2.9 GENERAL REQUIREMENTS FOR GROUP I

Size: px
Start display at page:

Download "2.9 GENERAL REQUIREMENTS FOR GROUP I"

Transcription

1 2.9 GENERAL REQUIREMENTS FOR GROUP I Group I represents closed sources of hazard that contain Class I flammable products with lighter-than-air gases or vapors located outdoors that are sufficiently ventilated and which are classified in accordance with the information in Section I. Figure 1-1. The major requirements for classifying the location as shown in Fig. 1-1 are as follows: Items pertaining to the degree of danger: Bl - type of product = flammable gas Cl - system operating mode = closed Dl - location with/without source of hazard = with D2 - above or below grade = above D3 - how is location considered = outdoors D5 - type of location = compressor station El - type of ventilation = natural E3 - amount of ventilation = sufficient Fl - how is flammable gas/vapor released = occasional Items pertaining to the extent of danger: Al - type of source of hazard = compressor B6 - vapor density = lighter-than-air F5 - pump driver and size = as indicated in Fig. 1-1 Figure 1-1 represents a gas compressor located outdoors pumping flammable gas. Since the gas compressor is located outdoors, item D3, the location is considered sufficiently ventilated by natural ventilation, items El and E3. Because the gas compressor has a closed system and is located outdoors, the location for the gas compressor can be classified Div. 2. Since the flammable material in the gas compressor is lighter than air, the extent of the hazard horizontally need only be 15 feet for compressors rated up to 51 Hp, operating at high pressure and 25 feet for compressors rated between 50 and 201 Hp, operating at low or moderate pressure. The classification and extent of hazard for the location is in compliance with the following: Table Item Figure Item For low or moderate pressure ,3 1-2 A,C For high pressure ,2,4 1-2 B,C

2 CLOSED SYSTEM LIGHTER THAN AIR VAPORS SOURCE OF HAZARD CLASS 1 DIV. 1 CLASS 1 DIV. 2 UNCLASSIFIED X = 15 FEET FOR HIGH PRESSURE (UP TO 51 HP) x = & ^pqr ^MODERATE QR HIGH PRESSURE OR COMPRESSED LIQUIFIED FLAMMABLE GASES (60 HP-201 HP) FIG COMPRESSOR STATION HANDLING FLAMMABLE GASES OUTDOORS

3 Figure 1-2. The major requirements for classifying the location as shown in Fig. 1-2 are as follows: Items pertaining to the degree of danger: Bl - type of product = flammable gas Cl - system operating mode = closed Dl - location with/without source of hazard = with D2 - above or below grade = above D3 - how is location considered = outdoors D5 - type of location = compressor station El - type of ventilation = natural E3 - amount of ventilation = sufficient Fl - how isflammablegas/vapor released = occasional Items pertaining to the extent of danger: Al - type of source of hazard = compressor B6 - vapor density = lighter than air F5 - pump driver and size = as indicated in Fig. 1-2 Figure 1-2 represents a gas compressor located outdoors pumping flammable gas. Since the gas compressor is located outdoors, item D3, the location is considered sufficiently ventilated by natural ventilation, items El and E3. Because the gas compressor has a closed system and is located outdoors, the location for the gas compressor can be classified Div. 2. Since the flammable material in the gas compressor is lighter than air, the extent of the hazard horizontally need only be 10 feet for compressors rated up to 51 Hp, operating at low and moderate pressure, and 15 feet for compressors rated up to 51 Hp operating at high pressure. The classification and extent of hazard for the location is in compliance with the following: Table Item Figure Item For low or moderate pressure A For high pressure B Figure 1-3. Figure 1-3 represents an outdoor storage area for storing more than 400 CF of hydrogen gas. (CF = cubic feet of gas at psia and 7O 0 F.) The general safety requirement for hydrogen gas is to maintain a minimum safe clearance of 15 or 25 feet around the storage cylinders. The 25 feet clearance is required if ventilating air is obstructed.

4 CLOSED SYSTEM LIGHTER THAN AIR VAPORS SOURCE OF HAZARD CLASS 1 DIV. 1 CLASS 1 DIV. 2 UNCLASS.FIED X = 10 FEET FOR LOW AND MODERATE PRESSURE (UP TO 51 HP) x = ^ ^ FQR ^ pressure QR COMPRESSED LIQUIFIED FLAMMABLE GASES (UP TO 51 HP) FIG COMPRESSOR STATION HANDLING FLAMMABLE GASES OUTDOORS

5 CLOSED SYSTEM LIGHTER THAN AIR VAPORS riao CLASSI>DIV q,nivi ' 1 CLASS I, DIV. 2 UNCLASSIFIED X = 15 ft. WITH UNOBSTRUCTED NATURALAIRFLOW X = 25 ft. WITH OBSTRUCTED AIR FLOW FIG STORAGE CYLINDERS FOR GASEOUS HYDROGEN LOCATED OUTDOORS

6 Electrical equipment may be of the general purpose type if they are located outside the 15 or 25 feet boundary. Within the 15 or 25 feet boundary the electrical equipment is required to be suitable for a Class I, Div. 2 location. The storage cylinders for the hydrogen gas are not to be considered the actual source of hazard. Valves, screwed fittings, and gauges are normally the actual source of hazard. As an additional safety precaution, storage cylinders for hydrogen gas shall not be located underneath power lines or below piping systems containing flammable and combustible liquids. Where flammable and combustible liquids are involved a minimum horizontal safe distance of 25 feet must be maintained between the two. The classification and extent of hazard for the location is in compliance with the following: Figure 1-4. Table Item The major requirements for classifying the location as shown in Fig. 1-4 are as follows: Items pertaining to the degree of danger: A2 - size of source of hazard = small Bl - type of product = flammable gas Cl - system operating mode = closed Dl - location with/without source of hazard = with D2 - above or below grade = above D3 - how is location considered = outdoors D4 - number of vapor-tight walls of location = none, except upper part D5 - type of location = compressor station El - type of ventilation = natural E3 - amount of ventilation = sufficient Fl - how isflammablegas/vapor released = occasional Items pertaining to the extent of danger: Al - type of source of hazard = compressor B6 - vapor density = lighter-than-air C5 - system pressure = low or moderate F5 - pump driver and size = electric, 0-51 Hp F7 - probability factor = 5 Pu Figure 1-4 represents a shelter for gas compressors operating at low or moderate pressure. Since the shelter virtually has no walls it is considered an outdoor location, item D3. When the gas compressor breaks down, flammable

7 CLOSED SYSTEM LIGHTER THAN AIR VAPORS VAPOR TIGHT WALL!SOURCE OF HAZARD ROOF SUPPORT CLASS 1 DlV. 1 FLOORSPACEOCCUPIED =50% = 2 PU CLASS 1DlV 2 SYSTEMPRESSURE = MODERATE = 2 PU GAS RELEASE = SMALL = 1 PU UNCLASSIFIED TOTAL PROBABILITY FACTOR = 5 PU FIG. I-4. COMPRESSOR STATION WITHOUT WALLS HANDLING FLAMMABLE GAS AT LOW OR MODERATE PRESSURE (SUFFICIENTLY VENTILATED GAS STATION)

8 gases will escape from the gas compressor and since the gases are lighter than air, item B6, the gas will rise to the roof of the shelter. Because the roof of the shelter is open, no accumulation of flammable gases will occur under the roof of the shelter. Because the area under the roof is sufficiently ventilated, it may be classified Div. 2. The extent of the Div. 2 hazard above the roof shall be 15 feet horizontally and 25 feet vertically. At the source of hazard, the boundary shall also extend 15 feet horizontally. No additional danger zones are necessary since the 15 feet horizontal distance is shorter than the distance between the source of hazard and the outer perimeter of the building. Only when the location in the shelter is entirely classified is an additional danger zone required. The classification and extent of hazard for the location is in compliance with the following: Figure 1-5. Table Item The major requirements for classifying the location as shown in Fig. 1-5 are as follows: Items pertaining to the degree of danger: Bl - type of product = flammable gas Cl - system operating mode = closed Dl - control room without source of hazard = yes D3 - how is location considered = indoors D4 - number of walls of control room = 4 D5 - type of location = control room El - type of ventilation in control room = none Fl - how isflammablegas/vapor released = occasional Items pertaining to the extent of danger: Al - type of source of hazard = gas compressor B6 - vapor density = below 0.75 Figure 1-5 represents a control room located under a compressor station which is classified Div. 2. The control room in Fig. 1-5 is without ventilation and does not have to be classified. The reason for this is that the control room does not give access to a hazardous area, but most importantly the vapor density of the flammable product in the compressor station is below A vapor density of below 0.75 will cause a flammable gas in the air to rise quickly. These gases in the air, therefore, cannot enter the control room and in view of this, the control room is allowed to be classified nonhazardous without

9 ventilation. The classification and extent of hazard for the location is in compliance with the following: Table Item

10 CLOSED SYSTEM LIGHTER THAN AIR VAPORS SOURCE OF HAZARD CONTROL ROOM CLASS 1 DIV. 1 VAPOR DENSITY OF FLAMMABLE SUBSTANCE CLASS 1D,V. 2 is BELOW UNCLASSIFIED FIG. I-5. CONTROL ROOM BELOW DIV. 2 HAZARDOUS AREA (INSUFFICIENTLY VENTILATED CONTROL ROOM)

11 2.10 GENERAL REQUIREMENTS FOR GROUP J Group J represents open or closed sources of hazard that contain Class I flammable products with heavier- or lighter-than-air gases or vapors located in sufficiently or insufficiently ventilated locations and which are classified in accordance with the information in Section I. Figure J-I. Figure J-I represents two pits below finished grade located outdoors adjacent to a source of hazard. The pits must be classified as follows. If a pit is located in a hazardous area in which flammable gases or vapors released to the atmosphere have a vapor density greater than 0.75, the pit must be classified Div. 1 as shown in Fig. J-IA. The reason for this classification is that with a vapor density greater than 0.75 the gas or vapor will accumulate in the pit. The pit within the hazardous area can be classified nonhazardous if the flammable gases or vapors in the hazardous area have a vapor density below 0.75 as shown in Fig. J-IB. The reason for this classification is that airborne flammable gases or vapors with vapor densities below 0.75 will quickly rise when exposed to the open and, therefore, will not accumulate in the pit. The classification and extent of hazard for the location is in compliance with the following: Figure J-2. Table Item 1^J 1 and 2 Figure J-2 represents a loading platform for handling flammable liquid with heavier-than-air gases or vapors. A loading platform is normally part of a bulk storage plant which receives flammable and combustible liquid that is distributed to other locations by tank cars, tank vessels or pipe lines. The loading of the flammable product is either at the top or bottom of the tank car, with or without an atmospheric vent or recovery system. The degree and extent of the hazard is as indicated in columns 5 and 6 of the table in Fig. J-2. The classification and extent of hazard for the location is in compliance with: Figure J-3. Table Item 1-4J 2 Figure J-3 represents a building which is divided into two separate areas. One area is a pumphouse handling liquefied petroleum gas, and the other area is an adjacent location. Liquid petroleum gas (LP-gas) includes a material with a vapor

12 CLOSED SYSTEM HEAVIER AND LIGHTER THAN AIR VAPORS V.D. GREATER THAN 0.75 SOURCE OF HAZARD A (SEE ALSO FIG. C-8) SOURCE OF HAZARD V.D. SMALLER THAN 0.75 CIJVSS 1 DIV. 1 CLASS 1 DIV. 2 UNCLASSIFIED FIG. J-1. PITS IN OUTDOOR, DIV. 2 LOCATIONS

13 CLOSED/OPEN SYSTEM HEAVIER THAN AIR VAPORS ITEM NO. LOCATION LOADING AND UNLOADING PRESSURE CLOSEDOR OPEN WlTHOR WITHOUT ATM. VENT. WITHOR WITHOUT RECOVERYSYSTEM DEGREEANDEXTENT OFHAZARD DIV. 1 DIV. 2 1 TOP LOW CLOSED WITHOUT WITH O 3R 2 BOTTOM LOW CLOSED WITHOUT WITH O 3 V, 10 HO, 18Hl 3 TOP LOW OPEN WITH WITHOUT 3R 15V 15HO 4 TOP HIGH CLOSED WITHOUT WITH 5R 15V 15HO CLASS 1 DIV. 1 CLASS 1 DIV. 2 UNCLASSIFIED FIG. J-2 LOADING/UNLOADING PLATFORM, OUTDOORS FOR FLAMMABLE LIQUID

14 CLOSED SYSTEM HEAVIER THAN AIR VAPORS NON VAPOR TIGHT WALL ADJACENT ROOM VAPOR TIGHT WALL SOURCE OF HAZARD NON VAPOR TIGHT WALL ADJACENT ROOM VAPOR TIGHT WALL SOURCE OF HAZARD NON VAPOR TIGHT WALL CLASS 1 DIV. 1 SOURCE OF HAZARD CLASS 1 DIV. 2 UNCLASSIFIED FIG. J-3. PUMPHOUSE HANDLING LIQUID PETROLEUM GAS

15 pressure equivalent to that of propane that is mainly made up of the following hydrocarbons: propane, propylene, butane or butylene. For a pumphouse which is not sufficiently ventilated as shown in Fig. J-3A, the pumphouse must be classified Div. 1. For a pumphouse which is sufficiently ventilated as shown in Fig. J-3B and J-3C, the pumphouse is allowed to be classified Div. 2. Because the extent of hazard in the pumphouse reaches the open perimeter of the pumphouse, an additional danger zone of 15 feet wide must be applied at the opening of the pumphouse as shown in Fig. J-3. The location adjacent to the pumphouse does not have to be classified if the common wall between the pumphouse and the adjacent location is vapor proof and the distance between the opening of the adjacent location and the pumphouse opening is greater than 15 feet. A common wall which is not vapor tight requires that the adjacent location be classified as follows: (1) Div. 1 if the adjacent location is not sufficiently ventilated and the pumphouse is classified Div. 1 or Div. 2 (2) Also Div. 1 if the adjacent location is sufficiently ventilated and the pumphouse is classified Div. 1 (3) Div. 2 if the adjacent location is sufficiently ventilated and the pumphouse is classified Div. 2 (4) Also Div. 2 if the adjacent location is sufficiently ventilated but gives access to a Div. 2 hazardous area outdoors as a result of a distance between the opening of both locations being less than 15 feet. The classification and extent of hazard for the pumphouse and adjacent location is in compliance with the following: Figure J-4. Table Item Figure Item 1-4J 4 and A, B, and C 1-6 2, 3, 7 and 8 Figure J-4 represents minimum requirements for safe distances between containers filled with liquefied petroleum gas (LPG) and an electrical ignition source. The minimum safe distance between a container filled with LPG and an ignition source, a central air conditioning (AC) unit or window-type AC unit, is 5 feet if the container is of the DOT type. The minimum safe distance must increase to 10 feet if the DOT type containers are locally filled. The minimum safe distance should be 15 feet if the containers are of the

16 CLOSED SYSTEM HEAVIER THAN AIR VAPORS AIR INTAKE *5' MIN. *5' MIN. *5' MIN. WINDOW DOTCYLINDERS CENTRAL CRAWL A.C.UNIT FORLPG A.C. UNIT SPACE OPENING *MUST BE 10 FT. MIN. IF DOT CYLINDERS ARE FILLED LOCALLY. MUST BE 15 FT. MIN. IF NOT DOT CYLINDERS. FIG. J-4. SAFE DISTANCES BETWEEN IGNITION SOURCE AND DOT AND NONDOT CYLINDERS FILLED WITH LPG.

17 nondot type. The safe distances between containers for flammable products and electrical ignition sources is in compliance with the following: Figure J-S. Table Item 1-4J 6 Figure J-5 represents a 2-wall building with sources of hazard and two 4-wall spaces without sources of hazard. The two 4-wall spaces are marked "A" and "B" and are located within the hazardous boundary of the sources of hazard in the 2-wall building. The access opening of space "A" is located at grade level and the opening of space "B" gives access to an elevated boardwalk located above the hazardous boundary. The hazardous boundary from the sources of hazard extends to the outdoors horizontally to left and right as shown in Fig. J-5. Both boundaries are classified Div. 2. Since the door opening of space "A" gives direct access to the hazardous boundary space "A" must be classified Div. 2 although it may be sufficiently ventilated. The door opening of space "B" is above the hazardous boundary. Space "B" which gives access to the boardwalk need not be classified if the distance between the bottom of its access opening and the finished grade is twice the height of the 18" high hazardous boundary. Space "B" is not considered safe if the access opening is less than twice the height of the hazardous boundary. If the walls of space "A" and space "B" are not vapor tight, the horizontal distance between these walls and the perimeter of the 2-wall building shall not be smaller than twice the width of the additional danger zone. In this case, the additional danger zone is 10 feet wide and extends vertically to a height equal to the height of the 2-wall building. The horizontal distance, therefore, shall not be less than 20 feet if the walls of the spaces are not vapor tight. If the walls are vapor tight, but provided with nonbolted windows, then the horizontal distance between windows and the perimeter of the 2-wall building shall also not be smaller than twice the width of the additional danger zone. A distance smaller than twice the width of the 10 feet wide additional danger zone requires that the spaces be classified Div. 2. The 20 feet safe distance does not apply to the hazardous boundaries since the boundary is only 18" high. The classification of both enclosed spaces "A" and "B" is in compliance with the following: Table Item Figure Item 1-4J 7 and A and C 1-6 6

18 CLOSED SYSTEM HEAVIER THAN AIR VAPORS 2-WALL BUILDING ADDITIONAL DANGER ZONE, 1OFT. WIDE 4-WALL BUILDING 4-WALL BUILDING BOARDWALK HAZARDOUS BOUNDARY HAZARDOUS BOUNDARY CLASS 1 DIV. 1 CLASS 1 DIV. 2 UNCLASSIFIED BUILDING "A" SUFFICIENTLY VENTILATED MUST BE CLASSIFIED DIV. 2. BUILDING 11 B" NON-VENTILATED MAY BE CLASSIFIED NON-HAZARDOUS. FIG. J-5. ACCESS TO A DIV. 2 HAZARDOUS BOUNDARY

19 Figure J-6. Figure J-6 provides requirements for hazardous boundaries for small process areas associated with lighter-than-air Class I flammable gases. The lighter-thanair gases are processed and handled by operating personnel. The gases are transported from a single gas container, located outdoors, to the process area located indoors via a piping system which is sized not greater than 1/4" or 1/2". The components in the piping system are of the mini type and consist of a pressure reducer, valves, manifolds and gauges. The gas container is pressurized between 2,000 and 3,000 psi and its gas content is less than 400 CF. (CF = cubic feet of gas at psia and 7O 0 F.) The pressure reducer is located at the gas container outdoors and reduces the pressure in the piping system indoors to a desired lower pressure. The components in the piping system indoors are considered sources of hazard as follows: (1) valves and manifolds if they are connected to the piping system with low integrity seal connectors, (2) gauges regardless of how they are connected to the piping system. The hazardous boundary for the components are listed in Fig. J-6. The sizes of the boundaries are selected on the basis of the following requirements: 1) pressure in the piping system, 2) air brushing the sources of hazard, and 3) location of electrical equipment versus location of source of hazard. These requirements are shown in the diagram in Fig. J-6. The correct application of the diagram is to turn it 90 counter-clockwise. Since the flammable material is lighter-than-air, the air stream of the ventilating system must move upwards, i.e., from an air inlet in the wall 12" above the floor to a suction fan in the roof of the indoor location. Since only small quantities of gas can be released from each of the sources of hazard and since the gas is lighter-than-air, it is sufficient if ventilating air dilutes the gas to slightly below the LEL. If the process area is located in a relatively large room or space it is recommended that a fume hood is used above the sources of hazard. With a fume hood, ventilating air need not dilute the gas to slightly below the LEL. Since gases with vapor densities of 0.75 or less in the air will rise quickly, suction air in the fume hood need only be of sufficient quantity to accelerate the upward movement of the gas provided all ignitable gas particles in the air are caught by the fume hood. As shown in the diagram, a mini source of hazard is located between two electric devices "A" and "B." Also shown are two air flows: one which is brushing the mini source of hazard, and the other which is not. When the lighterthan-air flammable material is airborne, it will rise, it will not move in the opposite direction. If the gas is forced out by system pressure, the gas escaping

20 from underneath a source of hazard will move downwards before rising. For example, when a leak should occur underneath the source of hazard, the pressure in the system forces the gas down before it can rise. However, if the source of hazard is brushed by air, the downward movement of the gas is greatly negated by the rising air. If the pressure is low or moderate and if the rising air counteracts the downward movement of the gas and if it first reaches an electric device before reaching the source of hazard, a safety zone of 3 feet below the source of hazard is considered ample. Three feet is considered sufficient to allow the gas to move down before it is caught by the rising air. Therefore, any electric device, such as device "A" in the diagram, may be of the general purpose type if it is below the 3-feet boundary. However, if the system pressure is high, the downward movement of the gas is much greater and because of this a longer radius should be applied. The radius should be 5 feet instead of 3 feet. Also, if ventilating air is not brushing the source of hazard a radius of 5 feet must be applied. Any electric device or equipment located between 3 feet and 5 feet radius must be suitable for a Div. 2 location. Below 5 feet the electric device may be of the general purpose type. Electrical equipment within three feet of the source of hazard must be explosion proof. A much larger than 5 feet hazardous area must be applied above the source of hazard if ventilating air reaches the source of hazard first before reaching the electric device. In this case, the boundary above the source of hazard must extend at least 15 feet. Above the source of hazard the hazardous area is a cone from which the center line can be easily determined. The width of the cone, however, is not easily determined because it is a function of quantity of gas being released and the speed at which the gas rises. The greater the speed of the gas, the smaller the width of the cone required. Any electrical equipment in the cone must be suitable for a Div. 2 location and outside the cone electrical equipment can be of the general purpose type. The division between a 3 or 5 feet danger zone and a zone of a minimum of 15 feet length is called a "demarcation line." As indicated in the table, the greater the system pressure, the more conservative the area classification. When a pressure reducer is applied, a less conservative classification may be used. However, if the pressure reducer shares the same location as the components with the lower pressure, the classification should be based on the higher pressure. If the pressure reducer is not in the same location, the classification should be based on the lower pressure. The classification of the location is in compliance with the following: Table Item 1-4J 9

21 CLOSED SYSTEM LIGHTER THAN AIR GASES AIR OUTLET AlR INLET MINI SOURCE OF HAZARD WITH "LOW INTEGRITY SEAL- CONNECTORS ITEM NO. SYSTEM PROCESSURE AIR BRUSHING ELECTRIC DEVICE LOCATION ENCLOSURE RADIUS X1 X2 EXTENDED LENGTH X3 1 YES A G-P 3ft. 15ft. MIN. 2 3 LOW OR MOD NO YES A B X-P X-P 5ft. 3ft. 15ft. MIN. 15ft. MIN. 4 NO B X-P 5ft. 15ft. MIN. 5 6 HIGH YES/NO YES/NO A B X-P X-P 5ft. 5ft. 15ft. MIN. 15ft. MIN. A, B = LOCATION OF ARCING DEVICE WITH RESPECT TO LOCATION OF SOURCE OF HAZARD. G»P = GENERAL PURPOSE ENCLOSURE X-P = SUITABLE FOR DIV. 2 LOCATION FIG. J-6. PIPING SYSTEM WITH SCREWED FITTINGS, VALVE, ETC. FOR INDOOR GASEOUS SYSTEMS OF LESS THAN 400 CF.

22 Figure J-7. Figure J-7 represents two sufficiently ventilated enclosed process areas "1" and "2" in which lighter-than-air flammable gases are processed. The gases are processed via a piping system from a single container to a process tank. The gas content in the container is less than 400 CF. (CF = cubic feet of gas at 14.7 psia and 7O 0 F.) The piping system contains the following mini-type components: Pressure reducer located at the container outdoors, gauges located indoors. All components are connected to the piping system with low integrity seal connectors. (For low integrity seal connectors refer to Fig. J-IO.) Because of the low integrity seal connectors, valves and manifolds are considered sources of hazard. Gauges are considered sources of hazard by themselves. Both process areas (1) and (2) are identical except for the locations of the air inlets. In process area (1) the air inlet is located in the right building wall. As a result of the different air inlet locations, the sources of hazard in building (1) are brushed by ventilating air and in building (2) they are not. Since the vapor density of the flammable gas is below 0.75, the flammable gas does not necessarily have to be diluted to below 1/4 of the LEL. As airborne gas with a vapor density below 0.75 will rise quickly by itself, it is sufficient if ventilating air dilutes the gas to slightly below the LEL. The dilution needs not be slightly below the LEL if a fume hood is being used. In this case, ventilating air needs only be of sufficient quantity to accelerate the upward flow of the gas, provided all escaping gases are caught by the fume hood. Because the sources of hazard are of the mini-type and ventilated, each component can be provided with a small danger zone that needs only to be classified Div. 2. The radius of the danger zones shall be selected from a table in Fig. J-6. In building (1) the radius shall be 3 feet in accordance with item 1, column (4) in the table for a system pressure that is low or moderate. For building (2) the radius shall be 5 feet in accordance with item 2, column (4) in the table. In process area 1 the source of hazard is brushed by ventilating air, and in process area 2 it is not. Electrical equipment "A" in building (1) can be of the general purpose type since it is below the demarcation line and outside the 3 feet boundary. Electrical equipment "A" in building (2) is also below the demarcation line but at the boundary of the 5 feet danger zone and therefore must have an enclosure that is suitable for a Div. 2 location. Electrical equipment "B" in building (1) can be of the general purpose type since it is sufficiently away from the hazardous cone. If not, as in building 2, equipment "B" must be suitable for a Div. 2 location. In building (1) the cone is narrow as a result of air brushing the source of hazard. In building (2) the cone is wide because the source of hazard is not brushed by ventilating air and requires that the electrical equipment be suitable for a Div. 2 location. The electrical equipment "C" and "D" in both buildings may be of the general purpose type since they are far away from the hazardous cones. (Fifteen

23 CLOSED SYSTEM LIGHTER THAN AIR VAPORS EXHAUST FAN ELEC. EQUIP CONE PROCESS TANK PLATFORM DEMARCATION LINE SOURCE OF HAZ. ("NON SEAL" TYPE) AIR INLET VENTILATING AIR BRUSHING SOURCE OF HAZARD LESS THAN 400 CF CAPACITY EXHAUST FAN ELEC. EQUIP AIR INLET PLATFORM PROCESS TANK CONE DEMARCATION LINE SOURCE OF HAZ. ("NON SEAL" TYPE) VENTILATING AIR NOT BRUSHING SOURCE OF HAZARD LESS THAN 400 CF CAPACITY CLASS I, DIV. 1 CLASS I, DIV. 2 UNCLASSIFIED FIG. J-7. BRUSHING AND NON BRUSHING VENTILATING AIR

24 feet minimum without obstructions to ventilating air and 25 feet minimum with obstructions to ventilating air.) The classification of the location is in compliance with the following: Figure J-8. Table Item 1-4J 10 The major requirements for classifying the location as shown in Fig. J-8 are as follows: Items pertaining to the degree of danger: Bl - type of product = flammable gas Cl - system operating mode = closed Dl - location with/without source of hazard = with D2 - above or below grade = above D3 - how is location considered = indoors D4 - no. vapor tight walls of location = 4 D5 - type of location = process plant El - type of ventilation = fume hood E5 - safeguards = yes Fl - how isflammablegas/vapor released = occasionally Items pertaining to the extent of danger: A2 - size of source of hazard = small or large B5 - flammability class = I B6 - vapor density = lighter-than-air C5 - system pressure = low, moderate, or high Figure J-8 represents a process plant located indoors, handling lighter-thanair flammable gases. The building as shown in Fig. J-8 may be classified non hazardous if the source of hazard is provided with a fume hood. Since the source of hazard is closed, the area between the source of hazard and the fume hood shall be classified Div. 2. The inlet of the fume hood must be as close as possible to any point where the escape of flammable vapors may be expected. The entire exhaust duct system should operate below atmospheric pressure with the exhaust fan located in the roof. To maintain a nonhazardous environment around the source of hazard, the exhaust fan must be provided with an alarm system that operates when there is a suction fan failure. Lighter-than-air gases released by the source of hazard do not have to be diluted to below the LEL of the flammable gas. A lighter-than-air gas will rise quickly by itself when it is airborne. Ventilating air, therefore, needs only to be of sufficient quantity to accelerate the upward flow of the gas provided that all gas particles in the air are caught by the fume hood. An exhaust opening in the roof

25 CLOSED SYSTEM LIGHTER THAN AIR VAPORS FIREPROOFWALL FUME HOOD SOURCE OF HAZARD CLASS 1 DIV. 1 CLASS 1 DIV. 2 UNCLASSIFIED FIG. J-8. PROCESS EQUIPMENT PRODUCING FLAMMABLE GASES (SUFFICIENTLY VENTILATED BY FUME HOOD)

26 shall also be provided as an additional safety precaution. At the outlet of the suction fan, the degree and extent of the danger zone shall be as follows. For large, closed sources of hazard the danger zone around the outlet shall be Div. 2 with a 5-foot radius. For small, closed sources of hazard the danger zone shall have a 3-feet radius. For heavier-than-air flammable material refer to Fig. D-2. The classification of the location is in compliance with the following: Figure J-9. Table Item 1-4J 11 Figure J-9 provides safe clearances between buildings and building openings when lighter-than-air Class I flammable gases need to be released to the atmosphere. As shown in Fig. J-9 the gases are produced in a process area on the lower floor of a multi-story building "A." Removal of the gases in the process area to the outdoors is either by a fume hood connected to a wall opening or a suction fan in the wall. The flammable gases may be vented through the wall if the right wall above the process area is vapor tight. A vapor-tight wall with bolted windows is also considered vapor tight. If the right wall above the process area is not vapor tight, or if it is provided with non bolted windows or openings, the suction fan in the process area must be provided with a vertical riser that extends 7 feet above the roof of building "A". The 7-feet riser must also extend above the roof line of neighboring buildings. Without a riser the minimum horizontal distance between the suction fan in building "A" and the neighboring building "B" shall be 25 feet provided the neighboring wall is vapor tight. A much smaller clearance than 25 feet may be applied if the vapor-tight neighboring wall has a minimum fire resistance of 2 hours. If the neighboring wall is not vapor tight or if it is provided with an opening or air inlet the horizontal distance between the suction fan without a stack and the neighboring wall shall be 50 feet. The vertical distance between both roof openings in building "A" shall be 15 feet minimum and the horizontal distance between the two roof openings shall be 50 feet minimum. This horizontal distance may be smaller if the fan in "A" is a suction fan with a type "A" safeguard. Clearances are in compliance with the following subtable in Table 1-4: Figure J-IO. Table Item J 12 Piping systems used for hydrogen gas for a small process plant are generally sized 1/4" or 1/2". The components in the piping system normally consist of a

27 OPEN OR CLOSED SYSTEMS LIGHTER THAN AIR VAPORS 15 1 IF "A" IS WITH VENTILATION INTAKE 7' IF "A" IS WITHOUT VENTILATION INTAKE PRESSURE FAN IF WALL "A" IS VAPOR TIGHT SUCTION FAN PROCESS AREA SOURCE OF HAZARD PRESSURE FAN VT WALL * NOT APPLICABLE IF VT WAiI HAS A FIRE RESISTANCE RATING OF 2 HRS. A NOT APPLICABLE IF ROOF FAN IN 11 A" IS A SUCTION FAN WITH TYPE "A" SAFEGUARD. FIG. J-9. SAFE DISTANCES FOR FLAMMABLE GAS RELEASED TO THE OUTDOORS

28 pressure reducer, valves, manifolds, gauges and connectors. Figure J-IO gives an overview of the type of connectors normally used in a 1/4" or 1/2" piping system. The connectors may consist either of low-integrity or high-integrity seal connectors. For hydrogen gas low-integrity seal connectors are unreliable because they may cause leakage. Vibration and temperature fluctuation or remake of the connectors are the main reason for causing leakage. High-integrity seal connectors on the other hand are considered leak free because of their quality construction and their quality components. These seal connectors are made leak free because: 1) they are provided with metal gaskets of proper material, 2) are welded into the piping system, 3) are provided with proper workmanship (seal beads are not to rotate against the gasket) and 4) a new metal gasket is used every time the connector is loosened and retightened. Low-integrity seal connectors, therefore, are considered sources of hazard and high-integrity seals connectors are not. Gauges by themselves are also sources of hazard. They are the weakest component in the system because the pressure sensing element in the gauge is known to fail. Valves and manifolds of high quality are considered sources of hazard only if they are provided with low-integrity seal connectors or if they are systematically opened and closed at short intervals. For a piping system equipped with low-integrity seal connectors it is mandatory that sufficient ventilation be applied in accordance with the requirements of Fig. J-6. Classification of the location shall also be in compliance with Fig. J-6. Ventilation and classification of the location may be omitted if the piping system is provided only with high-integrity seal connectors welded into the piping system, and gauges in the piping system are omitted. Hydrogen gas containers and pressure reducers are normally not provided with high-integrity seal connectors. Therefore, they should be located outdoors unless sufficient ventilation is applied when they are located indoors. Indoors the piping system and components are considered leak free as long as they are provided with high-integrity seal connectors, gauges are omitted and the system is thoroughly leak tested. The classification and extent of hazard for the location is in compliance with the following: Figure J-Il. Table Item 1-4] 13 Figure J-Il covers safe clearances for air vents in connection with the possible presence of hydrogen gas in the air. Also covered in Fig. J-Il are safe clearances for public assemblies, cars and welding and cutting areas.

29 HIGH INTEGRITY AND LOW INTEGRITY SEAL CONNECTORS WELD TYPE HIGH PERFORMANCE COUPLINGS WITH METAL GASKET HELIUM LEAK RATE 4 x 1 (T 9 cc/sec HELIUM LEAK RATE 1 x 1 (T 9 cc/sec HIGH INTEGRITY SEAL CONNECTORS SINGLE FERRULE COMPRESSION FITTING DOUBLE FERRULE COMPRESSION FITTING LOW INTEGRITY SEAL CONNECTORS GAUGE CONNECTOR "AN" FLARED TUBE FITTING LOW INTEGRITY SEAL CONNECTORS FIG. J-10. 1/4" ~ 1/2" PIPE FITTINGS FOR H 2 GASES

30 Safe distances between containers filled with hydrogen gas and electric driven suction fans should not be less than 50 feet and 25 feet for welding and cutting areas and 15 feet for electrical arcing devices. As shown in Figure J-Il, there are three exhaust systems, #1, #2, and #3. A distance of 50 feet between air inlet #1 and the hydrogen gas containers must be considered unsafe because a hydrogen gas leak will be easily sucked into the building. However, if vent #3 is an air outlet, it is also unsafe during a gas leak it the vent driver breaks down. Air outlet #3 is safe only if it is provided with a type "A" safeguard. Clearances are in compliance with the following subtable of Table 1-4: Table Item J 14

31 CLOSED SYSTEM UGHTER THAN AIR VAPORS 1. AIR INLET 2. = AIR INLET 3. = AIR OUTLET H 2 CONTAINERSWITH A COMBINED CONTENT OF LESS THAN 3000 CF PUBLIC ASSEMBLY WELDING AC UNIT A = SAFE IF DISTANCE IS 50 FT. MIN. B = SAFE IF DISTANCE IS 15 FT. MIN. C = SAFE IF DISTANCE IS 25 FT. MIN. LOCATION AIR INLET 1 = SAFE LOCATION AIR INLET 2 = UNSAFE LOCATION AIR OUTLET 3 = UNSAFE UNLESS FAN IS PROVIDED WITH A TYPE "A" SAFEGUARD. FIG. J-11 SAFE DISTANCES FOR HYDROGEN GAS OUTDOORS

32 1.11 GENERAL REQUIREMENTS FOR GROUP K Group K represents closed sources of hazard that contain Class I flammable products with heavier-than-air gases or vapors located in sufficiently or insufficiently ventilated locations which are classified in accordance with the information in Section I. Figure K-I. Figure K-I represents components in a piping system for heavier-than-air flammable material operating at low, moderate, or high pressures located indoors which are either sufficiently or insufficiently ventilated. The classification and extent of the danger zone for the components in Fig. K- 1 is a function of: 1) size of the components, 2) their operating modes, 3) the pressure in the piping system, and 4) whether the location is sufficiently ventilated or not. For classification requirements for the components refer to the table in Fig. K-I. In the table in Fig. K-I there are two classifications shown, a location entirely classified and a location partially classified. Some of the partially classified locations are provided with an asterisk. This means that the location must be entirely classified if the piping system with components occupies more than 50% of the floor space. If they do occupy more than 50% of the floor space the components are considered to occupy 100% of the floor space. For example, the location for mini sources of hazard in item 3 of column (1) in Fig. K-I is marked with an asterisk. When these sources of hazard occupy more than 50% of the floor space, the location is considered 100% occupied and the asterisk indicates that it is required that the entire location be classified. As indicated in the table, the greater the system pressure, the more conservative the area classification. When a pressure reducer is applied, a less conservative classification may be used. However, if the pressure reducer shares the same location as the components with the lower pressure, the classification should be based on the higher pressure. If the pressure reducer is not in the same location the classification should be based on the lower pressure. If the flammable product is volatile or very flammable, a more conservative classification is required. To establish whether these locations require a more conservative classification, it is necessary that a severity factor of 1.0 PU be added to the probability factor which must be established for the location first. For example, if the sources of hazard in item 4, column (1) occupy more than 50% floor space, the probability factor for that location is 9 PU. An addition of a 1.0 PU severity factor makes the probability factor 10 PU. This 10 PU factor requires that the location be entirely classified Div. 2. As another example, the probability factor for item 5, column (2) is 8 PU when the location is unattended and more than 50% floor space is occupied. The addition of a 1.0 PU severity factor brings

33 the probability factor to 9 PU. In this case, where the probability factor is less than 10, the location need not be entirely classified. However, the boundary recommended for the sources of hazard in item 5, column (2) is required to be of a larger size when the flammable product is volatile or very flammable. For standard boundary sizes of 3, 5, 10 and 15 feet, increase the size to 5, 10 15, and 20 feet respectively. For volatile and very flammable products refer to the tables in the appendix. Add only a 1.0 PU severity factor if the flammable product in the location is marked with a "4" in the appendix tables. For information on how to determine a probability factor, refer to Section J in Chapter III. If the location needs to be sufficiently ventilated it is necessary to determine the suction fan location. Refer to Section D in Chapter VI for approximate locations of suction fans. Some of the locations in Fig. K-I do not require classification if the location is 1) sufficiently ventilated, 2) the process equipment well maintained, and 3) the probability factor is 5 PU or less. Locations which comply with these three conditions are marked in the table with "NC" which means "nonclassified." For example, the location in item 4, column (1) need not be classified if 1) the sources of hazard do not occupy more than 50% of the floor space, 2) the location is sufficiently ventilated, 3) the sources of hazard are well maintained, and 4) the probability factor for the above conditions is not more than 5 PU. There is a distinct difference between a nonclassified location and a nonhazardous location. A nonclassified location is a location with one or more sources of hazard but which is considered free from explosion danger because of tight inspections and maintenance procedures and sufficient ventilation. A nonhazardous location is a location free from explosion danger because it is provided with sufficient ventilation and suitable safeguards and generally without a source of hazard. Although there is a distinct difference between both locations, a location which needs no classification is in fact a nonhazardous location. Therefore, a nonclassified location can also be considered a nonhazardous location. "Well maintained" is defined as a maintenance procedure in which the probability of leakage or failure of a component in a piping system is almost nonexistent. This is normally accomplished by frequent inspections. Lack of frequent inspections requires that the location be classified. Column (1) and column (2) of item 5 in the table in Fig. K-I is marked with a *. This means that the classification shown in column (1) and column (2) of item 5 is valid only as long as the probability factor for the location does not exceed 5 PU. If the probability factor is higher than 5 PU, then the classification for the location in item 5 shall be as in item 3 of column (T) for mini sources of hazard and item 3 of column (2) for small sources of hazard. To maintain a probability factor of 5 PU, the piping system cannot carry Class IA liquid and the location

34 must be attended. The classification of the location is in compliance with the following: Figure K-2. Table Item 1-4K 1 Figure K-2 represents a piping system operating at low, moderate, or high pressure located outdoors. The classification and the extent of classification for the piping system is a function of 1) size of the source of hazard, 2) operating mode of the source of hazard, 3) vapor density of the flammable product, and 4) pressure in the system. The classification of the location is in compliance with the following: Table Item 1-4K 2

35 CLOSED SYSTEM HEAVIER THAN AIR VAPORS ITEM NO SYSTEM PRESSURE HIGH HIGH MOD. MOD. LOW LOW VENT. INDOORS NO YES NO YES NO YES CLASSIFICATION FOR INDOOR LOCATIONS MINI 6'ANDBELOW DIV. 1,5 Ra+ * DIV. 2, 7 Ra + 15 HO, 18" DIV. 2, 5 Ra + * 15 HO, 18" DIV. 1,3Ra+ * DIV. 2, 5 Ra +10 HO, 18" DIV. 2, 3 Ra NC DIV. 2, 5 Ra + 10 HO, 18" * NON HAZARDOUS IF WELL MAINTAINED SMALL BETWEEN 6" 14" DIV. 1 ENTIRE LOCATION DIV. 2 ENTIRE LOCATION DIV. 1,5Ra+ * DIV. 2, 7 Ra + 15 HO, 18" DIV. 2, 5 Ra+ * 15 HO, 18" DIV. 2, 5 Ra + 15 HO, 18" * DIV. 2, 3 Ra NC LARGE 14"ANDABOVE DIV. 1 ENTIRE LOCATION DIV. 2 ENTIRE LOCATION DIV. 1 ENTIRE LOCATION DIV. 2, 10 Ra+ * 25 HO, 18" DIV. 1,5 Ra+ * DIV. 2, 7 Ra + 25 HO, 18" DIV. 2, 3 Ra + 10 HO, 18" NC * = IF NOT OCCUPYING MORE THAN 50% FLOOR SPACE; OTHERWISE CLASSIFY ENTIRE LOCATION. NC= NON CLASSIFIED IF PROBABILITY FACTOR IS 5 OR LESS AND SOURCES OF HAZARD ARE WELL MAINTAINED AND OCCUPY NOT MORE THAN 50% FLOOR SPACE. * = FOR PROBABILITY FACTOR NOT OVER 5; FOR OVER 5 USE ITEM 3(1) AND 3(2). FIG. K-1 PIPING SYSTEM WITH SCREWED FITTINGS, FLANGES, VALVES, ETC., FOR INDOOR LOCATIONS CONTAINING FLAMMABLE LIQUID

36 CLOSED SYSTEM HEAVIER THAN AIR VAPORS ITEM NO SYSTEM PRESSURE HIGH MOD. LOW MINI 6'ANDBELOW DIV. 2, 3 Ra + 10 HO 1 18" DIV. 2, 3 Ra NON-HAZARDOUS IF WELLMAINTAINED CLASSIFICATION FOR OUTDOOR LOCATIONS SMALL BETWEEN 6" -14" DIV. 2, 5 Ra + 15 HO, 18" DIV. 2, 3 Ra + 10 HO, 18" DIV. 2, 3 Ra LARGE 14"ANDABOVE DIV. 2, 10 Ra + 25 HO, 18" DIV. 2, 5 Ra + 15 HO 1 18" DIV. 2, 3 Ra + 10 HO 1 18" FIG. K-2 PIPING SYSTEM WITH SCREWED FITTINGS, FLANGES, VALVES, ETC., FOR OUTDOOR LOCATIONS CONTAINING FLAMMABLE LIQUID

SECTION 2 APPLICATION OF FUNDAMENTALS

SECTION 2 APPLICATION OF FUNDAMENTALS SECTION 2 APPLICATION FUNDAMENTALS ENVIRONMENTAL CONDITIONS IN NEC CLASS I HAZARDOUS LOCATIONS Section II covers a great number of illustrations which can be applied directly to a hazardous area under

More information

CHAPTER 6 VENTILATION REQUIREMENTS

CHAPTER 6 VENTILATION REQUIREMENTS CHAPTER 6 VENTILATION REQUIREMENTS A. General When there is no air movement, a flammable gas or vapor released to the atmosphere will spread in all directions. With air movement, the flammable gas or vapor

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 12 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

Installation of Ballast Water Management Systems

Installation of Ballast Water Management Systems (Sept 2015) (Rev.1 May 2016) Installation of Ballast Water Management Systems 1. Application In addition to the requirements contained in BWM Convention (2004), the following requirements are applied to

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

COMPRESSED GASES CHAPTER 53

COMPRESSED GASES CHAPTER 53 CHAPTER 53 COMPRESSED GASES SECTION 5301 GENERAL 5301.1 Scope. Storage, use and handling of compressed gases in compressed gas containers, cylinders, tanks and systems shall comply with this chapter, including

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

CODE OF GUIDANCE. For the Storage of Full & Empty LPG Cylinders and Cartridges. Page 1

CODE OF GUIDANCE. For the Storage of Full & Empty LPG Cylinders and Cartridges. Page 1 CODE OF GUIDANCE For the Storage of Full & Empty LPG Cylinders and Cartridges. Page 1 Introduction LP Gas Association (LPGA) Code of Practice No. 7 Storage of Full and Empty LPG Cylinders and Cartridges

More information

WARNING: FOR OUTDOOR USE ONLY

WARNING: FOR OUTDOOR USE ONLY Certified to CSA International 4.96 US For Outdoor Gas Fireplaces A HIGHER STANDARD IN QUALITY AND APPEARANCE SAFE AND BEAUTIFUL OUTDOOR LARGO FIRE PIT FOR PROPANE AND *NATURAL GAS OWNER S MANUAL WARNING:

More information

National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/contentfetcher?commentparams=%28comment... Page 1 of 2 1/16/2014 Committee Input No. 104-NFPA 55-2013 [ Global Input

More information

Vision Painting Inc Safety Management System

Vision Painting Inc Safety Management System Abrasive Blasting 1. PURPOSE The purpose of this program is to provide training and qualification guidelines for the safe operation of Abrasive Blasting. The Safety Officer is responsible for facilitating

More information

Cylinder Exchange Training Manual

Cylinder Exchange Training Manual Cylinder Exchange Training Manual This manual and training program is provided by Root Enterprises, Inc. (Class 1) Revised 07/11 1 Table of Contents: 1. Description and Characteristics of Propane. 2. Cylinders

More information

New Hampshire Public Utilities Commission CFR 49 Part 192 Regulations. MINIMUM Pipeline Safety Regulations

New Hampshire Public Utilities Commission CFR 49 Part 192 Regulations. MINIMUM Pipeline Safety Regulations New Hampshire Public Utilities Commission CFR 49 Part 192 Regulations MINIMUM Pipeline Safety Regulations Application for Jurisdictional LPG Operators 1 Pipeline Safety Regulations 49 CFR Part 192 (NOTE:

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

WLPGA East African Summit

WLPGA East African Summit WLPGA East African Summit Good Practices Daniel Minda Mayieka Specialties Manager Total Kenya Limited Business Model Premise We respect the laws, rules and regulations of the countries in which we operate

More information

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT Reference: IFC, Denver Amendments, NFPA Approved: Joseph L. Gonzales, Division Chief, Fire Prevention and Investigation Division Number: IFC- 3001-1 Effective Date: February 1, 2012 Page 1 of 5 This policy

More information

Handling and Storage of Gases

Handling and Storage of Gases Handling and Storage of Gases Learning Outcome When you complete this module you will be able to: Describe the procedures for safe storage and handling of cylinders containing gases. Learning Objectives

More information

TABLE OF CONTENTS PART 2 - CONFINED SPACES

TABLE OF CONTENTS PART 2 - CONFINED SPACES May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3

More information

Drum / cylinder handling

Drum / cylinder handling Page 1 of 8 Drum / cylinder handling This Technical Measures Document covers the storage and handling of toxic and flammable substances in drums and cylinders and refers to relevant codes of practice and

More information

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT. Number: 2015 IFC Effective Date: February 1, 2017 Page 1 of 5

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT. Number: 2015 IFC Effective Date: February 1, 2017 Page 1 of 5 Subject: COMPRESSED GAS Reference: IFC, Denver Amendments, NFPA Approved: Manuel Almaguer Division Chief, Fire Prevention Division Number: 2015 IFC- 5301-1 Effective Date: February 1, 2017 Page 1 of 5

More information

CHAPTERS THE EXTENT OF EXPLOSION DANGER FOR NEC CLASS I LOCATIONS

CHAPTERS THE EXTENT OF EXPLOSION DANGER FOR NEC CLASS I LOCATIONS CHAPTERS THE EXTENT F EXPLSIN DANGER FR NEC CLASS I LCATINS A. General The purpose of classifying a hazardous location is to provide an acceptable level of safety against explosion danger for personnel

More information

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL ATD-8402 90LB PRESSURE BLASTER INSTRUCTION MANUAL SAVE THESE INSTRUCTIONS SAFETY INSTRUCTIONS FOR SANDBLASTER 1. Before opening the tank release the air pressure on the sand tank. To do this, turn off

More information

Title: Abrasive Blasting Effective Date: 11/17/2014 Control Number: THG_0034 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015

Title: Abrasive Blasting Effective Date: 11/17/2014 Control Number: THG_0034 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015 Title: Abrasive Blasting Effective Date: 11/17/2014 Control Number: THG_0034 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015 Abrasive Blasting CONTENTS I. PURPOSE II. SCOPE III.

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

Transferring and Storage

Transferring and Storage Organometallics Transferring and Storage A dip tube is available for Container 2 which can be screwed into the neck to permit safe transfer of product. Small quantities of metal alkyl can be withdrawn

More information

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848

Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848 Cal/OSHA Gas Systems for Welding GAS WELDING Cal/OSHA T8 CCR 1536 Cal/OSHA T8 CCR 4799 Cal/OSHA T8 CCR 4845 Cal/OSHA T8 CCR 4848 When performing gas welding, the following precautions, work procedures,

More information

Welding, Cutting, and Brazing

Welding, Cutting, and Brazing Welding, Cutting, and Brazing Hazards of Welding Operations Fire hazards Metal splatter Electric shock Explosion hazards Released gases Radiant energy Where would these hazards be found on oil and gas

More information

Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS

Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS TABLE OF CONTENTS Page A. Regulations, Standards and References 1.3-2 B. Scope 1.3-2 C. Design Features for the Storage

More information

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50 Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y OFFICE: (507) 843-4700 P.O. BOX 7079 Toll

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

INSTALLATION GUIDE Gas Rangetops

INSTALLATION GUIDE Gas Rangetops INSTALLATION GUIDE Gas Rangetops Contents Wolf Gas Rangetops........................... 3 Safety Instructions............................ 4 Gas Rangetop Specifications.................... 5 Gas Rangetop

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised Truck Module Page 1 of 5 GAS EMERGENCIES Introduction Natural gas and Liquid Propane Gas (LPG) are flammable gases. Many households and commercial buildings utilize these gases for everything from heating

More information

Bobtail DOT 407 / 412 Vacuum

Bobtail DOT 407 / 412 Vacuum PROCO INCORPORATED AUGER OPERATION Manual Bobtail DOT 407 / 412 Vacuum Vacuum Tank Operation This vacuum tank has been built for Dot work. Extreme care must be exercised regarding product handling. The

More information

Doc No: WELDHOT Midland Engineering Co., Inc. Initial Issue Date 12/14/15 Safety Management System

Doc No: WELDHOT Midland Engineering Co., Inc. Initial Issue Date 12/14/15 Safety Management System Revision Preparation: Safety Mgr Authority: President Issuing Dept: Safety Page: Page 1 of 7 PURPOSE To provide guidelines for the safe operation of welding, cutting and hot work of equipment, and to itemize

More information

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee Page: Page 1 of 5 1 Introduction Compressed gas cylinders can present a variety of hazards due to their pressure and/or contents. One of the contributing factor to these hazards is gas leak due to malfunction

More information

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,

More information

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces 1. SCOPE This document now includes provision for safe access to cable tunnels and culverts previously covered in PSSI 37 which is now withdrawn. The term Confined Space is defined in the Confined Spaces

More information

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks 1. Scope This document describes procedures for determining or confirming the fill condition of

More information

Hotspotter. Model WB-100 Professional Series. Assembly, Testing & Operating Instructions. Safety Information:

Hotspotter. Model WB-100 Professional Series. Assembly, Testing & Operating Instructions. Safety Information: Hotspotter Model WB-100 Professional Series Assembly, Testing & Safety Information: Safety publications related to safe practice and use: CSA 2-94 U.S. Requirements for Hand-Held LP Torches for use with

More information

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65 Data Sheet 819346-02 Issue Date: 05/17 Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300, 50, 65 UNA 45hl MAX, UNA 46hl MAX, UNA 46Ahl MAX UNA 45v MAX with cover for mounting electrode

More information

Working in Gas Hazard Areas

Working in Gas Hazard Areas / Health & Safety OPERATIONS STANDARDS Ref.: Aperam Safety ST 012 Working in Gas Hazard Areas Issue: 15.05.2012 Vers.: v0 Rev.: AM Safety ST 012 v1.2 08.05.2012 Working in Gas Hazard Areas Controlled Updated

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

I. Subject: Compressed gas cylinders, regulators, and portable liquid systems.

I. Subject: Compressed gas cylinders, regulators, and portable liquid systems. I. Subject: Compressed gas cylinders, regulators, and portable liquid systems. II. Objective: To provide safe and effective use, storage, and transport of therapeutic gases. II. Procedure: A. Compressed

More information

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors 1130050/4 IM-P113-02 ST Issue 4 UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors Installation and Maintenance Instructions 1. Safety information 2. General product information

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIG TEX VENTED GAS LOGS

INSTALLATION AND OPERATING INSTRUCTIONS BIG TEX VENTED GAS LOGS INSTALLER! PLEASE LEAVE WITH HOMEOWNER INSTALLATION AND OPERATING INSTRUCTIONS BIG TEX VENTED GAS LOGS by Please Note: It is important that you read instructions before installing or operating gas logs

More information

Annual Report on Liquefied Petroleum Gas (LPG) Related Accidents

Annual Report on Liquefied Petroleum Gas (LPG) Related Accidents Annual Report on Liquefied Petroleum Gas (LPG) Related Accidents (13 version) The High Pressure Gas Safety Institute of Japan (KHK) Information Services & Research Department International Affairs Office

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

CHAPTER 26 WELDING AND CUTTING

CHAPTER 26 WELDING AND CUTTING CHAPTER 26 WELDING AND CUTTING Revised 7/2010 1 WELDING AND CUTTING Responsibilities 1. The County Safety Officer is responsible for providing appropriate safety instructions for supervisor's use on welding

More information

Hazardous (Classified) Locations

Hazardous (Classified) Locations Hazardous (Classified) Locations Presented by: John Chambers UL HazLoc operations Presented at: Safety & You in 2002 2002 Safety Conference Flexible Packaging Association (FPA) 1 AREA CLASSIFICATIONS Class

More information

LP Gas Odorization and Testing

LP Gas Odorization and Testing LP Gas Odorization and Testing CFR 29 Labor OSHA Storage and Handling of Liquefied petroleum Gases CFR 29 1910 (b) 1 (b) Basic rules (1) Odorizing gases. (i) All liquefied petroleum gases shall be effectively

More information

Chapter 7. Coal Cargoes. Properties and Characteristics 7.1

Chapter 7. Coal Cargoes. Properties and Characteristics 7.1 Chapter 7 Coal Cargoes This chapter, and all of the chapters in Part 2, should be read in conjunction with the booklet Carrying Solid Bulk Cargoes Safely (Reference 16), published by Lloyd s Register/UK

More information

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50-P-Mini Portable Systems Outfitted with ABM-725 Monitor

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50-P-Mini Portable Systems Outfitted with ABM-725 Monitor INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50-P-Mini Portable Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y P.O. Box 7079 OFFICE: (507)

More information

NATURAL GAS MAINTENANCE. Part 192 Subpart "M"

NATURAL GAS MAINTENANCE. Part 192 Subpart M NATURAL GAS MAINTENANCE Part 192 Subpart "M" CONTACT INFORMATION Pamela West Pipeline Safety Specialist U.S. Department of Transportation PHMSA Inspector Training and Qualifications Main: (405) 686-2310

More information

LIVE STEAMERS GAS FIRING CODE OF PRACTICE GAS FIRING OF AMBSC BOILERS AUSTRALIAN ASSOCIATION OF

LIVE STEAMERS GAS FIRING CODE OF PRACTICE GAS FIRING OF AMBSC BOILERS AUSTRALIAN ASSOCIATION OF GAS FIRING Document control This document consists of the following sections with the version dates shown. Sections 1 to 9 dated: 07 April 2012 This document consists of 12 pages (including cover). Authoring,

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates Logamax plus GB62-80 kw 270,000 btu/hr Logamax plus GB62-00 kw 35,000 btu/hr This kit and instructions are for converting the

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Electrical Equipment

More information

Laboratory Ventilation. Environmental, Health, and Safety

Laboratory Ventilation. Environmental, Health, and Safety No.: BCF020.054 Page: 1 of 7 RECORD OF REVISIONS Date Rev # Details of Change 09/13 1 Updated job titles to reflect ICON job descriptions. Added a definition for Approved Ventilation Contractor and included

More information

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners BULLETIN MT2035-07/05 Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners M/MR Series M411, M511, M611 M420, M520, M620, MR410, MR510, MR610 MR212D, MR212E, MR212G and MR212J (Flanged),

More information

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

Mooney * Noise Controller Installation, Operation, and Maintenance Manual GE Oil & Gas Mooney * Noise Controller Installation, Operation, and Maintenance Manual imagination at work Scope This manual provides instructions for installation, operation and maintenance of the Mooney

More information

Standard Gas Countertop Griddle

Standard Gas Countertop Griddle Standard Gas Countertop Griddle This manual contains important information regarding your unit. Please read the manual thoroughly prior to equipment set-up, operation and maintenance. Failure to comply

More information

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* THIS KIT CONTAINS: AOPS7741 (NATURAL TO PROPANE CONVERSION PARTS FOR MODEL SIZE, 50) AOPS7742(NATURAL

More information

Gas Countertop Hot Plates

Gas Countertop Hot Plates Gas Countertop Hot Plates This manual contains important information regarding your Patriot unit. Please read the manual thoroughly prior to equipment set-up, operation and maintenance. Failure to comply

More information

4-W GAS ODORIZER WITH POSITIVE ACTION INDICATOR GAUGE (300 PSIG) 2014 INFORMATION MANUAL SUBMITTED BY:

4-W GAS ODORIZER WITH POSITIVE ACTION INDICATOR GAUGE (300 PSIG) 2014 INFORMATION MANUAL SUBMITTED BY: 4-W GAS ODORIZER WITH POSITIVE ACTION INDICATOR GAUGE (300 PSIG) 2014 INFORMATION MANUAL SUBMITTED BY: #3, 1470 28 Street NE Calgary, Alberta Canada, T2A 7W6 Phone: (403) 569-8566 Fax: (403) 207-5110 Submitted

More information

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION Jeff Strath Principal Engineer Paterson Flood Engineers Pty Ltd www.pfe.com.au INTRODUCTION This presentation provides an overview

More information

Scorched Nuts Fire Art Guide

Scorched Nuts Fire Art Guide Scorched Nuts Fire Art Guide This guide is to serve as a reference for the construction and use of flame effects while at Scorched Nuts. At this time, no pressurized effects(poofers) will be permitted

More information

Safety and Health Policy and Procedure Manual. WELDING, CUTTING, and BRAZING PROGRAM Section 0140

Safety and Health Policy and Procedure Manual. WELDING, CUTTING, and BRAZING PROGRAM Section 0140 Safety and Health Policy and Procedure Manual WELDING, CUTTING, and BRAZING PROGRAM Section 0140 I. INTRODUCTION II. SCOPE III. STANDARD IV. GENERAL REQUIREMENTS A. Basic Precautions for Fire Prevention

More information

Confined Space Entry

Confined Space Entry Confined Space Entry Purpose The purpose of this document is to establish methods to identify confined spaces, classify them according to their risks, and establish guidelines necessary for the safe preparation,

More information

LPG TANK INFORMATION An energy company that puts

LPG TANK INFORMATION An energy company that puts LPG TANK INFORMATION An energy company that puts Safety first. LPG TANKS Thanks Thank you for choosing Kleenheat for your LPG supply. We consider safety our number one priority, so please make time to

More information

PRESSURIZED EQUIPMENT AND SYSTEMS

PRESSURIZED EQUIPMENT AND SYSTEMS SECTION 20 PRESSURIZED EQUIPMENT AND SYSTEMS 20.A GENERAL 20.A.01 Inspections and tests - general. a. Pressurized equipment and systems shall be inspected and performance tested before being placed in

More information

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL 00, 0, 000 00, 000, 00 A. TECHNICAL INFORMATION Model 00 Inlet/Outlet " Air Inlet /" 0 / 000 /" /" 00 /" /" 000 /" /" 00 /" /" Flow Rate GPM/ 0LPM GPM/ 0LPM GPM/ LPM GPM/ LPM GPM/ 0LPM GPM/ 0LPM Maximum

More information

Full Internal Relief Valves Instruction Manual

Full Internal Relief Valves Instruction Manual Full Internal Relief Valves Instruction Manual MEV200FIR & MEV300FIR Application: Designed for use in mobile LPG & NH 3 containers as a primary pressure relief valve for bobtail and transport trailer installations.

More information

PORTABLE 5 GALLON AIR TANK ASSEMBLY & OPERATING INSTRUCTIONS

PORTABLE 5 GALLON AIR TANK ASSEMBLY & OPERATING INSTRUCTIONS PORTABLE 5 GALLON AIR TANK MODEL 472 ASSEMBLY & OPERATING INSTRUCTIONS 349 Mission Oaks Blvd., Camarillo, CA 930 Visit our Web site at http://www.harborfreight.com TO PREVENT SERIOUS INJURY, READ AND UNDERSTAND

More information

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES Sampling Valves Installation Commissioning and Operating Instructions SD IL 300 & SD IL 400 Inline Sampling Valve This

More information

Compressors. Basic Classification and design overview

Compressors. Basic Classification and design overview Compressors Basic Classification and design overview What are compressors? Compressors are mechanical devices that compresses gases. It is widely used in industries and has various applications How they

More information

Class 2 Gases Learning Tool

Class 2 Gases Learning Tool Class 2 Gases Learning Tool This work has been produced by DGL (Aust) Pty Ltd This Learner s Guide is about the skills and knowledge required to store and warehouse Class 2 Gases at DGL (Aust) facilities.

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES s of the IGF Code CONTENTS GF1 Test for gas fuel tank s high level alarm Rev.1 July 2017 GF2 Ship Steel Protection against Liquefied Gas Fuel (Part

More information

Model Secure-Gard Pilot Operated Vent Valve SECTION II. Remove all packing material inside and outside of the valve prior to installation.

Model Secure-Gard Pilot Operated Vent Valve SECTION II. Remove all packing material inside and outside of the valve prior to installation. INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) IOM - 1049 01-17 Model 1049 Secure-Gard Pilot Operated Vent Valve ISO Registered Company SECTION I I. DESCRIPTION AND SCOPE The Model 1049 Secure-Gard

More information

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the 1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method

More information

PV4 and PV6 Piston Valves

PV4 and PV6 Piston Valves 1181250/1 IM-P118-05 ST Issue 1 PV4 and PV6 Piston Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6.

More information

API RECOMMENDED PRACTICE 500 THIRD EDITION, DECEMBER 2012 ERRATA, JANUARY 2014

API RECOMMENDED PRACTICE 500 THIRD EDITION, DECEMBER 2012 ERRATA, JANUARY 2014 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2 API RECOMMENDED PRACTICE 500 THIRD EDITION, DECEMBER

More information

MB-SP Series Solvent Purification System

MB-SP Series Solvent Purification System Operation Manual MB-SP Series Solvent Purification System Table of contents 1. System overview 2 2. Column activation.. 5 3. System purging.. 6 4. Glove box integration.... 7 5. Solvent reservoir installation....

More information

Compressed Gases Storage and Handling Safety Policy. Individual Unit Function: Safety Procedure No.: SOP-0103 Page: 1 of 6

Compressed Gases Storage and Handling Safety Policy. Individual Unit Function: Safety Procedure No.: SOP-0103 Page: 1 of 6 Procedure No.: SOP-0103 Page: 1 of 6 MIDGA Reviewed: 07/09/18 Effective: 1/14/98 Supersedes: Original Preparer: Owner: Approver: Safety Safety Safety 1. PURPOSE The purpose of this procedure is to establish

More information

DSEAR- Storage, Use and handling of gas cylinders guidance.

DSEAR- Storage, Use and handling of gas cylinders guidance. OHSS: Storage, Use and handling of gas cylinders guidance 202 DSEAR- Storage, Use and handling of gas cylinders guidance. Contents Introduction... 2 General recommendations for storage, use and handling....

More information

Title of Paper Interpretation of IP15 in Process Plant Design: a Commonsense Approach ---------------------------------------------------------------------------------------------------------------------------

More information

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15)

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15) 1. PURPOSE: This SPI has been developed to ensure compliance to government regulations and to provide clear standards for storage of compressed gases. 2. CONTEXT The storage of compressed gases is legislated

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

CVS10 Sanitary Check Valves

CVS10 Sanitary Check Valves 0299050/4 IM-P029-11 ST Issue 4 CVS10 Sanitary Check Valves Installation and Maintenance Instructions 1. Safety information CVS10 with soft seat 2. General product information 3. Operation 4. Installation

More information

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems INTERNATIONAL STANDARD ISO 10239 Second edition 2008-02-15 Small craft Liquefied petroleum gas (LPG) systems Petits navires Installations alimentées en gaz de pétrole liquéfiés (GPL) Reference number ISO

More information

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS FILTER REGULATORS MODEL NO: CAT155 & CAT156 PART NO: 3120169 & 3120170 FITTING & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS GC0117 INTRODUCTION Thank you for purchasing this CLARKE Filter/Regulator.

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions 1326050/3 IM-P132-11 ST Issue 3 A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation

More information

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions 1490050/7 IM-P149-06 CMGT Issue 7 AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

SRV66 Sanitary Pressure Reducing Valve

SRV66 Sanitary Pressure Reducing Valve 1866350/4 IM-P186-09 CH Issue 4 SRV66 Sanitary Pressure Reducing Valve Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Commissioning

More information

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL www.modsafe.com SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL WARNING: Do not attempt to operate this equipment without first reading and understanding the service manual enclosed with this device.

More information