National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Size: px
Start display at page:

Download "National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: FROM: NFPA Technical Committee on XXXX Kimberly Shea DATE: September 9, 2013 SUBJECT: NFPA 70E SD TC Ballot Circulation (A2014) The September 6, 2013 date for receipt of the NFPA 70E First Draft ballot has passed. The preliminary First Draft ballot results are shown on the attached report. 25 Members Eligible to Vote 0 Ballots Not Returned In accordance with the NFPA Regulations Governing the Development of NFPA Standards, attached are reasons for negative votes for review so you may change your ballot if you wish. Abstentions and affirmative comments are also included. Ballots received from alternate members are not included unless the ballot from the principal member was not received. If you wish to change your vote, the change must be received at NFPA on or Monday, September 16, Members who have not returned a ballot may do so now. Such changes should be submitted through the NFPA Vote.net Ballot Site. The return of ballots is required by the Regulations Governing the Development of NFPA Standards.

2 NFPA 70E Second Draft Ballot (A14) Preliminary Results September 9, 2013 SR 16, Global Comment, See SR 16 SR 30, Global Comment, See SR 30 Affirmative 21 Affirmative with Comment 2 Palmer L. Hickman This revision will now clearly require the use of voltage rated gloves for systems rated at 208 and 240 volts. However, this revision may cause confusion for the user of 70E. The consequence could be less use of shock protection as the determination of the need to use gloves had been in the HRC table until now. Bobby J. Gray Staff should editorially add the word "nominal" after "120V" in new note d. This would not change intent or implementation but would prevent questions as to whether flucuations in voltage should be considered. There is no technical justification for this change. The vast majority of panels contain multiple voltages. In the range related to this change, normally there is up to 240 or 277 volts. There is no difference in the level of protection needed from a shock prospective between 150 and 277 volts. Both are in the same box. Requiring a 3 distance for 208 to 277 volts adds nothing to the level of safety for the individual, does not add clarity and is overly restrictive. The existing language is clear and represents real world installations. This change should not be made, the existing language should remain.

3 SR 44, Global Comment, See SR 44 Affirmative 20 Negative 4 Palmer L. Hickman We do not believe that the Technical Committee has received additional technical substantiation since the First Revision stage to warrant returning the threshold for dc shock protection to 100 volts. Vincent J. Saporita Based upon the OSHA cited instances, a dc shock hazard can still exist between V. Further study is warranted before accepting this change. This puts 70E in direct conflict with OSHA 1910 Subpart S. OSHA requirements are regulatory requirements and must be revised before a national consensus document can refute or change these requirements. This is a legal issue. This change sets people and companies up for willfull violations of the OSHA requirements Marcia L. Eblen Changing the lower limit of the DC table from 50V to 100V is in contradiction with Federal OSHA requirements. 70E should not encourage workers to disobey federal law. In addition, OSHA has provided specific USA incident data that shows fatalities from DC exposures between 50V and 100V. y changing the tables, inconsistencies now exist with section (D) describing when the restricted approach boundary requirements are invoked. However, I continue to be concerned about the action the 70E Committee took on actions related to the threshold requiring protection from energized DC circuit parts. At the meeting, the Committee voted to raise the threshold to 100 volts from 50 volts adopted at the last meeting. There is clear evidence before the Committee that voltages higher than 50 volts but lower than 100 volts can be, and have been, fatal. Papers submitted by those supporting the rise in the threshold indicate that there have been at least seven fatalities in China from contact with circuit parts energized at less than 100 volts DC. It was argued that the conditions typically involved working in very hot and confined locations and that those fatalities were in a country likely without confined space standards. I don t consider those arguments particularly persuasive. In the first place, the workers died of electric shock, not heat stress or other confined space hazards. I am aware of no evidence that heat stress exacerbates the effects of electric shock. While it is that perspiration can lower contact resistance, that is of wet conditions in general, and it has the same effect on AC electric shock events. It is one of the major reasons why the AC threshold is 50 volts. In the second place, China is not a third world country. China has adopted safety and health laws and has a professional occupational safety association. In addition, as I mentioned in an earlier , there have been at least three fatalities in the US involving DC circuits of less than 100 volts: These incidents, as well as the Chinese incidents, show that voltages over 50 volts DC are hazardous. Finally, setting the DC voltage threshold higher than 50 volts conflicts with the NEC and OSHA standards, which require guarding of exposed live parts operating at more than 50 volts DC. It s hard to understand why NFPA 70E would permit contact with 50 volt DC circuit parts that the installation codes require to be guarded. Clearly, if it is unsafe to install DC equipment with exposed live parts operating at more than 50 volts, it must also be unsafe to touch those parts during maintenance and repair. (Installation requirements will continue to prohibit contact during operation.) I believe that, given the accident history, it is unrealistic to believe that OSHA or the NEC will raise the existing 50 volt DC threshold.

4 SR 63, Global Comment, See SR 63 SR 1, Definition (100): Balaclava (Sock Hood)., See SR 1 Affirmative 21 Affirmative with Comment 1 Lee R. Hale The changed definition is now in alignment with the testing of an Arc Rated face shield and protects the back of the head as intended. Palmer L. Hickman The 2012 edition requires the nose to be covered. The committee has not been presented with evidence that workers should not be required to wear a balaclava that covers the nose area. Abstain 2 Drake A. Drobnick The current definition of Balaclava unconditionally excludes the nose from being covered directly by arc rated material. In some situations this guidance may not be prudent leading to burns to unprotected skin.

5 SR 2, Definition (100): Energized Electrical Work Permit., See SR 2 Affirmative 22 Negative 2 Bobby J. Gray I disagree with removal of the definition. The TC provided a negative statement to a proposal to the 2004 edition that the EEWP could be a procedure or other document that reflected the key elements of the permit. This is good information and should be placed into the defintion to help users understand the purpose of the permit. If we remove the defintion, there may be reluctance for the public to submit changes to fix the defintion as was pointed out in the commttee statement. This definition is still needed. The concept of permitting electrical work where electrical hazards are present has not yet been fully adopted by the general industry and is especially not generally understood by the construction industry. The reason the definition does not contain the criteria and expectations is that definitions cannot contain requirements. SR 68, Definition: Accessible, Readily (Readily Accessible)., See SR 68 Affirmative with Comment 1 I agree with the concept but the sentence needs to be re worded for it to make sense.

6 SR 3, Definition: Luminaire., See SR 3 SR 69, Definition: Premises Wiring (System)., See SR 69 SR 71, Definition: Switchboard., See SR 71

7 SR 72, Definition: Voltage, Nominal., See SR 72 SR 4, New Section after 110.1(A), See SR 4 Affirmative 22 Affirmative with Comment 1 Bobby J. Gray I applaud the TC for recognizing the need to formalize a requirement for an employer to have a documented maintenance program. But, I am disappointed the TC failed to see the value in a similar requirement for installation of electrical equipment and systems. I review many documented programs each year and invariably observe that these programs have no mention of an installation element, but instead focus on work practices only. Meanwhile cursory inspections indicate that electrical system modifications are being done by unqualified persons. The employees installing or modifying are not the qualified people that so many of you train. These are not the people that many of you represent as qualified workers or contractors. These are people the employer has assigned because he or she is not forced to put in writing how they will ensure their electrical equipment and systems are properly installed. As stated in 110.2(A), we rely on safe installations to protect the general worker from exposure to electrical hazards. Since more unqualified workers than qualified workers are electrocuted each year (NIOSH), perhaps we should re evaluate the priority we place on protecting those workers as well as the qualified workers. Louis A. Barrios While I agree that maintenance is an important element for the safe operation of electrical equipment, the proposed text is vague and uninforceable. Also the concept of maintenance and installation is already covered in the modifications to Informational Note 1 in SR 5 and as shown below, "Informational Note No. 1: Safety related work practices such as verification of proper maintenance and installation, alerting techniques, auditing requirements, and training requirements provided in this standard are administrative controls and part of an overall electrical safety program." Therefore the new subsectin "B" is redundant and unnecessary.

8 SR 5, Section No (A), See SR 5 It is the hazard that hurts people. The risk allows it to. The electrical safety program needs to address the hazards and elimination of the hazard first then a risk assessment needs to be performed for whatever hazard is left. If the focus is on the risk then people will not pay attention to elimination of the hazards SR 6, Section No (E), See SR 6 SR 7, Section No (G), See SR 7

9 SR 8, Section No (H)(1), See SR 8 SR 9, Section No (H)(2), See SR 9 SR 10, Section No (A), See SR 10 It is the hazard that hurts people. The risk allows it to. The electrical safety program needs to address the hazards and elimination of the hazard first then a risk assessment needs to be performed for whatever hazard is left. If the focus is on the risk then people will not pay attention to elimination of the hazards SR 11, Section No (B), See SR 11 Affirmative 22 Affirmative with Comment 1

10 Lee R. Hale Daleep C. Mohla I still believe we have not addressed the issue of new technology being introduced effectively or BAD habits being continually passed from one worker to the next. This version is better but still needs improvement to address changes for worker safety. Type of training required by 70E should be classroom and on the job. Electrical systems are getting very complex with the rapid introduction of electronics in every piece of electrical equipment (D) (2) requires Retraining in safety related work practices and applicable changes in this standard shall be performed at intervals not to exceed three years. This clearly implies that employees have to be trained in 70E based training. This can only be accomplished in an instructor lead classroom type environment. It is infeasible to perform this type of training on the job. On the job training is normally done by peers (e.g. a senior electrician training other electricians while working with them) Part of the training is risk assessment and I seriously doubt this can be accomplished in other than an instructor lead training in a class room. SR 13, Section No (C), See SR 13 Affirmative 22 Affirmative with Comment 2 Rodney J. West We recognize that some major certifying bodies provide CPR certification training that is valid for more than one year. As explained during the committee meetings, this section is not intended to require annual certification training but rather to require annual refresher training. While the document does not specify or define what constitutes refresher training, the employer can determine the type and extent of annual refresher training that is necessary to meet this requirement. Louis A. Barrios While I support the committee's efforts to simplify and provide additional clarity in this section, 110.2(C)(2)(a) should be modified to make it clear that "emergency procedures" are appropriate for the hazard or expected injuries and not left open to interpretation to cover all emergency procedures.

11 SR 14, Section No (D)(1), See SR 14 It is the responsibility of the employer to set the acceptable level of risk an employee can work under and the employer must establish the methods of protecting the employees. It is not the responsibility of the employee as outlined in 110.2(D)(1)(b)(4). The the concepts of hazard identification and risk assessment are being muddied with the changes to 70E related to risk and hazards. This will confuse those who will try to implement the requirements of this standard. SR 15, Section No (C), See SR 15 Affirmative 20 Negative 4 Louis A. Barrios The sole criteria for determining whether or not a documented meeting shall be held between a host employer and a contracto employer should not be dependent only on the hosts employer's qualifications and knowledge of the hazards. The contract employer and his/her knowledge of the hazards should also be considered. In fact, it may be more important for a documented meeting to occur when the host employer is not familiar with the electrical hazards at their site. Daleep C. Mohla The proposed new wording Where the host employer has knowledge of hazards covered by this Standard that are related to the contract employer s work, there shall be a documented meeting between the host employer and the contract employer is very ambiguous and has no merit at all. This leaves a big loop hole for not having a meeting at all. Why would a host employer have a meeting to explain the electrical hazards if it is not required (A) (1) requires the host employer is required to inform the contract employer of known hazards related to the contractor s work (A) (C) documentation is the next logical step to ensure requirements of 110.3(A) (1) have been met. The wording in the first draft There shall be a documented meeting between the host employer and the contract employer is needed to have some kind of formal transfer of knowledge and documentation to assure this hazards covered in 110.3(A) (1) have been conveyed to the contract employer. In absence of a clear requirement for documentation there will be no method to determine if contract employer has been informed of known hazards. A meeting should always take place before work begins. If the host employer does not have knowledge of hazards, it is their responsibility to find someone who does. The hazards must be communicated in order to allow proper protective measures to be taken. This wording will allow many host employers to simply not have a meeting and not communicate any hazard information. This weakens the document. James G. Stallcup This is an ambiguous statement. The host employer should be required to have a meeting.

12 SR 16, Section No (A)(4), See SR 16 SR 18, Section No (B)(3), See SR 18 The wording related to the handling of portable electric equipment in highly conductive locations should be removed and the guidance from this document should be to not do those things. Including phrases such as inundated with water, where employees are likely to contact or be drenched with water with guidance on how to handle portable electric equipment is completely contrary to the basic premise of the document. The guidance we should be providing in these situations is to not handle this equipment in those environments. We used to have language related to live line work and we took that out, the same should apply here. This is something that may have been accepted but should not be any longer. SR 19, Section No (C)(3), See SR 19

13 SR 20, Section No , See SR 20 Before verification can be done, an electrically safe work condition must first be established. This section of the standard should focus on establishing the electrically safe work condition. However, it seems to me that the section covers achieving, as well as verifying, an electrically safe working condition. SR 21, Section No (B)(2), See SR 21 Affirmative with Comment 1 Drake A. Drobnick Two new line items need to be added to the next edition in section 120.2(B) (3), (c) when there is a change in job assignment, (d) when the employee shows lack of knowledge or skill. SR 22, Section No , See SR 22 Affirmative with Comment 1 Palmer L. Hickman We wonder if the final wording accurately reflects all of what what is covered by Article 130. It almost sounds like a scope statement where only what is included it the scope of the article can be covered in the article. We submit that this wording may be inaccurate, incomplete and not necessary. Perhaps restating or incorporating the title of Article 130, "Work Involving Electrical Hazards", would be have beenmore appropriate.

14 SR 24, Section No [Excluding any Sub Sections], See SR 24 Affirmative 21 Negative 3 Palmer L. Hickman A worker s presence within the arc flash boundary seems as predictive of the likelihood that an arc flash hazard will exist as a worker s presence within the limited approach boundary is predictive of the likelihood that a shock hazard will exist. Drake A. Drobnick The definition of Arc Flash Hazard states that exposed energized parts or employee interaction could create a hazard. The Standard requires in section that an Electrically Safe Work Condition be established whenever an employee works within an exposed shock hazard boundary or when the employee interacts with enclosed equipment. It totally ignores the exposed arc flash hazard condition it recognizes within the definition. PI 63 sought to remedy this inconsistency and was accepted by the committee and included in FR 72. The Committee reversed its decision and removed the language by accepting PC 115. In the Committee s statement for removing FR 72, they suggest that a worker s presence within the arc flash boundary is not predictive of the likelihood that an arc flash incident will occur. Conversely, by mandating de energizing whenever an employee is located within the exposed shock protection boundary appears to conclude that the employee will always receive a shock at this location without regard to predictive likelihood. Abstain 1 The condition described in (3) still requires an electrically safe work condition to be established. The arc flash boundary can exceed the limited approach boundary and create a hazardous situation. Excluding this sets up a condition that will lead to misunderstanding the arc flash hazard, and will cause injuries. If within the arc flash boundary, an individual would be exposed to the hazard. The hazard should be removed by establishing an electrically safe work condition. SR 25, Section No (B)(1), See SR 25 Affirmative 21 Affirmative with Comment 2 Palmer L. Hickman Why is the arc flash boundary not listed here in this section? Lee R. Hale With the revised text the EWP can now be used effectively as it was orginally intended. Drake A. Drobnick The Committee's departure from the 2012 language in section 130.2(B) (1) dilutes and limits the application of the Energized Electrical Work Permit. By the acceptance of FR 75 and PC 116 which deletes the arc flash boundary and reduces the shock boundary action trigger for < 600 volts to < 12" or

15 SR 26, Section No (B)(2), See SR 26 Affirmative with Comment 1 Lee R. Hale With the revised text the EWP can now be used effectively as it was orginally intended. SR 27, Section No (B)(3), See SR 27 Affirmative with Comment 1 Lee R. Hale With the revised text the EWP can now be used effectively as it was orginally intended. SR 28, Section No (A) [Excluding any Sub Sections], See SR 28 Identification of the hazards is done through a hazard analysis. This section discusses hazards, not risk.

16 SR 29, Section No (A), See SR 29 Hazard identification determines voltage. Then the level of risk can be determined. SR 31, Sections 130.4(C), 130.4(D), See SR 31 There is no technical justification for the change from 300 to 150 volts. The vast majority of panels contain multiple voltages. In the range related to this change, normally there is up to 240 or 277 volts. There is no difference in the level of protection needed from a shock prospective between 150 and 277 volts. Both are in the same box. Requiring a 3 distance for 208 to 277 volts adds nothing to the level of safety for the individual, does not add clarity and is overly restrictive. The existing language is clear and represents real world installations. This change should not be made, the existing language should remain. However, I continue to be concerned about the action the 70E Committee took on actions related to the threshold requiring protection from energized DC circuit parts. At the meeting, the Committee voted to raise the threshold to 100 volts from 50 volts adopted at the last meeting. There is clear evidence before the Committee that voltages higher than 50 volts but lower than 100 volts can be, and have been, fatal. Papers submitted by those supporting the rise in the threshold indicate that there have been at least seven fatalities in China from contact with circuit parts energized at less than 100 volts DC. It was argued that the conditions typically involved working in very hot and confined locations and that those fatalities were in a country likely without confined space standards. I don t consider those arguments particularly persuasive. In the first place, the workers died of electric shock, not heat stress or other confined space hazards. I am aware of no evidence that heat stress exacerbates the effects of electric shock. While it is that perspiration can lower contact resistance, that is of wet conditions in general, and it has the same effect on AC electric shock events. It is one of the major reasons why the AC threshold is 50 volts. In the second place, China is not a third world country. China has adopted safety and health laws and has a professional occupational safety association. In addition, as I mentioned in an earlier , there have been at least three fatalities in the US involving DC circuits of less than 100 volts: These incidents, as well as the Chinese incidents, show that voltages over 50 volts DC are hazardous. Finally, setting the DC voltage threshold higher than 50 volts conflicts with the NEC and OSHA standards, which require guarding of exposed live parts operating at more than 50 volts DC. It s hard to understand why NFPA 70E would permit contact with 50 volt DC circuit parts that the installation codes require to be guarded. Clearly, if it is unsafe to install DC equipment with exposed live parts operating at more than 50 volts, it must also be unsafe to touch those parts during maintenance and repair. (Installation requirements will continue to prohibit contact during operation.) I believe that, given the accident history, it is unrealistic to believe that OSHA or the NEC will raise the existing 50 volt DC threshold.

17 SR 32, Section No , See SR 32 SR 33, Section No (D), See SR 33 SR 34, Section No (H), See SR 34 SR 35, Section No (A), See SR 35

18 SR 36, Section No (C)(9), See SR 36 SR 37, Section No (C)(10), See SR 37 Affirmative 22 Negative 2 Palmer L. Hickman We disagree that "this change clarifies that a balaclava is only required to be worn when the exposure is greater than 4 cal/cm2." This is not a clarification. This creates an unsubstantiated change and a conflict within Article 130. Section 130.7(C)(6) requires all parts of the body to be be protected by arc rated FR. The entire head is part of the body. In addition, the substantiation for the the public comment, which is the basis for this second revision, incorrectly correlates HRC 1 with an incident energy calculation of 4 calories. Rodney J. West We believe the clarification may conflict with the requirements in Sections 130.7(C)(1) and 130.7(C)(6). SR 40, Section No (C)(11), See SR 40

19 SR 41, Section No (C)(13), See SR 41 The change removes any requirements associated with trim, names or logos that may be attached to arc flash PPE. An informational note does not mean that any one will follow the requirements of the referenced standard. This dilutes the effort of providing arc flash PPE that will protect a person.

20 SR 45, Section No (C)(15), See SR 45 Affirmative 15 Affirmative with Comment 3 Rodney J. West The new table format provides additional clarity and gives guidance to users of the document. While the lists of tasks that do not require arc flash PPE remained the same, the new format clarifies that arc flash PPE is required for those same tasks when electrical equipment is not properly installed or maintained, when equipment doors or covers are off or open, or when there is evidence of impending failure. Dennis K. Neitzel I agree with the overall revisions of Table 130.7(C)(15)(A)(a), however I do not agree with the following part of it: In the Table 130.7(C)(15)(A)(a) section that states Task Normal operation of a circuit breaker (CB), switch, contactor, or starter, and where it goes on to state that Equipment Condition All of the following: The equipment is properly installed The equipment is properly maintained All equipment doors are closed and secured All equipment covers are in place and secured There is no evidence of impending failure Where it then states: Arc Flash PPE Required No This is not ; there will never be a case when there is a 100% guarantee that an arc flash will not occur, that may even blow the equipment enclosure door open or the cover off. Granted the risk is very low but not zero as implied here. The substantiation does not provide proof that the risk is zero and that no arc flash PPE is required for this task. This comment also applies to FR 68. Lee R. Hale The tables have a much cleaner and simplified look. The Arc Flash PPE Required header coupled with the "properly installed and maintained.."" section could be interperated two ways. However (A) (4) passed through the FR stage without an attendent PC submitted so the tables do match to 130.2(A)(4). The metal clad switchgear section had it's upper Kv value reduced from 38Kv to 15Kv which is safer for the worker. On balance, simplier and cleaner, there may need to be some revisions in Only time will tell. Negative 6 Daleep C. Mohla Please see document separately submitted for negative statement on SR 45 James G. Stallcup It has been our experience that well maintained equipment can sometimes fail and create an electrical arc. This concept in Table 130.7(C)(15)(A)(a) should have been rejected at the First Daft meeting. The continued effort to water down the arc flash requirements contained in this document is evident by acceptance of this concept. Even listed equipment, installed per the NEC and properly maintained fails. Numerous cases can be provided to show evidence that, at a certain level of arc flash incident energy, the equipment will not contain an arcing fault unless it has been designed and tested to contain it. There is no one who can walk up to piece of electrical equipment and determine whether it is listed, installed correctly, or properly maintained. There are just too many factors to consider in addition to those listed here, age of the equipment for example. Unless the equipment is put into an electrically safe work condition, electrical hazards exist and protection from those hazards is required. While in some cases a site may establish a policy that does not require PPE under conditions of extremely low risk, they are doing that with full knowledge that the risk, or likelihood of an event occurring is not zero, it is never zero as long as the equipment is energized. The titles at the top of the table should not say arc flash PPE required, yes or no, it should say high or low risk and the site has to then decide if they are going to require PPE to be worn. We cannot provide guidance from this document that says definitively, in all cases, without exception, that an individual will be safe without PPE even if the equipment is energized. That is a hazard/risk/likelihood evaluation that must be made, which is also a requirement of this document. Improvements have been made in the table, clearly, but this is not one of them. I am opposed to saying no PPE is required if the equipment is energized and the hazards are present. The text should be returned to the 2012 edition of 70E.

21 James B. Hayes Marcia L. Eblen Drake A. Drobnick The old document was better, and the Term (properly installed equipment ) is nebulus, and we should not sub for PPE, and there are other parts that are made i think un clear I think we are going the wrong way with this SR. The changes to the table made in this revision indicate that NO arc flash PPE is required for some activities (specifically operating equipment that has been properly installed and maintained). While the arc flash risk is low in this condition, it is not zero or gone. This in combination with the elimination of HRC 0 (PPE 0), will likely result in people wearing any clothing they choose. While section 130.7(C)(12) prohibits melting fabrics, the new tables do not specifically state that this section applies in all situations, even when the table indicates NO arc flash PPE required. By re titling the Table column header to PPE Required Y/N (PC 146) the Committee has created language that can easily be misconsd. The column provides a list of tasks that the Committee believes could create an arc flash hazard. Tasks marked yes (Y) require employee interaction, meaning they could create an initiating event. The column should more appropriately be titled "Likelihood of an Arc Flash Hazard Occurring." Another concern is the elimination of HRC 0. Previously the standard provided guidance for PPE when task exposures were at less than 1.2 calories. The new Tables provide no such guidance. As an example according to the new Tables, the normal operation of a 480 volt safety switch within a 36 arc flash boundary does not require PPE and does not disallow the employee from wearing a polyester tank top and shorts while performing this operation.

22 70E 2015 SR 45 Negative Statement Daleep Mohla The second revision SR 45 has some serious defects. These defects are so fundamental that an application of the provisions is likely to expose users to a greater risk than before. The fundamental defects in the table are: Conditions described in table 130.7(C) (15) (a) under which no arc flash PPE is required.i.e equipment is properly installed and maintained etc. It is indefensible and incorrect to state that no arc flash PPE is required under described conditions if equipment is energized. This can only be true if the equipment has been tested to withstand arcing fault conditions. Equipment not tested as Arc Resistant equipment is only tested for bolted faults. Informational Note 3 in 70E-2012 describes why bolted faults and arcing fault are entirely two different phenomena. The occurrence of an arcing fault inside an enclosure produces a variety of physical phenomena very different from a bolted fault. For example, the arc energy resulting from an arc developed in the air will cause a sudden pressure increase and localized overheating. 70E is permitting operation of non-arc resistant equipment with no arc flash PPE. Utilizing these conditions is not limited to any parameters of available short circuit current and overcurrent device clearing time. Following this table, there is no requirement for Arc Flash PPE, indoor or outdoor non arc resistant equipment, when operating a circuit breaker, switch, contactor, or starter up to 38 kv and 63,000 Amperes short circuit under the described conditions. Do we really want to find out equipment was not properly installed or maintained after an arc flash incident? Conditions under which an arc flash hazard exists and to be mitigated by use of PPE in table 130.7(15) (b) i.e. if equipment is not properly installed or maintained etc. Table (15) ((b) can only be used if maximum short circuit current and fault clearing times are known. The term equipment includes Overcurrent devices. Overcurrent device clearing time is dependent on maintenance of the equipment. Improper or inadequate maintenance can result in increased in opening time of overcurrent protective device thus increasing the incident energy it is infeasible to determine fault clearing time if equipment has not been properly maintained rendering the use of table totally useless for conditions for the equipment that has not been properly maintained. PPE for equipment not properly maintained cannot be selected from this table. Deletion of PPE 0 ( previously HRC 0) PPE Category 0 (previously HRC 0) has been deleted for all activities. HRC 0 as a minimum was required for all activities in the table. Now statement No arc flash PPE required will encourage operation of equipment in any clothing even in clothing made of materials such as flammable synthetic materials instead of non-melting fabrics required by HRC 0. HRC 0 required as a minimum Eye protection (safety glasses or safety goggles,) hearing protection (ear canal inserts) and heavy duty leather gloves for hand protection. Safety goggles or glasses, hearing protection and heavy duty leather gloves specified in HRC 0 will no longer be worn when people see certain operations do not require arc flash PPE. Hand injuries are most common due to the close proximity to the task. Previously, this protection from arc flash was provided by Heavy duty leather gloves even for HRC 0 According to 70E-2012, (10)(d) (1) Informational Note Heavy duty leather gloves have been shown to the have ATPV values in excess of 10 cal/cm2 1 of 2

23 70E 2015 SR 45 Negative Statement Daleep Mohla These tables will reduce the maintenance of the equipment..the 70E now provides an option to mitigate arc flash hazard by using PPE in Table 130.7(15)(b) even if equipment has not been properly installed or maintained.this is wrong message to send that arc flash PPE is a substitute for proper maintenance. Proper maintenance of equipment is essential The table (15) (a) permits normal operation of a circuit breaker, switch, contactor, or a starter is permitted without arc flash PPE. From experience, we all know, that most arc flash incidents occur during interaction with the equipment i.e. opening or closing operation The equipment is properly installed: How can a worker determine this? Just because it has been in service for 20 years does not guarantee that it was installed properly The equipment is properly maintained: How can a worker know this? Even if records or labels indicate recommended maintenance was done, this does not assure it was done properly. Maintenance normally is done at a frequency of one to five years depending on the equipment. How do we assure that equipment condition has not deteriorated to an unsafe level since the last maintenance? All equipment doors are closed and secured: A worker may be able to assess this by visual inspection All equipment covers are in place and secured: A worker may be able to assess this by visual inspection There is no evidence of impending failure: How can a worker assess this without opening doors or covers? If we could assess likelihood of impending failure by external inspection, infrared inspection and other diagnostic testing would not be necessary. The criteria listed in SR 45 suggest that risk of injury is determined by the equipment condition. There are two major reasons for disagreement with this rationale One: The arc flash hazard should be established by whether or not there is energy inside the equipment. If there is zero electrical energy inside the equipment, then No PPE would be a correct statement, however if there is electrical energy inside the equipment, then the PPE requirement should be based on the incident energy analysis and an assessment of the capability of the specific equipment to prevent or limit a worker s exposure to that energy. Two: The criteria listed in SR 45 ignore the possibility of human error in the installation, inspection and maintenance of electrical installations. Down playing this highly likely possibility by using the terms proper installation and proper maintenance as the default condition for establishing the need for PPE is counter to sound safety management practices. There is also possibility of human error on the part of the worker performing the task at hand and potentially at risk for serious injury will the worker follow the plan?, is it possible the worker may deviate from the plan? Is it possible the worker may make an error in equipment identification and be working in the wrong place/ etc., etc. If there is energy inside the equipment, a proper risk assessment may show there is residual risk, even if proper installation, proper maintenance, and enclosure integrity are verified. In my opinion, it is incorrect and inappropriate, and in some circles could be considered professionally unethical, to state No PPE Required without performing a hazard and risk assessment for the specific task and conditions current at that time. 2 of 2

24 SR 66, Section No (C)(16), See SR 66 Affirmative 20 Affirmative with Comment 1 Lee R. Hale The deletion of PPE Category 0 is problematic. We've "lost" the 100% cotton and heavy duty leather gloves component of PPE 0 and those requirements. With the new tables concept I can't see how to put this back in 130.7(C)(16)without a conflict to the rest of the standard. This needs to be addressed as a PI for Negative 3 Daleep C. Mohla PPE Category 0 (previously HRC 0) has been deleted for all activities. HRC 0 as a minimum was required for all activities in the table. Now statement No arc flash PPE required will encourage operation of equipment in any clothing even in clothing made of materials such as flammable synthetic materials instead of non melting fabrics required by HRC 0. HRC 0 required as a minimum Eye protection (safety glasses or safety goggles,) hearing protection (ear canal inserts) and heavy duty leather gloves for hand protection. Safety goggles or glasses, hearing protection and heavy duty leather gloves specified in HRC 0 will no longer be worn when people see certain operations do not require arc flash PPE. Hand injuries are most common due to the close proximity to the task. Previously, this protection from arc flash was provided by Heavy duty leather gloves even for HRC 0 According to 70E 2012, (10)(d) (1) Informational Note Heavy duty leather gloves have been shown to the have ATPV values in excess of 10 cal/cm2 James G. Stallcup I believe a Hazard/Risk Category 0 should be retained to provide a minimum risk category because facilities have their electrical safety program based on minimum requirements. Marcia L. Eblen Eliminating a specific definition of minimum clothing requirements below PPE 1 (HRC 1), without specific reference to (C)(12) will likely result in workers wearing melting and prohibited fabrics. Additionally, with the removal of PPE 0, other PPE is also not specifically shown as required e.g. hard hat and safety glasses. SR 42, Section No , See SR 42

25 SR 43, Section No , See SR 43 SR 39, Section No , See SR 39 SR 64, Section No , See SR 64 SR 46, Section No , See SR 46

26 SR 48, Section No , See SR 48 Note that the SR does not appear to indicate any change to this section. SR 49, Section No (C)(1), See SR 49 Total Voted : 25 For two third majority election, the affirmative votes needed are 16 For Simple majority, the affirmative votes needed are 13 SR 50, Section No (A)(1), See SR 50 Total Voted : 25 For two third majority election, the affirmative votes needed are 16 For Simple majority, the affirmative votes needed are 13

27 SR 51, Section No (A)(4), See SR 51 Total Voted : 25 For two third majority election, the affirmative votes needed are 16 For Simple majority, the affirmative votes needed are 13 SR 52, Section No (A)(5), See SR 52 SR 53, Section No (B)(1), See SR 53 Affirmative 22 Affirmative with Comment 1 Drake A. Drobnick The use of chemical goggles under a face shield is required where splash hazards exist. Goggles are listed as primary eye protection. The use of the word AND (PC 167) is correct. Rodney J. West While we agree with most of the revisions that resulted from SR53, we do not believe that adequate substantiation was provided to change the protective equipment requirements from Goggles or face shield to Goggles and face shield.

28 SR 54, Section No (B), See SR 54 SR 55, Section No , See SR 55 SR 65, Annex A, See SR 65 Marcia L. Eblen ASTM standards revision information in Annex A is not consistent with information approved by the TC at the second draft meeting. ASTM standards list the revision information in the number of the document, not separately. For example, ASTM F a is the correct representation of this standard, not (R2010a) listed after the document title.

29 SR 57, Sections B, See SR 57 Marcia L. Eblen ASTM standards revision information in Annex B is not consistent with information approved by the TC at the second draft meeting. ASTM standards list the revision information in the number of the document, not separately. For example, ASTM F a is the correct representation of this standard, not (R2010a) listed after the document title. SR 58, Section No. C.1.2.2, See SR 58 SR 73, Section No. C.2.1.1, See SR 73

30 SR 59, Section No. D.5.3, See SR 59 SR 60, Section No. F.3.1.5, See SR 60 SR 67, Section No. H.2, See SR 67 Affirmative 22 Affirmative with Comment 1 Lee R. Hale The revised text is now in alignment with the other PPE sections and requirments within the document. See my explanation of negative vote on SR 45.

31 SR 61, Section No. H.3, See SR 61 Rodney J. West While we agree with many of the revisions that result from SR61, we are voting negative to correlate with our vote and ballot comment on SR37. SR 62, Section No. O.2.3, See SR 62

Major Changes. Standard. TECH TOPIC standards and. By Peter Walsh, PE

Major Changes. Standard. TECH TOPIC standards and. By Peter Walsh, PE Major Changes to NFPA 70E Standard 2015 Edition TECH TOPIC standards and codes note 5 By Peter Walsh, PE Industrial Solutions Engineer Introduction NFPA 70E, Standard for Electrical Safety in the Workplace,

More information

Leader s Guide ERI Safety Videos

Leader s Guide ERI Safety Videos 1717 SAFE ELECTRICAL WORK PRACTICES & THE 2018 NFPA 70E Leader s Guide ERI Safety Videos SAFE ELECTRICAL WORK PRACTICES & THE 2018 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting

More information

Selection of Electrical PPE Tables

Selection of Electrical PPE Tables Selection of Electrical PPE Tables Instructions Table 1 - Starting with Table 1, select the task you plan to do (right-hand column) and the condition of the equipment you will be working on, (center column).

More information

Leader s Guide ERI Safety Videos

Leader s Guide ERI Safety Videos 1419 SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E Leader s Guide ERI Safety Videos SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a

More information

2012 NFPA 70E: Electrical Safety In The Workplace

2012 NFPA 70E: Electrical Safety In The Workplace ERI Safety Videos Preventing Injuries Through Employee Training 2984 2012 NFPA 70E: Electrical Safety In The Workplace Leader s Guide ERI Safety Videos 2012 NFPA 70E: Electrical Safety In The Workplace

More information

to the 2009 Edition Standards & Codes Introduction Background Byron Jordan Sr. Field Engineer

to the 2009 Edition Standards & Codes Introduction Background Byron Jordan Sr. Field Engineer Critical Changes to the NFPA 70E Standard Standards & Codes Note 2 Byron Jordan Sr. Field Engineer Introduction Since its inception in 1979, NFPA 70E: Standards for Electrical Safety in the Workplace has

More information

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace Technical Committee Members James Dollard,

More information

D Square Construction LLC

D Square Construction LLC D Square Construction LLC Lock Out-Tag Out (LOTO) and Zero Voltage Verification (ZVV) Process and Plan Energized Work Process and Permit - 1 - Table of Contents 1) Instruction for using Decision Tree Analysis

More information

Arc Flash 101. presented by Arc Flash Blaster LLC

Arc Flash 101. presented by Arc Flash Blaster LLC Arc Flash 101 presented by Arc Flash Blaster LLC ARC FLASH? ARC FLASH INCIDENT STANDARDS AND REGULATIONS Arc flash accidents... 35,000 F Molten Metal Pressure Waves Sound Waves Copper Vapour: (Solid to

More information

Appendix A: Energized Work Permit

Appendix A: Energized Work Permit Appendix A: Energized Work Permit Part I: To be completed by the Supervisor Description of Circuit & Equipment: Job Location: Description of Work to Be Done: Justification of why the circuit cannot be

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program The University Of Iowa Environmental Health & Safety 122 Grand Avenue Court Iowa City, IA 52242-1000 Phone: 319-335-8501 Date Revised/Reviewed: 6/8/2018 Table of Contents 1. Summary...

More information

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , , ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.331 335-29 CFR 1926.302, 1926.416, 1926.417 BASIS: The National Safety Council estimates that there are at least 300 deaths

More information

Electrical Safety For Managers Updated For E. ElectricalTrainingPro.com

Electrical Safety For Managers Updated For E. ElectricalTrainingPro.com Electrical Safety For Managers Updated For 2018 70E Daryn Lewellyn daryn@electricaltrainingpro.com ElectricalTrainingPro.com 877.393.9901 1 Fatalities From Exposure To Electricity 1992-334 Bureau of Labor

More information

NECA Personal Protective Equipment (PPE) Selector

NECA Personal Protective Equipment (PPE) Selector NECA Personal Protective Equipment (PPE) Selector Objectives Explain why electrical contractors should follow the precautions set forth in NFPA 70E List the hazards which demonstrate why an arc flash risk

More information

EFCOG Best Practice # 206

EFCOG Best Practice # 206 EFCOG Best Practice # 206 Title: Adoption of NFPA 70E 2018 in place of NFPA 70E 2015 Facility: DOE Complex Points of Contact: John (Jackie) McAlhaney EFCOG ESTG Past Chair, jackie.mcalhaney@srs.gov, 803-557-9002

More information

CSA Z462 2 nd TO 3 rd EDITION DIFFERENCES CHANGES & UPDATES

CSA Z462 2 nd TO 3 rd EDITION DIFFERENCES CHANGES & UPDATES CSA Z462 2 nd TO 3 rd EDITION DIFFERENCES CHANGES & UPDATES Provided to you by: Terry Becker, P.Eng., CESCP, IEEE Senior Member, Electrical Safety Expert CSA Z462 First Past Vice-Chair, Voting Member,

More information

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC 2017 NWHA TECHNICAL SEMINAR Arc Flash Hazard Awareness WHAT IS ARC FLASH Arc Flash is a short circuit that flashes from one exposed live part to another, or to ground The result is ionized air that creates

More information

Definitions found in several locations:

Definitions found in several locations: Definitions found in several locations: NFPA 70 - National Electric Code NFPA 70B Recommended Practice for Electrical Equipment Maintenance. NFPA 70E Electrical Safety in the Workplace OSHA 1910 Subpart

More information

Management Plan for Electrical Safety ISD #535

Management Plan for Electrical Safety ISD #535 Management Plan for Electrical Safety ISD #535 Health & Safety Office Maintenance Service Building 10 SE 9 ½ Street Rochester, MN 55904 507-328-4507 MANAGEMENT PLAN FOR ELECTRICAL SAFETY Table of Contents

More information

Why do I need to do an Arc-Flash Analysis?

Why do I need to do an Arc-Flash Analysis? Why do I need to do an Arc-Flash Analysis? Presented By Tom Norwood for Alexander Nizov, P.E. Principal/Manager Electrical Engineering Division TRAINING INSTITUTE, INC. A SUBSIDIARY OF MEGGER Hazards Analysis

More information

PURE H2O FORUM. Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program

PURE H2O FORUM. Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program Shenandoah Valley Wastewater Treatment Plant Network PURE H2O FORUM Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program September 25, 2015 Presenter: Steve

More information

ARC FLASH HAZARD ANALYSIS

ARC FLASH HAZARD ANALYSIS I. ARC FLASH HAZARD ANALYSIS IS REQUIRED ARC FLASH HAZARD ANALYSIS By Mike Lang Principal Field Engineer OSHA s 29 CFR Part 1910.132(d) states: The employer shall assess the workplace to determine if hazards

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program For Adopted LC-1005 Rev. 06/16 Page 1 I. Introduction As part of Organization s overall safety and health program, an

More information

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs.

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. The hazard level must be quantified and workers properly protected before entering

More information

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6 Procedure This electrical safety procedure structures safety procedures to meet the requirements of the NFPA-70E Standard. The program is designed for qualified employees who occasionally must perform

More information

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association General Requirements of the NEC Advanced Course Building Officials and Inspectors Educational Association General Requirements -NEC Course Outcome Explain general requirements found in Article 110 of the

More information

NFPA 70E What Changed? Keeping People Safe from Electrical Hazards for over 50 Years

NFPA 70E What Changed? Keeping People Safe from Electrical Hazards for over 50 Years NFPA 70E -2018 What Changed? Keeping People Safe from Electrical Hazards for over 50 Years Moderator Ron Spataro AVO Training Institute Marketing Manager Q&A Send us your questions and comments during

More information

arc flash hazard analysis

arc flash hazard analysis arc flash hazard analysis arc flash note 3 By mike lang, principal field engineer Arc Flash Hazard Analysis is Required OSHA s 29 CFR Part 1910.132(d) states: The employer shall assess the workplace to

More information

Arc Flash. Safety 21

Arc Flash. Safety 21 Arc Flash Safety 21 Arc Flash Introduction Electrical Hazards Safety Planning De-Energizing Equipment Working Hot Summary Introduction Most people don t think about electricity very much, which is surprising

More information

2018 NFPA 70E Significant Changes 7/27/2017. EFCOG Electrical Safety Task Group Workshop, July 2017

2018 NFPA 70E Significant Changes 7/27/2017. EFCOG Electrical Safety Task Group Workshop, July 2017 Significant Changes EFCOG Electrical Safety Task Group Workshop, July 2017 Appreciation Thanks to: Paul Dobrowsky creating the base PPT program Chair, Dave Dini for leading the Committee through the process

More information

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager Procedure No.: BMEHS-002.033 Page: 1 of 10 Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager Document Revision Change Table Revision Revision Description Revised Revision Number New By

More information

100 Questions on Electrical Safety Study Guide

100 Questions on Electrical Safety Study Guide 100 Questions on Electrical Safety Study Guide Be advised that only 95 of 100 questions are presented here for the purpose of discouraging cheating on the final exam. 1. Why is electrical safety important?

More information

This is (Enter Company Name Here) Arc Flash Prevention policy. (Enter Name Here) will be responsible for overall direction of the Safety Program.

This is (Enter Company Name Here) Arc Flash Prevention policy. (Enter Name Here) will be responsible for overall direction of the Safety Program. Company Name: Policy/Procedure ID Number: 222 Date: Grainger Safety Services Inc. 2012 Arc Flash Prevention Policy This is (Enter Company Name Here) Arc Flash Prevention policy. (Enter Name Here) will

More information

Removing Yourself from Hazards During Equipment Operation

Removing Yourself from Hazards During Equipment Operation Removing Yourself from Hazards During Equipment Operation The safest way to work around electrical equipment is to turn it off. This is usually required by OSHA and NFPA 70E, but with some exceptions.

More information

Progressive Safety Services LLC - All Rights Reserved

Progressive Safety Services LLC - All Rights Reserved Estimated that 2,000 workers are treated in specialized burn centers each year as a result of arc flash (Electrical Safety Foundation International). According to the National Safety Council, medical costs

More information

2015 Revision to NFPA 70E & CSA Z462

2015 Revision to NFPA 70E & CSA Z462 2015 Revision to NFPA 70E & CSA Z462 The only thing that is constant is change. -- Heraclitus (500 BC) There are few universal truths in life: The sun will rise in the east every morning. There is nothing

More information

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual SECTION 51 NFPA 70E POLICY Health & Safety Policy and 1. Protection Against Arc Flash A. Policy: An arc flash is a dangerous condition associated with the release of energy caused by an electric arc. An

More information

Public Comment No. 151-NFPA 70E-2016 [ Global Input ]

Public Comment No. 151-NFPA 70E-2016 [ Global Input ] of 403 9/2/2016 9:49 AM Public Comment No. 151-NFPA 70E-2016 [ Global Input ] Action Number 1 120.5(8)(c) (c) Equipment Approval. Temporary protective grounding equipment shall be approved. shall meet

More information

NFPA 70E, Proposed Changes. Electrical Safety in the Workplace NFPA Conference & Expo

NFPA 70E, Proposed Changes. Electrical Safety in the Workplace NFPA Conference & Expo 2017 NFPA Conference & Expo NFPA 70E, Electrical Safety in the Workplace Proposed Changes Presented by:: Paul Dobrowsky Innovative Technology Services Dave Dini Retired, Corporate Fellow Underwriters Laboratories

More information

ELECTRICAL SAFE WORK PRACTICES

ELECTRICAL SAFE WORK PRACTICES STAFF ELECTRIC ELECTRICAL SAFE WORK PRACTICES PURPOSE The purpose of this procedure is to protect all workers from injuries resulting from exposure to arc flash, arc blast and electrical shock and to comply

More information

Electrical Hazards: Overhead and underground power lines. tools. Ungrounded electrical systems and tools. in wet/damp environments

Electrical Hazards: Overhead and underground power lines. tools. Ungrounded electrical systems and tools. in wet/damp environments ELECTRICAL SAFETY Electrical hazards pose a serious threat to worker safety. Many workers are unaware of the potential electrical hazards present in their work environment which makes them more vulnerable

More information

Electrical Safety Program

Electrical Safety Program Facilities Operations and Development Environmental Health and Safety 1314 Kinnear Road #106 Columbus, OH 43212-1168 614-292-1284 Phone 614-292-6404 Fax www.ehs.osu.edu Electrical Safety Program Prepared

More information

IWU PHYSICAL PLANT SAFETY PROGRAM. Revision: 1 ELECTRICAL SAFETY Section: 4

IWU PHYSICAL PLANT SAFETY PROGRAM. Revision: 1 ELECTRICAL SAFETY Section: 4 STANDARDS Title 29 Code of Federal Regulations (CFR) Part 1910 Subpart S 301-399; NFPA 70E 2012 1.0 INTRODUCTION Electricity is a serious workplace hazard, capable of causing both employee injury and property

More information

USA Mobile, AL Electrical Safe Working Practices

USA Mobile, AL Electrical Safe Working Practices Compliance Compliance with these safe work practices is mandatory. Failure to comply may result in disciplinary action. These Safe Working Practices apply to any person performing electrical work at the

More information

Original Date of Issue: 04/09

Original Date of Issue: 04/09 POLICIES AND PROCEDURES DEPARTMENT: Environmental Health and Safety SUBJECT: Electrical Safety Program Original Date of Issue: 04/09 Reviewed 12/2011 Revised 12/2011 BACKGROUND ELECTRIC SHOCK It is well

More information

POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH

POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH ISU Senior Design Group: Dec15-22 Dan Dye Project Web Site: http://dec1522.sd.ece.iastate.edu/ Project Sponsor: CIPCO Project Advisor: Professor Mani

More information

By: Bruce Bowman, P.E.

By: Bruce Bowman, P.E. Welcome to The NFPA 70E Electrical Safety Presentation Updated for 2012 www.nfpa.org By: Bruce Bowman, P.E. What is the best way to prevent the hazards of electricity? Stop Think Options Protection - Before

More information

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks Selecting the right MCC equipment leads to improved plant safety, helping protect people and

More information

NFPA 70E Policies and Best Practices

NFPA 70E Policies and Best Practices NFPA 70E Policies and Best Practices Overview o Understand Compliance Requirements o Provide guidelines for a safe work environment o Effectively communicate policies to employees and customers o Express

More information

WHAT IS THE N.F.P.A. 70E

WHAT IS THE N.F.P.A. 70E WHAT IS THE N.F.P.A. 70E N.F.P.A. 70E Standard for Electrical Safety in the Workplaces HAZARDS of ELECTRICITY FIRE-Faulty wiring-building fires. Clothing fires(arc flash). SHOCK-When electrical current

More information

Electrical Safety Program

Electrical Safety Program Safety Manual Page 1 of 53 1. Purpose A. The purpose of the USPL (the Program ) is to provide a practical, safe working environment for USPL employees and contractors regarding the hazards arising from

More information

Welcome to this training session about arc flash. In this session, we ll talk about the hazards and risks of working around exposed, energized

Welcome to this training session about arc flash. In this session, we ll talk about the hazards and risks of working around exposed, energized Welcome to this training session about arc flash. In this session, we ll talk about the hazards and risks of working around exposed, energized electrical equipment. We ll also discuss common arc flash

More information

The Pennsylvania State University Energized Electrical Safety Program

The Pennsylvania State University Energized Electrical Safety Program Introduction: The Pennsylvania State University Energized Electrical Safety Program Purpose: Electricity is a serious workplace hazard, capable of causing both employee injury and property damage. It is

More information

2018 NFPA 70E Electrical Safe work practices

2018 NFPA 70E Electrical Safe work practices This course provides a thorough knowledge of the dangers and recommended safe behaviors for those who work daily around electrical hazards. This course goes into examples of real life application to give

More information

CALIFORNIA STATE UNIVERSITY, LOS ANGELES ELECTRICAL SAFETY PROGRAM

CALIFORNIA STATE UNIVERSITY, LOS ANGELES ELECTRICAL SAFETY PROGRAM CALIFORNIA STATE UNIVERSITY, LOS ANGELES ELECTRICAL SAFETY PROGRAM January 2017 PROGRAM APPROVAL AND AUTHORIZATION William A. Covino, President Date TABLE OF CONTENTS TITLE SECTION PURPOSE 1.0 ORGANIZATIONS

More information

Environmental, Health and Safety. Electrical Safety in the Workplace Program

Environmental, Health and Safety. Electrical Safety in the Workplace Program Environmental, Health and Safety Electrical Safety in the Workplace Program September 2016 Table of Contents 1.0 Purpose... 1 2.0 Scope... 1 3.0 Definitions... 2 4.0 Responsibilities... 7 5.0 Requirements...

More information

LOCKOUT/TAGOUT PROGRAM

LOCKOUT/TAGOUT PROGRAM LOCKOUT/TAGOUT PROGRAM HOW CLIMATE ENGINEERS INC. COMPLIES WITH THELO/TO STANDARD It is the intent of Climate Engineers Inc. to comply with OSHA s Control of Hazardous Energy Standard (1910.147). The following

More information

Lockout/Tagout - Energy Control Program

Lockout/Tagout - Energy Control Program Lockout/Tagout - Energy Control Program Lockout and Tagging of ELECTRICAL Circuits This portion of the K.R. Miller Contractors, Inc. safety program has been created to maintain a written copy of procedures

More information

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY 1. CONTROL OF HAZARDOUS ENERGY POLICY AND PROCEDURES A. OSHA References: 29 CFR 1910.147, 29 CFR 1910.332, 29 CFR 1910.333, 29 CFR 1926.417 B.

More information

Lockout / Tagout Safety Program

Lockout / Tagout Safety Program Lockout / Tagout Safety Program Prepared by: The Ohio State University Environmental Health and Safety Occupational Safety & Industrial Hygiene 1314 Kinnear Road Columbus, OH 43212-1168 614-292-1284 Phone

More information

Lockout/Energy Control

Lockout/Energy Control Lockout/Energy Control Presented By: Sotaris, LLP 2000 Auburn Drive, Suite 200 Beachwood, Ohio 44122 P: 216-378-7650 F: 866-794-5756 W: www.sotaris.com E: awj@sotaris.com 1 About Me Andrew W. Johnson,

More information

Electrical Safety Work Practices

Electrical Safety Work Practices Work Practices I. SCOPE This program covers any SOUTHWESTERN COMMUNITY COLLEGE employee that may work or be exposed to exposed electrical systems: To assure that employees are not exposed to potentially

More information

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY FALL HAZARD CONTROL REQUIREMENTS SERIES & NO. SMI - 157

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY FALL HAZARD CONTROL REQUIREMENTS SERIES & NO. SMI - 157 1 of 6 1.0 PURPOSE To establish minimum requirements and guidelines for controlling hazardous exposure of personnel to falls from working elevations in conformance with Federal and State OSHA rules and

More information

Best Practice #207. Facility: Entire DOE Complex. Best Practice Title: Identification of Look-Alike Electrical Equipment

Best Practice #207. Facility: Entire DOE Complex. Best Practice Title: Identification of Look-Alike Electrical Equipment Best Practice #207 Facility: Entire DOE Complex Best Practice Title: Identification of Look-Alike Electrical Equipment Point of Contact: Stephanie Collins, LBNL, SLCollins@lbl.gov, 510-486-4914; Mark Mathews,

More information

Arc flash versus arc resistant; different concerns

Arc flash versus arc resistant; different concerns Technical Collection Technical paper N PCIC Middle-East -78 Arc flash versus arc resistant; different concerns Didier FULCHIRON, Schneider Electric France. Abstract "Arc flash" and "arc resistant" terms

More information

SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment CAT A-1 SOP #4

SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment CAT A-1 SOP #4 SUNCOR ENERGY PRODUCTS DISTRIBUTION TERMINAL OPERATING MANUAL STANDARD OPERATING PROCEDURE SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment Lifesaving Rules Supporting Document Verify

More information

Ground Fault Circuit Interrupter(GFCI) Policy

Ground Fault Circuit Interrupter(GFCI) Policy NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com

More information

Electrical. OSHA Office of Training and Education 1

Electrical. OSHA Office of Training and Education 1 Electrical OSHA Office of Training and Education 1 Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program 6300-3.1 Associated OHS Process: General Industry and Construction Safety The master copy of this document resides in electronic format. Printed copies of this document are for

More information

Purpose. Scope. Process flow OPERATING PROCEDURE 07: HAZARD LOG MANAGEMENT

Purpose. Scope. Process flow OPERATING PROCEDURE 07: HAZARD LOG MANAGEMENT SYDNEY TRAINS SAFETY MANAGEMENT SYSTEM OPERATING PROCEDURE 07: HAZARD LOG MANAGEMENT Purpose Scope Process flow This operating procedure supports SMS-07-SP-3067 Manage Safety Change and establishes the

More information

SPECIALIZED ONLINE TRAINING COURSE LIST

SPECIALIZED ONLINE TRAINING COURSE LIST SPECIALIZED ONLINE TRAINING COURSE LIST Grainger Online Safety Manager provides you with access to online training courses covering today's most relevant safety topics. The training content is designed

More information

2100 ELECTRICAL SAFETY PROGRAM

2100 ELECTRICAL SAFETY PROGRAM 2100 ELECTRICAL SAFETY PROGRAM Document History Version Date Comments 0.1 For Internal Review 1.0 May 13, 2016 Final Version 2.0 May 10, 2017 Annual Review 2.1 July 21, 2017 Formatting changes. Updated

More information

Electrical & Arc Flash Safety Program 2007

Electrical & Arc Flash Safety Program 2007 University of Louisville Physical Plant Department Electrical & Arc Flash Safety Program 2007 Introduction Electricity is a serious workplace hazard, capable of causing both employee injury and property

More information

Recommended Facilitator Notes: (read the following text out-loud to participants while showing this slide)

Recommended Facilitator Notes: (read the following text out-loud to participants while showing this slide) Slide 1 Confined Space Entry for General Industry These materials have been developed based on applicable federal laws and regulations in place at the time the materials were created. The program is being

More information

Electrical Safety PPT-SM-ELECTSFTY V.A.0.0

Electrical Safety PPT-SM-ELECTSFTY V.A.0.0 Electrical Safety 1 Electrical Safety OSHA s electrical safety standard covers Work on or near exposed energized equipment Proper use of electrical protective equipment Safe use of portable electric equipment

More information

2. The purpose of this program is to achieve the following objectives:

2. The purpose of this program is to achieve the following objectives: Section 16A. Lockout and Tagout Program 1. In the course of their duties, personnel at the TFREC may need to secure controls, switches, and equipment in order to prevent injury caused by the sudden, unexpected

More information

Lock Out/Tag Out Control of Hazardous Energy

Lock Out/Tag Out Control of Hazardous Energy Lock Out/Tag Out Control of Hazardous Energy University Facilities Internal Procedure: July 1, 2013 Effective date: July 1, 2013 Last Modified: April 2013 Approved by: Bob Wells 1.0 Program Objective UF

More information

Pulp & Paper Electrical Safety

Pulp & Paper Electrical Safety Pulp & Paper Electrical Safety Ties to LOTO and NFPA 70E Contact Info: Brian Downie Group Manager Faith Technologies, Inc. PO Box 627 Appleton, WI 54944 800-274-2345 ext. 6513 www.faitherm.com Today s

More information

HIGH-IMPACT SAFETY TRAINING FOR QUALIFIED ELECTRICAL WORKERS

HIGH-IMPACT SAFETY TRAINING FOR QUALIFIED ELECTRICAL WORKERS HIGH-IMPACT SAFETY TRAINING FOR QUALIFIED ELECTRICAL WORKERS This easy-to-use Leaders Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description

More information

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Electrical Safety Standard

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Electrical Safety Standard CITY AND COUNTY OF DENVER CR&CF RISK UNIT 65.5.3 Electrical Safety Standard 1.0 Introduction 2.0 Scope The purpose of this standard is to establish safe work practices that are intended to prevent electric

More information

Elements of a Lockout/Tagout Program OSHA

Elements of a Lockout/Tagout Program OSHA September 15, 2015 Elements of a Lockout/Tagout Program OSHA 1910.147 Dayna Noble Industrial Safety Consultant Specialist Ohio BWC 567-204-8917 Dayna.noble@bwc.state.oh.us Top 10 most frequently cited

More information

Risk Assessment Procedure

Risk Assessment Procedure Voltage, current testing, troubleshooting Infrared inspection Visual inspection, data collecting Risk Register ES Acc 6 4 1 1 6 36 ES < Acc 6 4 3 3 10 60 AF/AB 40 Acc 8 3 2

More information

ENVIRONMENTAL HEALTH AND SAFETY PERSONAL PROTECTIVE EQUIPMENT

ENVIRONMENTAL HEALTH AND SAFETY PERSONAL PROTECTIVE EQUIPMENT ENVIRONMENTAL HEALTH AND SAFETY PERSONAL PROTECTIVE EQUIPMENT PERSONAL PROTECTIVE EQUIPMENT Table of Contents A. Scope... 1 B. General Requirements... 1 C. Responsibility... 1 1. Supervisor... 1 2. Department

More information

Personal Protective Equipment Program

Personal Protective Equipment Program Personal Protective Equipment Program Document History Version Date Comments 0.1 June, 2017 Pinnacle Draft 0.2 August, 2017 FM-OHS Internal Review 1.0 November, 2017 Final Version Table of Contents Definitions...

More information

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT)

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT) PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT) WAC Page 296-307-320 Control of hazardous energy (lockout-tagout). 1 296-307-32001 What does this section cover? 1 296-307-32003 When does this section

More information

Electrical Workplace Safety. Top 10 Mistakes. 1. The 100 cal/cm² Delusion: The err-onthe-side-of-safetymistake

Electrical Workplace Safety. Top 10 Mistakes. 1. The 100 cal/cm² Delusion: The err-onthe-side-of-safetymistake Top 10 Mistakes 1. The 100 cal/cm² Delusion: The err-onthe-side-of-safetymistake Hazards Arc Flash How Bad is Bad? How much protection would work in this arc? Is over protection a good idea? What works

More information

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.147 BASIS: Approximately three million workers in the United States face risks from uncontrolled energy when servicing machinery

More information

University of Vermont Department of Physical Plant Burlington, Vermont

University of Vermont Department of Physical Plant Burlington, Vermont University of Vermont Department of Physical Plant Burlington, Vermont CONTROL OF HAZARDOUS ENERGY SOURCES AND ELECTRICAL HAZARDS LOCKOUT AND TAGOUT PROGRAM in accordance with OSHA 29 CFR 1910.147 REVISED

More information

UNDERSTANDING ARC FLASH REQUIREMENTS

UNDERSTANDING ARC FLASH REQUIREMENTS UNDERSTANDING ARC FLASH REQUIREMENTS With an Introduction to arc flash labeling Provided by: Leaders in Arc Flash Labeling Page 1 Table of Contents Section Subject Page 1 Arc Flash Background 3 2 Types

More information

Hazardous Energy Control (Lockout-Tagout)

Hazardous Energy Control (Lockout-Tagout) Hazardous Energy Control (Lockout-Tagout) The purpose of this program is to prevent inadvertent operation or energization of machines, equipment, or processes in order to protect employees and establish

More information

Safe Work Practices and Permit-to-Work System

Safe Work Practices and Permit-to-Work System CHAPTER 24 Safe Work Practices and Permit-to-Work System 24.1 INTRODUCTION OSHA s Process Safety Management (PSM) Standard (OSHA, 1992) requires employers to develop and implement safe work practices (SWPs)

More information

Portland Community College Facilities Management Services ENERGIZED ELECTRICAL WORK PERMIT AND WORK PLAN

Portland Community College Facilities Management Services ENERGIZED ELECTRICAL WORK PERMIT AND WORK PLAN Portland Community College Facilities Management Services ENERGIZED ELECTRICAL WORK PERMIT AND WORK PLAN Section 1 - PROJECT INFORMATION Project Work Request No. Building Room/Location Equip. Serial No.

More information

ARKANSAS TECH UNIVERSITY FACILITIES MANAGEMENT HEALTH AND SAFETY MANUAL (LOCKOUT/TAGOUT) 30.0

ARKANSAS TECH UNIVERSITY FACILITIES MANAGEMENT HEALTH AND SAFETY MANUAL (LOCKOUT/TAGOUT) 30.0 () 30.0 The purpose of the Energy Control Policy (Lockout/Tagout) is to ensure that before any employee performs any servicing and/or maintenance on machinery or equipment, where the unexpected energizing,

More information

THE CONTROLLED COPY OF THIS DOCUMENT IS ON THE COMPUTER NETWORK PRINTED COPIES ARE ONLY CURRENT FOR THE DATE AT THE BOTTOM OF THE PAGE.

THE CONTROLLED COPY OF THIS DOCUMENT IS ON THE COMPUTER NETWORK PRINTED COPIES ARE ONLY CURRENT FOR THE DATE AT THE BOTTOM OF THE PAGE. TE CONTROLLED COPY OF TIS DOCUMENT IS ON TE COMPUTER NETWORK PRINTED COPIES ARE ONLY CURRENT FOR TE DATE AT TE BOTTOM OF TE PAGE. Title Using Angle Grinders SWMS No. 8 Authorized and email Signed by the

More information

Electrical Safety. Hazard Awareness

Electrical Safety. Hazard Awareness Electrical Safety Hazard Awareness What does Hazard mean? Hazard means: any potential or actual threat to the wellbeing of people, machinery or environment Electrical hazard safety means: taking precautions

More information

Northern Kentucky University Issue Date: 11/02/2018 Revised Date: Title: PERSONAL PROTECTIVE EQUIPMENT PROCEDURE OBJECTIVE AND PURPOSE

Northern Kentucky University Issue Date: 11/02/2018 Revised Date: Title: PERSONAL PROTECTIVE EQUIPMENT PROCEDURE OBJECTIVE AND PURPOSE Northern Kentucky University Issue Date: 11/02/2018 Revised Date: Policy Link: Occupational Safety Policy Title: PERSONAL PROTECTIVE EQUIPMENT PROCEDURE OBJECTIVE AND PURPOSE The objective of this procedure

More information

29. Personal Protective Equipment

29. Personal Protective Equipment 29. Personal Protective Equipment This Personal Protective Equipment (PPE) procedure has been prepared to inform employees of potential hazards in the workplace and to identify the proper PPE to be used

More information

PERSONAL PROTECTIVE EQUIPMENT PROGRAM INTERNAL AND EXTERNAL PAGE: 1 DEPARTMENT: ALL OF: 5

PERSONAL PROTECTIVE EQUIPMENT PROGRAM INTERNAL AND EXTERNAL PAGE: 1 DEPARTMENT: ALL OF: 5 INTERNAL AND EXTERNAL PAGE: 1 1.0 OBJECTIVE The Federal Occupational Safety and Health Administration (OSHA) requirements for personal protective equipment (PPE) are presented in 29 CFR 1910.132 General

More information

Electrical Hazard Assessments: OSHA & The NFPA 70E?

Electrical Hazard Assessments: OSHA & The NFPA 70E? Electrical Hazard Assessments: OSHA & The NFPA 70E? AWEA Health & Safety Mike Moore Key Learning Objectives Key Learning's Statistical Electrical Incidents & Injuries What Does OSHA Want? A quick Glimpse

More information

PERSONAL PROTECTIVE EQUIPMENT SAFETY PROGRAM

PERSONAL PROTECTIVE EQUIPMENT SAFETY PROGRAM PERSONAL PROTECTIVE EQUIPMENT SAFETY PROGRAM REGULATORY STANDARD: 29 CFR 1910.132-138. BASIS: This safety program establishes the requirements to ensure protective equipment is provided, where required,

More information