1 VERSAFLOW VORTEX Handbook Vortex flowmeter

2 : IMPRINT :::::::::::::::::::::::::::::::::::::::::: V Notices and Trademarks Copyright 2013 by Honeywell WARRANTY/REMEDY Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use. While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application. Honeywell Field Solutions 512 Virginia Drive Fort Washington, PA

3 VERSAFLOW VORTEX ABOUT THIS DOCUMENT Abstract This document provides descriptions and procedures for the Installation, Configuration, Operation, and Troubleshooting of your device. Contacts World Wide Web: The following lists Honeywell s World Wide Web sites that will be of interest to our customers. Honeywell Organization Corporate Field Solutions Technical tips WWW Address (URL) Telephone: Contact us by telephone at the numbers listed below. Organization United States and Canada Honeywell Phone Number Tech. Support: Service:

4 ABOUT THIS DOCUMENT VERSAFLOW VORTEX 4

5 VERSAFLOW VORTEX CONTENTS 1 Safety instructions Intended use Certifications Safety instructions from the manufacturer Copyright and data protection Disclaimer Product liability and warranty Information concerning the documentation Warnings and symbols used Safety instructions for the operator Device description Scope of delivery Device versions Devices with connection flange Sandwich version Devices for dual measurement and twofold reliability Device version remote Device description Free air delivery measurement - FAD (optional) Gross heat meter Dual seal Nameplate Installation Notes on installation Storage Transport Installation conditions Measurement of liquids Measurement of vapours and gases Pipelines with control valve Preferred mounting position Turning the connection housing Turning the display Heat insulation Inlet and outlet runs Minimum inlet runs Minimum outlet runs Flow straightener Installation General installation notes Installing devices in flange design Installing devices in sandwich design

6 CONTENTS VERSAFLOW VORTEX 4 Electrical connections Safety instructions Connecting the signal converter Electrical connection of current and pulse output Power supply Totalizer / pulse output Remote version connection Grounding connections Protection category Start-up Start Start-up and control Operation Display and operating elements Operating principles Functional description of the keys Switch from measuring mode to menu mode Navigation within the menu structure Changing the settings in the menu Changing units Measures in the event of faulty indications Overview of the most important functions and units Error messages Menu structure Overview of firmware versions Entering values in change mode Character selection in change mode Menu item Quick Setup Menu item Tests Menu item Setup (firmware version - basic) Menu item Setup (firmware version - steam) Menu item Setup (firmware version - gas) Service Replacing signal converter / LC display Spare parts availability Availability of services Returning the device to the manufacturer General information Form (for copying) to accompany a returned device Disposal

7 VERSAFLOW VORTEX CONTENTS 8 Technical data Functional principle Technical data Dimensions and weights Flange versions Sandwich version Dimensions remote version Flow tables

8 CONTENTS VERSAFLOW VORTEX 8

9 VERSAFLOW VORTEX SAFETY INSTRUCTIONS Intended use The vortex flowmeters are made to measure the flow of gases, vapours and liquids. The devices are particularly suitable for the measurement of: Clean liquids with low viscosity (< 10 cp) Hydrocarbons with low viscosity (< 10 cp) Water Chemicals with low corrosiveness Saturated steam Superheated steam, including CIP and SIP applications in the food industry Industrial gases The devices are rated for the following flow velocities: Liquids: m/s / ft/s Gases and steam: m/s / ft/s DN15: m/s / ft/s; DN25: m/s / ft/s If the danger of waterhammers can occur in steam networks appropriate condensate separators have to be installed. Suitable measures must be taken to avoid water cavitation if it is a possible risk. CAUTION! Responsibility for the use of the measurement devices with regard to suitability, intended use and corrosion resistance of the used materials against the measured fluid lies solely with the operator. The sensors are made from Stainless Steel 316 L (1.4404) or Hastelloy C22. In your project planning, please observe the data given in the corrosion tables. The pressure-bearing parts have been designed and rated for stationary operation taking into account the maximum pressure and temperature. Observe the data indicated on the nameplate for PS, TS and PT (PED 97/23/EC). External forces and moments, caused e.g. by pipe stresses, have not been taken into account. Primarily, volumetric flow and temperature are measured, with pressure measurement as an option. From these parameters the measuring device calculates the mass flow or standard volumetric flow using pre-programmed density data and then exports the measured values via various communication interfaces. 9

10 1 SAFETY INSTRUCTIONS VERSAFLOW VORTEX 1.2 Certifications CE marking The device fulfils the statutory requirements of the following EC directives: Pressure Equipment Directive 97/23/EC EMC Directive 2004/108/EC as well as EN EMC specification acc. to EN 61326/A1 NAMUR recommendations NE 21 and NE 43 The manufacturer certifies successful testing of the product by applying the CE marking. 10

11 VERSAFLOW VORTEX SAFETY INSTRUCTIONS Safety instructions from the manufacturer Copyright and data protection Disclaimer The contents of this document have been created with great care. Nevertheless, we provide no guarantee that the contents are correct, complete or up-to-date. The contents and works in this document are subject to copyright. Contributions from third parties are identified as such. Reproduction, processing, dissemination and any type of use beyond what is permitted under copyright requires written authorisation from the respective author and/or the manufacturer. The manufacturer tries always to observe the copyrights of others, and to draw on works created in-house or works in the public domain. The collection of personal data (such as names, street addresses or addresses) in the manufacturer's documents is always on a voluntary basis whenever possible. Whenever feasible, it is always possible to make use of the offerings and services without providing any personal data. We draw your attention to the fact that data transmission over the Internet (e.g. when communicating by ) may involve gaps in security. It is not possible to protect such data completely against access by third parties. We hereby expressly prohibit the use of the contact data published as part of our duty to publish an imprint for the purpose of sending us any advertising or informational materials that we have not expressly requested. The manufacturer will not be liable for any damage of any kind by using its product, including, but not limited to direct, indirect or incidental and consequential damages. This disclaimer does not apply in case the manufacturer has acted on purpose or with gross negligence. In the event any applicable law does not allow such limitations on implied warranties or the exclusion of limitation of certain damages, you may, if such law applies to you, not be subject to some or all of the above disclaimer, exclusions or limitations. Any product purchased from the manufacturer is warranted in accordance with the relevant product documentation and our Terms and Conditions of Sale. The manufacturer reserves the right to alter the content of its documents, including this disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable in any way for possible consequences of such changes. 11

12 1 SAFETY INSTRUCTIONS VERSAFLOW VORTEX Product liability and warranty The operator shall bear responsibility for the suitability of the device for the specific purpose. The manufacturer accepts no liability for the consequences of misuse by the operator. Improper installation and operation of the devices (systems) will cause the warranty to be void. The respective "Standard Terms and Conditions" which form the basis for the sales contract shall also apply Information concerning the documentation To prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards, safety requirements and accident prevention regulations. If this document is not in your native language and if you have any problems understanding the text, we advise you to contact your local office for assistance. The manufacturer can not accept responsibility for any damage or injury caused by misunderstanding of the information in this document. This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. Special considerations and precautions are also described in the document, which appear in the form of underneath icons. 12

13 VERSAFLOW VORTEX SAFETY INSTRUCTIONS Warnings and symbols used Safety warnings are indicated by the following symbols. DANGER! This information refers to the immediate danger when working with electricity. DANGER! This warning refers to the immediate danger of burns caused by heat or hot surfaces. DANGER! This warning refers to the immediate danger when using this device in a hazardous atmosphere. DANGER! These warnings must be observed without fail. Even partial disregard of this warning can lead to serious health problems and even death. There is also the risk of seriously damaging the device or parts of the operator's plant. WARNING! Disregarding this safety warning, even if only in part, poses the risk of serious health problems. There is also the risk of damaging the device or parts of the operator's plant. CAUTION! Disregarding these instructions can result in damage to the device or to parts of the operator's plant. INFORMATION! These instructions contain important information for the handling of the device. LEGAL NOTICE! This note contains information on statutory directives and standards. HANDLING This symbol designates all instructions for actions to be carried out by the operator in the specified sequence. i RESULT This symbol refers to all important consequences of the previous actions. 1.4 Safety instructions for the operator WARNING! In general, devices from the manufacturer may only be installed, commissioned, operated and maintained by properly trained and authorized personnel. This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. 13

14 1 SAFETY INSTRUCTIONS VERSAFLOW VORTEX 14

15 VERSAFLOW VORTEX DEVICE DESCRIPTION Scope of delivery INFORMATION! Inspect the cartons carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer. INFORMATION! Do a check of the packing list to make sure that you have all the elements given in the order. INFORMATION! Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate. Figure 2-1: Scope of delivery 1 Measuring device in ordered version 2 Quick Start 3 Certificates, calibration report and parameter datasheet 4 CD with complete documentation 5 Bar magnet 2.2 Device versions The devices are delivered in the following variants: Signal converter with display Flange Version, Sensor: F Sandwich version, Sensor: S Remote version - Sensor with on-site remote converter The following designs are available as options: with pressure sensor with shut-off valve for the pressure sensor Flange version with single reduction, Sensor: FR Flange version with double reduction, Sensor: F2R 15

16 2 DEVICE DESCRIPTION VERSAFLOW VORTEX Devices with connection flange The measuring system consists of a measuring sensor and a signal converter. These elements form a permanent mechanical unit. Figure 2-2: Flanged devices with display 1 Version with temperature sensor 2 Version with temperature sensor and optional pressure sensor 3 Version with temperature sensor, optional pressure sensor and shut-off valve 4 Version flange-sensor with inlet reduction Sandwich version The sandwich version features 2 centring rings to aid with installation. Figure 2-3: Sandwich versions with display 1 Version with temperature sensor 2 Version with temperature sensor and optional pressure sensor 3 Version with temperature sensor, optional pressure sensor and shut-off valve 16

17 VERSAFLOW VORTEX DEVICE DESCRIPTION Devices for dual measurement and twofold reliability This is a genuine redundant system with two independent measuring sensors and two signal converters. This provides twofold functional reliability and availability of the measurement. This variant is ideally suited for measurements in multi-product pipelines. In such pipelines, two different products are moved through one after the other. One signal converter can be programmed for one product, and the other signal converter for the other product Device version remote 1 Sensor terminal box 2 Sensor 3 Signal converter 4 Wall mount bracket connection box With the remote variant, sensors and converters are separate. The 10-pin, shielded connection cable may not exceed 15m in length. 17

18 2 DEVICE DESCRIPTION VERSAFLOW VORTEX Device description Figure 2-4: Device description 1 Signal converter 2 Cable feedthrough grey, standard version 3 Pressure sensor, optional 4 Shut-off valve, optional 5 Measuring sensor 6 Centering ring Free air delivery measurement - FAD (optional) A (air) compressor draws air from the ambient atmosphere, compresses it and delivers it at the required pressure. Since the ambient atmosphere also contains water vapour, what the compressor draws in is a mixture of air and water vapour. Free air delivery measurement is to be understood under this condition. Most manufacturers specify free air delivery only at standard intake conditions. What the user ultimately requires as process air must first be determined before measuring can take place with an accuracy of ±1%. The vortex flowmeter with the optional FAD function can measure the free air delivery online, humidity and speed compensated, regardless of its function as standard flowmeter. The integrated software evaluates the free air delivery automatically online. The menu-driven, user-friendly software prompts the operator to enter the pressure, relative humidity, the required as well as current discharge pressure. The steam tables and compressibility tables are saved as standard. The measuring device is optionally available with a pressure sensor which measures the discharge pressure online, making manual input of the values unnecessary. 18

19 VERSAFLOW VORTEX DEVICE DESCRIPTION Gross heat meter In almost all applications with saturated steam, the steam is used for heating. It is much more interesting to know how great the heat flow volume is that is available to the process, than to know how great the flow is in kg/h. As the enthalpy of steam changes with the temperature, it cannot be assumed as a constant. The vortex flowmeter has a special feature that can calculate the flow of vapour and water as power output. The enthalpy tables are permanently programmed in the memory of the device. The online density-compensated mass flow is multiplied by the correct enthalpy to obtain the flow as power output. Power {Q H ] = mass flow [Q m ] x enthalpy [H] If the gross heat meter is activated, both the totalizer for the absolute steam consumption as well as that for the energy run internally. 19

20 2 DEVICE DESCRIPTION VERSAFLOW VORTEX Dual seal To cover the requirements of ANSI/ISA Requirements for Process Sealing Between Electrical Systems and Flammable or Combustible Process Fluid Dual seal, a membrane vent is integrated in the neck of the instrument. This vent works in the improbable case of a leakage as an annunciation valve between the primary seal (Process) and secondary seal (electronic compartment). 1 Annunciation valve (Membrane vent) The sealing between the pick-up and the Flow tube is considered as the primary seal. Its construction material is always the same as the Flow tube itself (e.g. Stainless steel 316L or Hastelloy C22). Chemicals used for the process, going through the Flow tube, must be compatible with the designated material. By using the membrane vent as annunciation valve, all requirements for a dual seal device in accordance to above mentioned standard, are fulfilled. It protects the electronic compartment against access by process media, due to possible leakages. The leakage of the primary seal is visible. Regular maintenance should be performed by the customer to ensure this Dual Seal notification system is working properly or that there is no leak. If a leakage is noticed: The manufacturer service should be contacted for servicing or replacement of the meter. 20

21 VERSAFLOW VORTEX DEVICE DESCRIPTION Nameplate INFORMATION! Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate. Figure 2-5: Example for nameplate 1 Device type 2 Manufacturer 3 Sensor: S - Sandwich F - Flange FR - Flange single reduced F2R - Flange double reduced 4 Notified ATEX & DGRL bodies (only available if this option was ordered) 5 Connection data: nominal diameter and pressure rating 6 PED data 7 Ex data (only available if this option was ordered) 8 Electrical connection data 9 Manufacturer's website Figure 2-6: Example for nameplate 1 Serial number 2 Order Number 3 Type code 4 Item number 5 Fluid data 6 Software variant 7 TAG number 21

22 2 DEVICE DESCRIPTION VERSAFLOW VORTEX 22

23 VERSAFLOW VORTEX INSTALLATION Notes on installation INFORMATION! Inspect the cartons carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer. INFORMATION! Do a check of the packing list to make sure that you have all the elements given in the order. INFORMATION! Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate. 3.2 Storage Store the device in a dry and dust-free location. Avoid extended direct exposure to the sun. Store the device in its original packing. The permissible storage temperature for standard devices is C / F. 3.3 Transport Use lifting straps wrapped around both process connections for transport. Do not lift measuring devices by the signal converter housing for transport. Never lift the measuring device by the pressure sensor. Do not use lifting chains as they may damage the housing. Figure 3-1: Transport instructions CAUTION! Non-secured devices can pose risk of injury. The centre of mass of the device is often higher than the point at which the lifting straps are attached. Prevent the measuring device from sliding or rotating accidentally. 23

24 3 INSTALLATION VERSAFLOW VORTEX 3.4 Installation conditions INFORMATION! For accurate volumetric flow measurement the measuring device needs a completely filled pipe and a fully developed flow profile. Please observe the instructions regarding inlet and outlet pipe runs as well as the installation position. In the event of vibrations on the piping, select the installation site so that the vibrations are at their lowest in a transverse direction to the flowmeter. CAUTION! When installing the device in the piping, the following points must be observed: Nominal diameter of connection pipe flange = nominal flange diameter of pipe! Use flanges with smooth holes, e.g. welding neck flanges. Align carefully the holes of the connecting flange and the flowmeter flange. Check the compatibility of the gasket material with the process product. Make sure that the gaskets are arranged concentrically. The flange gaskets must not project into the pipe cross-section. The flanges have to be concentric. There must not be any pipe bends, valves, flaps or other internals in the immediate inlet run. Devices in sandwich version may only be installed using a centering ring. Never install the device directly behind piston compressors or rotary piston meters. Do not lay signal cables directly next to cables for the power supply. INFORMATION! If the danger of waterhammers can occur in steam networks appropriate condensate separators have to be installed. Suitable measures must be taken to avoid water cavitation if it is a possible risk. 24

25 VERSAFLOW VORTEX INSTALLATION Measurement of liquids Prohibited installation Figure 3-2: Upper pipe bend CAUTION! Prohibited: Installing the device in an upper pipe bend 1, because there is a risk of gas bubbles 2 forming. Gas bubbles can lead to pressure surges and inaccurate measurement. Figure 3-3: Downpipe and outlet CAUTION! Prohibited: Installing the device in a downstream pipe 3 or upstream pipe of a outlet 4. There is the risk of partially filled pipes. 25

26 3 INSTALLATION VERSAFLOW VORTEX Recommended installations for measurement of liquids CAUTION! It is absolutely necessary to comply with the required inlet and outlet runs. 1 If the device is installed in a downpipe, a standpipe must be installed immediately after it. 2 Installing the device in an inclined standpipe. 3 Installing the device in a vertical standpipe. 4 Installing the device in the lower pipe bend. 1 Above a horizontal pipe 2 On a vertical pipe INFORMATION! Depending on the installation position, you may have to rotate the display and/or the connection housing. 26

27 VERSAFLOW VORTEX INSTALLATION Measurement of vapours and gases Prohibited installation 1 Lower pipe bends 2 Condensate DANGER! Prohibited: Installing the device in a lower pipe bend 1, because there is a risk of condensate forming 2. Condensate can lead to cavitation and inaccurate measurement. Under certain circumstances the device can be destroyed and the measured product can leak. Recommended installations CAUTION! It is absolutely necessary to maintain the required inlet and outlet runs. 1 Inlet and outlet falling 2 Rising inlet - falling outlet 27

28 3 INSTALLATION VERSAFLOW VORTEX Pipelines with control valve INFORMATION! To ensure smooth and correct measurement, the manufacturer recommends not installing the measuring device downstream from a control valve. This would run the risk of vortex formation, which would distort the measuring result. Figure 3-4: Pipeline with control valve 1 Recommended: installing the device upstream from the control valve at a distance of 5 DN 2 Not recommended: Installing the flowmeter directly downstream of control valves, due to vortex formation Preferred mounting position Preferred mounting position 1 Above a horizontal pipe 2 underneath a horizontal pipe (not permitted with lines at risk for condensate) 3 On a vertical pipe INFORMATION! Depending on the installation position, you may have to rotate the display and/or the connection housing. For further information refer to Turning the display on page

29 VERSAFLOW VORTEX INSTALLATION Turning the connection housing DANGER! All work on the device electrics may only be carried out by appropriately trained personnel. The regional occupational health and safety directives must always be observed. CAUTION! Do not damage the electrical cable by overtwisting it. Do not remove the electrical connector. Figure 3-5: Allen screws on connection housing Disconnect the power supply from the measuring device. Loosen the four screws 1 on the rear side of the connection housing. Lift the connection housing and turn it to the required position in 90 steps. Screw the connection housing back on. 29

30 3 INSTALLATION VERSAFLOW VORTEX Turning the display DANGER! All work on the device electrics may only be carried out by appropriately trained personnel. The regional occupational health and safety directives must always be observed. INFORMATION! If the measuring device is installed in a vertical pipe, you will have to turn the display by 90 ; if installed below a pipe, turn 180. Figure 3-6: Turning the display Turn the display as follows: Disconnect the power supply from the measuring device. Unscrew the cover in front of the display 1 from the connection housing. Pull the display 2 carefully a few centimetres out of the anchor fitting and turn it to the required position 3. Press the display onto the spacer pins 4, until it clicks. Turn the cover with gasket 5 back onto the housing and tighten it by hand. 30

31 VERSAFLOW VORTEX INSTALLATION Heat insulation CAUTION! The area above the converter support must not be heat-insulated. The heat insulation 3 may only extend to the maximum height 1 shown below up to the connecting screws of the measuring sensor. Figure 3-7: Heat insulation on connection piece and signal cable 1 Max. height of insulation up to intermediate piece between measuring sensor and signal converter 2 Max. thickness of the insulation up to the bend of the pressure pipe 3 Insulation CAUTION! The heat insulation 3 may only extend as far as the bend of the pressure sensing line 2. 31

32 3 INSTALLATION VERSAFLOW VORTEX 3.5 Inlet and outlet runs Minimum inlet runs 1 General inlet run without disturbing flow 20 DN 2 Behind a control valve 50 DN 3 After a pipe diameter reduction 20 DN 1 After a single bend DN 2 After a double bend 2x90 30 DN 3 After a double three-dimensional bend 2x90 40 DN 32

33 VERSAFLOW VORTEX INSTALLATION Minimum outlet runs Figure 3-8: Minimum outlet runs 1 Upstream of pipe expanders, pipe bends, control valves, etc. 5 DN 2 Upstream of metering points 5 6 DN INFORMATION! The interior of the pipe at the metering points must be free of burrs and other flow impediments. The measuring device has an internal temperature sensor. External temperature sensor must be located 5 DN behind the flow sensor outlet. Use sensors that are as short as possible to avoid disturbing the flow profile Flow straightener If, due to the type of installation, the required inlet runs are not available, the manufacturer recommends using flow straighteners. Flow straighteners are installed between two flanges upstream of the device and shorten the required inlet run. Figure 3-9: Flow straightener 1 Straight inlet run upstream of straightener 2 DN 2 Flow straightener 3 Straight pipe run between flow straightener and device 8 DN 4 Minimum straight outlet run 5 DN 33

34 3 INSTALLATION VERSAFLOW VORTEX 3.6 Installation General installation notes CAUTION! Installation, assembly, start-up and maintenance may only be performed by appropriately trained personnel. The regional occupational health and safety directives must always be observed. The following procedures have to be carried out before installing the device: Remove all transportation safety devices and protective coverings from the device. Ensure that the gaskets have the same diameter as the pipelines. Note the correct flow direction for the device. This is indicated by an arrow on the housing of the measuring sensor. On metering points with varying thermal loads, the flowmeters have to be mounted with stress bolts (DIN 2510). Stress bolts or bolts and nuts are not included in the scope of delivery. Ensure that the measuring flange is concentrically fitted. Note the exact installation length of the measuring device when preparing the metering point. Figure 3-10: Preparing the metering point 1 Installation length of measuring device + thickness of gaskets. CAUTION! The internal diameter of the pipelines, the measuring sensor and the gaskets must match. The gaskets may not protrude into the flow. Figure 3-11: Internal diameter 1 Internal diameter connection pipe 2 Internal diameter flange and gasket 3 Internal diameter measuring sensor 34

35 VERSAFLOW VORTEX INSTALLATION Installing devices in flange design Figure 3-12: Installing devices in flange design 1 Gasket 2 Bolts with fixing nuts Use bolts and fastening nuts 2 to attach the measuring device to one side of the flange. While doing so, insert the gaskets 1 between measuring sensor and flange and align them. Check that the gasket is concentric and that it is not protruding into the pipe cross-section. Install the gasket, bolts and fastening nuts on the other side of the flange. Align the measuring device and the gaskets so they are concentric. Now tighten all nuts bit by bit alternately across the diagonal. 35

36 3 INSTALLATION VERSAFLOW VORTEX Installing devices in sandwich design Figure 3-13: Installation using centering ring 1 Measuring sensor 2 Centering ring 3 Bolts with fixing nuts 4 Hole 5 Gasket Push the first bolt 3 through the hole 5 of both flanges. Screw on the nuts and washers to both ends of the bolt 3 but do not tighten them. Install the second bolt through the holes 4. Place the measuring sensor 1 between the two flanges. Insert the gaskets 6 between measuring sensor 1 and flanges and align them. Check that the flange is concentric. Install the remaining bolts, washers and nuts. Do not yet tighten the nuts. Turn the centring ring 2 in a counter-clockwise direction and align the device. Check that the gaskets 6 are concentric; they must not protrude into the pipe cross-section. Now tighten all nuts bit by bit alternately across the diagonal. 36

37 VERSAFLOW VORTEX ELECTRICAL CONNECTIONS Safety instructions DANGER! All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate! DANGER! Observe the national regulations for electrical installations! DANGER! For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation. WARNING! Observe without fail the local occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists. INFORMATION! Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate. 37

38 4 ELECTRICAL CONNECTIONS VERSAFLOW VORTEX 4.2 Connecting the signal converter Figure 4-1: Signal converter housing with housing cover 1 Housing cover of the electrical terminal compartment 2 Electrical connection terminals with the housing cover open 3 Terminal A current output - 4 Terminal A+ current output + 5 Terminal B pulse output - 6 Terminal B+ Pulse output + 7 PE terminal in housing 8 PE terminal on connection piece between measuring sensor and signal converter. Both grounding terminals 7 and 8 are equally effective from a technical point of view. The following procedures are to be performed: Unscrew the housing cover 1 of the electrical terminal compartment. Thread the connection cable through the leadthrough in the housing. Connect the cable for the current output and the cable for the optional pulse output as shown in the cable terminal diagrams below. To facilitate installation the connection plug can be removed from the device. The plug is configured in such a way as to prevent reverse polarity. Connect the grounding to terminal 7 alternatively use the PE terminal on the connection piece between measuring sensor and signal converter 8. Tighten the cable glands. Hand-tight the housing cover with gasket. 38

39 VERSAFLOW VORTEX ELECTRICAL CONNECTIONS Electrical connection of current and pulse output Current output: In some cases, a shielded or twisted cable may be necessary. The cable shield may only be earthed (grounded) at one place (on the power supply unit). Pulse output: When using the pulse output, two separate signal circuits are necessary if the pulse output is utilized together with analogue signals. Each signal circuit requires its own power supply. The total resistance must be adapted so that the total current I tot does not exceed 100 ma. Connection current output on terminals A, A+ Connection pulse output on terminals B, B+ Figure 4-2: Electrical connection of current and pulse output 1 Power supply per signal circuit 2 Optional display unit 3 Load for HART 250 Ω 4 e.g. counter The maximum load resistance is calculated as follows: 39

40 4 ELECTRICAL CONNECTIONS VERSAFLOW VORTEX Power supply INFORMATION! The supply voltage has to be between 14 VDC and 36 VDC. This is based on the total resistance of the measuring loop. To determine this, add up the resistances of each component in the measuring loop (not including the measuring device). The required supply voltage can be calculated using the formula below: U ext. = R L * 22mA + 14V where U ext. = the minimum supply voltage and R L = the total measuring loop resistance is. INFORMATION! The power supply has to be able to supply a minimum of 22 ma Totalizer / pulse output The base units for the totalizer and the pulse output are m 3 for volume, m 3 norm. for standard volume and kg for mass. The unit and the conversion factor can be changed in menu item "Conf.Tot". User specific units (User Def.) can also be entered but the conversion factor must always be entered based on the base unit. For a sample calculation see chapter "Change units". The maximum frequency of the pulse output is 0.5 Hz. Figure 4-3: pulse output 1 f max 0.5 Hz 2 closed 3 open 4 Pulse 250 ms 40

41 VERSAFLOW VORTEX ELECTRICAL CONNECTIONS 4 The pulse output is a passive "open collector" output which is electrically separated from the current interface and the measuring sensor. It can be configured as a high current output or NAMUR output using a jumper on the amplifier board. Jumper in NAMUR setting R i = 900 Ω U max = 36 VDC The maximum frequency of the pulse output is f max = 0.5 Hz Jumper in high current setting Open: Maximum voltage U max = 36 VDC Closed current I R < 1 ma Closed: Maximum current I max = 100 ma Voltage U < 2 VDC The maximum frequency of the pulse output is f max = 0.5 Hz Figure 4-4: Jumper settings pulse output 1 Electronic insert 2 Jumper on board 3 Jumper in high current setting 4 Jumper in NAMUR setting 41

42 4 ELECTRICAL CONNECTIONS VERSAFLOW VORTEX 4.4 Remote version connection The connections in the sensor and wall mount bracket connection boxes are identical in construction. Connection cable strand colour Connection Terminal no.: Strand colour a Pressure sensor 5 brown 4 rose / pink 3 green 2 grey 1 white b Temperature sensor 2 black 1 purple c Vortex Sensor 3 red 2 yellow 1 blue Remote connection cable 1 Sensor connection side - strand length approx. 100mm 2 Length of shrink hose approx. 30mm 3 Wall housing connection side - prefabricated shielding - length approx. 15mm 42

43 VERSAFLOW VORTEX ELECTRICAL CONNECTIONS 4 Connection of shielding connection cable remote version CAUTION! The cable shielding is connected only on one side under the U-clamp terminal 1 in the wall mount bracket connection box. 4.5 Grounding connections The grounding can be done either by connecting the PE terminal in the housing or the PE terminal on the connection piece between measuring sensor and signal converter. Both of these electrical connections are equally effective from a technical point of view. Grounding connection compact version 1 Electrical grounding connection on connection piece between measuring sensor and signal converter. 2 Electrical grounding connection on housing CAUTION! The measuring device has to be grounded properly to achieve accurate measurement. The grounding wire may not transfer any interference voltage. Do not use this grounding wire to ground any other electrical devices. 43

44 4 ELECTRICAL CONNECTIONS VERSAFLOW VORTEX Grounding connection remote version 1 Grounding connection on sensor side 2 Grounding connection on signal converter side CAUTION! Both parts of the remote versions has to be grounded properly to achieve accurate measurement. The grounding wire may not transfer any interference voltage. 44

45 VERSAFLOW VORTEX ELECTRICAL CONNECTIONS Protection category The measuring device meets all requirements of protection category IP66/67. CAUTION! After all servicing and maintenance work on the device, the specified protection category has to be ensured again. Figure 4-5: Cable feedthrough Therefore it is essential to observe the following points: Use only original gaskets. They must be clean and free of any damage. Defective gaskets must be replaced. The electrical cables used must be undamaged and must comply with regulations. The cables must be laid with a loop 1 upstream of the measuring device to prevent water from getting into the housing. The cable feedthroughs 2 must be tightened. Align the measuring device so that the cable feedthrough is never facing up 3. Close the unused cable feedthroughs using blind plugs 4. Do not remove the required cable bushing from the cable feedthrough. 45

46 4 ELECTRICAL CONNECTIONS VERSAFLOW VORTEX 46

47 VERSAFLOW VORTEX START-UP Start After the device is switched on, the display shows the following in sequence 1. Testing Device type Sofware Version - Revision The device performs a self-test and switches to measurement mode. Here, all of the parameters preset for the customer are analysed and checked for plausibility, and the current measured value is displayed. 5.2 Start-up and control INFORMATION! The flowmeter is largely maintenance-free. Observe the application limits in respect of temperature and medium. Additional information refer to Technical data on page

48 5 START-UP VERSAFLOW VORTEX 48

49 VERSAFLOW VORTEX OPERATION Display and operating elements With the cover open the device is operated by using the mechanical keys on the front; with the cover closed a bar magnet is used. CAUTION! The switching point of the magnetic sensors is directly under the glass panel above the appropriate symbol. Only touch the symbol vertically and from the front using the bar magnet. Touching it from the side may cause a malfunction. Figure 6-1: Display and operating elements 1 Enter button (bar magnet) 2 Right button (bar magnet) 3 Up button (bar magnet) 4 Up button (mechanical) 5 Enter button (mechanical) 6 Right button (mechanical) 7 Display 49

50 6 OPERATION VERSAFLOW VORTEX The mechanical keys and keys for the bar magnet have the same functionality. In this documentation the keys are represented as symbols to describe the operating functions: Mechanical Bar magnet Symbol ^ Table 6-1: Description of keys 6.2 Operating principles Functional description of the keys Switch from measuring mode to menu mode Switch to one menu level lower Open menu item and activate change mode In change mode: Move the input cursor one position to the right; after the last digit the input cursor jumps back to the beginning. In measuring mode: Switch between measured values and error messages Change between the menu items within a menu level In change mode: Changing parameters and settings; running through the available characters; shifting the decimal point to the right. ^ Switch to one menu level higher Return to measuring mode with a query whether the data should be accepted Table 6-2: Description of the operating keys Switch from measuring mode to menu mode Measuring mode Operation Menu mode kg/h Language 50

51 VERSAFLOW VORTEX OPERATION Navigation within the menu structure Navigation within the menu is by means of the and ^ buttons. Pressing button takes you one menu level lower, ^ takes you one menu level higher. If you are already located at the lowest level (function level), you can use the button to go in the change mode, which can be used to set data and values. If you are located at the first level (main menu), you can use the ^ key to exit the menu mode and return to the measuring mode. Measuring mode Main menu Sub-menu Function Edit ^ Table 6-3: Navigation menu structure ^ ^ ^ ^ Changing the settings in the menu Use the and keys to navigate in the menu in which you want to change a setting or value. Use the key to activate the change mode in the selected menu. i The current values or settings are displayed. Use the and keys to change the value or setting. Save the new value or setting using the ^ key. Some menu items contain several setting options. They are displayed in sequence by pressing the ^ key. i Takes you back to the main menu. Press the ^ key to save the settings. i The query "Save Yes" appears. Switch between "Yes" and "No" by pressing the key. Switch between "YES" and "NO" by pressing the key. Save Yes ^ Changes saved. An update is carried out and the display returns to measuring mode. Save No ^ Changes not saved. The display returns to measuring mode. CAUTION! Each time parameters or settings are changed, the measuring device carries out an internal plausibility check. If implausible inputs have been made, the display remains in the current menu, and the changes are not saved. 51

52 6 OPERATION VERSAFLOW VORTEX Example: changing the default parameter from m 3 /h to l/min Procedure Display Procedure Display m 3 /h 1 3 x Language 2 3 x Max. Flow 3 m 3 /h Unit 4 3 x L/min Unit 5 ^ L/min 6 ^ Display Unit 7 ^ Max. Flow 8 ^ Save Yes 9 ^ L/min Changing units When entering numbers and values in floating point format, the maximum possible accuracy is 0.003%. The accuracy depends on both the position of the decimal point and the length of the number entered. Numerical values and factors are displayed in the first line of the 10-digit display. Numerical values are either displayed in floating point format ( ) or are expressed in exponential format (123456E002). The conversion factor of the totalizer and the pulse output is, however, expressed in whole numbers. Input values exponential format Display position Decimal point Input values E To select the exponential function, the decimal point must be located between the 2nd and 5th decimal position. Flow units The base units are m 3 /h for volume flow measurement, m 3 /h stand. for standard volumetric flow measurement and kg/h for mass flow measurement. The flow units can be changed in menu item "Max.Flow". User defined units can be entered using "User Def." The unit (text) as well as the conversion factor (number) can be entered here. The conversion factor must always be entered based on the base unit. Conversion Formula New unit (User Def.) = A1 Coeff. * Base unit Example: 1 litre / h = * m 3 /h ōr Menu items Maes.Inst Volume / Standard volume / Mass Max. Flow Unit (User Def.) / Text / A1 Coeff. / Max. Flow / Flow Displ 52

53 VERSAFLOW VORTEX OPERATION 6 Totalizer / pulse output The base units for the totalizer and the pulse output are m 3 for volume, m 3 norm. for standard volume and kg for mass. The unit and the conversion factor can be changed in menu item "Tot.Conf.". User defined units (User Def.) can be selected and entered. The conversion factor of the unit must always be entered based on the base unit. The maximum pulse output frequency is 0.5 Hz. To ensure that the pulse output does not exceed 0.5 Hz, the conversion factor of the totalizer must be selected and set accordingly. The pulse output represents an exact copy of the whole number value of the internal totalizer. Max. pulses per hour fmax. 0.5 Hz 1 pulse-break 2 seconds Max. pulses / hour = 1800 pulses Example Flow Qmax. Factor A1 Coef. Pulses / litre Pulses / h Comment 5.6 m 3 /h pulse / 1 litre 5600 not possible pulse / 10 litres < 1800 = ok. Menu items Maes.Inst Volume / Standard volume / Mass Max. Flow Unit (User Def.) / Text / A1 Coeff. / Max. Flow / Flow Displ Function P Yes / No Totalizer Tot. on / Tot. off Tot. Conf. User def. / Unit Text / A1 Coeff. / Preset Value / Reset / Display Measures in the event of faulty indications If the indications on the display or the responses to keypad commands are faulty, you have to do a hardware reset. Switch the power supply OFF and ON again. 53

54 6 OPERATION VERSAFLOW VORTEX 6.3 Overview of the most important functions and units INFORMATION! A complete list of all functions and short descriptions is provided in the appendix. All default parameters and settings are adapted for the specific customer. Level Designation Explanation Language Select the menu language Max. Flow Maximum flow rate The value set is represented by a 20 ma analogue current output. If the current value exceeds the preset value, an alarm is indicated Min. Flow Minimum flow rate The set value does not represent the 4 ma value of the current output Timeconst. Time constant, damping value [s] Test I Check current output Test P Test pulse output Error Msg. Error indicator Yes: error messages are displayed No: error messages are suppressed. A flashing cursor at the top left indicates that error messages are present. Table 6-4: The most important functions Volume mass units Volume Standard volume Mass Liquids, steams, gases Air Gas Liquids, steams, gases m 3 /h m 3 /min m 3 /s L/h L/min L/s ft 3 /h ft 3 /min ft 3 /s gal/h gal/min gal/s ImpGal/h ImpGal/min ImpGal/s cm 3 /h cm 3 /min cm 3 /s dm 3 /h dm 3 /s bbl/h bbl/d User Def. FAD m 3 /h FAD m 3 /min FAD m 3 /s FAD L/h FAD L/min FAD L/s FAD ft 3 /h FAD ft 3 /min FAD ft 3 /s User Def. m 3 /h (norm) m 3 /min (norm) m 3 /s (norm) L/h (norm) L/min (norm) L/s (norm) ft 3 /d (std.) ft 3 /h (std.) ft 3 /min (std.) ft 3 /s (std.) User Def. kg/h kg/min kg/s t/h t/min t/s lb/h lb/min lb/s g/min g/s User Def. Table 6-5: Flow measurements and units 54

55 VERSAFLOW VORTEX OPERATION 6 Unit totalizer Volume Standard volume Mass Liquids, steams, gases Gas Liquids, steams, gases m 3 L ft 3 /h ft 3 gal ImpGal cm 3 dm 3 bbl User Def. Table 6-6: Totalizer units m 3 norm L norm ft 3 std. User Def. kg t lb g User Def. Temperature - Pressure - Power - Energy - Density units Temp. C F K User Def. Table 6-7: Additional units Absolute pressure (over) Pa(g) kpa(g) MPa(g) kg/ms 2 (g) kp/cm 2 (g) atm(g) torr(g) bar(g) mbar(g) psi(g) lbf/ft 2 (g) kgf/cm 2 (g) inhg(g) mmhg(g) mmh 2 O(g) User Def. Power Energy Density kj/h MJ/h GJ/h Btu/h th kcal/h User Def. kw MW TR kj MJ GJ Btu th kcal kwh MWh User Def. kg/m 3 kg/l g/l h/ml g/cm 3 g/ft 3 g/impgal g/gal kg/gal Lb/gal Lb/ImpGal User Def. 55

56 6 OPERATION VERSAFLOW VORTEX 6.4 Error messages Error message Cause Measure No Signal No signal from vortex amplifier Check connector In the event of measuring sensor problems contact service. Low freq Sample frequency too low Contact service. High Freq Sample frequency too high Contact service. Low Flow Q too high Inv. Config. Flow rate less than the set minimum flow rate q min Flow rate higher than the set maximum flow rate q max Invalid configuration data in FRAM (permanent memory) Signal converter continues to display the current flow rate but the accuracy of the measurement may be affected. Corrective measures depend on the application! If the flow rate exceeds the maximum value, the measuring sensor may be physically damaged. Check entire configuration! Contact service if error message persists. Amp. Fail Error in the pre-amplifier stage Contact service. Chk. Instal. Quality of the vortex signal too poor 1. Check q min 2. Excessive pipe vibration and faulty flow profile Low Signal Amplitude of vortex signal is too low 1. q min ok? 2. If q min OK, contact service Hi. Signal Amplitude of vortex signal is too high Occurs with media of high density 1. Check q max 2.If q max OK, contact service L.Temp.Phy H.Temp.Phy Hi.P.Phys Operating temperature lower than specified Operating temperature higher than specified Pressure higher than specified Take corrective measures within process. Take corrective measures within process as quickly as possible, otherwise both the measuring sensor and the signal converter may be damaged. Tsens Shrt. Temperature sensor short circuit Shows error at temperature sensor! Tsens Open Open temperature sensor Contact service. P. Sen. Fail Faulty pressure sensor Displays error at pressure sensor! Contact service. Table 6-8: Error messages 56

57 VERSAFLOW VORTEX OPERATION Menu structure Overview of firmware versions There are three firmware versions, each of which is tailored to a different use of the measuring device: Basic: liquids and gases without compensation, saturated steam with density compensation using the temperature Steam: saturated and superheated steam with density compensation using pressure and temperature, gross heat meter Gas: gas, gas mixture and wet gas with density compensation using pressure and temperature, FAD (free air delivery measurement) The menu structures differ from one another depending on the firmware version. The following table contains an overview of all menu items in the first menu level. For a complete description of the menu, note the firmware version of your measuring device and follow the relevant instructions in the table. Menu items Firmware version Basic Firmware version Steam 1. Quick setup refer to Menu item Quick Setup on page Tests refer to Menu item Tests on page Setup refer to Menu item Setup (firmware version - basic) on page 61 refer to Menu item Setup (firmware version - steam) on page 64 Firmware version Gas refer to Menu item Setup (firmware version - gas) on page Service The service menu is only accessible to service personnel and is not described. Table 6-9: Overview of menu structure INFORMATION! The measuring device has been preset at the factory in accordance with the customer order. Therefore, subsequent configuration via the menu is only necessary if the intended use of the measuring device changes. 57

58 6 OPERATION VERSAFLOW VORTEX Entering values in change mode Moves the insertion point one position to the right; after the last position, the insertion point returns to the beginning. Cycles through available values and characters; moves the decimal point to the right. ^ Accepting the entry Character selection in change mode Depending on the menu function, you can choose from the following characters: Numbers Lowercase letters a b c d e f g h i j k l m n o p q r s t u v w x y z Uppercase letters A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Special characters 2 3 " % & : < = > -. / 1 1 "blank" 58

59 VERSAFLOW VORTEX OPERATION Menu item Quick Setup Level Designation Selection / entry field Explanation Language Select menu language German... German language Location Maes.Inst Max. Flow Min. Flow Timeconst. French English...^ Location......^ Volume Norm. Vol. 1 Mass...^ 2 m 3 /h Unit...^ Upp.Limit or other value m 3 /h......^ Display Unit / Display %Max Flow...^ 3 m 3 /h norm Unit...^ or other value m 3 /h norm......^ Display Unit / Display %Max Flow...^ 4 kg/h Unit or other value kg/h......^ Display Unit / Display %Max Flow...^ m 3 /h ^ s......^ 1 only with gas 2 available if Maes.Inst = Volume (see menu item 1.1.3) 3 available if Maes.Inst = Norm. Vol. (see menu item 1.1.3) 4 available if Maes.Inst = Mass (see menu item 1.1.3) French language English language Enter the name of the location (max. 10 characters) Select type of flow measurement Volume measurement Standard volume flow measurement Mass flow measurement Set maximum flow rate Select unit for volume flow measurement Enter value for the maximum volume flow Display flow rate in units / in % of maximum flow rate Select unit for standard volume flow measurement Enter value for the maximum standard volume flow rate Display flow rate in units / in % of maximum flow rate Select unit for mass flow measurement Enter value for the maximum mass flow rate Display flow rate in units / in % of maximum flow rate The minimum flow rate value is factory-set. Enter the time constant for the measured value output in seconds (0 20s) 0: disabled 59

60 6 OPERATION VERSAFLOW VORTEX Menu item Tests Level Designation Selection / entry Explanation Test I Test P 4 ma ^ Test current output 8 ma ^ 12 ma ^ 16 ma ^ 20 ma ^ Hz ^ Test pulse output Table 6-10: Menu item Test Every current value has to be confirmed with ^. Only after this is the current output set to the respective value. The following is then displayed: "Contin. Yes": continue with the test of current output function "Contin. No": back to menu The test current is maintained until the menu has been exited. 60

61 VERSAFLOW VORTEX OPERATION Menu item Setup (firmware version - basic) Version Basic Level Designation Selection / entry Explanation 3.1 Set display Error message Display error Yes... Shows error messages in measuring mode in plain text alternating with the measured values No...^ Flashing cursor in the top left corner of the display indicates errors Cycle.Disp. Display measured values Yes... Cyclically display measured values in measuring mode (6 s intervals) No...^ Do not display measured values cyclically Code 1 Set security query 1 (menu) Yes... Activate access code: ^^^ No...^ Deactivate access code 3.2 I/O settings mA off Current output 4-20 ma and error current 4-20mA... Current output 4-20 ma Function P Totalizer Tot. Conf. (available if Maes.Inst = Volume, see menu item 1.1.3) (available if Maes.Inst = Norm. Vol., see menu item 1.1.3) 4-20/22E /3.55E...^ Yes... No...^ Tot. on... Current output 4-20 ma or error current 22 ma Current output 4-20 ma or error current 3.55 ma pulse output Activate pulse output Deactivate pulse output Totalizer Start Totaliser Tot. off...^ Stop totalizer (value is held) Configure totalizer m 3 Unit...^ m ^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ m 3 norm Unit...^ m 3 norm......^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ Select totalizer unit for volume flow measurement Enter preset totalizer value Reset totalizer / Do not reset totalizer/ Display totalizer / Do not display totalizer Select totalizer unit for standard volume flow measurement Enter preset totalizer value Reset totalizer / Do not reset totalizer/ Display totalizer / Do not display totalizer 61

62 6 OPERATION VERSAFLOW VORTEX Version Basic Level Designation Selection / entry Explanation (available if Maes.Inst = Mass, see menu item 1.1.3) kg Unit...^ kg......^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ Select totalizer unit for mass flow measurement Enter preset totalizer value Reset totalizer / Do not reset totalizer/ Display totalizer / Do not display totalizer 3.3 HART settings Poll. Adr HART SV HART TV HART 4V ^ Total Flow ^ Temp. ^ Density ^ Density ^ Temp. ^ Enter HART polling address for "Multidrop operation" HART secondary variable HART tertiary variable HART quaternary variable 3.4 Set fluid and medium Fluid 1 Set fluid type Gas... Gas Medium (available if Fluid = Gas or Liquid, see menu item 3.4.1) 1 Density check (available if Fluid = Steam, see menu item 3.4.1) Liquid.... Steam...^ Custom... Sat.Steam...^ Custom Liquid Steam Set medium Customer medium Saturated steam 3.5 Set pressure, temperature and density T-sensor Internal temperature sensor No... No temperature sensor available Sat.P/T (available if Fluid = Steam, see menu item 3.4.1) Oper. Temp. Yes...^ Sat. T ^ C Unit...^ C ^ Disp. on / Disp. off...^ Temperature sensor available Density calculation for saturated steam Density calculation for saturated steam with the saturated temperature Operating temperature Set temperature unit Operating temperature Display temperature / Do not display temperature 62

63 VERSAFLOW VORTEX OPERATION 6 Version Basic Level Designation Selection / entry Explanation Oper. Dens Dens. Norm 2 kg/m 3 Unit...^ kg/m 3 ^ kg/m ^ Remote length/m Cable Coef Cable Coef 1 Disp. off Disp. on 2 available if Maes.Inst = Norm.Vol. Density at operating pressure and operating temperature Set density unit Operating density Enter density for reference conditions (pressure and temperature) (max. = 15m) 63

64 6 OPERATION VERSAFLOW VORTEX Menu item Setup (firmware version - steam) Version Steam Level Designation Selection / entry Explanation 3.1 Set display Error message Display error Yes... Shows error messages in measuring mode in plain text alternating with the measured values No...^ Shows a flashing cursor in the top left corner of the display to indicate that there are errors Cycle.Disp. Display measured values Yes... Cyclically display measured values in measuring mode (6 s intervals) No...^ Do not display measured values cyclically Code 1 Set security query 1 (menu) Yes... Activate access code: ^^^ No...^ Deactivate access code 3.2 I/O settings mA off Current output 4-20 ma and error current 4-20mA... Current output 4-20 ma Variable I (available if DEVICE TYPE = GROSS HEAT, see menu item 5.4.1, service menu) Power Unit (available if DEVICE TYPE = GROSS HEAT, see menu item 5.4.1, service menu) FS power (available if Variable I = Power, see menu item 3.2.2) Function P Variable P (available if DEVICE TYPE = GROSS HEAT, see menu item 5.4.1, service menu) Totalizer 4-20/22E /3.55E...^ Maes.Inst... Power...^ kj/h Unit...^ Disp. on / Disp. off...^ kj/h ^ Yes... No...^ Total Flow... Energy...^ Tot. on... Current output 4-20 ma or error current 22 ma Current output 4-20 ma or error current 3.55 ma Set display variable for current output Flow rate Power Set unit for heat output Select unit for measuring heat output Display measured value/ Do not display measured value End value for power measuring range Power value at 20 ma current output Pulse output Activate pulse output Deactivate pulse output Set output variable for the pulse output Total flow Energy Totalizer Start Totaliser Tot. off...^ Stop totalizer (value is held) 64

65 VERSAFLOW VORTEX OPERATION 6 Version Steam Level Designation Selection / entry Explanation Tot. Conf. (available if Maes.Inst = Volume, see menu item 1.1.3) (available if Maes.Inst = Norm. Vol., see menu item 1.1.3) (available if Maes.Inst = Mass, see menu item 1.1.3) E.tot. on (available if DEVICE TYPE = GROSS HEAT, see menu item 5.4.1, service menu) Energ.Unit (available if DEVICE TYPE = GROSS HEAT, see menu item 5.4.1, service menu) m 3 Unit...^ m ^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ m 3 norm Unit...^ m 3 norm......^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ kg Unit...^ kg......^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ Tot. on... Configure totalizer Select totalizer unit for volume flow measurement Enter preset totalizer value Do not reset totalizer/ Reset totalizer Do not display totalizer Display totalizer / Select totalizer unit for standard volume flow measurement Enter preset totalizer value Do not reset totalizer/ Reset totalizer Do not display totalizer Display totalizer / Select totalizer unit for mass flow measurement Enter preset totalizer value Do not reset totalizer/ Reset totalizer Do not display totalizer Display totalizer / Energy totalizer Start Totaliser Tot. off...^ Stop totalizer (value is held) kj Unit...^ kj......^ Reset No / Reset Yes...^ Disp. on / Disp. off...^ Set unit for heat energy Set unit for heat energy Enter preset totalizer value Do not reset heat energy/ Reset heat energy Display heat energy / Do not display heat energy 3.3 HART settings Poll. Adr ^ Enter HART polling address for "Multidrop operation" 65

66 6 OPERATION VERSAFLOW VORTEX Version Steam Level Designation Selection / entry Explanation HART SV HART TV HART 4V Total Flow... Energy...^ #available if Meter Type = Gross Heat (menu item 5.3.1, service menü) Temperature.. Pressure... Density...^ Temperature.. Pressure... Density...^ HART secondary variable HART tertiary variable HART quaternary variable 3.4 Set fluid and medium Fluid 1 Fluid type Steam ^ Steam Medium Process medium Sat.Steam... Saturated steam Dry. Fact. (available if Medium = Sat.Steam, see menu item 3.4.2) 1 Density check Sup.Steam...^ Overheated steam Enter portion of dryness in saturated steam Factor = 1 - %water mass 0.85 TO ^ 3.5 Pressure, temperature and density T-sensor Internal temperature sensor No... No temperature sensor available P-sensor Sat.P/T (available if Medium = Sat.Steam, see menu item 3.4.2) Yes...^ Temperature sensor available Pressure sensor Intern... Internal pressure sensor ^ No pressure sensor available Density calculation for saturated steam Sat. T... Density calculation for saturated steam from saturated temperature Sat. P...^ Density calculation for saturated steam from saturated pressure 66

67 VERSAFLOW VORTEX OPERATION 6 Version Steam Level Designation Selection / entry Explanation Oper. Temp. (for saturated steam with Sat. Temp. or Sup.Steam, see menu items and 3.5.3) Oper. press. (available for SAT.STEAM with SAT. P or SUP.STEAM, see menu items and 3.5.3) Oper. dens P-Excit. V (available if P-Sensor = Internal, see menu item 3.5.2) P-Sen.P1V1 (available if P-Sensor = Internal, see menu item 3.5.2) P-Sen.P2V2 (available if P-Sensor = Internal, see menu item 3.5.2) 3.6 C Unit...^ C ^ Disp. on / Disp. off...^ Pa Unit...^ Pa ^ Disp. on / Disp. off...^ kg/m 3 Unit...^ kg/m 3 ^ V ^ P1 kg/cm 2 g...^ V1 mv......^ P2 kg/cm 2 g......^ V2 mv......^ Remote length/m Cable Coef Cable Coef Operating temperature Set temperature unit Operating temperature Display temperature / Do not display temperature Operating pressure Set pressure unit Operating pressure Display pressure / Do not display pressure Density at operating pressure and operating temperature Set density unit Operating density Exciting voltage of pressure sensor Pressure sensor: Enter 1st calibration point Pressure sensor: Enter 2nd calibration point (max. = 15m) 67

68 6 OPERATION VERSAFLOW VORTEX Menu item Setup (firmware version - gas) Version gas Level Designation Selection / entry Explanation 3.1 Set display Error message Display error Yes... Shows error messages in measuring mode in plain text alternating with the measured values No...^ Shows a flashing cursor in the top left corner of the display to indicate that there are errors Cycle.Disp. Display measured values Yes... Cyclically display measured values in measuring mode (6 s intervals) No...^ Do not display measured values cyclically Code 1 Set security query 1 (menu) Yes... Activate access code: ^^^ No...^ Deactivate access code 3.2 I/O settings mA off Current output 4-20 ma and error current 4-20mA... Current output 4-20 ma Function P Totalizer Tot. Conf. (available if Maes.Inst = Volume, see menu item 1.1.3) (available if Maes.Inst = Norm. Vol., see menu item 1.1.3) 4-20/22E /3.55E...^ Yes... No...^ Tot. on... Current output 4-20 ma or error current 22 ma Current output 4-20 ma or error current 3.55 ma Pulse output Activate pulse output Deactivate pulse output Totalizer Start Totaliser Tot. off...^ Stop totalizer (value is held) Configure totalizer m 3 Unit...^ m ^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ m 3 norm Unit...^ m 3 norm......^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ Select totalizer unit for volume flow measurement Enter preset totalizer value Reset totalizer Do not reset totalizer/ Do not display totalizer Display totalizer / Select totalizer unit for standard volume flow measurement Enter preset totalizer value Reset totalizer Do not reset totalizer/ Do not display totalizer Display totalizer / 68

69 VERSAFLOW VORTEX OPERATION 6 Version gas Level Designation Selection / entry Explanation (available if Maes.Inst = Mass, see menu item 1.1.3) kg Unit...^ kg......^ Reset Yes / Reset No...^ Disp. off / Disp. on...^ Select totalizer unit for mass flow measurement Enter preset totalizer value Reset totalizer Do not reset totalizer/ Do not display totalizer Display totalizer / 3.3 HART settings Poll. Addr HART SV HART TV HART 4V ^ Total Flow... FAD...^ #available if Meter Type = FAD meter (see menu item 5.3.1, service personnel only) Temp... Pressure... Density... FAD...^ #available if Meter Type = FAD meter (see menu item 5.3.1, service personnel only) Temperature.. Pressure... Density... FAD...^ #available if Meter Type = FAD meter (see menu item 5.3.1, service personnel only) Enter HART polling address for "Multidrop operation" HART secondary variable HART tertiary variable HART quaternary variable 3.4 Set fluid and medium Fluid 1 Set fluid type Gas... Gas 1 When changing fluid: check density Gas Mix.... Gas mixture Wet Gas...^ Wet gas 69

70 6 OPERATION VERSAFLOW VORTEX Version gas Level Designation Selection / entry Explanation Medium (available if Fluid = Gas / Wet Gas, see menu item 3.4.1) % Gas (available if Fluid = Gas Mix., see menu item 3.4.1) %Rel.Hum (available if Fluid = Wet Gas, see menu item 3.4.1) FAD unit (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) Suct.Temp. (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) Atm. Pressure (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) Fil. P. Drop. (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) Inlet RH (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) Actual Rpm (available if Meter Type = FAD meter, see menu item 5.3.1, service personnel only) Rated Rpm. (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) Air... Ammonia... Argon... Set process medium Air Ammonia Argon etc....^ other gases not listed here Determine composition of gas mixture Select gas and enter percentage Air......^ Total % ^ % Rel.Hum......^ FAD m 3 /h Unit...^ Disp. on / Disp. off...^ C Unit...^ C......^ Pa Unit...^ Pa......^ Pa Unit...^ Pa......^ % Rel.Hum......^ RPM ^ RPM ^ Total percentage Determine relative humidity Determine unit for FAD Set unit for FAD Display measured value / Do not display measured value Enter temperature in suction area of compressor Select temperature unit Enter temperature value Atmospheric pressure Select pressure unit Enter pressure value Pressure drop via filter at compressor inlet Select pressure unit Enter pressure value Enter relative humidity in suction area of compressor Current speed of compressor motor in revolutions per minute Rated speed of compressor motor in revolutions per minute 70

71 VERSAFLOW VORTEX OPERATION 6 Version gas Level Designation Selection / entry Explanation Outlet RH (available if Meter Type = FAD meter, see menu item 5.4.1, service personnel only) % Rel.Hum......^ Enter relative humidity at measuring device (compressor outlet) 3.5 Pressure, temperature and density T-sensor Internal temperature sensor No... No temperature sensor available P-sensor Oper. temp Oper. press. Yes...^ Temperature sensor available Pressure sensor Intern... Internal pressure sensor ^ C Unit...^ C ^ Disp. on / Disp. off...^ Pa Unit...^ Pa ^ Disp. on / Disp. off...^ No pressure sensor available Operating temperature Set temperature unit Operating temperature Display temperature / Do not display temperature Operating pressure Set pressure unit Operating pressure Display pressure / Do not display pressure Oper. dens. Density at operating pressure and operating temperature Temp.Norm. (available if Maes.Inst = Norm. Vol., see menu item 1.1.3) Press.Norm (available if Maes.Inst = Norm. Vol., see menu item 1.1.3) Dens. norm (for unknown gases using standard volume flow measurement, see menu items 1.1.3, and 3.4.2) P-Excit. V (available if P-Sensor = Internal, see menu item 3.5.2) kg/m 3 Unit...^ kg/m 3 ^ C......^ Pa......^ kg/m 3 ^ V ^ Set density unit Operating density Enter normal temperature Unit as Enter normal pressure Unit as Enter density for reference conditions (pressure and temperature) Exciting voltage of pressure sensor 71

72 6 OPERATION VERSAFLOW VORTEX Version gas Level Designation Selection / entry Explanation P-Sen.P1V1 (available if P-Sensor = Internal, see menu item 3.5.2) P-Sen.P2V2 (available if P-Sensor = Internal, see menu item 3.5.2) P1 kg/cm 2 g...^ V1 mv......^ P2 kg/cm 2 g......^ V2 mv......^ Remote length/m Cable Coef Cable Coef Pressure sensor: 1st calibration point Pressure sensor: 2nd calibration point (max. = 15m) 72

73 VERSAFLOW VORTEX SERVICE Replacing signal converter / LC display The signal converter has to be replaced by a converter of the same type. The following parameters must be observed: The item number must correspond: xxx The software version 2 must match. The basic version has no software identification The gas version is marked: "gas" The steam version is marked: "steam" Figure 7-1: Board, example 1 Connector for display 2 Version number, software identification 3 Connector for measuring sensor 4 Spacer pins 5 Fixing screw (Phillips) The following steps are to be performed: Switch off the power supply. Unscrew the front cover. Detach the display from the spacer pins. Detach the display cable 1. Detach the measuring sensor cable 3. Loosen the three fixing screws 5 (Phillips). Pull out signal converter. Insert new signal converter. Tighten the three screws. Attach measuring sensor cable 3 (Caution: ensure that the measuring sensor cables are not on top of the spacer pins 4 May be damaged). Attach display cable 1. Attach display in desired position, apply even pressure to the entire surface. Screw on cover by hand. 73

74 7 SERVICE VERSAFLOW VORTEX 7.2 Spare parts availability The manufacturer adheres to the basic principle that functionally adequate spare parts for each device or each important accessory part will be kept available for a period of 3 years after delivery of the last production run for the device. This regulation only applies to spare parts which are subject to wear and tear under normal operating conditions. 7.3 Availability of services The manufacturer offers a range of services to support the customer after expiration of the warranty. These include repair, maintenance, technical support and training. INFORMATION! For more precise information, please contact your local sales office. 7.4 Returning the device to the manufacturer General information This device has been carefully manufactured and tested. If installed and operated in accordance with these operating instructions, it will rarely present any problems. CAUTION! Should you nevertheless need to return a device for inspection or repair, please pay strict attention to the following points: Due to statutory regulations on environmental protection and safeguarding the health and safety of our personnel, manufacturer may only handle, test and repair returned devices that have been in contact with products without risk to personnel and environment. This means that the manufacturer can only service this device if it is accompanied by the following certificate (see next section) confirming that the device is safe to handle. CAUTION! If the device has been operated with toxic, caustic, flammable or water-endangering products, you are kindly requested: to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from such dangerous substances, to enclose a certificate with the device confirming that is safe to handle and stating the product used. 74

75 VERSAFLOW VORTEX SERVICE Form (for copying) to accompany a returned device Company: Address: Department: Name: Tel. no.: Fax no.: Manufacturer's order no. or serial no.: The device has been operated with the following medium: This medium is: water-hazardous toxic caustic flammable We checked that all cavities in the device are free from such substances. We have flushed out and neutralized all cavities in the device. We hereby confirm that there is no risk to persons or the environment through any residual media contained in the device when it is returned. Date: Signature: Stamp: 7.5 Disposal CAUTION! Disposal must be carried out in accordance with legislation applicable in your country. 75

76 7 SERVICE VERSAFLOW VORTEX 76

77 VERSAFLOW VORTEX TECHNICAL DATA Functional principle Vortex flowmeters are used to measure the volumetric flow of gases, vapours and liquids at completly filled pipes. The measuring principle is based on the Karman vortex street. The measuring tube contains a bluff body, behind which vortex shedding occurs. The frequency f of the vortex shedding is proportional to the flow rate v. The nondimensional Strouhal number S describes the relationship between vortex frequency f, width b of bluff body and the mean flow velocity v: f = S. v b The vortex frequency is recorded at the sensor and evaluated at the converter. Figure 8-1: Functional principle 77

78 8 TECHNICAL DATA VERSAFLOW VORTEX 8.2 Technical data INFORMATION! The following data is provided for general applications. If you require data that is more relevant to your specific application, please contact us or your local sales office. Additional information (certificates, special tools, software,...) and complete product documentation can be downloaded free of charge from the website. Measuring system Application range Measuring principle Flow measurement of liquids, gases and vapours Karman vortex street Measured value Primary measured value Secondary measured value Number of separated vortices Operating and standard volumetric flow, mass flow Signal converter Versions Compact Remote version - cable length 15m (49 ft) Option: Ex version Measuring sensor Standard Optional Flange version (with integrated temperature measurement), sensor: F Sandwich version (with integrated temperature measurement), sensor: S Basic device with additional pressure measurement Basic device with additional pressure measurement and shut-off valve for pressure sensor Dual measuring device in both flange and sandwich version (redundant measurement) Dual measuring device in flange version with additional pressure measurement Flange version with simple reduction, sensor: FR Flange version with double reduction, sensor: F2R Display and user interface Local display Operating and display languages 2 lines, 10 characters per line German, English, French 78

79 VERSAFLOW VORTEX TECHNICAL DATA 8 Measuring accuracy Reference condition Water at 20ºC Accuracy Air at 20 C and bar abs. Based on volume flow Liquids ±0.75% of measured value (Re 20000) ±2.0% of measured value (10000 < Re < 20000) Gases and steams ±1.0% of measured value (Re 20000) Repeatability Long-term stability Operating conditions ±2.0% of measured value (10000 < Re < 20000) Pressure and temperature compensation: ±1.5% of measured value (Re 20000); ±2.5% of measured value (10000 < Re < 20000) ±0.1% of measured value ±0.01% of measured value Temperature Product Ambient Storage Pressure Product Ambient C / F Non-Ex: C / F Ex: C / F C / F Max. 100 bar / 1450 psi; Information on higher pressures on request. Atmosphere Chemical properties Density Viscosity Taken into consideration when sizing. < 10 cp Reynold's number Recommended flow velocities Liquids Gases and steams Other conditions Protection category IP 66/ m/s / ft/s (optional up to 10 m/s / 32.8 ft/s taking cavitation into account) m/s / ft/s DN15: m/s / ft/s; DN25: m/s / ft/s For detailed information, see chapter "Flow tables". 79

80 8 TECHNICAL DATA VERSAFLOW VORTEX Installation conditions Inlet run Outlet run Dimensions and weights Materials Measuring sensor and process connections Converter housing Pressure sensor gasket Measuring tube gasket 20 x DN (without disturbing flow, after pipe narrowing, after a single 90 bend) 30 x DN (after a double bend 2x90 ) 40 x DN (after a double three-dimensional bend 2x90 ) 50 x DN (after control valves) 2 DN before flow straightener; 8 DN after flow straightener (specified values apply only to original 20 DN inlet run) 5 x DN For detailed information refer to chapter "Dimensions and weights". Standard: /316L Option: Hastelloy C-22 on request Die-cast Aluminium Standard: FPM Option: FFKM Standard: /316L Option: Hastelloy C-276 Selection depends on measuring sensor material/medium. Process connections Flange version DIN EN ASME B16.5 JIS B 2220 DN in PN ½...12" in lb Process connections Sandwich version DIN ASME JIS DN in JIS K For detailed information on combination flange/pressure rating, refer to chapter "Dimensions and weights". DN in PN100 (higher pressures on request) ½...4" in 600 lb (higher pressures on request) DN in K (higher pressures on request) Electrical connections Power supply Current output Description of the used abbreviations Measuring range Load Error signal Non-Ex: VDC Ex: VDC U ext = external voltage; R L = load + resistance ma (max ma) + HART protocol Minimum 0 Ω; maximum R L = ((U ext - 14 VDC) / 22 ma) Acc. to NAMUR NE43 Upper value: 21.0 ma Lower value: 3.6 ma (not with HART protocol) 80

81 VERSAFLOW VORTEX TECHNICAL DATA 8 Pulse output Pulse rate Power supply Max. 0.5 pulse/s (corresponds to 1800 pulses/hour) Non-Ex: 24 VDC as NAMUR or open < 1 ma, maximum 36 V, closed 100 ma, U < 2 V Ex: 24 VDC as NAMUR or open < 1 ma, maximum 30 V, closed 100 ma, U < 2 V HART HART protocol via current output Device revision 1 Physical layer FSK Device category Transmitter, galvanically isolated System requirements Load min. 250 Ω Multidrop operation 4mA Approvals and certifications ATEX FM ATEX II 2G Ex d ia [ia] IIC T6 Class I, II, III Div 1/2, groups A-G 81

82 8 TECHNICAL DATA VERSAFLOW VORTEX 8.3 Dimensions and weights Flange versions Option: version with 2 transmitters a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Specified weight kg Flange version EN Size Pressur e Dimensions [mm] Weight [kg] rating d d FR 1 d F2R 2 D L H l with without DN PN pressure sensor , , ,

83 VERSAFLOW VORTEX TECHNICAL DATA 8 Size Pressur e Dimensions [mm] Weight [kg] rating d d FR 1 d F2R 2 D L H l with without DN PN pressure sensor , FR - single reduction 2 F2R - double reduction 83

84 8 TECHNICAL DATA VERSAFLOW VORTEX a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Flange version ASME B16.5 Size Pressure rating Dimensions [mm] Weight [kg / lb] d d d D L H l with without NPS Class FR 1 F2R 2 pressure sensor ½ / / 9.9 ½ / / 10.8 ½ / / / / / / / / ½ / / ½ / / ½ / / / / / / / / / / / / / / / / / / / / , / / , / / , / / , / / , / / , / / ,7 154, / / ,5 202, / / ,5 202, / /

85 VERSAFLOW VORTEX TECHNICAL DATA 8 a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Flange version ASME B16.5 Size Pressure rating Dimensions [inches] Weight [kg / lb] d d d D L H l with without NPS Class FR 1 F2R 2 pressure sensor ½ / / 9.9 ½ / / 10.8 ½ / / / / / / / / ½ / / ½ / / ½ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / , / / , / /

86 8 TECHNICAL DATA VERSAFLOW VORTEX Sandwich version a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Sandwich version EN Size Pressure rating Dimensions [mm] Weight [kg] DN PN d D L H l With Without pressure sensor

87 VERSAFLOW VORTEX TECHNICAL DATA 8 a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Sandwich version ASME Size Pressure rating Dimensions [inches] Weight [lb] NPS Class d D L H l With Without pressure sensor ½ ½ ½ ½ ½ ½

88 8 TECHNICAL DATA VERSAFLOW VORTEX Dimensions remote version Dimension a Flanged version Sandwich version - DN NPS ½ 1 1½ [mm] ["] b c d e f g h j k l m n [mm] (4x) ["] (4x)

OPTISWIRL 4070 Handbook

OPTISWIRL 4070 Handbook OPTISWIRL 4070 Handbook Vortex flowmeter KROHNE : IMPRINT ::::::::::::::::::::::::::::::::::::::: All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the

More information

OPTISWIRL 4070 C. Handbook. Vortex-flowmeter

OPTISWIRL 4070 C. Handbook. Vortex-flowmeter OPTISWIRL 4070 C Handbook Vortex-flowmeter CONTENTS OPTISWIRL 4070 C 1 Safety... 5 1.1 Intended use... 5 1.2 Certifications... 6 1.3 Safety instructions from the manufacturer... 6 1.3.1 Notes about the

More information

VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet. Specification. The all-in-one solution. Highlights. Industries.

VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet. Specification. The all-in-one solution. Highlights. Industries. VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet 34-VF-03-05 September 3rd, 2008 Specification The all-in-one solution The VERSAFLOW is the only vortex flowmeter with integrated pressure and

More information

GA24. GA24 Handbook. Variable-area flowmeter. KROHNE 02/ MA GA24 R01 en

GA24. GA24 Handbook. Variable-area flowmeter. KROHNE 02/ MA GA24 R01 en GA24 Handbook Variable-area flowmeter KROHNE : IMPRINT :::::::::::::::::::::::::::::::::: All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the prior written

More information

DK48 - DK800. Quick Start. Variable area flowmeter

DK48 - DK800. Quick Start. Variable area flowmeter Quick Start Variable area flowmeter General safety notes You can find the newest and/or additional information in the handbook, the datasheet, special manuals, certificates and the download center at www.krohne.com.

More information

DK46 - DK800 Supplementary instructions

DK46 - DK800 Supplementary instructions DK46 - DK800 Supplementary instructions Variable area flowmeter Device category II2G with electrical internals Additional Ex manual KROHNE CONTENTS DK46 - DK800 1 Safety instructions 3 1.1 General... 3

More information

T EK-COR 1100A Coriolis Mass Flowmeter

T EK-COR 1100A Coriolis Mass Flowmeter T EK-COR 1100A Coriolis Mass Flowmeter Instruction Manual Document Number: IM-1100A NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance,

More information

Flow Measurement SITRANS F X

Flow Measurement SITRANS F X SITRANS FX00 Overview The main applications of SITRANS FX00 can be found in the following sectors: Chemical Petrochemical Oil & Gas Power plants -Air - Heating - Cooling -Chilling Food & beverage - Pharmaceutical

More information

GA24 Technical Datasheet

GA24 Technical Datasheet GA24 Technical Datasheet Variable-area flowmeter Sturdy construction for several applications Local indication without auxiliary power Replaceable mounting parts KROHNE CONTENTS GA24 1 Product features

More information

C-Flow Coriolis Mass Flow Meters

C-Flow Coriolis Mass Flow Meters Coriolis Mass Flow Meters Ready for Take Off The New Compact C-Flow Küppers Elektromechanik GmbH The C-Flow The C-Flow Coriolis Mass Meters consist of two components: KCE Transmitter KCM Transducer 2 KEM

More information

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm) Pressure Sensor (Stainless Steel Diaphragm) CSM DS_E_3_1 Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications Incorporates double diaphragms consisting of SUS316L stainless

More information

Vortex flowmeters. Product family introduction Principle of operation Product review Applications Key product features

Vortex flowmeters. Product family introduction Principle of operation Product review Applications Key product features Vortex flowmeters introduction Product review s Key product features This document should not be duplicated, used, distributed, or disclosed for any purpose unless authorized by Siemens. Page 1 Vortex

More information

INSTRUCTION MANUAL Pressure Relief Device LPT

INSTRUCTION MANUAL Pressure Relief Device LPT INSTRUCTION MANUAL Pressure Relief Device LPT 5COV475800 LPT REV00 CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment operation 2 2 PRESSURE RELIEF

More information

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25 Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating

More information

OPTIBAR P 1010 C Technical Datasheet

OPTIBAR P 1010 C Technical Datasheet Technical Datasheet Pressure transmitter with recessed diaphragm for general applications Wide variety thanks to modular design Measuring ranges up to 250 bar / 3750 psi High overload and temperature stability

More information

Pro-V Multivariable Flowmeter Model M22 In-line Vortex

Pro-V Multivariable Flowmeter Model M22 In-line Vortex Pro-V Multivariable Flowmeter Model M22 In-line Vortex Pro-V TM Advantage: Volumetric or mass flow monitoring of most liquids, gases, and steam Multivariable meter delivers mass flow, temperature, pressure,

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information Liquid Level EK-L CSM_EK-L_DS_E 3 Liquid Level That Is Unaffected by the Color of the or Liquid Mount to bypass pipes. Fit a wide range of pipe diameters: 8 to mm or to mm Built-in Amplifiers to save space.

More information

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars. Simply a question of better measurement SCHMIDT Flow Sensor SS 20.261 The cost-effective alternative in pressurised systems up to 10 bars. Compressed air technology Industrial processes A cost analysis

More information

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar EN - english Instructions for installation and operation Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar Dear customer, Thank you for deciding in favour of the METPOINT

More information

DC5A. Cyclone Separator Trap for Air. Copyright 2015 by TLV Co., Ltd. All rights reserved ISO 9001/ ISO MA-03 (DC5A) 19 June 2015

DC5A. Cyclone Separator Trap for Air. Copyright 2015 by TLV Co., Ltd. All rights reserved ISO 9001/ ISO MA-03 (DC5A) 19 June 2015 172-65205MA-03 (DC5A) 19 June 2015 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Cyclone Separator Trap for Air DC5A Copyright 2015 by TLV Co., Ltd. All rights

More information

Electro-Pneumatic Converter YT-940 SERIES

Electro-Pneumatic Converter YT-940 SERIES Electro-Pneumatic Converter YT-940 SERIES PRODUCT MANUAL VERSION 1.00 Contents 1. Introduction 3 1.1 General information for the users. 3 1.2 Manufacturer Warranty 3 1.3 Explosion Proof Warning. 4 2. Product

More information

Calibration Gas Instrument INSTRUCTION MANUAL. Release I. Advanced Calibration Designs, Inc.

Calibration Gas Instrument INSTRUCTION MANUAL. Release I. Advanced Calibration Designs, Inc. Advanced Calibration Designs, Inc. Calibration Gas Instrument INSTRUCTION MANUAL Release I www.goacd.com Instruction Manual Gas Generator Release I TABLE OF CONTENTS I. General Description Page 2 II. Start-Up

More information

OPERATING INSTRUCTIONS MANUAL FOR QACV PNEUMATIC DOSING PUMP

OPERATING INSTRUCTIONS MANUAL FOR QACV PNEUMATIC DOSING PUMP This operating instructions contains safety information that if ignored can endanger life or result in serious injury. They are indicated by this icon. Use of this pump with radioactive chemicals is forbidden!

More information

SonoMeter 30 Energy Meters

SonoMeter 30 Energy Meters Data Sheet SonoMeter 30 Energy Meters Description The Danfoss SonoMeter 30 is a range of ultrasonic, compact energy meters intended for measuring energy consumption in heating and cooling applications

More information

Vortex Flow Meter Wafer or Flange Connection. - Steam - Liquid - Gas

Vortex Flow Meter Wafer or Flange Connection. - Steam - Liquid - Gas Vortex Flow Meter Wafer or Flange Connection - Steam - Liquid - Gas Working Principle & Circuit Diagram Working Principle When a column body placed in flowing fluids in pipe, a series of vortices will

More information

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2 Self-operated Pressure Regulator Pressure Reducing Valve Type M 44-2 Type M 44-2, connection G 1 4, K VS = 0.15 Type M 44-2, connection G 1, K VS = 6 Fig. 1 Type M 44-2 Pressure Reducing Valve Mounting

More information

FTC130 Transmitter. Operating Manual

FTC130 Transmitter. Operating Manual Seite 1 von 11 FTC130 Transmitter Fast Thermal Conductivity Analyzer Operating Manual 1.09KD180724CWI1V05 Messkonzept GmbH Seite 2 von 11 1. Intended Use... 3 2. Description... 4 3. Measuring gases and

More information

400C & 450C DUAL PERFORMANCE VALUE PACKS

400C & 450C DUAL PERFORMANCE VALUE PACKS (Chrome) PART NO. 40013 (Silver) PART NO. 45012 (Chrome) PART NO. 45013 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before

More information

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Page 1 of 20 Page 2 of 20 TABLE OF CONTENTS Safety Warnings

More information

Operating Instructions

Operating Instructions Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table

More information

Magnetic level switch type MR783 Instruction Manual

Magnetic level switch type MR783 Instruction Manual Magnetic level switch Magnetic level switch type MR783 1. DESCRIPTION page 3 1.1 Operation page 3 1.2 Application page 3 1.3 Description page 3 2. SPECIFICATIONS page 3 2.1 Service Conditions page 4 2.2

More information

Instruction Manual Contact Pressure Vacuum Gauge

Instruction Manual Contact Pressure Vacuum Gauge MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery

More information

Operating Instructions. Ball valve fitting according to ZB For pressure transmitter VEGABAR 82. Document ID: 50027

Operating Instructions. Ball valve fitting according to ZB For pressure transmitter VEGABAR 82. Document ID: 50027 Operating Instructions Ball valve fitting according to ZB 2553 For pressure transmitter VEGABAR 82 Document ID: 50027 Contents Contents 1 About this document 1.1 Function... 3 1.2 Target group... 3 1.3

More information

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14 15 Elster GmbH Edition 7.15 Translation from the German 519 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas VG VG 15/1 Contents Solenoid valve for gas

More information

Instruction Manual Differential Pressure Transmitter

Instruction Manual Differential Pressure Transmitter DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance

More information

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO 420C AIR COMPRESSOR KIT PART NO. 42042 460C AIR COMPRESSOR KIT PART NO. 46043 420C 460C IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this

More information

SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual

SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual 8 Executive Drive P.O. Box 2105 Toms River, NJ 08754 (732) 244-0010 (800) 337-3762 fax (732) 244-8140 www.permapure.com info@permapure.com

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

Pro-V Multivariable Flowmeter

Pro-V Multivariable Flowmeter Pro-V Multivariable Flowmeter Model M23 Insertion Meter M23-V flowmeter provides cost-effective volumetric flow monitoring solution for most liquids M23-VT incorporates temperature sensing to provide a

More information

453 Series Steam Heated Vaporizing Regulator

453 Series Steam Heated Vaporizing Regulator ADI 0453A Certified ISO 9001:2000 453 Series Steam Heated Vaporizing Regulator INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions Controls Corporation

More information

Flow VA 520. incl. temperature measurement. Intelligent solutions for ac- for compressed air and gases R 1/4 (DN 8) DN 15 R 3/4 (DN 20) DN 25

Flow VA 520. incl. temperature measurement. Intelligent solutions for ac- for compressed air and gases R 1/4 (DN 8) DN 15 R 3/4 (DN 20) DN 25 VA 520 incl. temperature R 1/4 (DN 8) DN 15 R 3/4 (DN 20) DN 25 R 1 1/4 (DN 32) DN 40 R 2 (DN 50) Intelligent solutions for ac- for compressed air and gases work according to the approved calorimetric

More information

Flow VA 520. incl. temperature measurement. Intelligent solutions for ac- for compressed air and gases R 1/4 (DN 8) DN 15 R 3/4 (DN 20) DN 25

Flow VA 520. incl. temperature measurement. Intelligent solutions for ac- for compressed air and gases R 1/4 (DN 8) DN 15 R 3/4 (DN 20) DN 25 VA 520 incl. temperature R 1/4 (DN 8) DN 15 R 3/4 (DN 20) DN 25 R 1 1/4 (DN 32) DN 40 R 2 (DN 50) Intelligent solutions for ac- for compressed air and gases work according to the approved calorimetric

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

Integral type Differential pressure flowmeter VNT Series

Integral type Differential pressure flowmeter VNT Series Integral type Differential pressure flowmeter VNT Series OUTLINE VH series Wafer-Cone differential pressure flowmeter and high precision differential pressure transmitter are integrated into one flowmeter.

More information

SITRANS F I Gardex. Flowmeter. SITRANS F I Intra/Prima. Flap Flowmeter. Contents. English. General 1. SITRANS F I Gardex 2. SITRANS F I Intra/Prima 3

SITRANS F I Gardex. Flowmeter. SITRANS F I Intra/Prima. Flap Flowmeter. Contents. English. General 1. SITRANS F I Gardex 2. SITRANS F I Intra/Prima 3 Contents SITRANS F I Gardex Flowmeter English General 1 SITRANS F I Gardex 2 SITRANS F I Intra/Prima 3 SITRANS F I Intra/Prima Flap Flowmeter Instructions A5E00129182 Version 02 09/2003 SITRANS F ED Automatic

More information

Flow metering in gases Introduction to COMBIMASS family

Flow metering in gases Introduction to COMBIMASS family Flow metering in gases Introduction to COMBIMASS family - physical principle, basic information - different types of instruments, pricing & delivery time Sales Training Germany October 17 th to 19 th,

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock: - Do not disassemble. Do not attempt repairs or modifications. Refer to qualified service agencies for all service and repairs.

More information

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters www.kem-kueppers.com info@kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters Description The Tricor Mass Flow Meters measure simultaneously mass

More information

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS POP Safety Valve POP Safety Valve INTRODUCTION The effects of exceeding safe pressure levels in an unprotected pressure vessel or system, can have catastrophic effects on both plant and personnel. Safety

More information

Differential Pressure Transmiter

Differential Pressure Transmiter Differential Pressure Transmiter Description The is an economical alternative to established differential pressure transmitters. It combines state of the art electronics and a high performance sensor;

More information

User's Manual. Heavy Duty Dissolved Oxygen Meter. Model

User's Manual. Heavy Duty Dissolved Oxygen Meter. Model User's Manual Heavy Duty Dissolved Oxygen Meter Model 407510 Introduction Congratulations on your purchase of Extech's Heavy Duty Dissolved Oxygen / Temperature Meter which simultaneously displays Dissolved

More information

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures MINT-0289-XX TABLE OF CONTENTS Limited Warranty... 3 User Responsibility... 3-4 General Service... 4 Safety Precautions.... 5 Physical Dimensions..

More information

VA40 - VA45 Technical Datasheet

VA40 - VA45 Technical Datasheet VA40 - VA45 Technical Datasheet Variable area flowmeter Local indication without auxiliary power Adaptable to meet customers' requirements Replaceable mounting parts KROHNE CONTENTS VA40 - VA45 1 Product

More information

Coriolis Mass Flow Meter

Coriolis Mass Flow Meter Coriolis Mass Flow Meter TMFW Series Mini Type Coriolis Mass Flow Meter Xi an Tosilon Automation Co., Ltd No.299, Daqing Rd, Lianhu District, Xi'an Shaanxi, China Tel: +86-29-8823 8550 info@tosilon.com;

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany Multi-way diverting valves Series 29a and Series 29b, with packing with lever 1. The valves are

More information

DPC-30 DPC-100. Reference Manual

DPC-30 DPC-100. Reference Manual DPC-30 DPC-100 Reference Manual 1. Introduction 1.1 Description The Martel DPC Digital Pneumatic Calibrator improves upon traditional dial gauge pneumatic calibrators. The Martel DPC improves accuracy,

More information

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable GEP-6075 Rev. B 101574 Ref. I.D.: 16973 Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable WARNING USER SHOULD READ AND THOROUGHLY UNDERSTAND THESE

More information

7000 Series OPTIMASS Mass Flowmeters. Titanium Hastelloy Stainless Steel

7000 Series OPTIMASS Mass Flowmeters. Titanium Hastelloy Stainless Steel KROHNE 04/2003 7.02445.71.00 GR 7000 Series OPTIMASS Mass Flowmeters with single straight measuring tube Titanium Hastelloy Stainless Steel One tube no limits No limits with tube material No limits with

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

The affordable consumption counter for compressed air and gases R 3 /4 (DN 20)

The affordable consumption counter for compressed air and gases R 3 /4 (DN 20) VA 420 new The affordable consumption counter for compressed air and gases R 1 /4 (DN 8) DN 15 R 3 /4 (DN 20) DN 25 R 1 1 /4 (DN 32) DN 40 R 2 (DN 50) With mit und and ohne without Flansch flange Intelligent

More information

Flow Measurement SITRANS F X

Flow Measurement SITRANS F X Overview Using a vortex flowmeter with integrated pressure and temperature compensation such as the allows you not only to lower installation costs but also increase the measuring accuracy of the measuring

More information

Technical Data Sheet. OPTIMASS 7000 Custody Transfer Mass Flowmeter

Technical Data Sheet. OPTIMASS 7000 Custody Transfer Mass Flowmeter Technical Data Sheet KROHNE 12/2004 7.02516.21.00 CH/GR OPTIMASS 7000 Custody Transfer Mass Flowmeter with single straight measuring tube OIML R117 Pattern Approval Accuracy classes 0.3 / 0.5 / 1.0 / 1.5

More information

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22. *09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection

More information

CAST IRON SAFETY VALVE TYPE 6301

CAST IRON SAFETY VALVE TYPE 6301 CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a

More information

3000 Series OPTIMASS Mass Flowmeter. Stainless Steel Hastelloy

3000 Series OPTIMASS Mass Flowmeter. Stainless Steel Hastelloy KROHNE 07/2005 7.02446.25.00 GR 3000 Series OPTIMASS Mass Flowmeter with single Z-shaped measuring tube Stainless Steel Hastelloy Status: 10/99 One tube no limits No limits with tube material No limits

More information

Variable Area Flow Meters

Variable Area Flow Meters PDF Published May, 04 Variable Area Flow Meters Chemline F Series Variable Area Flow Meters are ideal for plastic piping. They provide a combination of accurate visual flow rate measurement and clear flow

More information

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644 Technical Services: Tel: (00) 31-9312 / Fax: (00) 791-5500 Model C Pipe Line Strainer 6, & 10 Inch (150, & 250) 250 psi (17,2) General Description The welded steel body Model C Pipe Line Strainers (Ref.

More information

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please

More information

Vortex Flow Sensor VA Di Ex-d for flow measurement in gases; with integrated, configurable transducer UVA in Ex-d housing

Vortex Flow Sensor VA Di Ex-d for flow measurement in gases; with integrated, configurable transducer UVA in Ex-d housing Vortex Flow Sensor VA Di Ex-d Vortex Flow Sensor VA Di Ex-d for flow measurement in gases; with integrated, configurable transducer UVA in Ex-d housing Drawing 1 Measurable variables actual flow rate actual

More information

OxyScan Graphic. Operating Instructions. UMS Micro-oxygen sensor 501. Microprocessor instrument

OxyScan Graphic. Operating Instructions. UMS Micro-oxygen sensor 501. Microprocessor instrument OxyScan Graphic Operating Instructions UMS Micro-oxygen sensor 501 Microprocessor instrument Introduction Thank you for choosing the UMS Micro Oxygen Sensor 501 - a highly advanced product! Please read

More information

T EK-SUB 4800C 19 mm Submersible Level Transmitter

T EK-SUB 4800C 19 mm Submersible Level Transmitter Technology Solutions T EK-SUB 4800C 19 mm Submersible Level Transmitter Instruction Manual Document Number: IM-4800C www.tek-trol.com Table of Contents 1 Safety Instructions... 2 1.1 Intended Use... 2

More information

Digital Vacuum Regulator

Digital Vacuum Regulator Temperature Control for Research and Industry Digital Vacuum Regulator User s Manual Model 300 INDEX SECTION PAGE 1. QUICK OPERATING INSTRUCTIONS........................... 3 Safety Notices.................................................

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

GasSense NDIR User Manual

GasSense NDIR User Manual INDEX INDEX... 1 1. OVERVIEW... 2 2. TECHNICAL DATA... 3 3. SPECIFICATIONS... 4 4. PRODUCT DESCRIPTION... 5 4.1 Mechanical details... 5 4.2 Piping... 7 4.3 Connections... 7 5. INSTALLATION... 10 6. CALIBRATION

More information

Vortex flow sensor VA Di Ex-d with integrated, configurable transducer UVA in a flameproof enclosure for applications in explosive atmospheres

Vortex flow sensor VA Di Ex-d with integrated, configurable transducer UVA in a flameproof enclosure for applications in explosive atmospheres Vortex flow sensor VA Di Ex-d with integrated, configurable transducer UVA in a flameproof enclosure for applications in explosive atmospheres Drawing 1 VA Di ZG1 Ex-d Measured variables actual flow rate

More information

AND OPERATION INSTRUCTIONS

AND OPERATION INSTRUCTIONS ADI 2111-D Certified ISO 9001 MEDICAL FLOWMETER (Back Pressure Compensated Thorpe Tube) INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions Controls

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens A 207 Overview Application The SITRANS P Compact pressure transmitter is designed for the special requirements of the food, pharmaceutical and biotechnology industries. The use of high-grade materials

More information

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please

More information

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection) Self-operated Regulators Type 42-10 RS Check Valve (backflow protection) Type 42-10 RS Check Valve (backflow protection) Mounting and Operating Instructions EB 3009 EN Edition December 2015 Definition

More information

Nitrogen Supply System

Nitrogen Supply System ATMOSCOPE Nitrogen Supply System NS500 Users Guide Copyright 2001 EDSYN, INC. ATMOSCOPE Nitrogen Supply Systems TABLE OF CONTENTS Introduction............................. 3 General Information.......................

More information

Sensor for Air Bubble Detection at Liquid Filled Tubes. SONOCHECK Type ABD06.xx. Operating Manual

Sensor for Air Bubble Detection at Liquid Filled Tubes. SONOCHECK Type ABD06.xx. Operating Manual Sensor for Air Bubble Detection at Liquid Filled Tubes SONOCHECK Type ABD06.xx Operating Manual Manufacturer: Model: Type: SONOTEC Ultraschallsensorik Halle GmbH Air Bubble Detector ABD06.xx SONOTEC Ultraschallsensorik

More information

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers MASS-STREAM TM Instruction Manual D-6200 Analog Mass Flow Meters / Controllers Doc. No.: 9.17.112A Date: 17-03-2017 ATTENTION Before installing and operating the instrument it is strongly recommended that

More information

Operating Instructions

Operating Instructions LPL Series LED Pendant Lighting Operating Instructions IM0102 COOPER Electronic Technologies (Shanghai) Co., Ltd. No. 955 Shengli Road, East Area of Zhangjiang High-Tech Park, Shanghai 201201 China 1.

More information

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN Type 3709 Pneumatic Lock-up Valve Translation of original instructions Mounting and Operating Instructions EB 8391 EN Edition July 2017 Note on these mounting and operating instructions These mounting

More information

D10S/D20S Wall/Post Mount Inflator Quick Start Manual

D10S/D20S Wall/Post Mount Inflator Quick Start Manual PART NUMBER SERIAL NUMBER D10S/D20S Wall/Post Mount Inflator Quick Start Manual Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product

More information

Engineering Data Sheet

Engineering Data Sheet Page 1 of 6 CE MARKING AND THE PRESSURE EQUIPMENT DIRECTIVE 97/23/EC Valves must be installed into a well designed system and it is recommended that the system be inspected in accordance with the appropriate

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany Continuous, inline sampling valves Series 27f, with packing Operate with either; Star lever, or

More information

ATD /8 x 50 Retractable Air Hose Reel Owner s Manual

ATD /8 x 50 Retractable Air Hose Reel Owner s Manual ATD-31166 3/8 x 50 Retractable Air Hose Reel Owner s Manual Features Heavy-gauge, all-steel reel assembly 8-position ratchet mechanism locks reel at desired hose length 5-position adjustable roller outlet

More information

ASDX Series Silicon Pressure Sensors

ASDX Series Silicon Pressure Sensors ASDX Series Silicon Pressure Sensors DESCRIPTION The ASDX Series is a Silicon Pressure Sensor offering a ratiometric analog interface for reading pressure over the specified full scale pressure span and

More information

Operating Instructions DB41

Operating Instructions DB41 PKP Process Instruments Inc. 10 Brent Drive Hudson, MA 01749 Tel: +1-978-212-0006 Fax: +1-978-568-0060 PKP Prozessmesstechnik GmbH Borsigstrasse 24 D-65205 Wiesbaden-Nordenstadt Tel: 06122 / 7055-0 Fax:

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

Liquid level instruments BM 24 /BM 51

Liquid level instruments BM 24 /BM 51 KROHNE 09/2001 7.02362.21.00 GR/PRINTO Liquid level instruments / Status: 10/99 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters

More information