CHAPTERS THE EXTENT OF EXPLOSION DANGER FOR NEC CLASS I LOCATIONS

Size: px
Start display at page:

Download "CHAPTERS THE EXTENT OF EXPLOSION DANGER FOR NEC CLASS I LOCATIONS"

Transcription

1 CHAPTERS THE EXTENT F EXPLSIN DANGER FR NEC CLASS I LCATINS A. General The purpose of classifying a hazardous location is to provide an acceptable level of safety against explosion danger for personnel and equipment. This is accomplished not only by establishing the degree of explosion danger as shown in Table 1-3, but also by establishing the extent of the explosion danger, and by furnishing suitable electrical equipment in compliance with the established degree and extent of explosion danger. The determination of the degree of the explosion danger is a rather simple procedure. By applying the guidelines in Chapter 2 and in Table 1-3, the degree of danger for the hazardous location can be established without any difficulty. The determination of the extent of explosion danger, however, is far more complex and requires an in-depth understanding of the nature of the explosion danger. For example, in Item 8 of Table 1-3, a closed source of hazard is located in a sufficiently ventilated building. According to Item 8 the classification of the location must be Div. 2. The question now is; how far does the Div. 2 area extend in horizontal and vertical direction? Should it be 10, 15, 25, 50 or 100 feet, or should the entire indoor location be classified, or only partially classified Div. 2? These questions shall be addressed later on. B. The Dimensional utline of a Div. 1 and Div. 2 Zone As a general rule, the dimensional outline of a Div. 1 and a Div. 2 zone is measured from the outline of the source of hazard in horizontal and vertical directions as shown in Fig 1-4. The distance between the outline of the source of hazard and the boundary line is called the extent of danger, or simply, the boundary, or boundary distance. The vertical and horizontal distances are expressed in, respectively, "V" and "H." As shown in Fig 1-4, the distance "V" starts from the top of the source of hazard in a vertical direction. "Hi" is also a vertical distance, measured from the floor or grade. Thus, a boundary with a 5V, 25H and 3 Hi means a boundary of 5 feet vertical, 25 feet horizontal, and 3 feet high. All "V" and "H" dimensions are measured in feet. When "Hi" reads

2 18Hi, it means a vertical distance of 18 inches high. This figure is the only figure which is related to inches. All other figures are in feet. C. Quantity of Flammable Substances Versus Extent of Explosion Danger The extent of explosion danger is primarily a function of the quantity of the flammable gas or vapor released into the atmosphere. These quantities are influenced by the discharge and evaporation rates, and the rupture opening through which the flammable gas, vapor or liquid will escape. This in turn is a function of the type and size of the source of hazard, the vapor density, the flammability class of flammable products and the temperature and pressure in the system. These conditions must be considered before the extent of the explosion danger can be established. However, it is not practical to make predictions of the size of the rupture opening through which a flammable gas, vapor or liquid will escape if the source of hazard breaks down. It requires a great deal of study and analysis, making the evaluation too involved and too cumbersome. It is also not practical to determine the rate of release of the flammable gas, vapor or liquid, or the diffusion rate of the flammable gas or vapor in the air. It is far more practical to predict a quantity of flammable gas or vapor that a given size source of hazard is capable of releasing into the atmosphere, when the source of hazard should break down. It is also far more practical to establish whether a static type or dynamic type source of hazard is involved. The quantities of flammable gases or vapors released into the atmosphere are proportional to the traveling distance of the flammable gas or vapor. The greater the quantity, the longer the traveling distance. The smaller the quantity, the shorter the traveling distance. Before the flammable gas or vapor has reached its maximum traveling distance there is a point in space at which the flammable gas or vapor will reach a nonhazardous concentration. It is the distance between the source of hazard and this point that determines the extent of the explosion danger. The size of the hazardous area must not be less than this distance. A more indepth discussion on traveling distances can be found under Section G, "Transition Zones for NEC Class I Locations" in Chapter 3. The quantity of flammable gases or vapors released into the atmosphere and consequently, the traveling distance of the flammable gas or vapor, therefore, is a valid basis for determining the extent of the danger area. Large sources of hazard are normally capable of releasing large quantities of flammable gases or vapors, whereas small and mini sources of hazard are more likely to produce small quantities. To simplify the method for establishing the proper size of a hazardous area, the quantity of the flammable gas, vapor or liquid released into the atmosphere is taken as the basis for establishing the size of the hazardous area. Consequently, the size of a hazardous area is established by the

3 FINISHED GRADE SURCE F HAZARD H H SURCE F HAZARD LEGEND V = VERTICAL DISTANCE IN FEET H = HRIZNTAL DISTANCE IN FEET Hi = VERTICAL HEIGHT IN INCHES R = RADIUS IN FEET 1-4. BUNDARIES FR NEC CLASS I LCATINS

4 size of the source of hazard, and since the source of hazard is either large, small or mini, the quantity of flammable substances released to the atmosphere can only be large or small. Unfortunately, the size of the source of hazard alone cannot be relied upon completely in determining the size of the hazardous area. This is due to the fact that the quantity of the flammable gas or vapor released to the atmosphere is greatly influenced by temperature and pressure in the system, and type of source of hazard. The higher the temperature or pressure in the system, the greater the quantity released. Therefore, small sources of hazard may also produce large quantities of flammable gases or vapors when their temperature or pressure is high, and large sources of hazard may produce small quantities of flammable gases or vapors when their temperature or pressure is low. Consequently any source of hazard, regardless of its size, that is capable of releasing large quantities of flammable gases or vapors, requires large hazardous areas, whereas sources of hazard that can release only small quantities of flammable gases or vapors require small hazardous areas. The different boundary requirements with respect to the size of the source of hazard clearly indicate that the size of the source alone is not a valid guideline for determining the amount of flammable gases or vapors which the source is capable of releasing. In order to determine whether a source of hazard is capable of releasing small or large quantities of flammable gases or vapors into the atmosphere, it is necessary to take into account several additional factors which are explained in Section D of this chapter. These will affect the relationship between source of hazard size and small or large hazardous areas. It is important to understand, however, that the wording "small and large quantities of flammable gases or vapors released" as used above must not be confused with the wording, "in quantities sufficient" as described in article 500 of the NEC which reads: "Class I locations are those in which flammable gases or vapors are or may be present in the air 'in quantities sufficient 1 to produce explosive or ignitible mixtures." To eliminate confusion between the two wordings, it is important to understand the intent of the wording in the NEC. Misinterpretation of the intent of the wording in the NEC could lead to the conclusion that a flammable gas or vapor in the air is not dangerous if its quantity in the air is small. That is not so. The wording "in quantities sufficient" in the NEC is related to the explosion range of the flammable product and the wording "small or large quantities released" as explained in here to the bulk of the flammable product. A large bulk of flammable gas or vapor in the air, therefore, could be of insufficient quantity if it has not entered its explosion range. n the other hand a small bulk of flammable gas or vapor in the air will have a sufficient quantity when it has entered its explosion range. Hydrogen gas, for example, has an explosion range between 4 and 75%.

5 When the hydrogen gas in the air has a concentration of less than 4%, the NEC considers it as being of insufficient quantity to produce an explosive mixture. When the flammable gas or vapor is within its explosion range, the NEC considers it to have a concentration of sufficient quantity to produce an explosive mixture. Therefore, for a small or large quantity of flammable gas or vapor to become explosive, it is necessary that its concentration in the air be present in sufficient quantities, which is only possible when it has entered its explosion range. D. Factors Influencing Quantities of Flammable Gases or Vapors Factors that influence the quantity of a flammable gas or vapor released into the air are: 1) the type and size of the source of hazard, 2) the temperature and the pressure in the system, and 3) the flammability class of the flammable product. The larger the quantity released into the air, the greater the danger in the location. The extent of the danger is mainly dictated by the vapor density of the flammable product. The vapor density and any one or more of the factors listed above will influence the traveling distance of the flammable gas or vapor in the air and subsequently the degree and extent of the hazardous area. Sufficient ventilation is another factor which has a great impact on the traveling distance of the flammable gas or vapor and subsequently also on the extent of the hazardous area. The traveling distance is inversely proportional to air velocity. Information on traveling distances of flammable gases and vapors in the air with respect to ventilation is outlined under "Ventilation Requirements" in Chapter 6. An extremely important factor is pressure in the system. Pressure is directly related to failure or breakdown of process equipment. Pressure in the system is defined as "low," "moderate," and "high." The failure of process equipment is also a function of wear, but mainly of pressure in the system. They, then, will also have an impact on the extent and degree of the hazardous area. Higher pressure in a system requires a more conservative approach than lower system pressures. For example, mini sources of hazard such as piping systems including screwed fittings, bolted flanges, valves and meters located in a sufficiently ventilated indoor area must be classified Div. 2 if operating at moderate pressure. The extent of the Div. 2 area shall only be a circular zone of 3 feet radius around each individual component of the piping system. The reason for this classification is the presence of sufficient ventilation and because of the moderate pressure in the system. If the indoor location containing the same piping system is not sufficiently ventilated, then the location must be classified Div. 1 with a 3 feet radius and Div. 2 with a 5 feet radius, 10 feet horizontal and 18 inches high. The same indoor location without sufficient ventilation must be classified Div. 1 with a 5 foot radius and Div. 2 with a 7 foot radius, 15 feet horizontal and

6 18 inches high if the piping system is operating at high pressure. At high pressure the risk of breakdown is much greater, and the fact that there is not sufficient ventilation makes the location more dangerous. In outdoor locations the individual components of the same piping system must be provided with a Div. 2 circular zone of 3 feet radius, 10 feet horizontal, 18 inches high. The reason for this classification is that outdoor locations are allowed to have smaller hazardous boundaries. An all welded piping system without screwed fittings, bolted flanges, valves and meters operating at any pressure, on the other hand is allowed to be classified nonhazardous. This is because the breakdown of an all welded piping system is considered remote. A well-maintained mini-type piping system with screwed fittings, bolted flanges, valves and meters operating at low pressure located in sufficiently ventilated indoor areas is also allowed to be classified nonhazardous. The supporting arguments for this classification are 1) low pressure, 2) sufficient ventilation, 3) only small quantities of flammable material will be released to the atmosphere in case a component should break down, and most important, 4) the piping system is well maintained. For detailed classification requirements refer to Section II, Figs. K-I and K-2. Sources of hazard other than the mini type such as sources of hazard which are small and large are required to have a larger area size. For example, a large pump handling a Class I flammable liquid outdoors operating at high pressure will produce much larger quantities of flammable material into the air in case of breakdown or failure than a mini static type source of hazard. The supporting reasons for this case are: type, because the pump is a rotating equipment; size, because it is large; pressure, because it is high; flammable product, because it is Class I. All of these factors support the conclusion that large quantities of vapor, much larger than by mini sources of hazard, will be formed under accidental failure. Thereby, when the flammable product is heavier-than-air, the traveling distance will be long and subsequently a large hazardous area, say of 50 feet horizontal, is required. A large quantity of flammable gases or vapors is associated with boundary sizes of 50 and 100 feet. (See Figs. 1-2 and 1-3.) If the same pump should handle a Class II heavier-than-air flammable product at the same high pressure, then smaller quantities of flammable vapors are expected in the air requiring a smaller hazardous area. This means that a horizontal hazardous area of only say 25 feet maximum is needed, even though it is a large source of hazard. Justification for this is that Class II flammable products will cover smaller areas than Class I flammable products. In this example then, the flammability class of the flammable product becomes more important than the size of the pump, the high pressure and type of the equipment. The question may arise as to what impact the type of source of hazard may have on the classification of the hazardous area. The answer is that the particular kind of source of hazard will indicate how much mechanical wear may be

7 expected, which will then influence the ultimate classification of the hazardous area. If mechanical wear is nonexistent or low, then only the size of the source of hazard, the product and its pressure are relevant factors in classifying the area. But if there is continuous mechanical wear, the type of source of hazard becomes an important matter. Generally, a more conservative approach is required for a high rate of mechanical wear than for a low rate of wear. Therefore, the mechanical wear must also be taken into consideration in establishing the classification and the size of the hazardous area. When a source of hazard is frequently operated or worked on, it is subjected to greater wear and will break down sooner and will also more often release ignitable concentrations of gases or vapors to the atmosphere. This puts the closed mini source of hazard in the same category as an open source of hazard which is normally releasing flammable vapors to the atmosphere continuously. For example, if a mini source of hazard, such as a valve, is operated often or is frequently worked on, the source is considered to have a high rate of wear. In this case a circular Div. 1 zone with a 3 or 5 feet radius for the mini source of hazard would be required instead of a Div. 2 circular zone. For dynamic type sources of hazard the required size of the hazardous area is generally larger than for the static type sources of hazard even when the static type sources of hazard are larger. The reason for this is that the dynamic type source of hazard is normally subjected to a higher rate of wear and the static type is not. However, if the static type source of hazard has a greater wear, it must be provided with a Div. 1 classification because the equipment may break down more often. n the other hand, a dynamic source of hazard having the same wear does not have to have a Div. 1 classification because it may not break down as often. Process equipment, therefore, that might frequently break down requires a Div. 1 classification and process equipment that only occasionally breaks down requires a Div. 2 classification. If frequent breakdowns can be expected, the process equipment becomes comparable with an open source of hazard which is normally classified Div. 1. The process equipment of the dynamic type source of hazard which breaks down only occasionally is not comparable with an open source of hazard and therefore it can be classified Div. 2. In view of these considerations the determination of whether quantities of flammable gases or vapors released into the atmosphere, and whether their associated traveling distances are large or small, becomes more meaningful. However, whether the quantity of the flammable gas or vapor and the traveling distance is large or small, it is still necessary to determine the required dimensions of the size of the hazardous area in order to produce a safe and economical electrical installation. These dimensions must be large enough to cover the entire distances which the flammable gas or vapor must travel to reach a nonhazardous concentration. Since the dimensions of a hazardous area must cover each

8 individual traveling distance, a great number of hazardous area dimensions is needed. It is, however, impractical to provide a great number of hazardous area dimensions for each individual traveling distance. It is more practical to apply a limited number of dimensions that cover a given group of traveling distances of different lengths. Each one of these dimensions must also cover the largest possible distance a Class I flammable product will travel. Therefore, for some flammable products the size of the hazardous area for a given group of traveling distances is more than ample, and for others they may be just right. The groups of dimensions are broken down in horizontal distances of 100, 50, 25, 15, 10, 5, 3, and less than 3 feet. They are classified Div. 1 or Div. 2 depending on the situation in the location as explained above. Large sources of hazard normally require 100 and 50 feet boundaries. Small sources of hazard normally will require 25,15,10, 5 and 3 feet boundaries. Mini sources of hazard are generally in the range between 15 and 3 feet or less. The various groups of dimensions are listed in Tables 1-4 and 1-5. They are also shown in the illustration in Section II. All dimensions listed and shown are prepared for Class I flammable products. For area dimensions required for Class II flammable products refer to section "F" in this chapter. To maintain conservatism for Class II flammable products, it is best to apply the dimensions for Class I flammable products. The question as to how the Div. 2 classification should extend in Item 8 of Table 1-3 can now be answered as follows: The main ingredients shown in Item 8 of Table 1-3 are: 1) a closed operating mode, 2) an indoor location and 3) sufficient ventilation. With these 3 ingredients known, the size of the hazardous area can be obtained from item 1 through item 11 in Table 1-4. A number of items in Table 1-4 are for heavier-than-air flammable products, and others are for lighter-than-air flammable products. If it is assumed that the flammable substances in Item 8 of Table 1-3 are heavier than air, then only Item 1 of Table 1-4 will apply. The next important ingredient is to establish the size of the source of hazard and the pressure in the system. With the size of the source of hazard and the pressure in the system known, the size of the hazardous area is narrowed down more to one particular dimension. For example, say the source of hazard is of the dynamic type. If the size of the source is "small" (up to 51 HP) and the pressure in the system is "moderate," and flammable gases or vapors which might escape from the enclosed confinement are "heavier than air," the required dimensions of the Div. 2 hazardous area can be obtained from the subtables listed in column (7) of Table 1-4. nly Subtable "A" will apply and from this subtable only item 1 which reads "5V, 25Ho, 3Hi" will apply. Because of the strong relationship between the quantity of a flammable gas

9 or vapor released to the atmosphere and the temperature in the system, one method is to divide the temperature into a number of temperatures, each of which can be associated with a given quantity of flammable gases or vapors in the air. However, since only two quantities of flammable gases or vapors released to the atmosphere are considered important, "small" and "large," the temperature must also be equally divided into two ranges. ne range is a temperature "above" flash point up to and including 5 0 F. The other is a temperature "far above" flash point which is associated with a temperature of at least 5 times the flash point. However, since the temperature is in direct proportion to the system pressure, it is much simpler to use the other method which equates temperature to system pressure. System pressure is defined as low, moderate and high. Low pressure in a system is below 100 PSI. Moderate pressure is generally 100 PSI up to and including 500 PSI, and high pressure is above 500 PSI. The three pressure categories: low, moderate and high, are included in the subtables "A" through "K." Table 1-4 has 5 self-explanatory columns. Column 5 of Table 1-4 refers to the subtables marked with a letter. For example: If the system operating mode of a source of hazard is "closed" and the source of hazard is handling a "heavier"-than-air flammable product "outdoors," refer to Item 3 of Table 1-4. Col. 5 of Table 1-4 reads the associated subtable for Item 3 of Table 1-4, which for this case is subtable "C." In subtable C there are 15 different conditions. nly one of the 15 conditions will apply. The solution of the proper condition is based on the pressure in the system, the size of the source of hazard, the size of the driver if any, and the type of locations. Whether or not an additional danger zone must be applied can be found in Column 8 of each subtable. Instead of using the boundary dimensions in the subtables, the dimensions in the illustrations in Section II can be used, or the boundaries in Table 1-5 for less common sources of hazard. The illustrations in Section II will show various conditions that may reflect actual situations encountered in chemical and petrochemical industries. The illustrated boundaries in Section II can be applied for gas compressors and for conditions where Class I flammable liquid is used with either lighter or heavier than air vapors. The illustrations may also be used for actual conditions that are similar to the illustrations, or for Class II flammable liquid with the requirements explained in this chapter. E. Early and Remote Permanent Ignition Sources As explained in Section D-3 of Chapter 1, early ignition is defined as a condition in which no explosion will occur if an ignitable concentration of

10 flammable gases or vapors in the air comes in contact with a "local" ignition source, with a temperature above the ignition temperature of the flammable product. Also explained in Section D-3 is a condition in which an explosion will occur if the ignitible concentration comes in contact with a "remote ignition source" with a temperature above the ignition temperature of the flammable product. Even when the flammable material is confined in a closed system from which it can escape only if the system breaks down, the location cannot be classified Div. 2 if the above conditions exist. If a "local" or "remote" ignition source exists with a temperature above the ignition temperature of the flammable product, the location must be classified Div. 1. These types of ignition sources can be compared with conditions in which flammable gases or vapors are released into the atmosphere continuously or frequently which, as a result of this condition, require that the location be classified Div. 1. Therefore, a location containing a "local" of "remote" ignition source is also required to be classified Div. 1. The "local" ignition source is required to have a circular zone of 3 feet diameter. A Div. 2 transition zone surrounding the Div. 1 zone may be applied but is not necessarily required. When a "remote" ignition source is involved, the area between the source of hazard and the remote ignition source must be classified Div. 1. This is only true if the flammable gases or vapors in the area have not reached safe concentrations before contacting the remote ignition source. If the flammable gas or vapor has reached safe concentrations before contacting the remote permanent ignition source, then the area need not be classified Div. 1. To avoid a possible explosion as a result of a remote ignition source, it is necessary to maintain sufficient distance between the source of hazard and the remote ignition source. But first, what is sufficient distance? Sufficient distance is the proper boundary size for a hazardous location which is selected from Table 1-4 on the basis of 1) the type and size of the source of hazard, 2) the pressure in the system and 3) the flammability class and the vapor density of the flammable product. For example, if the recommended boundary size for a source of hazard is to be 25 feet long, and the actual distance between the source of hazard and remote ignition source is within the 25 feet boundary, an explosion can be expected if the flammable gas or vapor in the air comes in contact with the remote ignition source. If, on the other hand, the actual distance should be longer than 25 feet, no explosion will be expected, in which case the 25 feet area can be considered remotely hazardous. The following example will illustrate the conditions mentioned above. Consider, for example, an area with four electric motor driven pumps and one pump driven by a high pressure steam turbine as shown in Fig 1-5. All pumps are handling volatile flammable liquid. The high pressured steam turbine

11 DIV. 2 AREA DIV. 2 AREA DIV. 1 AREA DIV. 2 TRANSITINZNE LEQEND "a" = HIGHPRESSURESTEAMTURBINE P1.P2.P3 = 50 HP PERATING AT HIGH PRESSURE P4. P5 = 250 HP PERATING AT MDERATE PRESSURE 1-5. NN-ELECTRICAL PERMANENT IGNITIN SURCE

12 TABLE 1-4 SUMMARY F SPECIFIC CNDITINS INFLUENCING THE DEGREE AND EXTENT F HAZARD N. SYSTEM PERATING MDEF SURCESF HAZARD TYPE F LCATIN t LCATIN SUFFICIENTLY VENTILATED? t HEAVIERR LIGHTERTHANAIR GASESR VAPRS IDENTIFICATIN LEHERSFR SUBTABLES if- 1 CLSED INDRS YES HEAVIER A 2 CLSED INDRS N HEAVIER B 3 CLSED UTDRS YES HEAVIER ' I 4 PEN INDRS YES HEAVIER D 5 PEN INDRS N HEAVIER E 6 PEN UTDRS YES HEAVIER F 7 CLSED INDRS YES LIGHTER G 8 CLSED INDRS N LIGHTER H 9 CLSED UTDRS YES LIGHTER I * 10 PENRCLSED INDRS/UTDRS YES/N HEAVIERRLIGHTER J 11 CLSED INDRS/UTDRS YES/N HEAVIER K * = INCLUDESCNTRLRMINHAZARDUSLCATlNS. A = INCLUDES PERMANENT IGNITIN SURCES t = APPLIES T SURCES F HAZARD if- = THE DATA IN CL 1,2,3 AND 4 IS INCLUDED IN THE TITLE BLCK F THE SUBTABLE. THE DATA IN THE TITLE BLCK APPLIES NLY T THE SURCE F HAZARD UNLESS INDICATED THERWISE. EACH SUBTABLE IS IDENTIFIED BY A CAPITAL LEHER.

13 TABLE A DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED INDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZEF SURCE F HAZARD SIZEF PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T A-1 A-2 A-3 PUMPHUSE PUMPHUSE PUMPHUSE AND UP AS INDICATED IN A-1 AS INDICATED IN A-2 LW/MD. 5 V, 25 H, 3 Hi# 5 V, 25/50 H, 3Hi ENTIRE INDR LCATIN N t YES * YES 4 A-4 PUMPHUSE 201 AND UP HIGH 25V.50H+50H* 3 Hi R ENTIRE INDR LCATIN YES 5 A-5 STRE HUSE AND LW N 6 7 A-6 A-7 STRAGEF CNTAINERS PIPING SYSTEM MINI R MDERATE ENTIRERM * 10 V, 25 H 1 18 Hi N N 8 A-8 PIPING SYSTEM MINI MDERATE 3R * N t = WHEN 50% F FLR SPACE IS CCUPIED PER A-1. = WHEN 50, 75 AND 100% F FLR SPACE IS CCUPIED AND H = 50' PER FlG. A-2. t = FR CLASS I FLAMMABLE PRDUCTS NLY. * = DES NT HAVE T BE CLASSIFIED IF PRB. FAC. IS 5 R LESS AND WELL MAINTAINED. # = CNSERVATIVE FR LW AND MD. PRESSURE. MAY BE LESS IF PUMP IS BRUSHED BY AIR?ft = 3 Hi FR INDRS; 2 Hi FR UTDRS

14 TABLE B DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN INSUFFICIENTLY VENTILATED INDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZEF SURCE F HAZARD SIZE F PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T B-1 B-2 B-3 PRCESS PLANT PRCESS PLANT PUMPHUSE LW/MD. HIGH AS INDICATED IN B-3 ENTIRE INDR LCATIN ENTIRE INDR LCATIN 5 V, 25 H, 3 Hi 25 V, 50 H 1 2 Hi IF HAZARD EXTENDS BEYND BUILDING 25 V, 100 H, 2 Hi IF HAZARD EXTENDS BEYND BUILDING ENTIRE INDR LCATIN YES * YES t YES t B-4 B-5 B-5 B-6 PUMPHUSE PUMPHUSE PUMPHUSE PUMPHUSE AND UP 201 AND UP 201 AND UP AS INDICATED IN B-4 MDERATE HIGH LW * ENTIRE INDR LCATIN ENTIRE INDR LCATIN ENTIRE INDR LCATIN 5 V, 25 H, 3 Hi 25/50 H, 2 Hi IF t HAZARD EXTENDS BEYND BUILDING 50 H, 2 Hi IF t HAZARDEXTENDS BEYND BUILDING 100 H, 2 Hi IF HAZARD EXTENDS BEYND BUILDING 5 V AND 5 H BEYND DIV. 1 ZNE YES t YES t YES t N * = FR MDERATE AND HIGH SYSTEM PRESSURE SEE TABLE IN B-6. = 50 H FR HP RANGE AND HIGH PRESSURE. t = NLY IF ENTIRE BLDG. IS CLASSIFIED, R HAZARD EXTENDS T BLDG. PENING, t = 2 Hi FR HP AND UP

15 TABLE C DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED UTDR LCATINS N. 1 N TYPE SURCE F HAZARD R LCATIN PRCESS PLANT SIZE F SURCE F HAZARD SIZE F PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY MD7HIGH DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV V H, 2 Hi ADDITINAL DANGER ZNES REFERT N 2 3 PUMPWELL LW 5 V 1 10 H 1 18 Hi N 3 4 PUMP STATIN UP T 51 LW/MD. 3 V, 10 H, 18 Hi N 4 4 PUMP STATIN UP T 51 HIGH 5 V, 15 H 1 18 Hi N 5 05 PUMP STATIN LW/MD. R HIGH 5 V, 25 H 1 2 Hi N 6 06 PUMP STATIN 201 AND UP MDERATE HIGHLYVLATILE 25 V 1 50 H 1 2 Hi N PUMP STATIN STRAGE TANKS PITS 201 AND UP MDERATE FLAMMABLE * = +50 H, 2 Hi WHEN PRESSURE HIGH AND QUANTITIES F VLATILE MATERIAL CULD BE RELEASED, t = FR HIGH AND LW PRESSURE SEE TABLE IN FIG C-6. LW 5 FT FIXED RF 10 FT FLAT RF ENTIRE LCATIN A AND C 5 V, 50 H 1 2 Hi 1FT ENTIRE LCATIN NLYWHEN VENTILATED N N N

16 TABLE C (Cont'd) DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED UTDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZE F SURCE F HAZARD SIZEF PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFERT 10 11* C-9 C-1 0 VALVE * PUMP STATIN STEAM TURBINE MD./HIGH HIGH 3R 5R 3R 5/1 0 V, 10/1 5 H, 18Hi 5 V, 25 H 1 2 Hi N N 12* C11 PUMP STATIN STEAM TURBINE MD./HIGH 3 V, 25 H 5 V, 25 H, 18Hi N 13 C-12 MARINE TERMINAL MDERATE AS INDICATED IN C-12 N C-1 3 C-1 4 CNTRL RM CNTRL RM x HIGH HIGH ' YES YES * = PERMANENT IGNITIN SURCE; C-10 EARLY IGNITIN, C-11 REMTE IGNITIN, t = REGUURLY PERATED R WRKED N, IF NT DIV. 1 = ; DIV. 2 = 3 V, 10 H, 18 Hi AND AS INDICATED IN C-9. = CLASSIFICATIN APPLIES T CNTRL RM. = NT VENTILATED; N ACCESS T HAZARDUS AREA, x = VENTILATED + SAFEGUARD; ACCESS T HAZARDUS AREA.

17 TABLE D DEGREE AND EXTENT F DANGER AREA FR PEN SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED INDR LCATINS N. N. TYPESURCE FHAZARDR LCATIN SlZEF SURCE F HAZARD SlZEF PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFERT D-2 D-3 DRUM FILLING PRCESS EQUIPMENT TESTING FACILITY R MINI " LW LW LW 3R AS INDICATED IN D-2 12" R LESS 5 V 1 10 H, 18 Hi t AS INDICATED IN D-2 ENTIRE INSIDE LCATIN N N N t «FLR SPACE IS FR INDIVIDUAL DRUMS * PRVIDED WITH FUME HD. TABLE E (SAME AS TABLE D, EXCEPT INSUFFICIENTLY VENTILATED) 1 E-1 DISPENSING AREA LW 5R ENTIREAREA N 2 E-2 PRCESS PLANT LW ENTIRE INDR LCATIN RSSVJ H, 2 Hi YES

18 TABLE F DEGREE AND EXTENT F DANGER AREA FR PEN SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED UTDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZE F SURCE F HAZARD SIZE F PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T 1 F-1 PEN TANK LW 5R 3V, 25 H, 3 Hi N 2 F-2 F-3 TANK FARM LW 5R 10 V, 10 H * N 3 F-4 IMPUNDING BASIN MINI VERY LW 15 H, 18Hi N 4 F-5 CNTRL RM J NNE N t * = FR F-3 ALL THE WAY UP T THE DIKES. t = NT VENTILATED; N ACCESS T HAZARDUS AREA, f = APPLIES T LCATIN WITH SURCE F HAZARD = CLASSIFICATIN APPLIES T CNTRL RM

19 TABLE G DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH LIGHTER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED INDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZE F SURCE F HAZARD SIZEF PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T 1 G-1 CMPRESSR STATIN R VAPR DENSITY BELW 0.75 ENTIRE INDR LCATIN N t 2 G-2 CNTRL-RM R VAPR DENSITY BELW 0.75 YES x 3 G-3 STRAGE AND PRCESSAREA MINI VAPR DENSITY BELW 0.75 ENTIRELY R PARTIALLY N = CLASSIFICATIN APPLIED T CNTRL RM. CNTRL RM HAS ACCESS T HAZARDUS LCATIN. VENTILATIN IN CNTRL RM PRVIDED WITH TYPE "B" SAFEGUARD. t = N; BECAUSE FRCED VENTILATRED X = YES; BECAUSE NT FRCED VENTILATED

20 TABLE H DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH LIGHTER THAN AIR GASES R VAPRS IN INSUFFICIENTLY VENTILATED INDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZEF SURCE F HAZARD SIZE F PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T H-1 H-2 H-3 H-4 H-5 H-6 H-7 CMPRESSR STATIN CMPRESSR STATIN CNTRL + RM CNTRL RM CNTRL RM CNTRL RM CMPRESSR STATIN * x R R R R AND ABVE 0-51 LW/MD. HIGH HIGH LW/MD. AS IN H-7 = CLASSIFICATIN APPLIES T CNTRL RM. t = APPLIES T LCATIN WITH SURCE F HAZARD. * = NT VENTILATED; N ACCESS T HAZARDUS AREA. = VENTILATED + SAFEGUARD; ACCESS T HAZARDUS AREA, x = VENTILATED; ACCESS T HAZARDUS AREA. + = VENTILATED + SAFEGUARD. ENTIRE UPPER PART ENTIRE INDR LCATIN 15 H MIN.+ UPPER PART V UP T DIV. 1 15H ENTIRE INDR * LCATIN * UPTBUILDING WALLS YES RF YES YES t YES t YES t YES t N

21 TABLE I DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH LIGHTER THAN AIR GASES R VAPRS IN SUFFICIENTLY VENTILATED UTDR LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZE F SURCE F HAZARD SIZE F PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFERT CMPRESSR STATIN UP T 51 HIGH 15 V 15 H N I-2 CMPRESSR STATIN CMPRESSR STATIN UP T 51 LW/MD. R HIGH LW/MD. 25 V, 25 H 10 V 1 10 H N N 4 I-2 CMPRESSR STATIN UP T 51 HIGH 15V.15H N 5 I-3 HYDRGEN GAS STRAGE MINI 25 V, 25 H N 6 7 I-4 I-5 CMPRESSR STATIN CNTRL RM * R 0-51 LW/MD. VAPR DENSITY BELW 0.75 ENTIRE UPPER PART 15 H LWER PART N YES t - CLASSIFICATIN APPLIES T CNTRL RM. t = APPLIES T LCATIN WITH SURCE F HAZARD. * = NT VENTILATED; BELW HAZARDUS AREA; VD IS < = 15 H WHEN N BSTRUCTIN AGAINST AIR FLW.

22 TABLE J DEGREE AND EXTENT F DANGER AREA FR PEN R CLSED SURCES F HAZARD WITH HEAVIER R LIGHTER THAN AIR GASES R VAPRS IN SUFFICIENTLY R INSUFFICIENTLY VENTILATED LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZEF SURCE F HAZARD SIZEF PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T 1 J-1A PIT ANY SIZE ENTIRE PIT t 2 J-1B PIT ANY SIZE NNHARZARDUS 3 4 J-2 J-3A LADING/ UNLADING PUMPHUSE ANY SIZE SEETABLE J-2 SEETABLE J-2 ENTIRE * LCATIN SEETABLE J-2 YES 5 J-3B PUMPHUSE ANY SIZE ENTIRE LCATIN t YES 6 7 J-4 J-5 CYLINDERS ACCESSTA DIV. 2 BUNDARY 201 HP ANDUP SAFE DISTANCE FR LP GAS AS INDICATED IN J-4 BUILDING "A" DIV. 2 YES x 8 J-5 ACCESSTA DIV. 2 BUNDARY 201 HP ANDUP BUILDING "B" N.H. YES x * = NT SUFFICIENTLY VENTILATED. t = ALS SEE C-8. t = SUFFICIENTLY VENTILATED, x = APPLIES T SURCE F HAZARD.

23 TABLE J (CNT.) DEGREE AND EXTENT F DANGER AREA FR PEN R CLSED SURCES F HAZARD WITH HEAVIER R LIGHTER THAN AIR GASES R VAPRS IN SUFFICIENTLY R INSUFFICIENTLY VENTILATED LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZEF SURCE F HAZARD SIZEF PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFER T 9 J-6 PIPING SYSTEM MINI LW, MD. R HIGH SEETABLE IN J J-7 J-8 J-9 BRUSHING/ NNBRUSHING AIR PRCESS PLANT SAFE DISTANCES FR PRCESS PLANT * R LW, MD. R HIGH LW, MD. R HIGH INLET AS SHWN IN J-8 LG. 1=3 FEET LC.2 = 5FEET UTLET 3 RA R 5 RA N N J-10 J-11 LW AND HIGH INTEGRITY SEAL FITTINGS SAFE DISTANCES FR H2 GAS UTDRS MINI MINI LW, MD. R HIGH LWR HIGH SEE J-6 * FR FLAMMABLE GAS RELEASED T THE UTDRS.

24 TABLE K DEGREE AND EXTENT F DANGER AREA FR CLSED SURCES F HAZARD WITH HEAVIER THAN AIR GASES R VAPRS IN SUFFICIENTLY R INSUFFICIENTLY VENTILATED LCATINS N. N. TYPE SURCE F HAZARD R LCATIN SIZEF SURCE F HAZARD SIZE F PUMP DRIVER IN H.P. SYSTEM PRESSURE R DENSITY DEGREEANDEXTENTF HAZARD IN LCATIN DIV. 1 DIV. 2 ADDITINAL DANGER ZNES REFERT 1 2 K-1 K-2 PIPING SYSTEM PIPING SYSTEM SEE K-1 SEE K-2 SEE K-1 SEE K-2 SEETABLE IN K-1 SEETABLE IN K-2 SEETABLE IN K-1 SEETABLE IN K-2

25 TABLE 1-5 SURCES F HAZARD FR LIGHTER AND HEAVIER THAN AIR FLAMMABLE SUBSTANCES N. TYPEF SURCE F HAZARD LCATIN DEGREE AND EXTENT F HAZARD 1 AIRUTLET 1 FRCEDAIR PEN SURCE F HAZARD VD = >0.75 UTDRS DIV. 1,3' RA + DIV. 2, 2' RA BEYND, DIV. 1 EXTENDING 10 H AT FLR FRM DlV. 1 2 AIR UTLET, FRCED AIR PEN SURCE F HAZARD VD =>0.75 UTDRS DIV. 1,5' RA + DIV. 2, 5 1 RA BEYND DIV. 1 EXTENDING 25 H AT FLR FRM DIV. 1 3 AIRUTLET 1 FRCEDAIR CLSEDSURCEF HAZARD VD = >0.75 UTDRS DIV. 2, 3' RA EXTENDING 10 H AT FLR FRM 3 RA 4 AIRUTLET 1 FRCEDAIR CLSED SURCE F HAZARD VD = >0.75 UTDRS DIV. 2, 5 RA EXTENDING 25 H AT FLR FRM 5 RA 5 AIR UTLET, FRCED AIR CLSEDSURCEF HAZARD VD = <0.75 UTDRS DIV. 2, 3 RA 6 AIR UTLET, FRCED AIR CLSEDSURCEF HAZARD VD = <0.75 UTDRS DIV. 2, 5 RA 7 BLEEDERS AND DRAIN VALVES UTDRS DIV. 2, 5' RA. UTDR LCATINS ARE SUFFICIENTLY VENTILATED

26 TABLE 1-5 SURCES F HAZARD FR LIGHTER AND HEAVIER THAN AIR FLAMMABLE SUBSTANCES N. TYPEF SURCEF HAZARD LCATIN DEGREEAND EXTENT F HAZARD 8 DRAINS, PEN T CLLECT AND REMVE FLAMMABLE LIQUIDS UTDRS Dl V. 2, 18" H, 18" V ABVE GRADE DIV. 1 BELW GRADE 9 DRAINS, PEN T CLLECT AND REMVE FLAMMABLE LIQUIDS INDRS DIV. 2, 18" H, 18" V ABVE GRADE DIV. 1 BELW GRADE 10 ENGINES RUNNING N DIESEL FUEL INDRS * NN HAZARDUS 11 FLARE UTDRS NN HAZARDUS 12 FLWING WELL WITHUT CELLAR UTDRS DIV. 2, 5 RA 13 FUME HD, FAN IN WALL PEN SURCE F HAZARD VD = >0.75 UTDRS DIV. 1, 5' RA + DIV. 2, 5' RA BEYND DIV.!,EXTENDING 25' H AT FLR FRM DIV. 1 t 14 FUME HD, FAN IN WALL, PEN SURCE F HAZARD VD = >0.75 UTDRS DIV. 1, 3 1 RA + DIV. 2, 2' RA BEYND DIV. 1,EXTENDINGI 1 H AT FLR FRM DIV. 1 ' UTDR LCATINS ARE SUFFICIENTLY VENTILATED INDR LCATINS ARE NT SUFFICIENTLY VENTILATED UNLESS MARKED BY * t APPLIESTFAN

27 TABLE 1-5 (CNT.) SURCES F HAZARD FR LIGHTER AND HEAVIER THAN AIR FLAMMABLE SUBSTANCES N. TYPEF SURCEF HAZARD LCATIN DEGREEAND EXTENT F HAZARD 15 FUME HD, FAN IN WALL, CLSEDSURCEF HAZARD VD = >0.75 UTDRS DIV. 2, 5' RA EXTENDING 25' HRIZNTALLYATFLR FRMWALL t 16 FUME HD, FAN IN WALL, CLSEDSURCEF HAZARD VD = >0.75 UTDRS DIV. 2, 3' RA EXTENDING 10' HRIZNTALLYATFLR FRM WALL t 17 FUME HD, FAN IN RF, CLSEDSURCEF HAZARD VD = <0.75 UTDRS DIV. 2, 5' RA t 18 FUME HD, FAN IN RF, CLSEDSURCEF HAZARD VD = <0.75 UTDRS DIV. 2, 3' RA t 19 GAS PERATED PNEUMATIC INSTRUMENTS FR HYDR- CARBN SERVICE FLW, PRESSUREANDCNTRL UTDRS Dl V. 1,1 8" RA + DIV. 2 18" RA BEYND DIV GAS PERATED INSTRUMENTS SAME AS IN 19 INDRS * DIV. 2 ENTIRE LCATIN VENTED SAME AS IN GAS PERATED INSTRUMENTS SAME AS IN 19 INDRS DIV. 1 ENTIRE LCATIN UTDR LCATINS ARE SUFFICIENTLY VENTILATED INDR LCATINS ARE NT SUFFICIENTLY VENTILATED UNLESS MARKED BY * t APPLIESTFAN

28 TABLE 1-5 (CNT.) SURCES F HAZARD FR LIGHTER AND HEAVIER THAN AIR FLAMMABLE SUBSTANCES N. TYPEF SURCE F HAZARD LCATIN DEGREE AND EXTENT F HAZARD 22 GASLINE DISPENSING SERVICE STATIN UTDRS DIV. 2, 18" H ' H, 18" HI 23 HYDRCARBN PRESSURE VESSEL UTDRS DIV. 2, 10 RA 24 HYDRGEN GAS STRAGE CYLINDER LESS THAN 400 CF UTDRS DIV. 2, 5' RA BELW DEMARCATIN LINE, 15 FT ABVE DEMARCATIN LINE 25 HYDRGEN GAS STRAGE CYLINDERS MRE THAN 400 CF UTDRS DIV FT WITHUT BSTRUCTIN 25 FT WITH BSTRUCTIN 26 HEADER (MANIFLD) INDRS * DIV. 2 ENTIRE LCATIN 27 INJECTINWELL UTDRS DIV. 2, 5' RA 28 IMPUNDING BASIN UTDRS DIV. 2, 15' H, 18" HI UTDR LCATINS ARE SUFFICIENTLY VENTILATED INDR LCATINS ARE NT SUFFICIENTLY VENTILATED UNLESS MARKED BY *

29 TABLE 1-5 (CNT.) SURCES F HAZARD FR LIGHTER AND HEAVIER THAN AIR FLAMMABLE SUBSTANCES N. TYPE F SURCEF HAZARD LCATIN DEGREEAND EXTENT FHAZARD 29 IL WATER SEPARATR UTDRS CLASSIFICATINSAMEAS PITWITHUTMECHANICAL VENTILATIN. HEAVIER THAN AIR FLAMMABLE VAPRS UTDRS DIV. 1,ENTIREPIT 31 PITWITHMECHANICAL VENTILATIN. HEAVIER THAN AIR FLAMMABLE VAPRS UTDRS DIV. 2, ENTIRE PIT 32 PIT NT WITHIN HAZARDUS LCATIN, CNTAINING PIPING, FITTINGS, VALVES, etc. UTDRS DIV. 1,ENTIRE PIT 33 PIPING SYSTEM WITH VALVES, FLANGES, FITTINGS FR FLAMMABLE LIQUID INDRS UTDRS SEE FIG K1 AND K2 34 PRTABLE CNTAINERS FR CLASS I FLAMMABLE LIQUID IN RM WITH N EXTERNAL WALLS INDRS * DIV. 2, ENTIRE RM 35 PRESSURERELIEFVALVE. LIGHTER R HEAVIER THAN AIRVAPRS. UTDRS Dl V. 2, 10' RA UTDR LCATINS ARE SUFFICIENTLY VENTILATED INDR LCATINS ARE NT SUFFICIENTLY VENTILATED UNLESS MARKED BY *

30 TABLE 1-5 (CNT.) SURCES F HAZARD FR LIGHTER AND HEAVIER THAN AIR FLAMMABLE SUBSTANCES N. TYPEF SURCEF HAZARD LCATIN DEGREEAND EXTENT F HAZARD 36 RECEIVER FUMMABLE LIQUID UTDRS Dl V. 1,5' RA + DIV. 2, 10' RA BEYND DIV SUMP, PEN T CLLECT AND CNTAIN FLAMMABLE LIQUIDS UTDRS DIV H, 1 1 V ABVE GRADE DIV. 1 BELW GRADE 38 SUMP, PEN T CLLECTANDCNTAIN FLAMMABLE LIQUIDS INDRS DIV.!,ENTIRE LCATIN 39 STRAGETANKFR DIESEL FUEL UTDRS NN HAZARDUS 40 VENTS, ATMSPHERIC TANK VENTS R BUILDING VENTS FR HEAVIER THAN AIR PRDUCTS UTDRS DIV. 1,5' RA + DIV. 2, 5' RA BEYND DIV VENT, ATMSPHERIC HEAVIER THAN AIR VAPRS FR STRAGETANKS UTDRS DIV. 1,5' RA + DIV. 2, 5' RA BEYND DIV VENT, ATMSPHERIC HEAVIER THAN AIR VAPRS FR STRAGETANKS UTDRS DIV. 1,3' RA + DIV. 2, 2' RA BEYND DIV VENT, ATMSPHERIC HEAVIER AND LIGHTER THAN AIR VAPRS FR MINI INSTRUMENTS AND CNTRLS UTDRS Dl V. 1 18" H + DIV. 2, 18" RA BEYND DIV. 1 UTDR LCATINS ARE SUFFICIENTLY VENTILATED INDR LCATINS ARE NT SUFFICIENTLY VENTILATED UNLESS MARKED BY *

31 in Fig 1-5 has a surface temperature in excess of the ignition temperature of the flammable product and is, therefore, considered a "remote permanent ignition source." The equivalent HP rating of the steam driven pump Pl is 50 HP. Pumps Pl, P2 and P3 are small pumps operating at high pressure and driven by 50 HP electric motors. Pumps P4 and P5 are large, operating at moderate pressure and driven by electric motors of 250 HP. Determine for each individual pump the recommended boundary distance. The boundary distance is influenced by the size of the pump and the pressure in the system. Since the pumps are located in an outdoor area refer to Fig 1-2 for the required boundary distance. Select in Fig 1-2 the recommended boundary distance for the particular pump driver on the basis of size, HP rating of electric motor and pressure in the system. According to Fig 1-2B the recommended horizontal boundary distance for Pumps Pl, P2 and P3 is 15 feet, and for Pumps P4 and P5, 50 feet. Since the permanent ignition source "a" in Fig 1-5 is within the 15 and 50 feet horizontal boundary distance of Pumps Pl, P2 and P4, the area between the ignition source and Pumps Pl, P2 and P4 must be classified Div. 1. The area in opposite direction of Pump P4, also 50 feet long, is allowed to be classified Div. 2. Since the actual distance between P3 and the ignition source "a" is longer than 15 feet, the area between Pump P3 and the ignition source need not be classified Div. 1. However, since Pump P3 is within the 50 feet Div. 1 zone of Pump P4, the area between Pump P3 and the ignition source automatically becomes Div. 1. The required 50 feet horizontal boundary for Pump P5 does not reach the permanent ignition source "a." Because of this, the area surrounding Pump P5 is not required to be classified Div. 1, but must be classified Div. 2 in compliance with Item 3 of Table 1-4. (Fig C-6 in Table "C," item 7). Since Div. 1 zones normally do not directly border to a nonhazardous area, a Div. 2, 5 feet wide transition zone is required between the Div. 1 zone and the nonhazardous area. The breakdown of Pump Pl, however, could cause early ignition of the flammable vapors released. If early ignition is possible, the Div. 1 area surrounding Pump Pl does not have to be 15 feet, but should be reduced to 3 feet without a Div. 2 transition zone. F. The Extent of Explosion Danger for Class n Flammable Products As pointed out previously, the required extent of explosion danger for locations storing, handling, and/or processing Class I flammable products can be obtained directly from Tables 1-4 and 1-5. These tables may also be used for Class II flammable products. However, bear in mind that the recommended hazardous areas in these tables are prepared exclusively for Class I flammable products because of their large vapor traveling distances, and not for Class II flammable products, which

32 generally have shorter vapor traveling distances. Although the vapor traveling distances for Class II flammable products are generally shorter, it is very convenient to apply Tables 1-4 and 1-5 for Class II flammable products. Greater safety is achieved by applying the larger areas. However, the larger areas for Class II flammable products of course are not the most economical. For additional feet of area, electrical equipment needs to be adequate. If for economical reasons or any other reason, smaller hazardous areas for Class II flammable products are preferred, the following steps are to be followed to establish the proper dimensions for these Class II flammable products. First, assume that the location under consideration does not contain a Class II flammable product, but a Class I flammable product. This is necessary to obtain the required area size for the Class I product which later must be reduced to suit the Class II flammable product. Second, the actual operating temperature of the Class II flammable product must be used for the Class I product. This is necessary to obtain vapor pressure of the Class I flammable product, which must be used to determine the required area size for the Class II product. Third, find in Fig 1-6 the vapor pressure for the Class I flammable product based on a 100% flash point, and the actual operating temperature of the Class II flammable product. Fig 1-6 shows flash points, operating temperatures and vapor pressures for Class I, Class II and Class III flammable products. Class III flammable products however are not considered. Next find in Fig 1-6 the vapor pressure for the Class II flammable product at its original flashpoint. Finally, establish the inverse ratio of both vapor pressures. This ratio is a measure for the actual boundary size for the class II flammable product. For example, assume a closed source of hazard containing a Class II flammable liquid has a flashpoint of F. Assume that the operating temperature of the Class II flammable product is 20 0 F. Consider the same source of hazard, processing a Class I flammable product, also operating at a temperature of 20 0 F. Find from Table 1-4 or Table 1-5, the required horizontal boundary distance for the Class I flammable product. Say the required boundary distance is 25 feet. From Fig 1-6 find the vapor pressure for the Class I flammable product at 10 0 F flashpoint by starting at the bottom of Fig 1-6 at 10 0 F flashpoint. Go straight up until the vertical line is intersected by the 20 0 F line and read at the left border line the vapor pressure for the Class I flammable product, which is.13 atmosphere. The vapor pressure for the Class II flammable product is found in the same manner, except start in Fig 1-6 at the original flashpoint for the Class II flammable product, which is F. Go straight up until the vertical line is intersected by the 20 0 F line, and read at the left border line the vapor pressure for the class II flammable product which is atmosphere. The inverse ratio of the two vapor pressures is Multiply the 25 feet

33 CLASSI PRDUCTS CLASS Il PRDUCTS CLASS III PRDUCTS FLASHPINTS AT DEGREES F TEMPERATURE VERSUS VAPR PRESSURE FR FLAMMABLE LIQUIDS

34 boundary for the Class I flammable product by 0.27 which equals to 6.7 feet. Boundary sizes are standardized in 3, 5, 10, 15, 50 and 100 feet. Take the next higher size above 6.76 feet. The boundary size required for the Class II flammable product is then 10 feet. Since the source of hazard is closed, and if it is assumed to be in a sufficiently ventilated location, the 10 foot size needs only to be classified Div. 2. If cost of the electrical installation for the Div. 2 area is a major consideration, 10 feet is a valid size. If cost has little impact on the hazardous area, then the 25 foot size should be applied. G. Transition Zones for NEC Class I Locations As previously pointed out, the size of a hazardous area is established on the basis of the horizontal distance a flammable gas or vapor in the air must travel to reach safe concentrations. Traveling distances are established by analysis, test and experiments. The traveling distance, however, is influenced by the quantity of flammable gases or vapors released into the atmosphere. Large quantities of flammable gases or vapors released into the atmosphere have the tendency to travel long distances before reaching safe concentrations, causing the point of safe concentration to shift farther away from the point of release. Small quantities of flammable gases or vapors in the air have the tendency to travel short distances before reaching safe concentrations. This brings the point of safe concentration closer to the point of release. Traveling distances, therefore, may have different sizes before reaching safe concentrations. They may be short or long, depending on the conditions under which a flammable gas or vapor is released into the atmosphere. To apply a hazardous area safely, the size of the hazardous area must match each individual distance a flammable gas or vapor will travel to reach safe concentrations. Because of the many conditions under which a flammable product can be released into the atmosphere, a great number of hazardous area sizes are required to cover each individual traveling distance. However, too many hazardous area sizes will cause confusion and makes the application too elaborate. To simplify the application of hazardous areas, the traveling distances are divided into groups based on specific conditions, whereas each group is assigned one specific hazardous area size. This reduces the number of hazardous area sizes and simplifies the application considerably. f course the size of the hazardous area selected for a particular group must match the longest traveling distance in that group. Since each selected hazardous area will cover a number of traveling distances of different sizes, the result is that the hazardous area in some cases may be too long, and in other cases, just right. To even further simplify the application of the hazardous areas, the groups are associated with a specific quantity of flammable gases or vapors released to

SECTION 2 APPLICATION OF FUNDAMENTALS

SECTION 2 APPLICATION OF FUNDAMENTALS SECTION 2 APPLICATION FUNDAMENTALS ENVIRONMENTAL CONDITIONS IN NEC CLASS I HAZARDOUS LOCATIONS Section II covers a great number of illustrations which can be applied directly to a hazardous area under

More information

2.9 GENERAL REQUIREMENTS FOR GROUP I

2.9 GENERAL REQUIREMENTS FOR GROUP I 2.9 GENERAL REQUIREMENTS FOR GROUP I Group I represents closed sources of hazard that contain Class I flammable products with lighter-than-air gases or vapors located outdoors that are sufficiently ventilated

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 12 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

CHAPTER 6 VENTILATION REQUIREMENTS

CHAPTER 6 VENTILATION REQUIREMENTS CHAPTER 6 VENTILATION REQUIREMENTS A. General When there is no air movement, a flammable gas or vapor released to the atmosphere will spread in all directions. With air movement, the flammable gas or vapor

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124 Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124 13.7 Pressure Equipment Directive (PED) 97/23/EC 1 The Pressure Equipment Directive (PED) 97/23/EC applies to the design, manufacturing and conformity

More information

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES M. R. Marshall* and P. L. Stewart-Darling* A simple mathematical model for the buoyancy driven ventilation of an enclosed space, using a two-pipe

More information

Gema s OptiColor System

Gema s OptiColor System Gema s OptiClr System The Gema OptiClr system is a simple, lw cst quick clr change slutin fr manual gun users that have multiple hppers set up t spray varius clrs. The OptiClr Manifld allws the user t

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Dean Pump Self-Priming Chemical Process Pumps

Dean Pump Self-Priming Chemical Process Pumps Bulletin C 1.2.34.7 Dean Pump Self-Priming Chemical Process Pumps php Series HEAD CAPACITY RANGE CHARTS php Self Primer - 2 Pole 3500 RPM 500 CAPACITY M 3 /HR 2900 RPM 50 HERTZ 25 50 75 125 150 400 TOTAL

More information

Title of Paper Interpretation of IP15 in Process Plant Design: a Commonsense Approach ---------------------------------------------------------------------------------------------------------------------------

More information

When you complete this module you will be able to: Describe procedures needed to enter into, or work safely in confined spaces.

When you complete this module you will be able to: Describe procedures needed to enter into, or work safely in confined spaces. Confined Space Entry Learning Outcome When you complete this module you will be able to: Describe procedures needed to enter into, or work safely in confined spaces. Learning Objectives Here is what you

More information

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks 1. Scope This document describes procedures for determining or confirming the fill condition of

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Electrical Equipment

More information

UTAS EH&S INSTRUCTION No. 036 June 2012 Revision No. 3. Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard)

UTAS EH&S INSTRUCTION No. 036 June 2012 Revision No. 3. Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard) Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard) APPLICABILITY: This EH&S Instruction applies to UTAS sites worldwide, including contractors working at UTAS facilities. The document

More information

Material Safety Data Sheet " Paving Grade Bitumen"

Material Safety Data Sheet  Paving Grade Bitumen Material Safety Data Sheet Page 1 f 6 Sectin 1 : Prduct and Cmpany Identificatin Prduct Name: Supplier: 40-50, 60-70, 80-100 and ther Penetratin Grade Bitumen MTA Updated: 26 April 2016 CAS Number: Mixture

More information

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS. A high-capacity EBA system [CSVS] [main purge]

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS. A high-capacity EBA system [CSVS] [main purge] PAGE : 1 / 9 5. CONTAINMENT PURGE (EBA [CSVS]) The Reactor Building purge system comprises the following: A high-capacity EBA system [CSVS] [main purge] A low-capacity EBA system [CSVS] [mini-purge] 5.1.

More information

Identification and Screening of Scenarios for LOPA. Ken First Dow Chemical Company Midland, MI

Identification and Screening of Scenarios for LOPA. Ken First Dow Chemical Company Midland, MI Identification and Screening of Scenarios for LOPA Ken First Dow Chemical Company Midland, MI 1 Layers of Protection Analysis (LOPA) LOPA is a semi-quantitative tool for analyzing and assessing risk. The

More information

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners BULLETIN MT2035-07/05 Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners M/MR Series M411, M511, M611 M420, M520, M620, MR410, MR510, MR610 MR212D, MR212E, MR212G and MR212J (Flanged),

More information

Air Operated Hydraulic Pumping Systems to 50,000 psi

Air Operated Hydraulic Pumping Systems to 50,000 psi High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air

More information

PENBERTHY SERIES LM, ELL, FL, GL, GH, U, L AND 2NC FOR PUMPING GASES

PENBERTHY SERIES LM, ELL, FL, GL, GH, U, L AND 2NC FOR PUMPING GASES Practical, simple and cost-effective alternatives for process industries to purge gases from chambers, exhaust, evacuate or prime using liquid, steam or air operating media FEATURES Simple design with

More information

SAFETY MANUAL PURGING, VENTING & DRAINING PROCEDURE TABLE OF CONTENTS 1. INTRODUCTION SCOPE DEFINITIONS PROCEDURE...

SAFETY MANUAL PURGING, VENTING & DRAINING PROCEDURE TABLE OF CONTENTS 1. INTRODUCTION SCOPE DEFINITIONS PROCEDURE... Page 1 of 11 TABLE OF CONTENTS 1. INTRODUCTION... 2 2. SCOPE... 2 3. DEFINITIONS... 2 4.... 3 5. RESPONSIBILTIES... 10 6. REFERENCES... 10 7. ATTACHMENTS... 11 8. APPENDICES... 11 Rev. Issue Date Amendment

More information

1.2.7 Hazard Communication

1.2.7 Hazard Communication 1.2.7 Hazard Communication YOUR ORGANIZATION STANDARD OPERATING PROCEDURES/GUIDELINES TITLE: Hazard Communication NUMBER: 1.2.7 PREPARED BY: SECTION/TOPIC: Member Health and Assistance Programs ISSUE DATE:

More information

Becker* Products Below Ground Ball Valve Regulators

Becker* Products Below Ground Ball Valve Regulators GE Oil & Gas Becker* Products Below Ground Ball Valve Regulators Reduce Noise Levels at Large Volume Regulator Stations GE s Becker* Below Ground ball valve regulator has the long-term proven reliability,

More information

Simplicity in VRU by using a Beam Gas Compressor

Simplicity in VRU by using a Beam Gas Compressor Simplicity in VRU by using a Beam Gas Compressor By Charlie D. McCoy and Mark Lancaster Abstract: Vapor Recovery Units are often expensive, complicated to operate and unable to deal with High H2S and liquids.

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES s of the IGF Code CONTENTS GF1 Test for gas fuel tank s high level alarm Rev.1 July 2017 GF2 Ship Steel Protection against Liquefied Gas Fuel (Part

More information

pumping gases JET PUMP TECHNICAL DATA

pumping gases JET PUMP TECHNICAL DATA Section 1000 Bulletin 100 Issued 9/87 Replaces 7/84 JET PUMP TECHNICAL DATA pumping gases This technical bulletin includes general information about Penberthy Jet Pumps plus specific details for selecting

More information

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels Inerting Control Systems by NTRON PROCESS ANALYZER DIVISION of NEUTRONICS INC. EXTON. PA. 19341 RJN Rev. A June 2001 Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert

More information

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces 1. SCOPE This document now includes provision for safe access to cable tunnels and culverts previously covered in PSSI 37 which is now withdrawn. The term Confined Space is defined in the Confined Spaces

More information

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION Jeff Strath Principal Engineer Paterson Flood Engineers Pty Ltd www.pfe.com.au INTRODUCTION This presentation provides an overview

More information

Challenges in Relief Design for Pilot Plants

Challenges in Relief Design for Pilot Plants Challenges in Relief Design for Pilot Plants Published on July 5, 2017 Michael Trainor Relief system design at the pilot scale presents unique challenges that don t always apply at the commercial scale.

More information

Installation of Ballast Water Management Systems

Installation of Ballast Water Management Systems (Sept 2015) (Rev.1 May 2016) Installation of Ballast Water Management Systems 1. Application In addition to the requirements contained in BWM Convention (2004), the following requirements are applied to

More information

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65 Data Sheet 819346-02 Issue Date: 05/17 Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300, 50, 65 UNA 45hl MAX, UNA 46hl MAX, UNA 46Ahl MAX UNA 45v MAX with cover for mounting electrode

More information

Confined Space Entry

Confined Space Entry Confined Space Entry Purpose The purpose of this document is to establish methods to identify confined spaces, classify them according to their risks, and establish guidelines necessary for the safe preparation,

More information

Responding to Natural Gas Pipeline Emergencies

Responding to Natural Gas Pipeline Emergencies Responding to Natural Gas Pipeline Emergencies Who is Florida Gas Transmission? Florida Gas Transmission operates nearly 5,000-miles of interstate natural gas transmission pipelines, a system that extends

More information

Applied Fluid Mechanics

Applied Fluid Mechanics Applied Fluid Mechanics 1. The Nature of Fluid and the Study of Fluid Mechanics 2. Viscosity of Fluid 3. Pressure Measurement 4. Forces Due to Static Fluid 5. Buoyancy and Stability 6. Flow of Fluid and

More information

API RECOMMENDED PRACTICE 500 THIRD EDITION, DECEMBER 2012 ERRATA, JANUARY 2014

API RECOMMENDED PRACTICE 500 THIRD EDITION, DECEMBER 2012 ERRATA, JANUARY 2014 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2 API RECOMMENDED PRACTICE 500 THIRD EDITION, DECEMBER

More information

Welding, Cutting, and Brazing

Welding, Cutting, and Brazing Welding, Cutting, and Brazing Hazards of Welding Operations Fire hazards Metal splatter Electric shock Explosion hazards Released gases Radiant energy Where would these hazards be found on oil and gas

More information

TABLE OF CONTENTS PART 2 - CONFINED SPACES

TABLE OF CONTENTS PART 2 - CONFINED SPACES May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3

More information

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the 1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method

More information

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3, 4, 6 Data Sheet 819584-00 Issue Date: 01/17 Ball Float Steam Trap UNA 43 PN 16/C 125/JIS 10K UNA 46 PN 40/C 150/C 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6" UNA 43 hl, UNA 46 hl UNA 43 v, UNA 46 v with

More information

Compressors. Basic Classification and design overview

Compressors. Basic Classification and design overview Compressors Basic Classification and design overview What are compressors? Compressors are mechanical devices that compresses gases. It is widely used in industries and has various applications How they

More information

FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering

FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering Fluid Mechanics is the branch of physics that studies fluids (liquids, gases, and plasmas) and the forces on them. Fluid

More information

Flammability Chart. Gas Formula Ignition

Flammability Chart. Gas Formula Ignition Leak Detection 101 Investigating a leak is simplified if you know the basics. By J. Scott Kleppe Sensit (J and N Enterprises, Inc.) Every day new gas services are added to provide economical energy to

More information

Pressure Systems Safety Regulation

Pressure Systems Safety Regulation Pressure Systems Safety Regulation Introduction This document informs Faculty of the key requirements of the UK and Chinese Pressure Systems Safety regulations. The aim of these regulations is to prevent

More information

PROCESS ROTATING EQUIPMENT (CENTRIFUGAL PUMPS )

PROCESS ROTATING EQUIPMENT (CENTRIFUGAL PUMPS ) PROCESS ROTATING EQUIPMENT ( ) Slide No: ١ Pumps can be divided into two main groups: Displacement pumps Dynamic pumps Slide No: ٢ Slide No: ٣ Slide No: ٤ Slide No: ٥ BASIC CENTRIFUGAL PUMP PARTS Casing

More information

Confined Space Entry

Confined Space Entry Confined Space Entry Purpose The purpose of this chapter is to establish methods to identify confined spaces, classify them according to their risks, and establish guidelines necessary for the safe preparation,

More information

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS SEC Project No. 1803007-000 November 20, 2006 TABLE OF CONTENTS I. ABSTRACT...1 II. INTRODUCTION...1 III. HISTORY...2 IV. VARIABLE SPEED

More information

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap 1250650/6 IM-P125-07 ST Issue 6 MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation

More information

Hazardous (Classified) Locations

Hazardous (Classified) Locations Hazardous (Classified) Locations Presented by: John Chambers UL HazLoc operations Presented at: Safety & You in 2002 2002 Safety Conference Flexible Packaging Association (FPA) 1 AREA CLASSIFICATIONS Class

More information

Features. General application. Technical data

Features. General application. Technical data Practical, simple and cost-effective alternatives for process industries to purge gases from chambers, exhaust, evacuate or prime using liquid, steam or air operating media Features Simple design with

More information

Scope: This plan applies to all personnel, including contractors, who enter or work in confined spaces, or supervise such activities.

Scope: This plan applies to all personnel, including contractors, who enter or work in confined spaces, or supervise such activities. 11/13/1995 4 5/20/2013 1 of 10 Authority and Scope Regulation: 29 CFR 1910.146 Scope: This plan applies to all personnel, including contractors, who enter or work in confined spaces, or supervise such

More information

ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994

ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994 ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor any part of this

More information

and its weight (in newtons) when located on a planet with an acceleration of gravity equal to 4.0 ft/s 2.

and its weight (in newtons) when located on a planet with an acceleration of gravity equal to 4.0 ft/s 2. 1.26. A certain object weighs 300 N at the earth's surface. Determine the mass of the object (in kilograms) and its weight (in newtons) when located on a planet with an acceleration of gravity equal to

More information

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps Exercise 4-2 Centrifugal Pumps EXERCISE OBJECTIVE Familiarize yourself with the basics of liquid pumps, specifically with the basics of centrifugal pumps. DISCUSSION OUTLINE The Discussion of this exercise

More information

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners M/MR Modulating Valves design certified For Atmospheric, Infrared, and Direct Fired urners TALE OF CONTENTS Description/Specifications... 1 Introduction... 2 Direct Fired Applications (Negative Pressure)...

More information

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances. CLASS Third Units PURE SUBSTANCE Pure substance: A substance that has a fixed chemical composition throughout. Air is a mixture of several gases, but it is considered to be a pure substance. Nitrogen and

More information

Fundamentals of Compressed Air Systems. Pre-Workshop Assignment

Fundamentals of Compressed Air Systems. Pre-Workshop Assignment Page 1 In order to ensure that the Compressed Air Challenge Fundamentals of Compressed Air Systems Training is most useful to you, it will be important for you to bring information about your plant s compressed

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

NOTES ON WATER HAMMER. 55

NOTES ON WATER HAMMER. 55 NOTES ON WATER HAMMER. 55 NOTES ON WATER HAMMER. By A. B. Robison. When the flow conditions of a liquid in a pipe line are varied by the opening or closing of a valve or the equivalent, a change in the

More information

QUANTIFYING THE TOLERABILITY OF POTENTIAL IGNITION SOURCES FROM UNCERTIFIED MECHANICAL EQUIPMENT INSTALLED IN HAZARDOUS AREAS

QUANTIFYING THE TOLERABILITY OF POTENTIAL IGNITION SOURCES FROM UNCERTIFIED MECHANICAL EQUIPMENT INSTALLED IN HAZARDOUS AREAS QUANTIFYING THE TOLERABILITY OF POTENTIAL IGNITION SOURCES FROM UNCERTIFIED MECHANICAL EQUIPMENT INSTALLED IN HAZARDOUS AREAS Steve Sherwen Senior Consultant, ABB Engineering Services, Daresbury Park,

More information

Fume Hood User Guidelines

Fume Hood User Guidelines Fume Hd User Guidelines 1. Intrductin A fume hd cabinet is an enclsed wrking chamber fitted with an exhaust ventilatin system. The primary functin f the fume hd cabinet is t prtect individuals wrking with

More information

Example: 25 C = ( ) K = 298 K. Pressure Symbol: p Units: force per area 1Pa (Pascal) = 1 N/m 2

Example: 25 C = ( ) K = 298 K. Pressure Symbol: p Units: force per area 1Pa (Pascal) = 1 N/m 2 Chapter 6: Gases 6.1 Measurements on Gases MH5, Chapter 5.1 Let s look at a certain amount of gas, i.e. trapped inside a balloon. To completely describe the state of this gas one has to specify the following

More information

HIGH FLOW PROTECTION FOR VARIABLE SPEED PUMPS

HIGH FLOW PROTECTION FOR VARIABLE SPEED PUMPS Proceedings of the First Middle East Turbomachinery Symposium February 13-16, 2011, Doha, Qatar HIGH FLOW PROTECTION FOR VARIABLE SPEED PUMPS Amer A. Al-Dhafiri Rotating Equipment Engineer Nabeel M. Al-Odan

More information

Confined Spaces. 1. Definition Permit/Non-Permit

Confined Spaces. 1. Definition Permit/Non-Permit 1. Definition Permit/Non-Permit Confined Spaces A. Non-Permit Required Confined Space: 1. Large enough and so configured that an employee can bodily enter and perform assigned duties. 2. Has a limited

More information

Gerald D. Anderson. Education Technical Specialist

Gerald D. Anderson. Education Technical Specialist Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions

More information

Item 404 Driving Piling

Item 404 Driving Piling Item Driving Piling 1. DESCRIPTION Drive piling. 2. EQUIPMENT 2.1. Driving Equipment. Use power hammers for driving piling with specified bearing resistance. Use power hammers that comply with Table 1.

More information

Moving Fluids Concept and Theory

Moving Fluids Concept and Theory Moving Fluids Concept and Theory Graco, Inc. P.O. Box 1441 Minneapolis, MN 55440-1441 1995 Graco Inc. Form No. 321-037 12/95 Rev 2 SL Training 11/14 Understanding Your Customer s Situation Characteristics

More information

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

CODE OF GUIDANCE. For the Storage of Full & Empty LPG Cylinders and Cartridges. Page 1

CODE OF GUIDANCE. For the Storage of Full & Empty LPG Cylinders and Cartridges. Page 1 CODE OF GUIDANCE For the Storage of Full & Empty LPG Cylinders and Cartridges. Page 1 Introduction LP Gas Association (LPGA) Code of Practice No. 7 Storage of Full and Empty LPG Cylinders and Cartridges

More information

University of Delaware

University of Delaware University f Delaware Design & Cnstructin Technical Guidelines Envirnmental Health & Safety LABORATORY EQUIPMENT STANDARDS University Cntact: Department f Envirnmental Health & Safety (302) 831 8475 PART

More information

INSPECTIONS OF THE LPG ESTABLISHMENTS IN PORTUGAL. Graça Bravo. 26th September 2017

INSPECTIONS OF THE LPG ESTABLISHMENTS IN PORTUGAL. Graça Bravo. 26th September 2017 INSPECTIONS OF THE LPG ESTABLISHMENTS IN PORTUGAL Graça Bravo 26th September 2017 SUMMARY 1. IDENTIFICATION OF THE LPG ESTABLISHMENTS 2. GENERAL DESCRIPTION OF THE LPG ESTABLISHMENT 3. INSPECTION SUPPORTING

More information

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company CIF A Tyco International Company 1 Foam Concentrate CIF 3% AFFF -UL Listed -UL Canada Listed 6% AFFF 6 parts AFFF concentrate to 94 parts water -UL Listed- Foam Liquid -UL Canada Listed 3% FLUOROPROTEIN

More information

CONFINED SPACE POLICY

CONFINED SPACE POLICY Policy No. 6 THE CITY OF POMONA SAFETY POLICIES AND PROCEDURES CONFINED SPACE POLICY City Manager I. PURPOSE The purpose of the City of Pomona Confined Space Policy is to ensure that employees are adequately

More information

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV 16-1 INTRODUCTION 16-1.1 Purpose. The purpose of this chapter is to familiarize divers with the techniques used to mix divers breathing gas. 16-1.2 Scope. This chapter

More information

Management: Shop Coordinator, Shop Supervisor and Fire Safety Staff

Management: Shop Coordinator, Shop Supervisor and Fire Safety Staff FACILITIES MANAGEMENT Ht Wrk Plicy fr Wrk Perfrmed By University Emplyees 03/13/18 - Last Revisin INTENT: The intended purpse f this Plicy is t prvide a safe wrk/learning envirnment in University buildings

More information

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump. Exercise 2-3 Centrifugal Pumps EXERCISE OBJECTIVE In this exercise, you will become familiar with the operation of a centrifugal pump and read its performance chart. You will also observe the effect that

More information

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors 1130050/4 IM-P113-02 ST Issue 4 UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors Installation and Maintenance Instructions 1. Safety information 2. General product information

More information

DF1 and DF2 Diffusers

DF1 and DF2 Diffusers 1550650/4 IM-P155-07 ST Issue 4 and Diffusers Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Maintenance

More information

SAFETY AND HEALTH STANDARD CONFINED SPACE ENTRY REQUIREMENTS Effective Date: 06/10/10 Standard: 16.2 Document Number: KUCSH0038 Rev: 07

SAFETY AND HEALTH STANDARD CONFINED SPACE ENTRY REQUIREMENTS Effective Date: 06/10/10 Standard: 16.2 Document Number: KUCSH0038 Rev: 07 16.2.1 INTRODUCTION 16.2.1.1 The purpose of this standard is to establish safety requirements, which include a permit system, for entry into confined spaces. 16.2.2 DEFINITIONS 16.6.2.1 Confined space

More information

Introduction to Emergency Response & Contingency Planning

Introduction to Emergency Response & Contingency Planning & Contingency Planning Rationale Why is it important for you to learn this material? Designed for those who may witness a release, this is an introductory course designed to help ensure those who are likely

More information

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS INTERNATIONAL MARITIME ORGANIZATION A 14/Res.567 16 January 1986 Original: ENGLISH ASSEMBLY - 14th session Agenda item lo(b) IMO RESOLUTION A.567(14) adopted on 20 November 1985 THE ASSEMBLY, RECALLING

More information

Confined Space Entry

Confined Space Entry Cnfined Space Entry What is a Cnfined Space? A space that: Is large enugh and s cnfigured that an emplyee can enter bdily and perfrm wrk; Has limited r restricted means f entry r exit; Is nt designed fr

More information

243 Service Regulators

243 Service Regulators Regulatr Installatin and Maintenance Instructins Service Regulatrs RM-06- Rev. Intrductin The is a large capacity general-purpse gas pressure regulatr. Its utstanding perfrmance and versatility make it

More information

ASHRAE made significant changes in 2001 to the calculations. Fundamentals of Safety Relief Systems

ASHRAE made significant changes in 2001 to the calculations. Fundamentals of Safety Relief Systems 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal, Vol. 50, February 2008. This posting is by permission of ASHRAE. Additional

More information

CHEMISTRY - CLUTCH CH.5 - GASES.

CHEMISTRY - CLUTCH CH.5 - GASES. !! www.clutchprep.com CONCEPT: UNITS OF PRESSURE Pressure is defined as the force exerted per unit of surface area. Pressure = Force Area The SI unit for Pressure is the, which has the units of. The SI

More information

Old-Exam.Questions-Ch-14 T072 T071

Old-Exam.Questions-Ch-14 T072 T071 Old-Exam.Questions-Ch-14 T072 Q23. Water is pumped out of a swimming pool at a speed of 5.0 m/s through a uniform hose of radius 1.0 cm. Find the mass of water pumped out of the pool in one minute. (Density

More information

Structural Design and Analysis of the New Mobile Refuge Chamber

Structural Design and Analysis of the New Mobile Refuge Chamber Key Engineering Materials Online: 2013-09-10 ISSN: 1662-9795, Vol. 584, pp 175-178 doi:10.4028/www.scientific.net/kem.584.175 2014 Trans Tech Publications, Switzerland Structural Design and Analysis of

More information

Practice Test FOR GAS POSITIONS APTITUDE BATTERY

Practice Test FOR GAS POSITIONS APTITUDE BATTERY Practice Test FOR GAS POSITIONS APTITUDE BATTERY INTRODUCTION The purpose of this Practice Test is to help you prepare for the Gas Positions Aptitude Battery placement exercise. A sample of questions based

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

OVERVIEW pg 3. Major Points to Consider pg 3 Minor Points to Consider pg 3. INSTRUCTIONS pg 4

OVERVIEW pg 3. Major Points to Consider pg 3 Minor Points to Consider pg 3. INSTRUCTIONS pg 4 TABLE OF CONTENTS OVERVIEW pg 3 Major Points to Consider pg 3 Minor Points to Consider pg 3 INSTRUCTIONS pg 4 How Does Nordic Freeze Work pg 4 How Long Will the Ice Plug Take to Form pg 4 How Do I Know

More information

Inerted Vessels: Preventing Hazards Caused by Gas Buoyancy

Inerted Vessels: Preventing Hazards Caused by Gas Buoyancy Inerted Vessels: Preventing Hazards Caused by Gas Buoyancy 2008 Mary Kay O Connor O Process Safety Center International Symposium College Station, Texas Tuesday, October 28, 2008 presented by Russell A.

More information

Confined Space Entry Program 8 CCR 5157

Confined Space Entry Program 8 CCR 5157 TABLE OF CONTENTS 1. POLICY... 2 2. PURPOSE... 2 3. SCOPE... 2 4. DEFINITIONS... 2 5. CONFINED SPACES IN THE SACRAMENTO STATE... 4 6. PERMIT SPACE ENTRY - PERSONNEL RESPONSIBILITIES... 4 6.1. CONFINED

More information

Permit-Required Confined Spaces...29CFR

Permit-Required Confined Spaces...29CFR (Compliance Audit) Section (c) General Requirements 1) Has the employer performed a workplace inspection to determine if there are Yes No NA permit-required confined spaces (PRCS) present? 2) If the workplace

More information

THE WAY THE VENTURI AND ORIFICES WORK

THE WAY THE VENTURI AND ORIFICES WORK Manual M000 rev0 03/00 THE WAY THE VENTURI AND ORIFICES WORK CHAPTER All industrial combustion systems are made up of 3 main parts: ) The mixer which mixes fuel gas with combustion air in the correct ratio

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information