HVAC Concept Design for Small Surface Combatant
|
|
- Preston Cameron
- 5 years ago
- Views:
Transcription
1 HVAC Concept Design for Small Surface Combatant Clint Domine Directorate Navy Platform Systems 1.0 OVERVIEW The objective of the concept study is to estimate the Heating, Ventilation and Air Conditioning (HVAC) cooling load for a Small Surface Combatant. The small surface combatant used for this study was a concept approximately 80 metres in length and could accommodate a crew of 45. The parameters were chosen to reflect a realistic situation of operating in the tropics. Also the ramifications of integrating a Chemical, Biological, Radiological and Nuclear (CBRN) Citadel system were considered. 2.0 SCOPE The scope of the study encompasses estimation of the total cooling load and required chiller water plant cooling capacity. To aid with the study, the following items were calculated using relevant heat transfer equations and HVAC design theory: Compartment heat gain and losses Total connected cooling load System air flow In addition, the study will address the general requirements for implementing a CBRN citadel to provide protection from CBRN threat. The following topics will also be discussed briefly in the report: Citadel system design requirements CBRN filters and airlocks Cleansing station arrangements The concept study aims to provide estimates of the Small Surface Combatant HVAC system and CBRN Citadel requirements to stimulate further discussion and research. It is not in the scope of this report to determine the specifications of individual compartment chillers, sizing of condensers, Air Filtration Units (AFU), HVAC ducting, citadel wash down facilities and total weight of the HVAC system. This report also does not discuss specific CBRN Defence arrangements and ventilation requirements for machinery spaces. 3.0 DESIGN ASSUMPTIONS 3.1 General The total cooling load is based on the total ship peak cooling. The chilled water plant (CWP) may not be required to produce the peak cooling capacity at all times but it must be able to 1
2 cope with extreme tropical environments where there is a possibility the ambient temperature will reach 40 degrees Celsius. 3.2 Design External Ambient Temperature The external ambient temperature was selected to be representative of the operational environment of the Small Surface Combatant. It is assumed that the Small Surface Combatant will operate in littoral waters close to the equator where the climate is extreme tropical. The extreme tropical regions such as the Persian Gulf and north Australia are examples of where the Small Surface Combatant may be operating and where ambient temperatures of 40+ degrees C dry bulb can occur. 3.3 Seawater Temperatures The seawater temperature does not affect the cooling load calculations; it does however have a profound effect on the performance of the CWP. Seawater is used as the cooling medium in the heat exchangers of the refrigerant circuit. Near surface seawater temperatures can reach as high as 35 degrees C in tropical waters. A high sea water temperature will decrease the heat transfer between the refrigerant and the seawater thus reducing refrigerant cooling capacity. This will have an adverse effect on the chiller which produces the chilled water. 3.4 Internal Design Temperature The internal design air temperature was chosen to be +27 deg C 50% relative humidity. 3.5 Boundary Heat Load Temperature differences between adjoining internal spaces The boundary heat load is the heat that is transferred through the bulkheads, deck and deckhead. The boundaries between adjacent compartments and external boundaries that would be susceptible to solar heat gain were established. The temperature differences between adjoining internal spaces such as a bulkhead, deckhead, or deck separating an air conditioned and non air-conditioned internal space was obtained from Table 1 of ISO-7547:2002(E). The heat transfer coefficient, U for each bulkhead, deck and deckhead was obtained using guidance values on commonly used materials as specified in ISO-7547:2002(E). It is also assumed that the temperature difference between adjacent air conditioned compartments is zero. 3.6 Equipment Heat load The lighting heat load is due to the heat produced from the lighting in a compartment. The occupancy heat load is the heat gain due to personnel in the compartment space. The equipment heat load is the heat gain from equipment within the space such as boilers, pipes etc. The lighting heat load is generally accepted as 16 watts/square metre of deck area. 3.7 Human heat load The human heat load due to perspiration is the following: * Sensible = 60 watts/person * Latent = 90 watts/person 2
3 3.8 Fresh air required per man The overall fresh air per person required is kg/sec ( m 3 /second). The minimum fresh air per person requirement is kg/sec. 3.9 Fan heat load The fan used for distribution of the air also produces sensible heat and will vary depending on ducting arrangements and filtration back pressures. For the purpose of this design study it is assumed to be 14% Outdoor air load (fresh air) The supply air entering the cooling apparatus is a mixture of fresh air and recirculated air from the compartment. The fresh air or outdoor air load is the sensible and latent heat that is contained in the fresh air supplied to the cooling apparatus of the air handling unit. It is an additional heat load that must be taken into account along with the compartment heat load. It is not in the scope of this study to calculate the bypass factors and mixture ratios which govern the amount of recirculated and fresh air entering the system. For the purpose of this design study, the fresh air percentages ranging from 50% to 100% will be assessed to provide a range of cooling loads. Outside air load (OATH) =.19 ( Fresh air percentage) Q ( h h ) Where, 1 c outside design Fresh air percentage = fresh air proportion of the airflow entering cooling apparatus Q c = the compartment airflow (kg/second) h outside = The enthalpy of the outside air (kj/kg) h = The enthalpy of the design air condition (kj/kg) design Using a psychrometric chart, the enthalpy difference for an internal ambient design temperature of 27 deg C 50% relative humidity and an ambient outdoor air temperature of 40 deg C 70% relative humidity is 69 kj/kg Electronic Equipment Heat Load In determining the cooling load, the heat gain from electronic equipment such as communications, navigation, radar, and electronic cabinets must be accounted for. It is not in the scope of this study to accurately calculate the electronic equipment heat load. Typically, the electronic equipment will have a dedicated fan coil unit and heat exchanger attached through which a refrigerant or chilled water line would pass through. For a vessel of 80 metres in length and combining the capabilities of a Hydrographic, mine hunter, and patrol boat the electronic equipment cooling load was estimated to be 58 kw. It was also assumed that the electronic equipment cooling load was constant regardless of the air 3
4 distribution arrangements. For the breakdown of the electronic cooling loads refer to Table 1 below. Electronic Component Estimated load Hydrographic survey 9 system Radar 17.5 Communication 31.6 Equipment Estimated Total 58.1 Table 1: Electronic cooling load breakdown 4.0 HVAC COOLING LOAD CALCULATIONS 4.1 General To determine the cooling capacity of the CWP to supplying the required cooling to achieve the design ambient air temperature, the total cooling load of the ship is to be calculated. The total compartment cooling load is the work that the CWP must produce to maintain the desired air temperature for all air conditioned compartments. Heat transfer equations were used to determine the total compartment heat gain. 4.2 Compartment Volumes The volume for each compartment on the ship was calculated. Annex A contains the volumes for all compartments including air conditioned spaces, citadel compartments, and non air conditioned space such as machinery spaces. 4.3 Compartment Heat gain calculation For each air conditioned compartment, the following sensible and latent heat loads were calculated and added to produce the compartment total heat load, Qt: Boundary heat load Lighting heat load Occupancy heat load Equipment heat load Fan allowance For breakdown of compartment total heat loads please refer to Annex B. 4.4 Compartment Supply air quantities Once the compartment heat load data was collated for all air-conditioned compartments, the individual heat loads was summed to produce the total compartment heat load. The total air quantity is the total compartment heat load divided by the enthalpy difference. TAQ = Total Heat Gain/Enthalpy Difference 4
5 The enthalpy difference is the difference in enthalpies of the air entering and leaving the cooling apparatus. For this study the air entering the apparatus was assumed to be 29 degrees (50% Relative humidity) or a few degrees higher than the design ambient of 27 degrees. The air leaving the cooling apparatus is assumed to be the accepted value of 13 degrees C (dry bulb) 12 degrees (wet bulb). Using a psychrometric chart, the enthalpy difference between the two values is calculated as 23.5 kj/kg. This value however will change; however, as air entering the cooling apparatus is influenced by the proportion of fresh air and the number of air changes required. Once the total air quantity (TAQ) is calculated the apportioning of air to each air-conditioned compartment is based on the following relationship: H SR Compartment Air Quantity = TAQ H SRT Where; TAQ = Total Air Quantity H = Compartment Sensible load SR H SRT = Sum of Compartment Sensible Loads 4.5 Application of six minimum air changes per hour per compartment Once the air quantity for each compartment is calculated it had to be checked against the minimum requirement of six air changes per hour. All air conditioned spaces which had air quantities less than six air changes per hour were increased to the minimum of six air changes per hour. This effectively increased the total air quantity and subsequently produced a revised total air quantity. 4.6 Total Cooling Load The total cooling load is the sum of the compartment heat gain, outside air loads (OATH) and additional loads from electronic equipment. Total Cooling load = Grand total heat + Electronic Equipment Cooling loads Where; Grand total heat (GTH) = Qt + OATH Qt = Sum of compartments heat gain (sensible and latent loads) OATH = Outside air total heat 5.0 RESULTS - HVAC SYSTEM 5.1 General This section outlines the estimates of total compartment heat gain, supply air requirements and total cooling load capacity for the HVAC system without a citadel. The internal ambient and external temperatures from Section 3 of this document were used as the design temperatures. The calculation process described in Section 5 was used to calculate the total cooling load capacity. 5
6 5.2 Total Compartment heat gain The total compartment heat gain was calculated to be 94.1 kw. The sensible heat and latent heat components were 72.3 and 21.8 kw respectively. 5.3 Supply Air Requirements The total air quantity for the HVAC system alone was initially calculated to be 4 kg/second (12015 m 3 /hr) but after applying a minimum six air changes per hour per compartment it was recalculated to be 5.3 kg/second (15789 m 3 /hr). 5.4 Total Cooling Load Capacity The total cooling load capacities for fresh air proportions ranging from 50% to 100% were graphed in figure 1 below. It can be observed that with increasing fresh air proportion, the cooling load increases. This is due to the fact that with a higher fresh air percentage, a greater quantity of fresh air at a higher temperature and humidity is brought into the system which must be conditioned. Ideally, a balanced proportion of fresh and recirculated air will be chosen based on air change, fresh air per man, and power consumption requirements. If cost was not a factor, a 100% fresh air system will be desirable as air will not be recirculated reducing the amount of stale air or impurities being recirculated. A higher fresh air quantity, however, will mean the cooling coils will have to remove a greater quantity of heat and therefore power consumption will increase. Please refer to Annex C for breakdown of compartment outside air heat and grand total heat loads. Total cooling load vs fresh air percentage Grand total cooling load Fresh air percentage (%) Figure 1: Total Cooling load vs. fresh air percentage 6
7 6.0 CITADEL SYSTEM DESIGN & REQUIREMENTS 6.1 General A citadel is defined as the compartments within a vessel which form a group of interconnecting compartments enclosed by a vapour-tight boundary, within which filtered air can be circulated at a positive pressure to provide collective nuclear, biological and chemical protection. In the context of the small surface combatant the chosen citadel is a hardened COLPRO system because it provides the highest level of protection to the crew from a CBRN threat. The hardened COLPRO system is effectively a citadel that is integrated into the ship structure as opposed to an unhardened COLPRO system where by a toxic free area is achieved through the application of an inflatable CBRN liner. The primary role of the citadel is to prevent the ingress of CRBN agents into compartments by providing an overpressure, gas tight boundary, and CBRN filters. To prevent CBRN agents from entering citadel during personnel entry and exit, cleansing stations and air locks are used for decontamination. Cleansing stations, air locks, and CBRN filters impose an additional air requirement on the vessel s HVAC system. Also to maintain the overpressure air losses due to uncontrolled leakages and breathing air replacement requires additional airflow. This section provides an overview of the process in calculating the additional airflow required to maintain the CBRN citadel system. The following additional air flow requirement was calculated and added to the total air quantity calculated in Section 6: Losses due to uncontrolled leakages; and Breathing air replacement (Control of CO 2 ). In this section the following areas are also addressed: Cleansing station and airlock purging; Cleansing station arrangements; and; Citadel Subdivisions; and CBRN Filter requirements. 6.2 Citadel Compartments Areas generally considered part of the citadel are spaces vital to ship operations such as the bridge, communications, and crew living quarters. The number and type of citadel compartments will vary with each vessel and is constrained by factors such as compartment arrangement, available space, and budget. The table in Annex D is a list of compartments that form the Small surface combatant CBRN citadel. 6.2 Air supply/intake Requirements For a citadel equipped ship in normal open state, the supply air is sufficient to provide the required compartment air changes and fresh air flow requirements. In a closed down state such as during wartime, supply air is diverted via dampers through pre-particulate, particulate, and vapour filters before entering the air treatment/handling units. For efficient removal of CBRN agents, each filter is normally loaded with airflow ranging between 270m 3 /hr to 340 7
8 m 3 /hr. Therefore the total supply air flow entering the citadel dictates the number of CBRN filters required to filter the air. The citadel air flow is usually air conditioned in a citadel system is the sum of the air flow required for the HVAC system including air changes, uncontrolled losses, and breathing air volume requirements. This leads to a total air quantity of m 3 per hour (5.9 kg/second). 6.3 Cleansing station and airlock purging requirements: General The purging air flow in the airlock shall be sufficient to provide at least five air changes per minute for removal of all contamination. This is equivalent to 300 air changes per hour (5 air changes/min x 60 mins/hr = 300 air changes/hr). The purging air flow for the airlocks and cleansing stations are only filtered air so it does not need to be added to the air-conditioned supply. The purging air requirements will only have an impact on the number of fans and filtration units required Airlock purging calculation To maintain a citadel system the Small Surface Combatant requires airlocks in the following locations: 1. 4 airlocks with 2 each in the fwd and aft cleansing stations; 2. 4 airlocks for the four machinery spaces (assuming that each machinery space is independent); 3. 2 airlocks for the contaminable spaces (hangar and paint storeroom); and 4. 1 airlock for access between the fwd and aft sub-citadels. This leads to a total of 11 airlocks for the Small Surface Combatant citadel. Each airlock occupies a volume of approximately 1 m 3. The total swept air lock volume will be 11 x 1 m 3 = 11 m 3. The required airlock purging airflow is 11 m 3 /air change x 300 air changes/hr = 3300 m 3 /hr Cleansing station air change calculation The largest volume compartment in the cleansing station generally receives a minimum of five air changes in the processing interval between men. The processing interval between personnel entering the cleansing station is specified to be no more than five minutes. The cleansing station air change requirement is five air changes per five minutes or 60 air changes per hour. The volume of a typical cleansing station with stretcher capabilities is 39 m 3. The largest compartment in the cleansing station is typically the first stage compartment at 24 m 3. Because there are two cleansing stations on the Small Surface Combatant (Aft and Fwd cleansing stations) the total volume is 2 x 24 m 3 = 48 m 3. For 60 air changes per hour the cleansing station air change equates to 48 m 3 /air change x 60 air changes/hr = 2880 m 3 /hr. 8
9 6.3.4 Total purging airflow requirement The total purging airflow requirement for cleansing station and airlocks is = 6180 m 3 /hr 6.4 Breathing Air Volume Requirements: Breathing Air Volume Formula The breathing air volume equation determines the quantity of filtered air that is required to offset the CO 2 generated from personnel breathing within a compartment. The breathing air volume varies depending on whether the person is resting, performing light work, or performing normal work. For this design exercise, the breathing air volume was assumed for personnel performing normal work loads at 1.25 m 3 /hr/person. Filtered air = Where: A BAV N B 2 B 1 BAV = breathing air volume; BAV resting = 0.5 m 3 /hr/person; BAV light work = 0.75 m 3 /hr/person; BAV Working = 1.25 m 3 /hr/person; N = number of persons A = CO 2 generated during breathing (4%) B 2 = Permitted CO 2 concentration in fully manned compartment; B 1 = CO 2 content in fresh air (0.03%) CO 2 permitted concentration in various types of compartments: Operational spaces 0.15% Berthing, resting spaces 0.25% Dining, lounge spaces 0.25% Workshops, offices, stores 0.45% Citadel Breathing Air volume calculation Breathing air volume was assumed worst case scenario so BAV working of 1.25 m 3 /hour/person was selected. The number of persons was taken as the total complement of the platform which was 45. An average figure of 0.25% was selected for the permitted CO 2 concentration in fully manned compartment. Given these parameters the filtered air required was calculated to be: = m 3 /hr
10 6.5 Uncontrolled Leakage Distribution: The uncontrolled leakages are based on a requirement of 900 m 3 /hr of filtered fresh air for every 3400 m 3 of citadel volume that is above the deep water line. It is assumed that the uncontrolled leakages were distributed evenly across the citadel areas of the ship. The breakdown of the citadel volume calculation is described in Annex D. The citadel volume, including 300 m 3 allowance for passageways, was calculated to be 3342 m = 884 m 3 /hr 3400 Therefore the air flow requirement due to uncontrolled leakages is calculated to be 884 m 3 /hr. 6.6 Citadel Sub-division Overpressure According to the overpressure requirements of Det Noske Veritas Part 6 Chapter 10 Nuclear, biological and chemical protection there shall be a positive overpressure of at least 500 Pa between the citadel and the external environment. 7.0 DISCUSSION From this HVAC design study, it can be observed that a chilled water plant with a cooling capacity of at least 300 kw is required to provide a design temperature of 27 degrees Celsius with 50% relative humidity. Increasing the amount of fresh air supplied to the HVAC system will increase the cooling load. At 100% fresh air system will require a cooling capacity of 454 kw. Another critical factor that determines the cooling capacity of the chilled water plants is the temperature of the seawater and the performance of the seawater condensers. It is vital that an appropriate condenser is chosen for the chilled water plant. An undersized or inefficient condenser will result in the refrigerant not being cooled sufficiently and consequently the cooling capacity of the plant will be reduced. High temperature seawater passing through the condensers will also reduce its heat transfer potential. 8.0 REFERENCES 1. International Standards Organisation 7547:2002(E) 2. DA9 Air conditioning load estimation, The Australian institute of Refrigeration heating and air-conditioning and heating (Inc.), Det Noske Veritas Part 6 Chapter 10 Nuclear, biological and chemical protection, Rules for high speed, light craft and Naval surface craft,
11 Annex A: Compartment Volumes Name Floor Area (m2) Height Width Length Fwd Bulk width Aft Bulk width Port Stbd Fwd Bulk (m2) Aft Bulk (m2) Port (m2) Stbd Head (m2) Com plim ent Volume (m^3) 03 Deck Bridge HVAC and Systems Public Head Deck HVAC and Systems Ships Op Office CO's Day Cabin Pantry CO's Sleeping Cabin Comcen Single Berth Officer HVAC and Systems Single Berth Officer Repair Base Deck Ships Magazine Public Head Battery Comp Electrical Equipment Compartment Unassigned Engineering
12 Admin Electronics Workshop Sickbay Public Head Hangar Small Arms Stowage Unassigned Paint Store Ships Office/ Pay Office Aviation Admin Office Avionics and Helo Workshop Emergency Generator Deck Naval Stores Naval Stores Berth (2) Berth (2) Berth PO Berth CPO Pantry Wardroom Public Head UUV Support and Battery Charging Demolition Magazine Boat Gear Store Diving Gear Store Repair Base
13 Damage Control Store Berth (2) Berth PO Berth PO Berth CPO Berth Officer Berth (2) Garbage Compactor/Store Dry Garbage Deck General Store Accommodation Store Laundry SS Mess SS Pantry and JS Servery Galley Stores Cool Cold and Dry Engineering Store Eng Workshop JS (2) JS (4) JS (4) JS (8) Unassigned Steering Gear General Store Canteen and Canteen Store JS Dining Scullery
14 JS Rec Area Dry Store MCR and DCC Central JS (2) JS (4) JS (2) Baggage Store JS (6) Gym Steering Gear Echo Sounder/ Equipment Room FWD Auxiliary Machinery Generator Room Engine Room AFT Auxiliary Machinery Room
15 Annex B: Compartment Heat loads Index Compartment Comp. Sensible Heat Gain Qs Comp.Total Heat Gain Qt Comp. Sensible Heat Ratio #Men Revised Comp air quantity Comp. Air Quantity Mc Compt. volume 6 Air changes per hour (minimum) Units kw kw SHRc N m^3/s m^3/s m^3 m^3/s 1 Bridge Ships Operation Office CO's Day Cabin CO's Sleeping Cabin Comcen Single Berth Officer Single Berth Officer Unassigned 01 Deck Fwd Port Engineering Admin Electronics Workshop Sickbay Unassigned 01 Deck Fwd Stbd Ships Office Aviation Admin Office Avionics and Helo Workshop Berth (2) 1 Port Berth (2) 2 Port Berth PO 1 Port Berth CPO Port Wardroom Berth (2) Stbd Berth PO 1 Stbd Berth PO 2 Stbd Berth CPO Stbd Berth Officer
16 26 Berth (2) Stbd SS Mess Eng Workshop JS (2) Aft Port JS (4) Aft Port JS (4) Aft Port JS (8) Unassigned 2 Deck Aft Port Canteen and Canteen Store JS Dining JS Rec Area MCR and DCC Central JS (2) Aft Stbd JS (4) Aft Stbd JS (2) Aft Stbd JS (6) Gym TOTAL
17 Annex C: Outside air total heat and Grand total heat with varying fresh air proportions 50% Fresh Air 60% Fresh Air 70% Fresh Air 80% Fresh Air 90% Fresh Air 100% Fresh Air Compartment OATH GTH OATH GTH OATH GTH OATH GTH OATH GTH OATH Bridge Ships Operation Office CO's Day Cabin CO's Sleeping Cabin Comcen Single Berth Officer Single Berth Officer Unassigned 01 Deck Fwd Port Engineering Admin Electronics Workshop Sickbay Unassigned 01 Deck Fwd Stbd Ships Office Aviation Admin Office Avionics and Helo Workshop Berth (2) 1 Port Berth (2) 2 Port Berth PO 1 Port Berth CPO Port Wardroom GTH 17
18 Berth (2) Stbd Berth PO 1 Stbd Berth PO 2 Stbd Berth CPO Stbd Berth Officer Berth (2) Stbd SS Mess Eng Workshop JS (2) Aft Port JS (4) Aft Port JS (4) Aft Port JS (8) Unassigned 2 Deck Aft Port Canteen and Canteen Store JS Dining JS Rec Area MCR and DCC Central JS (2) Aft Stbd JS (4) Aft Stbd JS (2) Aft Stbd JS (6) Gym TOTAL
19 Annex D CBRN Citadel Compartments Item Compartment Volume Item Compartment Volume m 3 m 3 03 Deck 1 Deck (cont.) 1 Bridge Damage Control Store HVAC and systems Berth (2) Public head Berth PO Deck 36 2 Berth PO Ships operation office Berth CPO CO s day cabin Berth Officer Pantry Berth (2) CO s Sleeping Cabin Deck 8 Comcen Accommodation Store Single Berth officer Laundry Repair Base SS Mess Deck 43 SS Pantry and JS Servery Ship s magazine Galley Public head Stores Cool Cold and Dry Battery compartment Engineering Store Electrical equipment 47 compartment 10.5 Eng Workshop Unassigned JS (2) Engineering Admin JS (4) Electronics workshop JS (4) Sickbay JS (8) Public head Unassigned Small arms stowage General Store Ships office/pay office Canteen and Canteen Store Aviation admin office JS Dining Deck 56 Scullery Naval Stores JS Rec Area Berth (2) Dry Store Berth (2) MCR and DCC Central Berth PO JS (2) Berth CPO JS (4) Pantry JS (2) Wardroom Baggage Store Public Head JS (6) UUV Support and Battery Charging Gym Repair Base
Considerations on the Calculation of Ventilation Systems for Special Ships
Considerations on the Calculation of Ventilation Systems for Special Ships PhD std. Eng. Octavian - Narcis VOLINTIRU 1, Prof. PhD. Eng. Anastase PRUIU 1, PhD. Eng. Ionut Cristian SCURTU 1 1 Naval Academy
More informationANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS
Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This
More informationMeans of escape from crew spaces on fishing ships
Means of escape from crew spaces on fishing ships May 2018 Maritime New Zealand Position Statement PS-02-18 This document is uncontrolled if printed. Please refer to the Maritime New Zealand website for
More informationVENTILATION DURING TUNNEL CONSTRUCTION INDUSTRY CONSIDERATIONS
VENTILATION DURING TUNNEL CONSTRUCTION INDUSTRY CONSIDERATIONS Air Quality Working Group Information Package - Part 7 of 12 December 2018 Doc No. AQWG_5_0.08 Page 1 of 12 Ventilation during Tunnel Construction
More informationINTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES s of the IGF Code CONTENTS GF1 Test for gas fuel tank s high level alarm Rev.1 July 2017 GF2 Ship Steel Protection against Liquefied Gas Fuel (Part
More informationADMINISTRATIVE INSTRUCTION No. STCW-14 QUALIFICATION / CERTIFICATION REQUIRED FOR OPERATION OF A DOMESTIC VESSESL
ADMINISTRATIVE INSTRUCTION No. STCW-14 QUALIFICATION / CERTIFICATION REQUIRED FOR OPERATION OF A DOMESTIC VESSESL (Issued under section 3(5) of the Gibraltar Merchant Shipping (Safety etc.) Ordinance 1993
More informationHAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction
Introduction A key task in commercial building HVAC design is determining outdoor ventilation airflow rates. In most jurisdictions in the United States, ventilation airflow rates must comply with local
More informationTHE IMPORTANCE OF SUCTION LINES
THE IMPORTANCE OF SUCTION LINES Analysis and connection to compressors Unicla Cat. No. B1801 Copyright 2018 All rights reserved No part of this document shall be reproduced in whole or in part without
More informationRESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS
INTERNATIONAL MARITIME ORGANIZATION A 14/Res.567 16 January 1986 Original: ENGLISH ASSEMBLY - 14th session Agenda item lo(b) IMO RESOLUTION A.567(14) adopted on 20 November 1985 THE ASSEMBLY, RECALLING
More informationUSS ALABAMA BATTLESHIP MEMORIAL PARK. Vocabulary
USS ALABAMA BATTLESHIP MEMORIAL PARK Vocabulary The following terms are common vocabulary for ships including battleships and submarines, like the USS ALABAMA and USS DRUM. ACOUSTIC - Means "sound" as
More informationIGO GROUP SAFETY STANDARD 30 - WORKPLACE VENTILATION INDEPENDENCE GROUP NL
IGO GROUP SAFETY STANDARD 30 - WORKPLACE VENTILATION INDEPENDENCE GROUP NL CONTENTS 1. INTENT... 3 2. APPLICATION... 3 3. UNDERGROUND VENTILATION... 3 3.2 Underground Ventilation Officer... 3 3.3 Risk
More informationINTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
INTERPRETATION IC 62-2001-06 OF ANSI/ASHRAE STANDARD 62-2001 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY REVISION APPROVED: 1/12/2002 Originally issued as interpretation of Standard 62-1989 (IC 62-1989-23)
More informationEXAM # 2. First Name Last Name CIRCLE YOUR LECTURE BELOW: INSTRUCTIONS
CIRCLE YOUR LECTURE BELOW: First Name Last Name Div. 1 08:30 am Prof. Chen Div. 2 11:30 am Prof. Braun EXAM # 2 INSTRUCTIONS 1. This is a closed book examination. You are allowed to have two single sheets
More informationPASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys
(Feb 2010) PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys Contents 1 Introduction 2 Preparations for Survey 2.1 General 2.2 Conditions for survey 2.3 Access to structures 2.4 Survey
More informationGuidelines for Clean Agent Fire Suppression Systems
References: S. T. Brady, Chief, Engineering Division a. National Fire Protection Association (NFPA) 2001, 2012 Edition (Clean Agent Fire Extinguishing ) b. International Code for Fire Safety (FSS), Chapter
More informationAPPENDIX 4 STANDARD FORMAT FOR THE PROCEDURES AND ARRANGEMENTS MANUAL
Page 42 APPENDIX 4 STANDARD FORMAT FOR THE PROCEDURES AND ARRANGEMENTS MANUAL Note 1: Note 2: The format consists of a standardized introduction and index of the leading paragraphs to each section. This
More informationSAMPLE RH = P 1. where. P 1 = the partial pressure of the water vapor at the dew point temperature of the mixture of dry air and water vapor
moisture starts to condense out of the air. The temperature at which this happens is called the dew point temperature, or the saturation temperature. What is commonly called saturation pressure or condensing
More informationATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN
ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN (This page intentionally blank) ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN TABLE OF CONTENTS O- Definitions... O- Objective... O- Design
More informationMSC Guidelines for Review of Emergency Evacuation Plans (Subchapter K)
S. E. HEMANN, CDR, Chief, Hull Division Purpose The purpose of this Plan Review Guideline is to provide the submitter with general guidance and information for the development of Subchapter K Emergency
More informationNational Standard for Commercial Vessels
National Standard for Commercial Vessels Part E Operations Published 17 May 2013 Endorsed by the Standing Council on Transport and Infrastructure 10 May 2013 Commonwealth of Australia This work is copyright.
More informationMSC Guidelines for the Review of Mobile Offshore Drilling Unit (MODU) General Arrangement Plans Procedure Number: C2-36 Revision Date: 10/18/2016
T. O. Phillips, CDR, Chief, Tank Vessel & Offshore Division Purpose: The purpose of this document is to provide guidance and information regarding the submission of MODU general arrangement plans under
More informationAt 60 metres and crowned by ten square-rigged sails Stavros S Niarchos cuts an impressive sight whether heeling under the wind or cruising the calms
STAVROS S NIARCHOS At 60 metres and crowned by ten square-rigged sails Stavros S Niarchos cuts an impressive sight whether heeling under the wind or cruising the calms of distant shores. Currently used
More information10 December 2010 GUIDANCE FOR WATERTIGHT DOORS ON PASSENGER SHIPS WHICH MAY BE OPENED DURING NAVIGATION
E 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: +44 (0)20 7735 7611 Fax: +44 (0)20 7587 3210 Ref. T4/3.01 MSC.1/Circ.1380 10 December 2010 GUIDANCE FOR WATERTIGHT DOORS ON PASSENGER SHIPS WHICH MAY BE
More informationAirborne Activity Sampling and Monitoring at Hinkley Point A Site. David Williams, Hinkley Point A Site
Airborne Activity Sampling and Monitoring at Hinkley Point A Site David Williams, Hinkley Point A Site Presentation objectives Ventilation controls in use at Hinkley Point A Site The air sampling and monitoring
More informationREDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2
RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 REDUNDANT PROPULSION JANUARY 1996 CONTENTS PAGE Sec. 1 General Requirements... 5 Sec. 2 System
More informationControl of Nuclear Gloveboxes and Enclosures Using the No- Moving-Part Vortex Amplifier (VXA)
Control of Nuclear Gloveboxes and Enclosures Using the No- Moving-Part Vortex Amplifier (VXA) ABSTRACT M.J. Crossley AEA Technology ES. Inc. 1100 Jadwin Ave, Richland, WA 99352, USA This paper describes
More informationCHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV
CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV 16-1 INTRODUCTION 16-1.1 Purpose. The purpose of this chapter is to familiarize divers with the techniques used to mix divers breathing gas. 16-1.2 Scope. This chapter
More informationCORESTA RECOMMENDED METHOD N 6
CORESTA RECOMMENDED METHOD N 6 DETERMINATION OF VENTILATION DEFINITIONS AND MEASUREMENT PRINCIPLES (2015 Revision September 2016) 1. SCOPE This CORESTA Recommended Method specifies a method for the determination
More informationUnderstanding Swimming Pool Ventilation. Presented by Tom Sands Mobile: CPD003/v03tcs2016
Understanding Swimming Pool Ventilation Presented by Tom Sands Mobile: 07768 244555 Email: tom.sands@ves.co.uk CPD003/v03tcs2016 1 Learning Objectives At the end of the presentation you should have a broader
More informationMANAGEMENT PROCEDURE FOR LABORATORY VENTILATION
UNIVERSITY OF ALASKA FAIRBANKS SAFETY SYSTEM POLICY AND PROCEDURE DOCUMENT NUMBER: 508 ISSUE DATE: SEPTEMBER 1996 SUBJECT: Management Procedure for Laboratory Ventilation MANAGEMENT PROCEDURE FOR LABORATORY
More informationSOP. Working in Confined Spaces
Purpose This procedure outlines the requirements for the management of entry into confined spaces in all work areas with the intention of minimising risks to health and safety from any potential hazards
More informationFOR SALE 34 Metre Offshore Vessel SHADOW BOAT CONVERSION OPPORTUNITY
FOR SALE 34 Metre Offshore Vessel SHADOW BOAT CONVERSION OPPORTUNITY vessel description The 34 metre multi role catamaran, has a tough workmanlike appearance typifying the work coming out of the specialist
More informationUNIFIED FACILITIES CRITERIA (UFC)
UNIFIED FACILITIES CRITERIA (UFC) SECURITY ENGINEERING: PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL, BIOLOGICAL, AND RADIOLOGICAL PROTECTION FOR BUILDINGS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED
More informationWalk in Modular Material Transfer Chamber Including Integration of a Bioquell Clarus L2 hydrogen peroxide vapour (HPV) generator
Walk in Modular Material Transfer Chamber Including Integration of a Bioquell Clarus L2 hydrogen peroxide vapour (HPV) generator Page 1 of 20 Walk in chamber and HPV integrated system - Product overview.
More informationNZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine
Page 1 of 5 Title Design and maintain effective ventilation systems for an underground coal mine Level 5 Credits 20 Purpose People credited with this unit standard are able to, for an underground coal
More informationNEW BUILD - Wildcat 53 Windfarm Support Vessel Listing ID:
Australia - Chile - Indonesia - Great Britain - New Zealand - Panama - Philippines - South Korea - Thailand - USA E: sales@seaboats.net (sales) - E: admin@seaboats.net (accounts) NEW BUILD - Wildcat 53
More informationBIOME DESIGN TECHNICAL DATA
March 03, 2006 BIOME DESIGN TECHNICAL DATA 1) Dimensions: Each biome has the following clear interior dimensions: length 6,096 m, width: 3,404 m Interior clearance throughout: 4,268 m (floor to underside
More informationPURE SUBSTANCE. Nitrogen and gaseous air are pure substances.
CLASS Third Units PURE SUBSTANCE Pure substance: A substance that has a fixed chemical composition throughout. Air is a mixture of several gases, but it is considered to be a pure substance. Nitrogen and
More informationResults of Field Measurements and CONTAM Simulation. Building Science
28 Building Science Corporation Tracer Gas Testing January 26 Results of Field Measurements and CONTAM Simulation Aaron Townsend Building Science Tracer gas test of a production Building America house
More informationNZQA unit standard New US 1Non-coal of 7145 version 1 Page 1 of 5
Page 1 of 5 Title Design and maintain effective ventilation systems for a non-coal underground operation Level 5 Credits 20 Purpose People credited with this unit standard are able to: explain the principles
More informationCrab and Lobster Live Holding System Part II (Water Pumps, Air Pumps and Pipework)
Crab and Lobster Live Holding System Part II (Water Pumps, Air Pumps and Pipework) 1990/2/SF/AM The increased demand for crabs and lobsters, and the requirement to export live shellfish has led to the
More informationTransient Analyses In Relief Systems
Transient Analyses In Relief Systems Dirk Deboer, Brady Haneman and Quoc-Khanh Tran Kaiser Engineers Pty Ltd ABSTRACT Analyses of pressure relief systems are concerned with transient process disturbances
More informationRESPIRATOR PERFORMANCE TERMINOLOGY
RESPIRATOR PERFORMANCE TERMINOLOGY The following terms were developed by the American Industrial Hygiene Association Respiratory Protection Committee to represent respirator performance in various contexts.
More informationOIL AND GAS INDUSTRY
This case study discusses the sizing of a coalescer filter and demonstrates its fouling life cycle analysis using a Flownex model which implements two new pressure loss components: - A rated pressure loss
More informationSpace Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series
Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies ASHRAE, St. Louis Chapter November10, 2014 Agenda Introduction (concept, purpose,
More informationMoisture levels in compressed breathing air. Prepared by QinetiQ Limited for the Health and Safety Executive 2006 RESEARCH REPORT 427
Moisture levels in compressed breathing air Prepared by QinetiQ Limited for the Health and Safety Executive 2006 RESEARCH REPORT 427 Moisture levels in compressed breathing air T G Anthony & P R Clarke
More informationAIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS
AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS Air conditioning control panel 1 MIN MAX Page 1 Air conditioning control panel 2 MIN MAX Page 2 Air conditioning control panel 3 MIN MAX Page
More informationVAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES
Proceedings: Indoor Air 005 A SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES PH Zhang * Jacobs Civil, Inc. 60 Madison Avenue, 1 th Floor, NYC, NY10016, USA ABSTRACT This paper discusses indoor
More informationEarlier Lecture. In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System.
17 1 Earlier Lecture In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System. Collins system is an extension of the Claude system to reach lower
More informationPOP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS
POP Safety Valve POP Safety Valve INTRODUCTION The effects of exceeding safe pressure levels in an unprotected pressure vessel or system, can have catastrophic effects on both plant and personnel. Safety
More informationRULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS SCOPE
PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS TITLE 12 CONTAINER SHIPS SECTION 1 NAVAL ARCHITECTURE CHAPTERS A SCOPE B DOCUMENTS, REGULATIONS AND STANDARDS
More informationGuidance on room integrity testing and its interpretation
Guidance Note Guidance on room integrity testing and its interpretation Guidance on room integrity testing and its interpretation 1. SCOPE... 6 2. INTRODUCTION AND BACKGROUND... 6 2.1. DEVELOPMENT OF INTEGRITY
More informationSingle- or Two-Stage Compression
The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationCHAPTER 44 NAVY DIVER (ND) NAVPERS A CH-70
CHAPTER 44 NAVY DIVER (ND) NAVPERS 18068-44A CH-70 Updated: April 2017 SCOPE OF RATING GENERAL INFORMATION SECOND CLASS DIVER TABLE OF CONTENTS NAVY DIVER (ND) CUTTING, WELDING AND ANCILLARY EQUIPMENT
More informationMSC Guidelines for Review of Emergency Evacuation Plans (NVIC 8-93)
Procedure Number: H2 Revision Date: 10/07/2014 K. B. FERRIE, CDR, Chief, Hull Division Purpose The purpose of this Plan Review Guideline is to provide the submitter with general guidance and information
More informationCanadian CBRN PPE Standards and Guidance March Eva Dickson Royal Military College of Canada Project Manager, Project CRTI RD
Canadian CBRN PPE Standards and Guidance March 2006 Eva Dickson Royal Military College of Canada Project Manager, Project CRTI 01-0029RD The project objectives To provide guidance to first responders in
More informationSOLAS requirements for nonpassenger ships 300 or above but less than 500 gross tonnage
SOLAS requirements for nonpassenger ships 300 or above but less than 500 gross tonnage Guidance for owners, masters and surveyors for ships undertaking international voyages SOLAS requirements applied
More informationPressure = 15.2 bar TXV. 10K super heat. Pressure = 1.82 bar. Line temp = 8 C. Line temp = 9 C
Technical ulletin dvanced compressor technology for the world December 2017 The importance of a good suction line Unicla at. No. T1703 Introduction The correct hose and pipe connecting the main components
More informationASSIGNMENT 3. Textbook Assignment: Water System, Trim and Drain System, Air Systems, and Main Hydraulic System Chapters 9-12.
ASSIGNMENT 3 Textbook Assignment: Water System, Trim and Drain System, Air Systems, and Main Hydraulic System Chapters 9-12. 1. (TRUE/FALSE) Sea water is used in many systems aboard the submarine because
More information2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A
2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR
More informationWork Permit Help Document For changes introduced in ShIPS Revision 7.1 (Released 11/12/2008)
Introduction Work Permit Help Document For changes introduced in ShIPS Revision 7.1 (Released 11/12/2008) The current ShIPS Revision 7.1 has introduced an automated work permit system which has the benefit
More informationNEW BUILD - SB-ST 19 Steel Trawler Listing ID:
Australia - Great Britain - Indonesia - New Zealand - Philippines - Thailand - USA E: sales@seaboats.net (sales) - E: admin@seaboats.net (accounts) NEW BUILD - SB-ST 19 Steel Trawler Listing ID: 411473
More informationRESPA SD / SDX HVAC PRECLEANER + FILTRATION + PRESSURISER (PFP) TECHNOLOGY
(1) RESPA SD / SDX HVAC PRECLEANER + FILTRATION + PRESSURISER (PFP) TECHNOLOGY (2) CONVENTIONAL HVAC FILTRATION / PRESSURISER DESIGN CONCEPTS & FUNCTIONS Mobile Plant / HVAC / Filtration- Background Mobile
More informationCERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER
CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER EXAMINATIONS ADMINISTERED BY THE SCOTTISH QUALIFICATIONS AUTHORITY ON BEHALF OF THE MARITIME AND COASTGUARD AGENCY STCW 95 CHIEF
More informationMSC Guidelines for Tank Barge General Arrangements Procedure Number: C1-16 Revision Date: June 1, 2017
T. O. PHILLIPS, CDR, Tank Vessel and Offshore Division Purpose: The purpose of this document is to provide guidance and information regarding the submission of General Arrangements plans for an Oceangoing
More informationInerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS
Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers The PRB Coal Users Group plans to develop a Design Guide for Mill Inerting as an aid to users when designing a mill inerting system.
More informationEgress and means of escape from passenger spaces
Egress and means of escape from passenger spaces May 2018 Maritime New Zealand Position Statement PS-01-18 This document is uncontrolled if printed. Please refer to the Maritime New Zealand website for
More informationFMU4X, FMC4X FMU4P, FMC4P
ENVIRONMENTALLY SOUND REFRIGERANT FMU4X, FMC4X FMU4P, FMC4P Product Specifications HORIZONTAL FAN COILS FMU4P and FMC4P 1 1/2, 2, 2 1/2, and 3 Tons FMU4X and FMC4X 1 1/2, 2 and 2 1/2 Tons ALL MODELS Horizontal
More informationRESOLUTION MSC.235(82) (adopted on 1 December 2006) ADOPTION OF THE GUIDELINES FOR THE DESIGN AND CONSTRUCTION OF OFFSHORE SUPPLY VESSELS, 2006
MSC 82/24/Add.2 RESOLUTION MSC.235(82) CONSTRUCTION OF OFFSHORE SUPPLY VESSELS, 2006 THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization
More informationSumerset FB Houseboat Bella Vita
Sumerset 70-14 FB Houseboat Bella Vita Make: Model: Length: Sumerset 70-14 FB Houseboat 70 ft Price: $ 92,500 Year: 1986 Condition: Used Boat Name: Hull Material: Number of Engines: 2 Fuel Type: Bella
More informationThe Metal Shark 75 Endurance is a welded aluminum pilothouse catamaran specially designed for use as a law enforcement, port security, and fire
The Metal Shark 75 Endurance is a welded aluminum pilothouse catamaran specially designed for use as a law enforcement, port security, and fire rescue response boat. Like all Metal Sharks, it may be fully
More informationFUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS. A high-capacity EBA system [CSVS] [main purge]
PAGE : 1 / 9 5. CONTAINMENT PURGE (EBA [CSVS]) The Reactor Building purge system comprises the following: A high-capacity EBA system [CSVS] [main purge] A low-capacity EBA system [CSVS] [mini-purge] 5.1.
More informationCERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER
CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER EXAMINATIONS ADMINISTERED BY THE SCOTTISH QUALIFICATIONS AUTHORITY ON BEHALF OF THE MARITIME AND COASTGUARD AGENCY STCW 95 CHIEF
More informationLECTURE 1 THE CONTENTS OF THIS LECTURE ARE AS FOLLOWS: 1.0 AIRWAYS CONNECTED IN SERIES AND PARALLEL. 1.1 Airways Connected in Series
LECTURE 1 THE CONTENTS OF THIS LECTURE ARE AS FOLLOWS: 1.0 AIRWAYS CONNECTED IN SERIES AND PARALLEL 1.1 Airways Connected in Series 1.2 Airways Connected in Parallel 1.3 Ratio of Resistances of Series
More informationLABORATORY SAFETY SERIES: Laboratory Hoods
ERI Safety Videos Videos for Safety Meetings 2956 LABORATORY SAFETY SERIES: Laboratory Hoods Leader s Guide Marcom Group Ltd. 1 INTRODUCTION TO THE PROGRAM Structure and Organization Information in this
More informationEQUIPMENT AND PERSONNEL
1 EQUIPMENT AND PERSONNEL Inland Rivers and Gulf Coast 2013 Section 4 Topics 4.1 Equipment Boats 4.1.1 Types and Sizes of Towboats 4.1.2 Main Propulsion Equipment 4.2 Equipment Barges 4.2.1 Barge Sizes,
More informationThis test shall be carried out on all vehicles equipped with open type traction batteries.
5.4. Determination of hydrogen emissions page 1 RESS-6-15 5.4.1. This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4.2. The test shall be conducted following
More informationTechnical Specification Bases Update to the NRC for Period Dated
...~Entergy Entergy Operations, Inc. 7003 Bald Hill Road PO. Box 756 Port Gibson, MS 39150 Tel 601 437 6299 Christina L. Perino Manager Licensing GNRO-2009/00017 March 4, 2009 U.S. Nudear Regulatory Commission
More informationBLUE DAWN 1959 SCHIPSWERT General Description: SCHIPSWERT M / M / 31 3 Cummins Lebanese 5 / 12
General Description: BUILDER: YEAR BUILT: L.O.A (m/ft).: BEAM (m/ft).: MAIN ENGINES: CRUISING SPEED (kn): MAX. SPEED (kn): FLAG: CABINS / GUESTS: SCHIPSWERT 1959 62.05M / 203 7 9.50M / 31 3 Cummins 10
More informationTABLE OF CONTENTS PART 2 - CONFINED SPACES
May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3
More informationRegulatory Basics for Facility Design (WHO GMP): Current GMP Requirements
Regulatory Basics for Facility Design (WHO GMP): Current GMP Requirements Main Topics of the Presentation Clean Room Requirements Interior Finishes and Air Tightness of Clean Rooms Pressure Cascade Concept
More informationFire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations
Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Grzegorz Kubicki, Ph.D. Department of Environmental Engineering, Warsaw University of Technology
More informationCW/BW Shipboard Decon Procedures. and Collective Protective System (CPS)
CW/BW Shipboard Decon Procedures and Collective Protective System (CPS) Enabling Objectives Perform buddy aid and self aid procedures Perform the procedures to detect and classify chemical agent stimulants
More informationLABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM
LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM Last Updated: Tuesday, January 31, 2006 1. INTRODUCTION AND SCOPE 2. RESPONSIBILITIES 3. USER GUIDELINES 4. SYSTEM DESIGN SPECIFICATIONS o The
More informationSTANDARDS FOR COMPRESSED GAS TESTING
STANDARDS FOR COMPRESSED GAS TESTING APPLICATION NOTE HPD-002 (US) Introduction This publication provides excerpts from some of the many guidelines and standards that pertain to compressed gases in cleanrooms.
More informationAir Handling Unit (AHU) Air handling unit which serves to condition the air and provide the required air movement within a facility.
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 13, Issue 5 Ver. I (Sep. - Oct. 2016), PP 28-35 www.iosrjournals.org. Heating, Ventilation and Air
More informationPTB Ex PT Scheme. Procedure Instruction of program Explosion Pressure - Test Round 2017
Procedure Instruction of program Explosion Pressure - Test Round 2017 Content 1 General Performance... 2 2 Measurand / Characteristic of interest... 2 3 Test Item and Configurations... 2 3.1 Components...
More informationST. VINCENT AND THE GRENADINES
ST. VINCENT AND THE GRENADINES MARITIME ADMINISTRATION CIRCULAR N SOL 001 Rev. 2 SOLAS 74 as Amended Ch. III Revised Reg. 32.3 IMO Resolution MSC.152 (78), MSC/Circ. 1046, MSC/Circ. 1047 MSC/Circ. 1114
More informationTesting Procedures of Watertight Compartments
(1996) (Rev.1 Feb 2001) (Rev.2 May 2001) (Rev.3 May 2010) (Rev.4 Aug 2012) Testing Procedures of Watertight Compartments.1 Application Revision 4 of this UR is to be complied with in respect of the testing
More informationThermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI
Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI Outline: Pure Substance Phases of pure substance Phase change process of pure substance Saturation temperature and saturation pressure
More informationControlling Cabin and Envelope Air Flows & Pressure Differentials
Controlling Cabin and Envelope Air Flows & Pressure Differentials To control envelope moisture and related problems Douglas S. Walkinshaw and Keith F. Preston ECHO Air Inc www.indoorair.ca 1 This paper
More informationHydronic Systems Balance
Hydronic Systems Balance Balancing Is Misunderstood Balancing is application of fundamental hydronic system math Balance Adjustment of friction loss location Adjustment of pump to requirements By definition:
More informationConfined Spaces. This procedure applies to all workers of the Diocese of Maitland Newcastle (DoMN).
Purpose To provide guidance in controlling the risks associated with confined spaces including identifying confined spaces, working in a confined space and issuing confined space entry permits. Scope This
More informationMSC Guidelines for Carbon Dioxide Fire Suppression Systems
C. J. Robuck, LCDR, Chief, Engineering Division References a. Title 46 CFR 34.15 (Subchapter D) b. Title 46 CFR 76.15 (Subchapter H) c. Title 46 CFR 95.15 (Subchapter I) d. Title 46 CFR 108.431 (Subchapter
More informationOIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply
OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions
More informationInstallation of Ballast Water Management Systems
(Sept 2015) (Rev.1 May 2016) Installation of Ballast Water Management Systems 1. Application In addition to the requirements contained in BWM Convention (2004), the following requirements are applied to
More informationPSSRA Work Package Overview The Mighty War Ship
PSSRA Work Package Overview The Mighty War Ship USS JOHN C. STENNIS (CVN 74) FY13 DPIA What s the Message? NW Contractors supporting the war fighter and Naval lsy. Opportunity good sized work package for
More information776 Cryogenic Safety Valve
776 Cryogenic Safety Valve INTRODUCTION 776 Cryogenic Safety Valve The effects of exceeding safe pressure levels in an unprotected pressure vessel or system, can have catastrophic effects on both plant
More information2017 Edition GUIDANCE NOTE GN 8 INVERTER DRIVES FOR FANS AND PUMPS GN 8 - INVERTER DRIVES FOR FANS AND PUMPS
GUIDANCE NOTE GN 8 INVERTER DRIVES FOR FANS AND PUMPS 2017 Edition COMMISSIONING SPECIALISTS ASSOCIATION Page 1 GUIDANCE NOTE GN 8 INVERTER DRIVES FOR FANS AND PUMPS Written By C. Shearer COMPILED BY THE
More informationA Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors Piero
More information