating pressure is 50 psi (3.5 bar). Shipping Assembly Part No. Description Pressure switch DPDT Component Material Thread Size/Type Electrical Rating Approvals Pressure Switch Housing: Conduit Inlet: 3/4 in. NPT Female 10A VAC FM Approved DPDT Malleable Iron Pressure Inlet: 1/4 in. NPT Female 5A VAC 1/4 IN. PIPE CONNECTION TO CYLINDERS 1/4 IN. UNION 3/8 IN. X 1/4 IN. BUSHING 3/4 IN. CONDUIT OUTLET 7 7/8 IN. (20 cm) 6 1/2 IN. (16.5 cm) 5 3/16 IN. (14.7 cm) 5 1/8 IN. (13 cm) NAMEPLATE 2 5/8 IN. (6.6 cm) 3 9/16 IN. (9 cm) 2 11/32 IN. MOUNTING HOLES /8 IN. (14.2 cm) 3/4 IN. CONDUIT OUTLET Note: Suitable for hazardous locations, Class I, Division I, Groups C, D, and Class II, Division I, Groups E, F, G. TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

28 System Components Page 1-20 Pressure Switch 3PST Description The pressure switch is operated by the nitrogen agent pressure when the system is discharged. The pressure switch can be used to open or close electrical circuits to either shut down equipment or turn on lights or alarms. The three pole, single throw (3PST) pressure switch is constructed with a gasketed, water tight housing. The switch may be used for 3 phase wiring requirements. The housing is constructed of malleable iron, painted red. A 1/4 in. NPT pressure inlet is used to connect the 1/4 in. pipe from the AQUASONIC system. The pressure switch can be installed either before or after the pressure reducer in the distribution piping. Minimum operating pressure is 50 PSI (3.5 bar) Shipping Assembly Part No. Description Pressure switch 3PST Component Material Thread Size/Type Electrical Rating Approvals Pressure Switch Switch: Conduit Inlet: 3/4 in. NPT Female 30A VAC FM Approved 3PST BAKELITE Pressure Inlet: 1/4 in. NPT Female 20A VAC Housing: 3 HP VAC Malleable 7.5 HP VAC Iron 15 HP VAC Piston: 3 PHASE AC Brass 4 IN. (10.1 cm) 3 1/16 IN. A (7.7 cm) RESET KNOB 3 3/4 IN. (9.5 cm) MOISTURE-PROOF GASKET SNAP LOCK-RING O RING GASKET 3/4 IN. NPT PISTON ROD 5 3/16 IN. (13.1 cm) 3 7/8 IN. (9.8 cm) SPRING HALF ROUND ARM TOGGLE SWITCH WITH FULLY ENCLOSED BAKELITE BASE SPACER HALF ROUND ARM SPRING NAMEPLATE BRASS SWITCH HOUSING PISTON ROD 4 9/32 IN. MOUNTING HOLES PISTON O RING GASKET PISTON PISTON-SPOT NUT 3/4 IN. BRASS PLUG SWIVEL NUT UNION HEX BUSHING 3/8 IN. X 1/4 IN. A SECTION A A BAKELITE is a trademark of Union Carbide Corp. TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

29 System Components Page 1-21 Pressure Trip Description The pressure trip is connected to the actuation or discharge line of an AQUASONIC system. By either pneumatic or manual actuation, the pressure trip can release spring or weight powered devices to close doors and windows, open fuel dump valves, close fire dampers or close fuel supply valves. The pressure trip is constructed of brass with two 1/4 in. NPT fittings for connection to discharge or actuation lines. The link on the pressure switch is released either pneumatically, by agent discharge pressure; or manually, by use of the pull ring. The link then releases the device which performs the auxiliary functions. Note: Operating pressure must be a minimum of 75 psi (5.2 bar) with a maximum load of 70 lb (31.8 kg) Shipping Assembly Part No. Description 5156 Pressure trip Component Material Thread Size/Type Approvals Pressure Trip Brass 1/4 in. NPT Female FM Approved TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

30 System Components Page 1-22 Water Tank Relief Valve Description The water tank relief valve (Part No ) is a high flow relief valve that protects the water tanks from overpressurization. Only one relief valve is required in the water tank pressurization piping. Shipping Assembly Part No. Description /2 in. Safety Relief Valve 150 psi (10.3 bar), CE marked TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

31 System Components Page 1-23 System Shut-Off Valves Description The following system shut off valves are available to provide for safe inspection and maintenance of the system. Handles are color coded red for nitrogen, black for water. Nitrogen Shut-Off Valves Shipping Assembly Part No. Description Material Approvals Ball Valve Assembly Brass FM 1 1/2 in. NPT, Approved Nitrogen Inlet Ball Valve Assembly Brass FM 1/2 in. NPT, Approved Nitrogen Inlet Water Shut-Off Valves Shipping Assembly Part No. Description Material Approvals Ball Valve Assembly Brass FM 3/4 in. NPT, Approved Tank Valve Ball Valve Assembly Brass FM 1 1/2 in. NPT, Approved Tank Valve Water/Nitrogen Visual Tamper Seal Shipping Assembly Part No. Description Visual Tamper Seal TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

32 System Components Page 1-24 Nitrogen Discharge Regulators Description The nitrogen discharge regulators are pilot operated, highflow regulators that provide the necessary pressure control at the high-flow rates demanded by the AQUASONIC system. The assemblies are equipped with an adjustable pilot regulator that allows the system pressure to be field set according to the requirements for each specific application. Nitrogen Regulators Shipping Assembly Part No. Description to 5 Atomizer Regulator 600 SCFM (1000 N m 3 /hour) Part No IN. NPT, MALE 15 IN. (379 mm) 10.5 IN. (266 mm) 1 1/2 IN. NPT, FEMALE Replacement Inlet Filter to 15 Atomizer Regulator 1800 SCFM (3000 N m 3 /hour) Part No IN. (264 mm) 1 IN. NPT, MALE 1 1/2 IN. NPT, FEMALE 16 IN. (408 mm) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

33 System Components Page 1-25 Water Pressure Regulator Description The regulator is factory set to provide a delivery pressure of 125 psi (8.3 bar), allowing the proper nitrogen pressure to discharge the water from the tank to the atomizer. 3/8 NPT connections. Material: Brass and chrome plated. Note: A maximum of four 50 gal (189 L) water tanks can be pressurized with a single regulator. Regulators must be piped in parallel to a common water tank pressurization manifold for systems requiring more than one regulator Water Regulator Shipping Assembly Part No. Description Regulator, Tested TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

34 System Components Page 1-26 Atomizer Description The AQUASONIC Atomizer utilizes patent pending advanced technology, combining separate feeds of compressed nitrogen gas and water to generate and uniformly distribute water droplets throughout a protected volume. WATER FLOW CONTROL ORIFICE MOUNTING PLATE NITROGEN INLET Each atomizer is delivered pre-trimmed with the appropriate water flow control orifice, strainer, mounting plate, and dust cap in place. The water supply inlet is 1/2 in. NPT, and the nitrogen supply inlet is 1 in. NPT. The AQUASONIC Atomizer utilizes an in-line restricting orifice plate to generate the appropriate water flow. The system design calculation procedure found in the design section must be used to determine the required atomizer. ATOMIZER DUST CAP WATER SUPPLY STRAINER WATER INLET Note: When ordering an AQUASONIC System, the atomizer is based on selected orifice size. Atomizer Assembly Selection Atomizer Pressure Range Atomizer Assembly Part No psi ( bar) psi ( bar) psi ( bar) psi ( bar) psi ( bar) Replacement Y-Strainer Screen Part No TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

35 System Components Page 1-27 Pneumatic Selector Valve Selector valves are used when two or more hazard enclosures will be protected with a single supply or a single main and reserve system. Selector valves are operated pneumatically or electrically. When electrical operation is required, a solenoid valve mounted in the actuation line manifold on the system sends actuation line pressure from the ANSUL AUTOMAN II-C release to the appropriate selector valve. Up to eight hazard enclosures may be protected by a single supply. Selector valve assemblies may be used in conjunction with optional pneumatic remote actuators where required. Part No /2 IN. DISCHARGE SELECTOR VALVE VISUAL INDICATOR PURGE VALVE 3/4 IN. WATER OUTLET 1 1/2 IN. NITROGEN OUTLET 3/4 IN. DISCHARGE SELECTOR VALVE An AQUASONIC selector valve assembly consists of a 3/4 in. selector valve for water, a 1 1/2 in. selector valve for nitrogen, brass inlet and outlet piping with union couplings, a regulator to control actuation pressure, actuation line connections and check valves, a poppet-style purge valve for the actuation line, an over pressure relief valve for the actuation line, and a mounting plate. Actuation line pressure is regulated at 50 psi (3.4 bar). Once activated, the selector valves will remain open until the actuation line pressure is purged from the actuation line. 1/4 IN. REGULATOR, PRESET 50 PSI (3.4 BAR) 1/4 IN. FROM OPTIONAL MANUAL REMOTE ACTUATOR C B 1/4 IN. TO CHECK VALVE ON SYSTEM ACTUATION LINE A 1/4 IN. INLET FROM SOLENOID VALVE OUTLET OVER PRESSURE RELIEF VALVE 3/4 IN. WATER INLET 1 1/2 IN. NITROGEN INLET The solenoid is 24 volt DC 11.6 watts 0.48 amps. Pneumatic Selector Valve Equivalent Length OUT TO SELECTOR VALVE ASSEMBLY 1/4 IN. CONTROL LINE SELECTOR VALVE 3/4 in ft 1 1/2 in ft A PORT TO CONNECT TO MANIFOLD PORT TO CONNECT TO MANIFOLD B IN TO SYSTEM FROM SELECTOR VALVE ASSEMBLY TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

36 System Components Page 1-28 Electric Selector Valves Description Solenoid-operated selector valves are available in two sizes: 3/4 in. and 1 1/2 in. The 3/4 in. selector valve has a 24 volt DC 11.6 watt coil that draws 0.48 amps. The 1 1/2 in. selector has a 24 volt DC 22.6 watt coil that draws 1 amp. Each valve can be used for either water or nitrogen lines. Electric Selector Valve Equivalent Length Part No /8 IN. (15.5 cm) 4 3/8 IN. (11.1 cm) 3/4 in ft 1 1/2 in ft Shipping Assembly Part No. Description /4 in. Electric Selector Valve /2 in. Electric Selector Valve Part No IN. (10.2 cm) 2 3/4 IN. (7 cm) /8 IN. (10.6 cm) 3 7/8 IN. (9.8 cm) 5 1/8 IN. (13 cm) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

37 System Components Page 1-29 Nameplate AQUASONIC System (US) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

38 System Components Page 1-30 Nameplate AQUASONIC System (EMEA) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

39 System Components Page 1-31 Nameplate MAIN Description The MAIN nameplate is available for labeling components and/or remote pull stations to distinguish them from reserve system components. The nameplate is furnished with four mounting holes for ease of installation. Shipping Assembly Part No. Description Nameplate MAIN Component Material Mounting Hole Size Approvals Nameplate Aluminum 13/64 in. (0.52 cm) FM Approved 5 1/2 IN. (13.9 cm) 4 7/8 IN. (12.4 cm) 5/16 IN. (.8 cm) 5/16 IN. (.8 cm) MAIN 1 7/8 IN. (4.7 cm) 2 1/2 IN. (6.4 cm) PART NO /64 IN. (.5 cm) DIAMETER HOLES TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

40 System Components Page 1-32 Nameplate RESERVE Description The RESERVE nameplate is available for labeling components and/or remote pull stations to distinguish them from main system components. The nameplate is furnished with four mounting holes for ease of installation. Shipping Assembly Part No. Description Nameplate RESERVE Component Material Mounting Hole Size Approvals Nameplate Aluminum 13/64 in. (.52 cm) FM Approved 5 1/2 IN. (13.9 cm) 4 7/8 IN. (12.4 cm) 5/16 IN. (.8 cm) 5/16 IN. (.8 cm) RESERVE 1 7/8 IN. (4.8 cm) 2 1/2 IN. (6.4 cm) PART NO /64 IN. (.52 cm) DIAMETER HOLES TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

41 System Components Page 1-33 Warning Plate Inside Room With Alarm Description The warning plate is available for mounting inside the hazard area to warn the personnel to vacate the hazard area when the alarm sounds. The warning plate is furnished with four mounting holes for ease of installation. The plate is constructed of aluminum. Shipping Assembly Part No. Description Warning Plate inside room with alarm Component Material Mounting Hole Size Approvals Warning Plate Aluminum 1/4 in. (0.64 cm) FM Approved WHEN ALARM SOUNDS VACATE AT ONCE AQUASONIC SYSTEM BEING RELEASED 7.00 LABEL NO TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

42 System Components Page 1-34 Warning Plate Outside Room Without Alarm Description The warning plate is available for mounting outside the hazard area to warn the personnel that the space is protected by an AQUASONIC system and no one should enter after a discharge without being properly protected. The warning plate is furnished with four mounting holes for ease of installation. Shipping Assembly Part No. Description Warning Plate outside room Component Material Mounting Hole Size Approvals Warning Plate Aluminum 7/32 in. (0.56 cm) FM Approved 8.00 WARNING THIS SPACE IS PROTECTED BY AN AQUASONIC FIRE SUPPRESSION SYSTEM. WHEN SYSTEM IS DISCHARGED AS A RESULT OF FIRE, CAUTION MUST BE TAKEN TO AVOID EXPOSURE TO PRODUCTS OF COMBUSTION. DO NOT ENTER WITHOUT APPROVED SELF- CONTAINED BREATHING APPARATUS OR UNTIL VENTILATION HAS BEEN OPERATED FOR AT LEAST 15 MINUTES LABEL NO TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

43 System Components Page 1-35 Pressure Test Assembly Description The Pressure Test Assembly, Part No , is required to properly perform the annual pressure check per NFPA 750. The pressure test assembly consists of a calibrated gauge, adaptor, and handwheel. The assembly is attached to the fill port of the CV-98 or nitrogen cylinder valve. As the handwheel is turned in, the fill port is opened and the pressure is read on the gauge. After verifying the pressure in the cylinder, the handwheel is turned out, closing the fill port, and the assembly can be removed. Shipping Assembly Part No. Description Pressure Test Assembly CV-98 Component Material Approvals Handwheel Cast Zinc Alloy FM Approved Body Brass Adaptor Brass Gauge Stainless Steel Case Laminated Safety Glass Lens TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

44 System Components Page 1-36 Check Valves Description Check valves are used in main/reserve and selector valve systems. On main/reserve systems, the check valve prevents pressurization of the reserve system manifold by blocking the flow of nitrogen and/or water from the main system to the reserve system. The check valve allows nitrogen and/or water flow from the reserve (if actuated) to pass through into the distribution piping. The check valves are available in sizes of 3/4 in., 1 in., and 1 1/2 in. Shipping Assembly Part No. Description /4 in. check valve in. check valve /2 in. check valve Equivalent Length Component Material Thread Size/Type Body Type Approvals (Sch. 80 Pipe) Check Valve Bronze 3/4-14 NPT Female Threaded FM Approved 24.0 ft (7.3 m) Check Valve Bronze /2 NPT Female Threaded FM Approved 28.0 ft (8.5 m) Check Valve Bronze 1 1/2-11 1/2 NPT Female Threaded FM Approved 51.0 ft (15.5 m) Note: For FM Approved systems, each FM Approved check valve, after discharge, must be disassembled, inspected for corrosion and wear, replace gasket and parts as necessary, and reassembled. A BONNET SPRING CHECK B BODY Check Valve Threaded Dimension A Dimension B Valve Size in. (cm) in. (cm) 3/4 in. 3 5/8 (9.2) 3 1/8 (7.9) 1 in. 4 1/8 (10.4) 3 3/4 (9.5) 1 1/2 in. 5 1/2 (13.9) 5 1/8 (13) TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI Form No. F Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved.

45 SECTION II Page 2-1 General Information The AQUASONIC Water-Atomizing Fire Suppression System conforms to the requirements of NFPA 750 "Standard on Water Mist Fire Protection Systems. System inspection, testing, maintenance, and personnel training shall be implemented in accordance with NFPA 750 or equivalent national or international standards. The AQUASONIC System is a total-flood water atomizing system designed to protect Class B flammable liquid hazards in machinery spaces, insulated and non-insulated combustion turbine enclosures, and incidental flammable liquid storage. The machinery space application includes rooms with machinery such as oil pumps, oil tanks, fuel filters, generators, transformer vaults, gear boxes, drive shafts, lubrication skids, diesel engine drive generators, and other similar machinery. The AQUASONIC System can protect a potential hazard with a volume exceeding 9200 ft 3 (260 m 3 ) up to and including ft 3 (1040 m 3 ) with atomizers that use lowpressure, dual-flow, advanced atomization technology to create a minimum 10 minute discharge plume of water droplets that are the optimum size to suppress a Class B fire. The AQUASONIC System has been fire tested within compartmentalized areas and found effective for the suppression of a wide variety of exposed and shielded Class B hydrocarbon pool, spray, and gravity fires. The mechanisms by which the discharge acts to extinguish a Class B fire normally involve a combination of the following factors: 1. Heat extraction from the fire as water is converted into vapor and the fuel is cooled. 2. Dilution of flammable vapors by the entrainment of water vapor, to such an extent that the resultant mixture of vapor will not burn. 3. Cooling of liquid hydrocarbon fuels below vaporization temperature, to such an extent that the vapor will not burn.! CAUTION Unnecessary exposure to systems resulting in low oxygen atmospheres shall be avoided. The normal atmosphere in a room contains approximately 21% oxygen. In enclosures with an extended AQUASONIC discharge, the oxygen concentration may be reduced below 12.5%. The maximum exposure time in any case shall not exceed five minutes from start of discharge. Unprotected personnel shall not enter the area during or after agent discharge.! CAUTION Water-atomizing systems shall not be used for direct application to materials that react with water to produce violent reactions or significant amounts of hazardous products. Such materials include the following: Reactive metals such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium, and plutonium. Metal alkoxides, such as sodium methoxide. Metal amides, such as sodium amide. Carbides, such as calcium carbide. Halides, such as benzoyl chloride and aluminum chloride. Hydrides, such as lithium aluminum hydride. Oxyhalides, such as phosphorus oxybromide. Silanes, such as trichloromethylsilane. Sulfides, such as phosphorus pentasulfide. Cyanates, such as methylisocyanate. Note: Non-acceptable hazards include rack or palletized storage of flammable or combustible liquids. SPRAY CHARACTERISTICS When sprayed into a hazard, the AQUASONIC Atomizer creates a conical spray pattern which has a diameter of approximately 36 in. (0.9 m) at a distance of 72 in. (1.8 m) and greater from the atomizer. When sprayed within an enclosure, the AQUASONIC Atomizer spray pattern expands slightly and the water droplets are primarily distributed (circulated) around the space through the high velocity atomizing media discharge. As the high velocity discharge plume of tiny droplets approaches the floor or other horizontal obstruction, a large majority of the plume is diverted laterally as well as vertically upwards, filling the space between the core spray patterns and the space above the atomizers. The circulation characteristics of the AQUASONIC Atomizer plume result in rapid, homogenous distribution of water droplets throughout the protected environment.

Worldwide Contacts. General Description

Worldwide Contacts.  General Description Worldwide Contacts www.tyco-fire.com AQUAMIST Red-E Mist Supply Skid Table of Contents Sections General Description....1 Training...3 Technical Data...3 Skid Operation...3 System Components...6 Planning...6

More information

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual 002694 IntroductIon 8-1-11 Page 1 ForEWord This manual is intended for use with

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Vertical Bladder Tanks

Vertical Bladder Tanks DATA SHEET Vertical Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

Horizontal Bladder Tanks

Horizontal Bladder Tanks DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

KFI Approved. High Pressure CO2 System Technical Datasheets

KFI Approved. High Pressure CO2 System Technical Datasheets KFI Approved High Pressure CO2 System Technical Datasheets CONTENTS CO 2 CYLINDER 1 CYLINDER VALVE 3 NEEDLE VALVE 4 FLEXIBLE HOSE 5 SAFETY VALVE 6 SELECTOR VALVE 7 ACTUATING DEVICE 9 DISCHARGE NOZZLE 10

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company CIF A Tyco International Company 1 Foam Concentrate CIF 3% AFFF -UL Listed -UL Canada Listed 6% AFFF 6 parts AFFF concentrate to 94 parts water -UL Listed- Foam Liquid -UL Canada Listed 3% FLUOROPROTEIN

More information

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013 Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release

More information

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA. Trimpac 244a. September 16, 2013 September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013 September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013 October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve

More information

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Horizontal Bladder Tanks DATA SHEET Model MTB-ASME Horizontal Bladder Tanks Features n UL Listed and FM Approved for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure

More information

Vertical and Horizontal Bladder Tanks

Vertical and Horizontal Bladder Tanks DATA SHEET Vertical and Horizontal Tanks Application The ANSUL bladder tank is one component in a balanced pressure proportioning system. Its operation requires no external power other than a pressurized

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Model PSI Compressor with 3-Gallon Air Tank 12VDC Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing

More information

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Sampler Model GSS-1 The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

RIX COMPRESSORS. MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230. November 21, 2002 APPLICABILITY [ A]

RIX COMPRESSORS. MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230. November 21, 2002 APPLICABILITY [ A] RIX COMPRESSORS MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230 November 21, 2002 APPLICABILITY [ A] INTRODUCTION Safety This electromechanical equipment is designed to produce high pressure gas.

More information

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002 Installation Guide English May 2002 Type ACE97 Introduction This installation guide provides instructions for installation, startup, and adjustment. To receive a copy of the instruction manual, contact

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated

More information

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation Size: inch / mm Every Ross Valve shall be hydrostatically tested for body integrity and tight seating

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated

More information

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves. Powers Controls RV 201 Pressure Reducing Valves Description Features Product Numbers Dual Pressure PRV Technical Instructions Document No. 155-049P25 RV 201-1 Single Pressure PRV The RV 201 Pressure Reducing

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

BGA158 Series CE Approved Class B Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.

More information

G96 Series BASOTROL Dual Operator Valve

G96 Series BASOTROL Dual Operator Valve Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without

More information

G92 Series BASOTROL Automatic Pilot Gas Valve

G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These

More information

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

1805 Series Relief Valves

1805 Series Relief Valves Instruction Manual Form 1211 1805 Series October 2011 1805 Series Relief Valves! WARNING Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion

More information

CLEAN AGENT FIRE EXTINGUISHING SYSTEM MX 1230 Extinguishing Agent Cylinders

CLEAN AGENT FIRE EXTINGUISHING SYSTEM MX 1230 Extinguishing Agent Cylinders The technical data described herein is for components of the Minimax Fire Products MX 30 Clean Agent System. For design, installation, and operation instructions, refer to the latest edition of the original

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

Tri-Tech Medical Inc.

Tri-Tech Medical Inc. Introduction Tri-Tech Medical manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists

More information

GM-7000 Series CE Approved Gas Control Valve

GM-7000 Series CE Approved Gas Control Valve Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

Pressure Dump Valve Service Kit for Series 3000 Units

Pressure Dump Valve Service Kit for Series 3000 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 000 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00, 400, 500, and 700 applicator

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

Storage Systems and Accessories

Storage Systems and Accessories Storage Systems and Accessories High Pressure Air and Inert Gases 4500-6000 PSIG DOT and ASME Cylinders High Pressure Storage Systems If an application requires storage, either in the form of a single

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record

More information

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Installation Instructions BGA Series Issue Date October 3, 2017 BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Applications The BGA Series shutoff gas valve is an electrically operated gas valve that

More information

TotalPac X Single interlock Preaction system Electric release

TotalPac X Single interlock Preaction system Electric release DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a preaction system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical

More information

Anti-flood device Model B-1

Anti-flood device Model B-1 December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET

More information

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401 THE MF-400 SERIES Operating and Service Manual Series includes all variants of MF-400/401 Issue A October 2013 1 TABLE OF CONTENTS 1. Description... 3 2. Installation... 3 3. Operation... 4 4. Special

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS 36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6 Sub Section INDEX Page Number 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6 6. INSTALLATION AND OPERATION 6 7. MAINTENANCE 8 8. REPAIR 9 9. ASSEMBLY 10 10.

More information

Pressure Regulator B-95

Pressure Regulator B-95 Pressure Regulator B-95 TYPE B WATER & AIR TYPE B INTERIOR WATER & AIR B SERIES VALVES DESTRIPTION The Cash Valve Series B pressure reducing and regulating valves are single seated, spring loaded, direct

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock: - Do not disassemble. Do not attempt repairs or modifications. Refer to qualified service agencies for all service and repairs.

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , & REDQ Regulators Model 411B Barstock Design Powreactor Dome Regulator OPERATION AND MAINTENANCE Contents Scope..............................1 Installation..........................1 General Description....................1

More information

Oxygen Usage Best Practice Guide

Oxygen Usage Best Practice Guide Oxygen Usage Best Practice Guide 1. Introduction Oxygen enriched systems possess a risk of fire and explosion since ignition and combustion hazards are present in all oxygen systems, and oxygen related

More information

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013 September 16, 2013 Trimpac 247a_Euro 1. DESCRIPTION DEsCrIpTIoN TRIMPAC Model B-11 LPCB Type 1 is a factory assembled trim package for a single interlocked electric release module in a metal enclosure.

More information

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION Page 1 of 6 1. DESCRIPTION The Model B-1 Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET condition,

More information

Section 3000 CONVEYOR CHAIN LUBRICATION SCHEMATIC...39 AIR OPERATED SPRAY DISPENSERS - CENTRAL ACRYLIC RESERVOIR Section 3000 Index

Section 3000 CONVEYOR CHAIN LUBRICATION SCHEMATIC...39 AIR OPERATED SPRAY DISPENSERS - CENTRAL ACRYLIC RESERVOIR Section 3000 Index Section 3000 AIR OPERATED SPRAY DISPENSERS - CENTRAL ACRYLIC RESERVOIR...36 Versatile type of lubrication able to feed liquid to elevated, distant or inaccessible points. CONVEYOR CHAIN LUBRICATION SCHEMATIC...39

More information

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50) Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge

More information

FOAM TANK (1/2) DATA SHEET

FOAM TANK (1/2) DATA SHEET FIRE FIGHTING EQUIPMENT DATA SHEET FOAM TANK (1/2) DATA SHEET JOB NO. : RFQ. NO. : ISSUE : SHEET OF 01 CUSTOMER : ITEM NO. : 02 PROJECT : QUANTITY : 03 LOCATION : SERVICE : FOAM SYSTEM 04 05 CODE & STANDARDS

More information

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012 Installation Guide English September 2012 299H Series Introduction This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5.

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5. Installation Instructions manual MUELLER table of contents PAGE A-20814 Wall Type General Information 2 Technical Data/ Dimensions Installation 4-5 Maintenance 6 Parts 7 Indicator Post! WARNING: 1. Read

More information

Operating Instructions Model and Hydrostatic Test Pump

Operating Instructions Model and Hydrostatic Test Pump Operating Instructions Model 39300 and 39301 Hydrostatic Test Pump Dimension Weight Pump Style Capacity Pressure Motor Lubrication Control Gauge Inlet Connection Outlet Connection Discharge Hose Hose Ends

More information

WaterSource Heat Pump Hose Kit Performance Specification-Summary

WaterSource Heat Pump Hose Kit Performance Specification-Summary WaterSource Heat Pump Hose Kit Performance Specification-Summary AUTOMATIC & MANUAL BALANCING HOSE KITS Contractor shall provide and install Hays Hose Kits. Each kit, shall include a Hays 2500 Series Mesurflo

More information

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,

More information

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301 THE HF-300 SERIES Operating and Service Manual Series includes all variants of HF-300/301 Issue A July 2015 1 TABLE OF CONTENTS 1. Description... 3 2. Installation... 3 3. Operation... 4 3.1. Spring Loaded...

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

ECS Protector Nitrogen Inerting Vent (PAV-WN)

ECS Protector Nitrogen Inerting Vent (PAV-WN) ECS Protector (PAV-WN) U.S. Pat. No. 8,636,023, 9,526,933 and 9,717,935 B2 Specifications Stock Number: Service Pressure: Regulator Setting: System Connection: Temperature Range: Dimensions: Weight: Clear

More information

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO 400H HARDMOUNT AIR COMPRESSOR KIT PART NO. 40042 450H HARDMOUNT AIR COMPRESSOR KIT PART NO. 45042 400H 450H IMPORTANT: It is essential that you and any other operator of this product read and understand

More information

SAPPHIRE SUPPRESSION SYSTEMS

SAPPHIRE SUPPRESSION SYSTEMS SAPPHIRE SUPPRESSION SYSTEMS Design, Installation, Recharge and Maintenance Manual EQUIPMENT: SAPPHIRE (UL) PUBLICATION: 570805 ISSUE No. 00 DATE: 2011-02 SAPPHIRE TOTAL FLOOD FIRE SUPPRESSION SYSTEMS

More information

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM IMI CORNELIUS INC One Cornelius Place Anoka, MN 55303-623 Telephone (800) 238-3600 Facsimile (612) 22-326 INSTALLATION INSTRUCTIONS FOR INSTALLING CO 2 BLENDER KIT (P/N 111612000 IN BEER SYSTEM SECONDARY

More information

BUTTERFLY VALVES Series 800

BUTTERFLY VALVES Series 800 BUTTERFLY VALVES Series 800 WARNING Before proceeding read ALL instructions and become familiar with the equipment and associated drawings. Follow ALL applicable safety regulations and codes for pressurized

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

GETZ EQUIPMENT INNOVATORS RECOVERY SYSTEM CLEAN AGENT FE-36 / HALOTRON 1 PART NO. 4G59751 OPERATIONS MANUAL

GETZ EQUIPMENT INNOVATORS RECOVERY SYSTEM CLEAN AGENT FE-36 / HALOTRON 1 PART NO. 4G59751 OPERATIONS MANUAL GETZ EQUIPMENT INNOVATORS CLEAN AGENT FE-36 / HALOTRON 1 PART NO. 4G59751 OPERATIONS MANUAL GETZ EQUIPMENT INNOVATORS PEKIN, ILLINOIS, U.S.A. PHONE: (888) 747-4389 FAX: (309) 495-0625 Limited Warranty

More information

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE Page 1 of 10 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm and flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge

More information

Tank Blanketing Pressure Regulators RHPS Series

Tank Blanketing Pressure Regulators RHPS Series www.swagelok.com Tank Blanketing Pressure Regulators RHPS Series Types: pressure reducing and vapor recovery 16L stainless steel construction 1/2, 1, and 2 in. end connections Working pressures up to 22

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information