Installation Instructions. Canoga Vehicle Detection System Model 702 Non-invasive Microloop

Size: px
Start display at page:

Download "Installation Instructions. Canoga Vehicle Detection System Model 702 Non-invasive Microloop"

Transcription

1 Installation Instructions Canoga Vehicle Detection System Model 702 Non-invasive Microloop

2 Model 702 Microloop Installation Instructions Table of Contents Section 1 About This Installation Instruction 1.1 Purpose Conventions Related Publications Installation Instruction Organization...1 Section 2 Safety Messages and Safety Labels 2.1 Safety Message Formats Damage Prevention Messages Safety Label Formats Safety Label Locations...4 Section 3 Safety 3.1 Safety Messages in this Installation Instruction Safety Labels on these Devices Electric Shock and Electrocution Work Zone Traffic Control Personal Safety Equipment and Clothing Excavation Disposal of Material...5 Section 4 Description Section 5 Features Section 6 Planning Section 7 Conduit Installation 7.1 Installed Conduit Recommendations Handholes Conduit Type Conduit Installation Specifications...10 Section 8 Microloop Installation Section 9 Installation Completion and Checkout 9.1 Installation Completion Splicing Lead-in Cables Installation Checkout...16 Section 10 Troubleshooting

3 Table of Contents Model 702 Microloop Installation Instructions (Blank Page)

4 Installation 1 1 About This Installation Instruction 1.1 Purpose This installation instruction provides step-by-step instructions for installing and setting-up the 3M Canoga Vehicle Detection System Model 702 Non-invasive Microloop. It is intended for use by maintenance personnel and others who are responsible for installation of the Canoga system. 1.2 Conventions The conventions in Table 1-1 help to make this installation instruction easier to use by presenting a uniform approach to the descriptions, phrases and nomenclature. 1.3 Related Publications The Canoga Vehicle Detection System Operation Manual, Canoga Model 800 Series Installation Instructions, Canoga 800IS Interface and Data Acquisition Software and Canoga Vehicle Detection Systems Model 701 Microloop Operation Manual. 1.4 Installation Instruction Organization This installation instruction is divided into 10 sections. Section 1. About This Installation Instruction This section describes the purpose of the installation instruction, identifies the audience, defines the writing conventions, lists the related publications, and summarizes the organization of the installation instruction. Section 2. Safety Messages and Safety Labels This section contains important information about the safety messages in this installation instruction. This section also contains important information about safety precautions and procedures for installation of this device and sources for other safety information. This section also contains a compilation of all the safety messages and warning labels that appear in the instructions or on the devices. Section 3. Safety This section contains important information for you to consider before beginning the installation. Table 1-1. Conventions Model Names Model Name First or formal reference: initial caps Subsequent use or informal reference: Initial caps for model, lowercase for remainder 3M Canoga Vehicle Detection System Model 702 Non-invasive Microloop Model 702 Microloop probes, or the Microloop probe(s) set(s) System Conditioners and Signal Names System mode or phase Initial caps Enable Microloop mode System status Initial caps The Status output or indication Signal name Initial caps the Reset signal

5 2 Installation Section 4. Description This section describes the function of the device, the theory of operation and depicts the physical configuration of the device. Section 5. Features This section contains a list of the features of the device. Section 6. Planning This section contains instructions about preparing for installing the conduit and Microloop. Section 7. Conduit Installation This section contains step-by-step instructions for preparing and installing the conduit. Section 8. Microloop Installation This section contains step-by-step instructions for preparing and installing the Microloop components. Section 9. Installation Checkout and Completion This section contains information and procedures on how to checkout and test the installed system. Section 10. Troubleshooting This section contains information on how to identify and correct problems.

6 Installation 3 2 Safety Messages and Safety Labels Your safety and the safety of others is very important. We provide important safety messages in this installation instruction and on the device. Please read the safety messages and safety labels carefully before beginning the work. We also provide important damage prevention messages in this installation instruction. 2.1 Safety Message Formats A safety message alerts you to potential hazards that can cause personal injury to you and others, or property damage. Each safety message includes a safety alert symbol ( ) and one of three words: DANGER, WARNING, or CAUTION to describe the relative level of hazard. The words and symbols and their meanings are shown below:! DANGER The safety message is in this box. DANGER means you and/or someone else WILL be KILLED or SERIOUSLY HURT if you do not follow these instructions. 2.2 Damage Prevention Messages We provide important safety messages in this manual to help you prevent damage to the devices. Each damage prevention message includes the word NOTICE. This word and its meaning are shown below: NOTICE The damage prevention message is in this box. NOTICE means that this device, or another device, may be damaged if you do not follow the instructions. These messages are to help you prevent damage to the device, other devices, and to the environment. 2.3 Safety Label Formats A safety label alerts you to potential hazards that can cause personal injury to you and others, or property damage. Each safety label includes a symbol or pictogram, a word to describe the relative level of the hazard and explanatory text. The words and symbols or pictograms and their meanings are shown below:! WARNING The safety message is in this box. WARNING means you and/or someone else MAY be KILLED or SERIOUSLY HURT if you do not follow these instructions.! CAUTION The safety message is in this box. CAUTION means you and/or someone else MAY be HURT or property damage may result if you do not follow these instructions. Each safety message explains what the hazard is, what can happen to you or others, and what you can and should do to avoid the risk of exposure to the hazard. Please read the safety messages and safety labels carefully before beginning the work. DANGER means you WILL be KILLED or SERIOUSLY HURT if you do not follow the instructions. WARNING means you MAY be KILLED or SERIOUSLY HURT if you do not follow the instructions.

7 4 Installation CAUTION means you MAY be HURT or property damage may result if you do not follow the instructions. Please read the safety messages and safety labels carefully before beginning the work. 2.4 Safety Label Locations We put safety labels on the devices where you will see them before you may be exposed to a hazard. Please read the safety labels. They contain important safety information. We consider safety labels to be an important part of the device and they should be replaced if they are damaged or they become hard to read. If any of the safety labels on this device are missing or cannot be read please contact your dealer or 3M Intelligent Transportation Systems Technical Service for a replacement.

8 Installation 5 3 Safety Below are some of the common hazards associated with the installation traffic control devices. Although we have included many of the hazards in this list it does not contain all of the possible hazards and this list should not be a substitute for your judgment and experience. Included below is a compilation of all of the safety messages contained in this installation instruction and a compilation of all of the safety labels on the device(s). 3.1 Safety Messages in this Installation Instruction There are no safety messages in this installation instruction: 3.2 Safety Labels on these Devices There are no safety labels on any of the Model 702 devices. 3.3 Electric Shock and Electrocution As a trained installer of electrical equipment you are aware of the dangers associated with installation of electrical devices. Always be sure that the power to the equipment, and all associated equipment, is off before beginning any procedure. Use the equipment, techniques and procedures that you learned during your training or apprenticeship or other electrical industry recognized safety procedures. 3.5 Personal Safety Equipment and Clothing Personal safety equipment includes high visibility vests, hard hats, gloves, electrical shock or electrocution protection clothing and equipment, safety shoes, and safety glasses. These are just some of the items available to you. Choose the right equipment for the job. If you are unsure of which safety equipment is recommended or appropriate for the job ask your supervisor or foreman. 3.6 Excavation Excavation in areas where buried utilities and services may be present is dangerous. The excavation, or piercing or boring equipment may come in contact with these and you could be exposed to the risk of injury or death. Please take appropriate steps to identify and locate buried utilities and services before you begin the work. Contact the appropriate agencies for information about the utilities or services. Contact your supervisor if you are unsure. Do not proceed. 3.7 Disposal of Material Please dispose of material or devices in accordance with local, state and federal laws and regulations. 3.4 Work Zone Traffic Control Proper control of vehicle traffic is important during many procedures. When you switch the traffic controller to and from the flash mode we recommend that you have people trained in manual traffic control, such as police officers, assist you. When you install devices that require you to position vehicles, equipment, or people in or near the roadway it is important that you use appropriate work zone traffic control techniques, equipment and procedures. Sometimes you may have to work on or near the roadway and these same techniques, equipment and procedures should be used for your protection. If you are unsure of which procedure is recommended or appropriate for the job ask your supervisor or foreman.

9 6 Installation 4 Description The following section contains general information concerning the installation and use of the system. The 3M Canoga Vehicle Detection System Model 702 Non-invasive Microloop is intended to replace conventional 6-foot by 6-foot loops for advance detection and traffic survey applications. The components of the Model 702 are the Microloop assembly and the carrier system which includes a conduit end cap, an end cap carrier with pull rope, carrier sections, cable ties with labels, conduit coupler, carrier cradle, cradle lock, landscape fabric and re-usable cable tie clamps. The system allows the Microloop to be installed under the roadway without cutting or sawing of the road surface. This is implemented by use of soil piercing or soil boring technology to install conduit under the roadway. Trenching methods may also be used as appropriate. Conduit can be installed prior to roadway paving on new construction projects. Each component is designed for quick assembly and insertion into the conduit. Installation preparation is made easy by marking on the pull rope the intended locations of the probes. Then, as the sections are assembled and pushed into the conduit, along with the pull rope, you can insert the probe(s) into the carrier when you reach a mark on the pull rope. The carrier sections are twelve inches long They are designed with probe placement openings on six-inch centers when the carriers are assembled. Each carrier section is secured to the previous section by a stainless steel clip. We recommend that the final section be secured to the cradle with the cradle carrier lock and screws provided. This step insures that final assembly is held securely in position. Note In a typical installation consisting of two probes per lane, the Model 702 Microloop probes are positioned four feet apart across the lane (two feet on each side of the center of each travel lane). Figure 4-1 shows cross sections of a roadway and of the conduit used under the roadway in a typical advance detection installation. Figure 4-1. Typical Microloop Installation

10 Installation 7 Figure 4-2 shows the location of the conduits, handholes, and probes in a typical traffic survey installation. Figure 4-2. Typical Model 702 Non-invasive Microloop Installation Speed Measuring Layout

11 8 Installation 5 Features Easily installed in three inch Schedule 80 PVC or seamless polyethylene conduit Easily modified to remove, relocate or add sensor probes as travel lanes are reconfigured or restriped Model 702 probes can be installed within three inches of desired position in the lane location Minimal interruption of traffic during installation Preserves pavement integrity - no cutting or drilling of road pavement Maintenance can be performed from side of roadway - no need to close lanes Road can be resurfaced without disturbing the underground sensors Sensors not affected by pavement deterioration Can be used under gravel or dirt roads Conduits can be installed prior to paving on new roadway construction projects Can detect closely spaced vehicles and reject most adjacent lane vehicles Five year warranty

12 Installation 9 6 Planning We recommend that you visit the site to allow you to plan the installation with accurate information and knowledge of the site. If you have a plan of the site, take it with you to record pertinent measurements and notes. You should determine the best location(s) for the probe(s) and the handhole(s). Mark the location(s) on the plan. Figure 6-5 shows a worksheet on which you can record measurements and notes. Next, determine the number of probe sets, probe set configuration(s) and the number of carriers required for the installation. For the probe configuration consider the number of Microloop probes per probe set, the desired spacing of the probes and the length of lead-in cable required to reach the handhole or control cabinet. Record the details of each probe set and cross-reference them to the plan. Figure 6-5. Site Plan Worksheet Discuss the locations and the installed conduit specifications with the piercing contractor to ensure that you both have a clear understanding of the requirements (be sure to ask for a copy of the piercing depth log). During installation you may find that a conduit run or a handhole must be relocated to suit the site, e.g. avoid previously buried utilities. Plan to revisit the site after conduit and pullbox/handhole installation to mark your diagram and revise your installation plans as required. Make accurate measurements of the location and length of the conduit run(s) and the location(s) of the handhole(s). Measure from the first probe location to the end of the conduit in the pullbox/handhole. Schedule the installation of the conduit. After the conduit is installed, plan to review the piercing depth log for each conduit.

13 10 Installation 7 Conduit Installation These instructions include recommendations for the installation of the conduit. 7.1 Installed Conduit Recommendations The installed conduit must meet or exceed the following recommendations to provide a useable installation of the 3M Canoga Vehicle Detection System Model 702 Non-invasive Microloop System Handholes The handholes must be a minimum of 24 inches, in diameter for round type or length of the side for rectangular type to allow space to install the conduit coupler and cradle to the conduit in the handhole Conduit Type We recommend rigid 3-inch PVC Schedule 80 conduit. The dimensions must comply with those shown in the Table 7-1. Table 7-1. Conduit Dimensions Inside Diameter Outside Diameter 2.9 inches 3.5 inches Mechanical joints are allowed if the carrier sections can slide freely over the joints. Seamless Polyethylene, PE Schedule 80, may also be used as an alternate. Polyethylene conduit must be free from welds or joints to allow free passage of the carrier sections along the length of the conduit Conduit Installation Specification The following specification must be met to provide a useable installation. 1. The conduit must be installed at a depth of 21 inches, +/- 3 inches, from the road surface to the conduit centerline. If the surface is crowned the conduit installation depth shall conform to the shape of the crown. (See Figure 7-1.) 2. We recommend that you leave 2 to 3.5 inches of conduit extending into the handhole to allow for connection of the coupler and the cradle (as shown in Figure 7-1). Figure 7-1. Graphical Representation of the Installed Conduit Depth Specification

14 Installation As it follows the surface contour, the conduit must consistently maintain its depth from the road surface to avoid vertical dips and horizontal deviations. The conduit should not deviate from a straight line direction by more than 0.25 inches per foot either horizontally or vertically. (See Figure 7-2.) Figure 7-2. Graphical Representation of the Installed Conduit Directional Truing Specification 4. We recommend that you check, and record, the depth of the conduit every two feet during the process of installing the conduit to ensure that the specified depth is maintained. 5. As the conduit extends beneath the surface from the roadway edge to the handhole/pullbox, it should taper slightly downward to help drain any moisture that has seeped in. (See Figure 7-3.) 6. Cap the end of the conduit opposite the handhole to prevent water flow that could introduce soil into the conduit. Large deposits of soil in the conduit will make system removal difficult or impossible without cleaning the soil out of the conduit. Drill a 3/16 inch diameter weep hole in the end cap. Position the weep hole at the bottom of the end cap to drain water from the conduit. To allow for service flexibility, we recommend that the end cap be pressfit, not glued, on the conduit. (See Figure 7-4.) Figure 7-3. Tapering Conduit for Drainage Figure 7-4. Positioning End Cap for Drainage

15 12 Installation 8 Microloop Installation The following steps detail the preparation and installation of the 3M Canoga Vehicle Detection System Model 702 Non-invasive Microloop Probes and Carrier System. Please read the safety messages and safety labels in Section 2 carefully before beginning the work. 1. Review the site plan you prepared earlier. It is assumed that the actual installation has differences from the plan. 2. Measure the distance from the end of the conduit in the handhole to the desired position that the first (furthest away) probe of each probe set to be inserted. Record these dimensions and the space between each probe of a multi-probe probe set on the plan. 3. Identify each probe set and check the continuity of each set with an ohmmeter. The ohmmeter reading should be within ±20% of the sum of 2.0 ohms per probe plus 3.0 ohms/100 feet of lead-in wire. 4. Lay the end cap carrier with pull rope attached out along the ground. 5. Using the site plan you updated and a suitable tape measure, mark the location of each probe on the pull rope using your own tape or using tie wraps provided. 6. Make a knot in the pull rope so that it will be at the end of the cradle when you have inserted all carriers necessary to properly position all probes. Remember to start measuring from the second hole in the end cap carrier. (The pull rope passes through the first hole in the end cap carrier.) 7. If cable ties with labels were used to mark the pull rope, write the plan designation probe set ID on each cable tie using a permanent ink marker. 8. Verify your measurements along the pull rope. Figure 8-1 shows a layout plan for single (one probe per lane), double (two probes per lane), and triple (three probes per lane) probe applications. On East-West roads the probes should be shifted one foot North from the locations shown in Figure 8-1. Figure 8-1. Probe Layout Plan

16 Installation Glue the cradle coupler (connector) onto the conduit stub in the handhole. 10. Pre-position the carrier cradle into the coupler and check for ability to rotate and position the cradle with open side up. See Figure 8-2 for details. 11. Remove cradle and then glue and install the cradle into the conduit coupler. Important: Quickly level the cradle using a torpedo level resting on the cradle lock attachment area to (+ or - 2 ) from level. This must be completed before the glue hardens. 12. Insert the end cap carrier into the cradle with the open side up and the probe insertion holes plumb (at a 90 angle, + or 2, from horizontal). See Figure 8-2 for details. Figure 8-2 Carrier Section Plumb in the Cradle 13. Locate the probe set that is to be installed in the farthest lane from the handhole. Place a cable tie about one foot from the end of the lead-in. Using permanent ink marker, write the plan designation ID for this probe set on the cable tie. 14. Place a second cable tie, labeled with the same information, at the probe of this probe set that is the furthest away (first probe of the probe set). 15. Carefully uncoil the lead-in and lay it out straight to simplify dressing of the cable into the carrier sections as those sections are inserted into the conduit. 16. Repeat Steps for each probe set that is to be inserted in this conduit. 17. Place the first probe of the first probe set (the farthest from the handhole) into the second hole of the end cap carrier. (The pull rope passes through the first hole.) Install the probe by pressing it firmly into the hole until it snaps into place. (Refer to Figure 8-1.) 18. Install another carrier onto the first and secure it with the attached clip. Dress the rope and the cable neatly inside the carrier. Make certain there is no slack in the rope. Push the carrier sections into the conduit. Check to ensure that probe installation holes are vertical. If necessary, rotate the carrier until it is vertical. 19. Continue clipping carriers together and inserting them into the conduit, until you reach the cable tie or tape marking the position for the next probe. 20. Install the next probe in the probe installation hole nearest the cable tie or tape marker. The cable between individual probes of a multiple probe set contains an extra six inches to allow for installation flexibility. 21. Dress this extra six inches of interconnecting cable into the carrier by making an S-fold and placing it into the cable holding area of the carrier. Also, carefully dress the pull rope into the carrier making certain there is no slack. 22. Continue installing carriers and probe sets as required to get to the knot that marks the end of the cradle, (indicating that all carriers necessary to position the Model 702 Microloop probes have been inserted). 23. Secure the last carrier by doing the following: a) Lower the wide end of the slotted holes in the cradle carrier lock over the screws provided. b) Slide the cradle carrier lock so the narrow end of the slotted holes are adjacent to the screws. c) Tighten the screws provided. See Figure 8-3. Figure 8-3 Securing the Cradle Carrier Lock 24. Cut off the excess pull rope.

17 14 Installation 9 Installation Completion and Checkout 9.1 Installation Completion This section explains how to prevent sediment from entering and accumulating inside the conduit. 1. Make sure that the carrier assembly is securely fastened in the carrier lock. 2. Make sure that the cables and pull rope are positioned in the carrier. 3. Check the continuity of the probe cables with an ohmmeter. 4. Wrap the landscape fabric material (provided in the installation kit) around the conduit coupler and cradle assembly. 5. Make sure the probe set identification tags are outside of the landscape fabric material. 6. Use the re-enterable tie wraps provided to secure one end of the landscape fabric material around the cradle connector, and the other end around the probe cables and pullrope. See Figure Drill a 3/16 inch weep hole in the end cap to let trapped water drain out. Position the weep hole downward and pressfit the end cap over the far end of the conduit. Do not glue on the end cap. See Figure 9-2. Figure 9-1. Installation Detail Figure 9-2. Positioning End Cap for Drainage

18 Installation Splicing Lead-in Cables This section explains how to make reliable splices. We recommend that all splices be soldered, insulated and waterproofed. The cable jacket ends must be sealed against moisture entry at the points the cables were cut to perform the splicing. 1. Obtain underground rated splice kits to provide the required protection (such as the 3M Scotchcast 3832 Buried Service Wire Encapsulation Kit). Read the instruction for using the splicing kits. 2. Prepare splice end cap ports to fit snugly over cable jackets, slide end caps over cables and down out of the way. Move cable ID markers, as required, to ensure that they will be visible after the splicing operation is complete. 3. Prepare the lead-in and home-run cables and wires for splicing. Remove 2 to 3.75 inches of cable jacket from each cable taking care not to damage the insulation on interior conductors. 4. If 3M Model Lead-in Cable is being used, it is necessary to heat the jacket with a heat gun or other safe heat source to slide the jacket off the interior shield and conductors. 5. Remove about 0.5 inches of insulation on each conductor that will be used. As instructed by the splicing kit instructions, scuff and clean surfaces that will come in contact with the encapsulating compound. 6. If shrink tubing is being used to insulate the splice, slide a piece of shrink tubing at least 1.5 inches long over the wires to be spliced. Twist the wires to be spliced as shown in Figure 9-3. Solder the twisted wires together. Insulate the soldered connection by shrinking the tubing or by wrapping with at least two layers of electrical tape. 7. Carefully dress all wires and cable jacket ends into the splice kit encapsulation area to prepare the splice kit for adding the encapsulation compound. 8. Complete the splice by adding the encapsulation compound if required. Figure 9-3 shows a typical splicing application. Figure 9-3. Typical Splicing Application

19 16 Installation Figure 9-4 shows how to splice probes or probe sets in series. Figure 9-4. Splicing Probes in Series 9.3 Installation Checkout Final checkout requires connection of the probes to an ohmmeter, a Megohmmeter and then to an inductive loop detector. These instructions assume a 3M Canoga C800 Series Loop Detector, for measurement of operating results. 1. At the cabinet where the loop detectors are located, measure the DC resistance of the sensor. Make certain the sensor is not connected to a loop detector. Touch the meter probes to terminal block contacts where the home-run cable for the sensor being checked is attached. Record the reading. Calculate the expected resistance using the information in Table 9-1. Table 9-1. Resistance Checks Resistance Checks Measuring Point Item Resistance Between Sensor M702 Probe 2.0 ohms/probe Leads Lead-in 3.0 ohms/ Home-run 1.7 ohms/100 Either Lead to Earth Test at 500 VDC >100 megohms 2. Using a Megohmmeter, measure the insulation resistance from each sensor terminal to Earth ground at 500 volts. Be certain the loop is not connected to a loop detector or transient suppresser during this test. The resistance should be greater than 100 megohms. 3. Connect the sensor (probe set) being tested to a C800 series loop detector. Connect a PC to the C800 and start the C800 user interface. Using the activity screen, observe the L that the C800 measures, record it, and compare it to the expected inductance calculated using the information in Table 9-2. The measured inductance should be within ±20% of the calculated inductance (usually within ±10%). Table 9-2 Inductance Checks Inductance Checks Measuring Point Item Inductance Between Sensor Leads Model 702 Probe 50 µh to 63 µh per probe Lead-in Cable 16.5 µh per 100 feet Home-run Cable 23 µh per 100 feet 4. Using the same set-up as described in Step 3, observe the change of inductance (DL) shown on the screen when different types of vehicles pass over the sensor (probe set) being checked. The DL values measured should be similar to those listed in Table 9-3. Record typical DL values for each type of vehicle. Then compare the values measured to those shown in the table.

20 Installation 17 Table 9-3. Typical DL Values Typical L Values: Vehicles Traveling Directly Over Model 702 Probe Sets Installed at a Depth of 24 Inches Vehicle Type Single Probe Double Probe (4 spacing) Triple Probe (3 spacing) Bicycle 130 nh 130 nh 130 nh Small Motorcycle 105 nh 105 nh 105 nh Intermediate Auto 475 nh 950 nh 1400 nh Van Truck 800 nh 1600 nh 2200 nh Tractor-Trailer 955 nh 1900 nh 3700 nh 5. Using the set-up in Step 3, record the value of the Reference Frequency. Also observe the Loop Frequency. It should return to the same value as the Reference Frequency, within one Hertz, after each vehicle has passed over the Microloop. 6. Set the sensitivity for the channel to which the Model 702 Microloop probe is attached to detect 1/8 to 1/16 of the peak auto L change. A ratio of 1/8 gives the most consistent occupancy readings, while 1/16 will detect nearly all vehicles, including small motorcycles. 7. Set the Bridge Time for this channel in the C800 to cover about 16 feet of vehicle travel for a vehicle traveling at the typical speed at this location. Assuming the typical speed is 55 mph: Bridge time = 16 feet / [55 mph * feet/(sec*mph)] = second or.2 seconds A Bridge time of.2 sec. to.4 sec. will give good results in this location, e.g. 27 mph. 8. Leave the Setback Time for this channel in the C800 set to the factory default setting.

21 18 Installation 10 Troubleshooting This section provides guidance on areas to examine, if any tests during installation check-out failed. Table 10-1 shows the symptoms of Model 702 Microloop installation problems. The table also shows the possible causes of the those problems and suggests actions to correct them. Many of the actions check L, L, Loop Frequency, Reference Frequency, fault indications require use of a Canoga 800 series vehicle detector, a personal computer (PC) and 3M Canoga 800IS Interface and Data Acquisition Software. Consult 3M Canoga 800 series Installation Instructions and Canoga 800IS on-line help for directions on using these products. Table Troubleshooting Symptoms, Possible Causes, and Actions Symptom Possible Cause Solution DC resistance too high. Home-run/lead-in may be connected to a different sensor than specified. Home-run/lead-in is longer than anticipated. Home-run/lead-in wire gauge is smaller than anticipated. Probe set contains more probes than anticipated. Confirm that the detector channel is connected to the proper sensor by inserting the Canoga 800 series detector into its rack slot and monitoring the Call indicator LED for this channel. You should see a Call only when a vehicle passes over the Model 702 to which the tested channel should be connected. If the vehicles and calls don t correlate, determine which Model 702 the channel is connected to and correct the wiring. Determine actual routing of home-run/leadin cable and that routing is acceptable. Correct as required. Determine AWG of home-run/lead-in wire. It is normally OK if the size of the wire is 22 AWG or larger for lengths of less than 1000 feet. Connect a Canoga 800 series detector to the sensor being checked. First check that vehicles are being sensed (calls occur). Using the Activity screen, check the channel L. If it is one or more increments of 56 µh more than expected, it is likely that the probe set contains additional probes. Then monitor the L caused by autos and compare it to that given in Table 9-3. Each additional probe will add approximately the L of a single probe. Correct as required.

22 Installation 19 Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution DC resistance too high. (Cont.) Poor wiring connection. 1. Flex, jar or otherwise manipulate each connection point, one connection point at a time. If the resistance changes, the connection is faulty. Repair it. 2. Connect a Canoga 800 series detector to the sensor being checked. Using the Activity screen, check the channel Loop Frequency. If the Loop Frequency does not return to the Reference Frequency after each vehicle or it strays several Hertz from the Reference Frequency when no vehicles are near, there is still a possibility that there is a poor connection that is being manipulated by vehicle induced vibrations. Recheck all splices and connections. Repair if required. DC resistance too low. Home-run/lead-in may be connected to a different sensor than specified. Home-run/lead-in is shorter than anticipated. Home-run/lead-in wire gauge is larger than anticipated. Probe set contains fewer probes than anticipated or probes are connected in parallel. Confirm that the detector channel is connected to the proper sensor by inserting the Canoga 800 series detector into its rack slot and monitoring the Call indicator LED for this channel. You should see a Call only when a vehicle passes over the Model 702 to which the tested channel should be connected. If the vehicles and calls don t correlate, determine which Model 702 the channel is connected to and correct the wiring. Determine actual routing of home-run/leadin cable and that routing is acceptable. Correct as required. Determine AWG of home-run/lead-in wire. It is normally OK if the size of the wire is larger than specified. Connect a Canoga 800 series detector to the sensor being checked. Using the Activity screen, check the channel L. If it is one or more increments of 56 µh less than expected, it is likely that the probe set contains fewer probes than anticipated. Then monitor the L caused by autos and compare it to that given in Table 9-3. Each missing probe will cause a reduction in L of approximately the L of a single probe. Correct as required. If the L is about ½ of that expected and the L is about ¼ of that expected, probe sets are likely connected in parallel. Correct by splicing in series.

23 20 Installation Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution DC resistance too low. (Cont.) Megohmmeter resistance too low. Short circuit in system. One of the following: Lead-in cable insulation damaged. Home-Run cable insulation damaged. Home-Run cable water-logged. Splice poorly insulated or waterlogged. Dirty terminal\block-home-run cable connections. Vehicle detector connected to the sensor. Model 702 probe(s) failed. Connect a Canoga 800 series detector to the Model 702 probe set being checked. First check that vehicles are being sensed. If vehicles are being sensed, it is unlikely that there is a short in the wiring. Most shorts will be directly indicated by the Canoga detector fault indicators or on the Activity screen. Test to determine the causes. Readings above 10 megohm indicate operation may continue temporarily, but that failure will occur in the future. Closely examine readings under 10 megohm. 1. Ensure that a detector is not attached to the home-run cable. Retest. If the results are OK, the problem is likely that the detector was plugged in. 2. Determine whether the sensor is working properly (e.g. inductance is OK, L caused by vehicles is OK, and the oscillation frequency is stable). If all functional parameters are as expected, decide whether to fix the low resistance problem. If one or more functional parameters are unacceptable, most likely oscillator stability, the problem must be fixed. 3. Determine whether the problem is in the cabinet or external to the cabinet by detaching the lead-in wires from the terminal block. Retest the lead-in. If the results are OK, the problem is in the cabinet and vice-versa. 4. If testing indicates the problem is not in the cabinet containing the vehicle detector, go to the first splice to the Model 702 lead-in, remove the splice, and retest the Model 702 and the homerun cable. 5. Correct the problem indicated by testing by replacing the Model 702 probe set, the home-run cable, or the splice.

24 Installation 21 Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution L is too high or too low. Lead-in and/or home-run cables longer than anticipated. If the inductance and the resistance are greater than expected, the lead-in and/or home-run may be longer than anticipated. Ensure that cable routing is acceptable. Verify that desired functionality is occurring, e.g. Ls caused by vehicles are OK and that the Loop Frequency is stable and returns to the same value after each vehicle. If there is a very long cable to the Model 702, e.g feet, the oscillator may be very unstable. Lead-in and/or home-run cables shorter than anticipated. Lead-in and/or home-run cable open. Probe count different than expected. Probe failed. If the inductance and the resistance are less than expected, the lead-in and/or home-run cable is shorter than anticipated. Shorter cable runs are not a problem. Use a Canoga 800 series detector. If there is an open in the cable to the sensor, the detector will indicate an open unless the lead-in/home-run cable length is very long, e.g. >2500 feet. An ohmmeter should have found this problem. If there are fewer probes than expected, probe L will be low by 56 µh per probe and probe L readings for vehicles will be much lower than expected. The reverse is true, if there are extra probes. Check the splicing and the probe set. Defective probes can fail in two ways. If a probe is defective via one failure mode, the L will be 500 µh larger than expected. While the failed probe will not detect, if it is one probe of a multi-probe set, detection will still occur at a lower than expected L. In the other failure mode the detector should indicate an open connection. This may be confirmed by measuring a very large resistance with an ohmmeter when the detector is not attached to the sensor. The open may be somewhere in the homerun or in the probe set. To determine that the open is in the probe set requires a resistance reading taken with the probe set lead-in disconnected from the home-run cable. If a defective probe set is indicated, replace it and retest.

25 22 Installation Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution L is too high or too low. (Cont.) L is too high or too low. Probes wired in parallel rather than in series. Incorrect probe depth. Probes not vertically aligned. Probes spliced in parallel rather than in series. Incorrect probe count. If a probe is connected in parallel in a probe set, L readings for vehicles, as well as the L reading, will be much lower, one-quarter or less, than expected. Check the splicing and the probe set. L readings increase as probe depth decreases and vice versa. Review the conduit depth plot. The installation contractor can check conduit depth using his depth measuring equipment. Have the contractor correct problems as required. The L readings will be lower than expected if the probes are not vertical. Remove the landscape fabric conduit cover and cradle lock. While holding the end carrier section vertical, push the carrier sections in and out of the conduit a few times to help the system rotate to vertical. Significantly more force is required than normal if the conduit is constricted by tight radius bends (a probable cause for probes not being vertical). Retest. If L readings are acceptable, reinstall the Cradle Lock and landscape fabric conduit end cover. If sharp lateral bends are suspected, remove all Model 702 pieces from the conduit and have the contractor replot the depth and position of the conduit. Have the contractor correct problems as required. L readings may be about ½ that expected and L readings may be about ¼ of that expected. Examine the splice. Fix as required. The L readings will increase if there are more probes than expected and L readings will decrease if there are fewer probes than expected. Check the number of probes in a probe set by removing all probes and carrier sections from the conduit. Carefully record the number of carrier sections from the conduit end and each probe in each probe set. Correct any problems found.

26 Installation 23 Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution L is too high or too low. (Cont.) Loop Frequency (F) and/or Reference Frequency (Fref) is unstable, e.g. false calls or missed calls or Loop Frequency doesn t return to same value between vehicles. Probes installed near pavement reinforcement rod (or other ferromagnetic structure). Incorrect probe-to-lane location. Probe or probe set failed. The L readings may be smaller than expected, if the probe is in a very high or very low magnetic field. Measure the magnetic field directly above the probe location using a magnetometer, such as 3M Model MM-9 or Meda Model µmag. If the magnetic field strength measured is significantly above or below the vertical component of Earth magnetic field at that general location, a problem may exist. Move the measuring probe 6 inches to the left and right (across the traffic lane). If the measured field is constant over this 1-foot distance, there is probably not a problem. If it varies significantly, look for a position to the left or right of the specified probe location (in the direction of the conduit) that has a constant magnetic field. Change the specified probe to this constant field location. (Proper fields must be between 200 millioerstads or gauss and 800 millioerstads or gauss.) The L may be smaller than expected or adjacent lane calls may occur, if the probe(s) are at the wrong location. Check the lane position of all probes by removing all probes and carrier sections from the conduit. Correct any problems found. Test by replacing the Model 702 probe set. Loop cross-talk. 1. Attach the loop and the Model 702 probe set to the same Canoga 800 series detector. 2. Ensure that the frequency at which a different detector is driving the loop is separated by more than 6000 Hz from the frequency at which the detector is driving the Model 702 Probe set.

27 24 Installation Table Troubleshooting Symptoms, Possible Causes, and Actions (Cont.) Symptom Possible Cause Solution Loop Frequency (F) and/or Reference Frequency (Fref) is unstable, e.g. false calls or missed calls or Loop Frequency doesn t return to same value between vehicles. (Cont.) Line frequency magnetic interference. Poor connection to sensor. Inconsistent resistance to Earth. Sensor physical rotational movement. Incorrect sensor location. Probes spliced in parallel rather than in series. Incorrect probe count. Turn on 60 Hz or 50 Hz filtering. If the calls disappear, they were caused by line frequency magnetic interference. Turning on line filtering is a method of distinguishing crosstalk from line frequency magnetic interference. NOTE: Detection tasks that require rapid measurement response, such as speed measurement, vehicle travel direction detection and occupancy measurement of high speed vehicles, are adversely affected when line filtering is on. 1. Flex, jar or otherwise manipulate each connection point, one connection point at a time. Changing resistance will cause calls, just like inductance changes. If the resistance changes, the connection is faulty. Repair it. 2. If the Loop Frequency does not return to the same value after each vehicle, there is still a possibility that there is a poor connection that is being manipulated by vehicle induced vibrations. Recheck each connection. See Megohmmeter resistance too low on Page 20. Check conduits mounted underneath bridges or other structures for movement and stabilize as required. To help prevent calls from tall tractors or trucks to a probe set in an adjacent lane, install probe sets on East-West roads with an offset reference one (1) foot north of lane center. Correct probe position as required. Examine the splice. Fix as required. Check the number of probes in a probe set by removing all probes and carrier sections from the conduit. Carefully record the number of carrier sections from the conduit end and each probe in each probe set. Correct any problems found.

28 Important Notice to the Purchaser THE FOLLOWING IS MADE IN LIEU OF ALL WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. 3M will, at its option, repair or replace any Canoga Vehicle Detection System component or components found to be defective in materials and/or workmanship within five (5) years from date of purchase provided the component has been installed, maintained, and used as instructed. This warranty does not apply to components that have been subjected to misuse, neglect, or accident or that have been damaged by extreme atmospheric or weather-related conditions, including chemical corrosion, hail, windstorm, lightning, or flooding. In no event shall 3M be liable for any injury, loss, or damage, whether direct, indirect, incidental, special or consequential, arising out of the use or inability to use the Canoga system or any component thereof. THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE. 3M has designed, developed and tested each Canoga Vehicle Detection System component as a part of a matched component system. 3M makes no assurance or representation whatsoever concerning the reliability or safety of Canoga system components when used with non-canoga system products. 3M shall not repair, replace or otherwise be responsible for any Canoga Vehicle Detection System component that 3M determines has been damaged in whole or in part by its use with a non-canoga system product. Intelligent Transportation Systems 3M Canada 3M Safety and Security Systems Division P.O. Box M Center, Bldg N-14 London, Ontario, Canada St. Paul, Minnesota N6A 4T MHELPS Printed in U.S.A (FAX)

Successful traffic operations require precise, real-time information.

Successful traffic operations require precise, real-time information. Successful traffic operations require precise, real-time information. Every year, more and more vehicles crowd the world s roadways aggravating congestion, increasing travel times and jeopardizing safety.

More information

Work Standard CABLE PULLING OPERATIONS

Work Standard CABLE PULLING OPERATIONS Page 1 of 19 ****This document supercedes BECo WMS 2.9-1.1**** 1.0 Purpose CABLE PULLING OPERATIONS 1.1 This Work Method Standard prescribes the preferred methods of removing and installing cables between

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS

TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS CONTENTS: 1.0 General Information 2.0 Preparation and Splicing of PinPoint Wire 3.0 PinPoint Direct Bury Splice Kit Specifications

More information

OPERATION AND INSTRUCTION MANUAL Flat Roof Anchor Model: FRA250L-10X-CTS

OPERATION AND INSTRUCTION MANUAL Flat Roof Anchor Model: FRA250L-10X-CTS OPERATION AND INSTRUCTION MANUAL Flat Roof Anchor Model: FRA250L-10X-CTS (Patent Pending) WARNING: ALL PERSONS USING THIS EQUIPMENT MUST READ AND UNDERSTAND ALL INSTRUCTIONS. FAILURE TO DO SO MAY RESULT

More information

SASK-A-POLE OWNERS AND USERS MANUAL

SASK-A-POLE OWNERS AND USERS MANUAL SASK-A-POLE OWNERS AND USERS MANUAL GENERAL INFORMATION The Saskatchewan Abilities Council s Sask-a-Pole accessibility and transfer aid is designed to help provide safe and easy access to chairs, beds,

More information

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Model PSI Compressor with 3-Gallon Air Tank 12VDC Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing

More information

Ground Fault Circuit Interrupter(GFCI) Policy

Ground Fault Circuit Interrupter(GFCI) Policy NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com

More information

GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used in a

More information

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm) Pressure Sensor (Stainless Steel Diaphragm) CSM DS_E_3_1 Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications Incorporates double diaphragms consisting of SUS316L stainless

More information

INSTRUCTION MANUAL. January 23, 2003, Revision 0

INSTRUCTION MANUAL. January 23, 2003, Revision 0 INSTRUCTION MANUAL Model 810A In-Vitro Test Apparatus for 310B Muscle Lever January 23, 2003, Revision 0 Copyright 2003 Aurora Scientific Inc. Aurora Scientific Inc. 360 Industrial Parkway S., Unit 4 Aurora,

More information

CHAPTER 8 STAKING SIGNALS AND LIGHTING FIELD GUIDE. 8.1 Staking Traffic Control Signal Systems

CHAPTER 8 STAKING SIGNALS AND LIGHTING FIELD GUIDE. 8.1 Staking Traffic Control Signal Systems CHAPTER 8 STAKING STAKING Correct staking of traffic control signal or lighting systems is critical to the appropriate placement of system components. 8.1 Traffic Control Signal Systems Locating the components

More information

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information Liquid Level EK-L CSM_EK-L_DS_E 3 Liquid Level That Is Unaffected by the Color of the or Liquid Mount to bypass pipes. Fit a wide range of pipe diameters: 8 to mm or to mm Built-in Amplifiers to save space.

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit Manual No: 577013-975 Revision: B Media-Isolated Mag Plus Probe Low Pressure-ISO Kit Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but

More information

STAKING TRAFFIC CONTROL SIGNAL SYSTEMS

STAKING TRAFFIC CONTROL SIGNAL SYSTEMS Locating the components of a traffic control signal is not an exact science; many factors influence the location of the components. These factors include: lane widths, radii, pedestrian curb ramp requirements,

More information

Preferred Instruments Danbury, CT USA

Preferred Instruments Danbury, CT USA Tank Level Sensor Model TG-EL-WF-xx Installation & Operation Instructions SDI-TG-EL-WF March 6, 2006 Preferred Instruments Danbury, CT USA www.preferredinstruments.com CONTENTS Installation Pg. 2 Calibration

More information

DESIGN CRITERIA DIVISION 4900 TRAFFIC SIGNALS

DESIGN CRITERIA DIVISION 4900 TRAFFIC SIGNALS DESIGN CRITERIA DIVISION 4900 TRAFFIC SIGNALS 4901 GENERAL: These criteria shall be adhered to for the design of all publiclyfinanced or privately-financed traffic signal systems to be installed in the

More information

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG33KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG33KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES 450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES PART NO. 45053 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing

More information

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN Loadbreak Apparatus Connectors MN650056EN Effective July 2018 Supersedes May 2017 COOPER POWER SERIES 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions DISCLAIMER OF WARRANTIES

More information

210 Series Transmitter with External Electrochemical Sensor

210 Series Transmitter with External Electrochemical Sensor 210 Series Transmitter with External Electrochemical Sensor INSTRUCTIONS Installation and Operation of the AMC-210 Series Transmitter with External Electrochemical Sensor IMPORTANT: Please read these installation

More information

Norrsken Family Booklet

Norrsken Family Booklet Section 1: Introduction Low Energy Designs produce efficient and effective LED based lighting products for commercial, retail and industry purposes. Each product may contain specific details on its operation

More information

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product. Instruction Manual Hydraulic Punch Driver 902-483 LIMITED 1 YEAR WARRANTY We make every effort to assure that its products meet high quality and durability standards, and warrant to the original purchaser

More information

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

Installation Instructions Air Compressor Part # 2780, 2781

Installation Instructions Air Compressor Part # 2780, 2781 Note: It is essential that the operator of this product read and understand the contents of this manual before installing and using this product. Parts Included Qty Parts Included Qty Compressor 1 Coil

More information

USER S GUIDE & SAFETY MANUAL USER S GUIDE & SAFETY MANUAL Duct Rodder

USER S GUIDE & SAFETY MANUAL USER S GUIDE & SAFETY MANUAL Duct Rodder USER S GUIDE & SAFETY MANUAL USER S GUIDE & SAFETY MANUAL Duct Rodder Table of Contents 1. 2. 3. 4. 5. Safety Notice... 3 Operator s Instructions... 4 Duct Rod Sizes... 5 Duct Rodder Assembly... 6 Duct

More information

GG-VL2-NH3 AMMONIA VENT LINE SENSOR. Installation and Operation Manual

GG-VL2-NH3 AMMONIA VENT LINE SENSOR. Installation and Operation Manual GG-VL2-NH3 AMMONIA VENT LINE SENSOR Installation and Operation Manual 2 GG-VL2-NH3 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

DT400/436 Tee Connector Installation Instructions

DT400/436 Tee Connector Installation Instructions Connectors Lorem ipsum and dolor Splices sit Amat Effective September 2014 Supersedes IS550-30-1 March 2011 MN650001EN DT400/436 Tee Connector Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

User Instruction Manual Fixed Beam Anchor

User Instruction Manual Fixed Beam Anchor User Instruction Manual Fixed Beam Anchor This manual is intended to meet the Manufacturer s Instructions as required by ANSI Z359.1 and ANSI A10.14, and should be used as part of an employee training

More information

3 Scotch-Weld Polyurethane Reactive Adhesive Applicator Replacement Part Installation Guide

3 Scotch-Weld Polyurethane Reactive Adhesive Applicator Replacement Part Installation Guide 3 Scotch-Weld Polyurethane Reactive Adhesive Applicator Replacement Part Installation Guide Description: AIR SUPPLY LINE KIT Product ID/Stock No.: 62-9895-0005-3 For use with: 3M Scotch-Weld Polyurethane

More information

SPECIFICATIONS APCEPH1

SPECIFICATIONS APCEPH1 APCEPH1 ph CONTROLLER SPECIFICATIONS APCEPH1 Input voltage 120 Volts AC Maximum amperage 14.5 amps @ 120 VAC ph Accuracy +/- 0.2 ph ph Control range Adjustable 4.5 8.5 ph Weight < 1 lbs Dimensions 3" x

More information

Apex Evaporator Manual

Apex Evaporator Manual Apex Evaporator Manual Table of Contents I. Handling/Transportation of Apex II. Placing the evaporator III. Connecting Power to the control Panel IV. Placing the control panel and weather station V. Attaching

More information

INSTALLATION PROCEDURE 1/4 & 1/8 MILE PERMANENT TRACK

INSTALLATION PROCEDURE 1/4 & 1/8 MILE PERMANENT TRACK INSTALLATION PROCEDURE 1/4 & 1/8 MILE PERMANENT TRACK 1) Unpack all of the equipment and immediately inspect for shipping damage. Damages should be immediately reported to the carrier and noted on the

More information

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS The Akron Style 3414/3416 & 3421/3423 Apollo Monitor is designed to provide efficient trouble-free operation

More information

RAM 4021 Operation Manual

RAM 4021 Operation Manual RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For your safety...3 Description...3 Set-up mode...4 Annunciator lights/alarms...4 Operation...5 Calibration...6

More information

PERSONAL AIR BREATHING UNIT

PERSONAL AIR BREATHING UNIT PERSONAL AIR BREATHING UNIT Operation & Maintenance Manual MARTECH SERVICES C O M P A N Y 1-800-831-1525 Table of Contents INTRODUCTION: Page 2 COMPONENTS DRAWING: Page 3 START UP: Page 4 OPERATION: Page

More information

PLAQUE MFM0680 UNDERWATER LIGHT. Operating Instructions

PLAQUE MFM0680 UNDERWATER LIGHT. Operating Instructions PLAQUE MFM0680 UNDERWATER LIGHT Operating Instructions CONTENTS Preface... 3 Features... 3 Precautions... 3 Controls and Connectors... 4 Underwater Light PLAQUE MFM0680... 4 Power Supply Unit MPS021000

More information

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP LIMITED WARRANTY Getz Equipment Innovators warrants its products, and component parts of any product manufactured by

More information

For ANCHOR WINCH Model: T Big Water 45 T sw Salt Water Series Big Water 45

For ANCHOR WINCH Model: T Big Water 45 T sw Salt Water Series Big Water 45 INSTALLATION AND OPERATING INSTRUCTIONS ANCHOR WINCHES For ANCHOR WINCH Model: T10110-45 Big Water 45 T10103-45sw Salt Water Series Big Water 45 If you have any questions or difficulty installing this

More information

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES EXTREME SERIES PART NO. 45043 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS

More information

Chapter 2 Rigging. Cutting Wire Rope. Anchoring Wire Rope to Drum. Winding Wire Rope Onto Drum

Chapter 2 Rigging. Cutting Wire Rope. Anchoring Wire Rope to Drum. Winding Wire Rope Onto Drum Chapter 2 Rigging Cutting Wire Rope The wire rope must be tightly seized on both sides of the point where the wire rope will be cut, as shown in Figure 2-1. Seize the wire rope with either seizing wire

More information

User s Guide Temperature Sensor Converter TSC-599

User s Guide Temperature Sensor Converter TSC-599 User s Guide Temperature Sensor Converter TSC-599 ILX Lightwave Corporation 31950 Frontage Road Bozeman, MT, U.S.A. 59715 U.S. & Canada: 1-800-459-9459 International Inquiries: 406-556-2481 Fax 406-586-9405

More information

2000 lb manual winch

2000 lb manual winch 2000 lb manual winch Model 41694 Operation Instructions Due to continuing improvements, actual product may differ slightly from the product described herein. 3491 Mission Oaks Blvd., Camarillo, CA 93011

More information

ES18 Security Theory/Regulations Answer Schedule

ES18 Security Theory/Regulations Answer Schedule ES18 Security Theory/Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker

More information

For ELECTRIC ANCHOR WINCH Models: T Pontoon 35 T sw Salt Water Series Coastal 35

For ELECTRIC ANCHOR WINCH Models: T Pontoon 35 T sw Salt Water Series Coastal 35 INSTALLATION AND OPERATING INSTRUCTIONS ANCHOR WINCHES For ELECTRIC ANCHOR WINCH Models: T10109-35 Pontoon 35 T10102-35sw Salt Water Series Coastal 35 If you have any questions or difficulty installing

More information

Installation, Compensation and Maintenance Instructions for. RITCHIE Compasses. Made In U.S.A

Installation, Compensation and Maintenance Instructions for. RITCHIE Compasses. Made In U.S.A Installation, Compensation and Maintenance Instructions for RITCHIE Compasses Made In U.S.A All Magnetic Compasses are vulnerable to magnetic interference, which will produce errors, called deviation.

More information

WINCH USER GUIDE WARN 3700 Utility Winch Part Number: 93700

WINCH USER GUIDE WARN 3700 Utility Winch Part Number: 93700 WINCH USER GUIDE WARN 3700 Utility Winch Part Number: 93700 Your safety, and the safety of others, is very important. To help you make informed decisions about safety, we have provided installation and

More information

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN Deadbreak Apparatus Connectors MN650043EN Effective February 2017 Supersedes October 2004 (S550-12-1) 200 A 15/25 kv class deadbreak straight connector installation instructions COOPER POWER SERIES DISCLAIMER

More information

Model SM/PL Series. Calibration Guide. Precision Loads. Anritsu Company 490 Jarvis Drive Morgan Hill, CA USA

Model SM/PL Series. Calibration Guide. Precision Loads. Anritsu Company 490 Jarvis Drive Morgan Hill, CA USA Calibration Guide Model SM/PL Series Precision Loads Anritsu Company 490 Jarvis Drive Morgan Hill, CA 95037-2809 USA Part Number: 10100-00056 Revision: B Published: January 2010 Copyright 2009-2010 Anritsu

More information

Check with local zoning official for property line distance requirements.

Check with local zoning official for property line distance requirements. RESIDENTIAL POOL PLAN SUBMITTAL GUIDELINES The following guidelines are intended to assist municipal residents with the permit acquisition process with regard to pools, spas and hot tubs for single family

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Table of Contents

More information

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips (GP110/GP00AA/GP101A /GP102B/GP103C/GP104D) 04/17 GP110/GP00AA/GP101A/GP102B/GP103C/GP104D Manual READ AND UNDERSTAND ALL OF THE INSTRUCTIONS AND SAFETY

More information

TWO KAYAK VERTICAL FOLD-DOWN CARRIER

TWO KAYAK VERTICAL FOLD-DOWN CARRIER S P X O TWO KAYAK VERTICAL FOLD-DOWN CARRIER TA R 2 50mm 40mm Stax Pro2 Kayak Carrier Red Load Straps Jawz Adapters Mounting Bolts Foam Blocks 9 Safety Strap 12 Tie-Downs Installation & Loading Instructions

More information

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr A DIVISION OF THE FREDERICKS COMPANY 2400 PHILMONT AVE. HUNTINGDONVALLEY, PA 19006 PARTS LIST 1 3 4 2 # QTY ITEM DESCRIPTION

More information

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING Please Note: Ranges above 500mbar are designed and manufactured in accordance with sound engineering

More information

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS 3K Puller (M3K-M)

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS 3K Puller (M3K-M) OPERATING and MAINTENANCE INSTRUCTIONS MAXIS 3K Puller (M3K-M) 04/17 (M3K-M) READ AND UNDERSTAND ALL OF THE INSTRUCTIONS AND SAFETY INFORMATION IN THIS MANUAL BEFORE OPERATING OR SERVICING THIS TOOL TABLE

More information

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions Compact Triple Cabinet Outlet Station Model 6258-1 Installation and Operating Instructions The Porter Compact Triple Outlet Station (6258-1) provides a quick, safe, and reliable method of connection to

More information

! Warning, refer to accompanying documents.

! Warning, refer to accompanying documents. About this Manual To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures accurate and adequate to operate this instrument

More information

HYDRAULIC WINCH FOR AUGERS UP TO WR10 X 71 / W130 X 41 ASSEMBLY & OPERATION MANUAL

HYDRAULIC WINCH FOR AUGERS UP TO WR10 X 71 / W130 X 41 ASSEMBLY & OPERATION MANUAL HYDRAULIC WINCH ASSEMBLY & OPERATION MANUAL Read this manual before using product. Failure to follow instructions and safety precautions can result in serious injury, death, or property damage. Keep manual

More information

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please

More information

RAM 4021-DPX Operation Manual

RAM 4021-DPX Operation Manual RAM 4021-DPX Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS ABL 4021-DPX / RAM 4021-DPX For Your Safety... 3 Description... 3 Setup Mode... 4 Lights/Alarms... 4 Operation...

More information

Instruction Manual. Model TC1-S TopSide Clamp. top side clamp. For your personal safety READ and UNDERSTAND instructions before using tools.

Instruction Manual. Model TC1-S TopSide Clamp. top side clamp. For your personal safety READ and UNDERSTAND instructions before using tools. Instruction Manual Model TC1-S TopSide Clamp top side clamp (406)755-4258 (406)257-2711 www.timberlinetool.com 90 Conestoga Ct. Kalispell, MT 59901 USA For your personal safety READ and UNDERSTAND instructions

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

CSA Sample Draw Aspirator Adapter Operator s Manual

CSA Sample Draw Aspirator Adapter Operator s Manual 30-0951-CSA Sample Draw Aspirator Adapter Operator s Manual Part Number: 71-0367 Revision: 0 Released: 4/30/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

MODEL NUMBER: P PORTABLE COMPRESSOR

MODEL NUMBER: P PORTABLE COMPRESSOR MODEL NUMBER: 44043-440P PORTABLE COMPRESSOR IMPORTANT: It is essential that you and any other operator of the product read and understand the contents of this manual before installing and using this product.

More information

MALONER. Installation & Loading Instructions - Please Read Before Beginning. Step 1: Installing Carriers to Cross Bars

MALONER. Installation & Loading Instructions - Please Read Before Beginning. Step 1: Installing Carriers to Cross Bars SeaWing V-STYLE KAYAK CARRIER 60mm 50mm Rubber Plugs SeaWing Kayak Carriers 12 Load Straps Jawz Universal Adapters Mounting Bolts T-Knobs 12 Safety Lines MD Series Only Installation & Loading Instructions

More information

Recommendations for Marking Power Facilities

Recommendations for Marking Power Facilities Recommendations for Marking Power Facilities with the Use of 3M EMS Electronic Markers 1.0 Overview Revised June 21, 2005 Page 1of 12 The 3М TM electronic marker system is intended to make the job of precisely

More information

FTS SUBMERSIBLE PRESSURE TRANSMITTER USER S MANUAL

FTS SUBMERSIBLE PRESSURE TRANSMITTER USER S MANUAL FTS SUBMERSIBLE PRESSURE TRANSMITTER USER S MANUAL TABLE OF CONTENTS PRODUCT OVERVIEW 2 I - USE AND CARE: 3 II - INSTALLATION: 5 III - GENERAL MAINTENANCE TIPS: 5 IV - APPENDIX: A-1 2-WIRE CURRENT LOOP

More information

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS 6K Puller (M6K-M)

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS 6K Puller (M6K-M) OPERATING and MAINTENANCE INSTRUCTIONS MAXIS 6K Puller (M6K-M) READ AND UNDERSTAND ALL OF THE INSTRUCTIONS AND SAFETY INFORMATION IN THIS MANUAL BEFORE OPERATING OR 04/17 (M6K-M) SERVICING THIS TOOL TABLE

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION

More information

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013 Switches MN008005EN Effective April 2016 Supersedes S328-120-1 June 2013 D-73P3 bypass switches installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Vessel Installation and Operating Manual

Vessel Installation and Operating Manual For In-ground and Aboveground Pools Vessel Installation and Operating Manual Important Safety Information Please read this manual prior to installation. Nature 2 Express is designed to sanitize in-ground

More information

WARNING! DO NOT THROW AWAY THESE INSTRUCTIONS! READ AND UNDERSTAND BEFORE USING EQUIPMENT!

WARNING! DO NOT THROW AWAY THESE INSTRUCTIONS! READ AND UNDERSTAND BEFORE USING EQUIPMENT! Guardian Fall Protection Kent, WA 800-466-6385 www.guardianfall.com GENERAL SYSTEM SELECTION CRITERIA: Selection of fall protection shall be made by a Competent Person. All fall protection equipment shall

More information

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions PORTER Parker Hannifin Corporation Porter Instrument Division 245 Township Line Rd. P.O. Box 907 Hatfield, PA 19440-0907 USA (215) 723-4000 / fax (215) 723-5106 Compact Triple Cabinet Outlet Station Model

More information

Installation and Operating Manual

Installation and Operating Manual Safety Instructions Important Information Please read prior to installation ATTENTION! ELECTRICAL HAZARD FOR INGROUND POOLS AND ABOVEGROUND POOLS Installation and Operating Manual IMPORTANT Pool Owner,

More information

Henry Pratt Diviner Position Indicator. Operation and Maintenance Manual. Job Name: Contractor: Date: Document #:DIVPOSNOM Revision Date: 2/9/11

Henry Pratt Diviner Position Indicator. Operation and Maintenance Manual. Job Name: Contractor: Date: Document #:DIVPOSNOM Revision Date: 2/9/11 Henry Pratt Diviner Position Indicator Operation and Maintenance Manual Job Name: Contractor: Date: Document #:DIVPOSNOM Revision Date: 2/9/11 SAFETY MESSAGES All safety messages in the instructions are

More information

HLM-2000-TX Gas Transmitter User Manual

HLM-2000-TX Gas Transmitter User Manual HLM-2000-TX Gas Transmitter User Manual Technical Support Continental North America Toll Free 1-(800) 387-9487 Ph: +1 (905) 829-2418 Fx: +1 (905) 829-4701 A Product of Arjay Engineering Ltd. Oakville,

More information

American Flagpole & Flag Co. 1(800)

American Flagpole & Flag Co.   1(800) SENTRY CONCEALED HALYARD-REVOLVING TRUCK GROUND SET INSTALLATIONS INSTRUCTIONS 1. Dig foundation as detailed in SECTION A FOUNDATION SPECIFICATIONS, set sleeve in enter of hole with top 2 above grade.

More information

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions Loadbreak Apparatus Connectors Effective October 2013 Supersedes March 2011 200 A, 15 and 25 kv class loadbreak bushing insert installation instructions S500-12-1 DISCLAIMER OF WARRANTIES AND LIMITATION

More information

Tire Inflation Cage Kit For servicing only single piece automotive, and most light truck tire/wheel assemblies

Tire Inflation Cage Kit For servicing only single piece automotive, and most light truck tire/wheel assemblies Tire Inflation Cage Kit 85608214 For servicing only single piece automotive, and most light truck tire/wheel assemblies This is a supplement to your operating manual and covers the setup and use of the

More information

PR4 Installation, Operation & Maintenance Instructions (DOT Certification Included)

PR4 Installation, Operation & Maintenance Instructions (DOT Certification Included) PR4 Installation, Operation & Maintenance Instructions (DOT Certification Included) March 2006 Form FVC 054 Rev. 6 KEEP THIS DOCUMENT WITH THE PRODUCT UNTIL IT REACHES THE END USER. The Passive - R4 device

More information

Proper Operation of Heath Consultants Incorporated Plunger Bar

Proper Operation of Heath Consultants Incorporated Plunger Bar Proper Operation of Heath Consultants Incorporated Plunger Bar Heath Consultants Incorporated 9030 Monroe Road Houston, TX 77061 (800) HEATH-US www.heathus.com Notice The contents of this manual are proprietary

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual WIKA FLR-SBDF / BLR-SBDF Magnetic Level Transmitter (Please retain for future usage) Contact: Gayesco-WIKA USA, L.P. 229 Beltway Green Boulevard Pasadena, TX 77503 www.wika.com

More information

Instruction Sheet. CP2000: 2000 lb Cable Puller IMPORTANT RECEIVING INSTRUCTIONS SAFETY ISSUES

Instruction Sheet. CP2000: 2000 lb Cable Puller IMPORTANT RECEIVING INSTRUCTIONS SAFETY ISSUES Instruction Sheet CP2000: 2000 lb Cable Puller RPS-0148 07/02 IMPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. If shipping damage is found, notify carrier at once.

More information

RC 195 Receiver-Controller

RC 195 Receiver-Controller Document No. 129-082 RC 195 Receiver-Controller Product Description The POWERS RC 195 Receiver-Controller is a pneumatic instrument that receives one, two or three pneumatic inputs. It produces a pneumatic

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel:

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel: PERMA PURE INSTRUCTION MANUAL FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model 3300 Version 4.06 Perma Pure LLC Tel: 732-244-0010 P.O. Box 2105, 8 Executive Drive Tel: 800-337-3762 (toll free US)

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO 420C AIR COMPRESSOR KIT PART NO. 42042 460C AIR COMPRESSOR KIT PART NO. 46043 420C 460C IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

Manual. FRESH AERO OneOP Model PC (Portable Compressors) Tire Inflator. Where Imagination Meets Innovation

Manual. FRESH AERO OneOP Model PC (Portable Compressors) Tire Inflator. Where Imagination Meets Innovation FRESH AERO OneOP Model PC (Portable Compressors) Tire Inflator For inflating aircraft tires and all types of other vehicle tires and air operated devices Manual The Fresh Aero Group Where Imagination Meets

More information

Fiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual

Fiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual Fiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual 27.75 23.75 25.50 20.75 Specifications: 8-13 GPM 100 strand fiber - Bubbler 75 strand fiber - Spillway Light Bar 45 ft. fiber tail

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

COMPACT METAL bender 99826

COMPACT METAL bender 99826 COMPACT METAL bender 99826 Set up And Operating Instructions Distributed exclusively by Harbor Freight Tools. 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our website at: http://www.harborfreight.com

More information

Operator s Manual 701 Test Kit for Static Control Surfaces (Megohmmeter)

Operator s Manual 701 Test Kit for Static Control Surfaces (Megohmmeter) Operator s Manual 71 Test Kit for Static Control Surfaces (Megohmmeter) INTENDED USE The 3M Model 71 Megohmmeter is designed to measure the resistance of static control work surfaces and flooring. This

More information

Procedure Troubleshooting the Interconnect Cables

Procedure Troubleshooting the Interconnect Cables Procedure 6.1 - Troubleshooting the Interconnect Cables Troubleshooting the upper interconnect cable 1. Remove the display housing per Procedure 7.13. Disconnect the upper interconnect cable from the upper

More information

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please

More information

Installation Instructions

Installation Instructions 48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical

More information