EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM

Size: px
Start display at page:

Download "EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM"

Transcription

1 EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM 1.0 OBJECTIVE To study the response of gas pressure control using PID controller. 2.0 INTRODUCTION TO THE APPARATUS a) The process plant consists of two air vessels T91 and T92 with the associated piping, valves and fittings. b) An external air supply from the compressor air system is connected to the Model plant at the process inlet at the pressure regulator, AR91, into the vessel T91. This inlet pressure (Barg, psig) is preset according to the pressure indicated at AR91, with its downstream manual valve MV91 shut. The maximum inflow rate can be varied by regulating the manual valve MV91 immediately downstream of AR91. c) The process air inlet flows into T91 and then along pipeline PLI-T92-FI92-PCV91- discharge via the process vent valve VP. The process air also flows from T92 along pipeline PLII-PCV92-discharge via either manual globe valve MV92A/orifice OR manual gate valve MV92B. The pressure in T91 is also measured by a gauge pressure transmitter PT91 and controlled by PID pressure controller PIC91, which throttles control valve PCV91 via the Current (4-20mA) to Air (3- psig) converter, PCY91 and the pneumatic positioner (PP). Control valve PCV91 is ATC (Air-to-Close).The process air finally discharges to atmosphere via the process vent VP through PCV91 and the variable area flowmeter FI92. d) The pressure measured by the gauge pressure transmitter PT92 is controlled ON/OFF by the ON/OFF pressure controller PIC92. PIC92 will switch to close the normally-open (NO) solenoid valve PSV92, when the preset high pressure limit is exceeded. The ON/OFF control valve PCV92 is ATC (Air-to-Close). Thus when the pressure in T92 or its discharge pipeline is above the preset high limit, PIC92 switches to close PSV92, cutting off the instrument air supply to the actuator of PCV92. PCV92 then opens to vent (V) air to the atmosphere. The rate of discharge can be manually set at the manual valves (MV92A, MV92B) at the common vent line (V) downstream of PCV92. e) Note that both the control valves PCV91 and PCV92 are Air-to-Close (ATC) so that when there is instrument air failure, they stay open to vent out any pressure inside the plant. 1

2 CONTROL SYSTEM AND INSTRUMENTATION PT91 PCV91 PP PCY91 PSV92 PCV92 PG91, PG92, PG93, PG94 TG91, TG92 FI92 PRV91, PRV92 SV91 : Gauge Pressure Transmitter. Calibrated Range: 0-25 psig Measures air pressure in T91 : Pressure control valve ½. Air-to-Close (ATC). Regulated by PID controller PIC91 or PIC92 : Pneumatic Positioner, with By-pass. : Current-to-Air Converter (I/P) : 4-20mA to 3- psig : Solenoid valve, Normally-Open (NO) : ON/OFF pneumatic control valve, Air-to-Close (ATC). PCV92 is opened by ON/OFF controller PIC92 via PSV92, when the pressure measured by PT91 is above its preset high pressure limit. : Pressure Gauges : Temperature Gauges : Variable area flowmeter (Rotameter). Metal construction safety type. : Pressure Relief Valves : ON/OFF Solenoid Valve The Annunciators are: PAD91 : The pressure at T91, measured by PT91, exceeds its preset Deviation from the setpoint, whether above or below. The Deviation alarm limit is set at DL1 at the PID1 page or panel. PAL91 : The pressure at T91, measured by PT91, drops below its preset Low alarm limit. The Low alarm limit is set at PL1 at the PID1 page or panel. 2

3 3.0 EXPERIMENTAL PROCEDURE 1. Make sure the Instrument Air Supply (IAS) or AR91 is set at psig. Adjust the manual valve MV91 till rotameter FI92 is at flowrate of 30Nm³/Hr max. DO NOT exceed the stated flowrate. 2. Check the pressure with PCV91 fully shut. The parameter PV1 at controller PIC91 (i.e. PT91) should be psig. Reset AR91 if the pressure is insufficient. 3. Check the flowrate with PCV91 fully open. The parameter PV1 at controller PIC91 (i.e. PT91) should be less than 5-6 psig and the flowrate at FI92 is not more than the recommended flowrate. Readjust MV91 for maximum flowrate. 4. Make sure the valve Positioner (PP) at PC91 is ON and connected. With PIC91 in Manual (M) mode, stroke the control valve PCV91 manually with MV = 100%, 50% and 0% and note that the corresponding valve stem position at its stem indicator scale is 0%, 50% and 100% opened. 5. With PIC91 in the Manual (M) mode, open the control valve PCV91 fully with MV= -6.3%. For confirmation, check the control valve stem position at PCV91. Take note of the minimum pressure PV1 (in PIC91). Concentrate on the Pressure PID panel controller PIC91/PIC92 and the recorder PR Check that vessels T91 and T92 are connected for air to flow in series from one vessel to the next. Check their respective pressure at the pressure gauges PG91 and PG92. The manual By-pass valve B92 around T92 should be fully shut. The final manual discharge valve (VP) downstream of the pressure control valve PCV91 should be fully opened. 7. Start the recorder PR91 by pressing the RCD pushbutton at the front of the recorder with its swing front cover opened. Note that PT91 response is shown by the Red pen (Channel 1), Input Range: % of 0-25 psig. The recorder chart drive is preset for fast speed (500mm/Hr). 8. Access the PID values in the pressure PID controller PIC91, at the PID1 page or panel. Set the following first (I) trial PID values. PB1 = 70 %, TI1 = 40 secs, TD1 = 0 9. Adjust the setpoint SV to 18 psig (72%) at PIC91. Make sure the chart drive of the recorder PR91 is running. Otherwise, press the RCD button at the front of the recorder with its swing front cover opened. 10. Transfer PIC91 to Auto (A) mode and watch the response at the recorder PR91 till it is steady at its setpoint SV to within ± 0.1 psig or continues to oscillate even after 3 cycles. 3

4 11. Continue the experiment for both 2-capacity and 1-capacity processes using the following settings: PIC91 PID Pressure Control of T91/92 PID Values Same PID, different SV. Different PID, same SV. 20/30/0 45/30/0 Fine tune Second (II) PID, increasing PB1 by 10% and reducing TI1 by 10 secs at a time. Setpoint, psig Test Setpoint step test 12. Apply the load step test as follows: When the response is steady, switch PIC91 to Manual (M) mode and decrease its MV by 5-10%. Quickly switch PIC91 back to Auto (A) and observe the pressure response at the recorder PR91 till it is almost steady to within ± 0.1 psi, or continue to show oscillatory response even after 3 cycles. The chart recording constitutes the results of your experiment. Note down on the chart the PB1, TI1, TD1 and SV values. Watch closely for overdamped and underdamped response and the possibility of any inlet load disturbance. Careful consideration must be taken then to provide effective control. 13. Apply the setpoint step test as follows: With PIC91 in Auto (A) mode, apply a step change in setpoint (SV) from 18 to 9 psig (72% to 36%). Observe the chart response similarly and note down the SV and PID1 values on the chart. 14. In order to check for process inlet load disturbance, carefully monitor the response. If the response tends to oscillate outside the desired control band of ±0.1 psig (i.e. below 8.9 and above 9.1 psig for SV = 9 psig; OR below 17.9 and above 18.1 psig for SV = 18 psig); switch PIC91 to Manual (M) mode and observe if the pressure i.e. process air inlet supply is still oscillating. Note: Oscillation of process air inlet supply is a load disturbance at the process inlet. 4

5 . If the load disturbance does occur, then the PID values (70% / 40 sec/ 0 sec) may have slowed down the controller action, till it is slower than the process inlet disturbance. Thus, try a faster TI i.e. set TI1 = 10 to 20 secs instead of 40 secs, for faster setpoint recovery. Observe similarly for any improvement. 16. To shut-down AP922: - Shut MV91 but do not adjust AR91. - Switch PIC91 to Manual (M) mode with its MV = 0% - Shut fully the isolation manual valve at the main air supply line to Model AP RESULTS/DISCUSSION Relevant portions of the recorder chart responses should be submitted as results of the experiment, with the following pertinent data marked on the corresponding chart recording:- Setpoint (SV), PB%, TI seconds, TD seconds. NOTE: The Recorder chart speed is occasionally printed on the chart, for example at 500 mm or mm or 7.2 secs Hr sec mm Provide your results and discussion by answering the following questions: a) Study and compare the different pressure responses for different PID values. Calculate the time constant and dead time for each response. b) Use the following terms to calculate the dynamics of underdamped process: Rise time, Settling time, Overshoot and Period of oscillation. c) What is the purpose of testing the PID at different setpoint? d) In your opinion, is PID a good controller for gas pressure control? State your reason(s). 5

EXPERIMENT 2 LEVEL CONTROL SYSTEM

EXPERIMENT 2 LEVEL CONTROL SYSTEM EXPERIMENT 2 LEVEL CONTROL SYSTEM 1.0 OBJECTIVE To study the response of level control process in open tank using the PID controller. 2.0 INTRODUCTION TO THE APPARATUS (MODEL WLF922). a) The process consists

More information

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller CHEMICAL ENGINEERING LABORATORY CHEG 239W Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller Objective The experiment involves tuning a commercial process controller for temperature

More information

Process & Instrumentation Diagram (P&ID) Purpose. Howitisdone? Methodology?

Process & Instrumentation Diagram (P&ID) Purpose. Howitisdone? Methodology? Process & Instrumentation Diagram (P&ID) Purpose 1. To indicate the instruments or control devices attached to the process. 2. To indicate the control system architecture associated with the process. Howitisdone?

More information

Control Valve : The Final Control Element. Nimish Shah

Control Valve : The Final Control Element. Nimish Shah Control Valve : The Final Control Element Nimish Shah VALVES How to select Control Valve??? selection parameters for the valve : size, material of construction, pressure and temperature ratings, and End

More information

Gerald D. Anderson. Education Technical Specialist

Gerald D. Anderson. Education Technical Specialist Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions

More information

Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST)

Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST) Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST) Application Positioner firmware for early detection of control valve faults giving maintenance recommendations. Valid

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

CHAPTER 7: THE FEEDBACK LOOP

CHAPTER 7: THE FEEDBACK LOOP When I complete this chapter, I want to be able to do the following. Identify the major elements in the feedback loop Select appropriate candidate variables to be controlled and manipulated Evaluate the

More information

PRESSURE CONTROL TRAINER

PRESSURE CONTROL TRAINER PRESSURE CONTROL TRAINER Product Code 314A (PCT version) (With Ethernet communication) Instruction manual Contents 1 Description 2 Specifications 3 Packing slip 4 Installation requirements 5 Installation

More information

GeQuip Joule Thomson Plant. Process Description (see Figure 1) Standard Control Instrumentation

GeQuip Joule Thomson Plant. Process Description (see Figure 1) Standard Control Instrumentation Process Description (see Figure 1) The purpose of the process configuration of a Joule Thomson plant is to refrigerate the gas by expanding the gas across a restriction (commonly referred to as a choke

More information

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler. Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure

More information

Dynamic Simulation for T-9 Storage Tank (Holding Case)

Dynamic Simulation for T-9 Storage Tank (Holding Case) Dynamic Simulation for T-9 Storage Tank (Holding Case) CASE 1: 19,642 Kg/Hr (Holding: 52 o C), No Liquid Draw Workshop Description Estimation of vapor flow rate coming out from the T-9 tank for holding

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Level Process Control. Penn State Chemical Engineering

Level Process Control. Penn State Chemical Engineering Level Process Control Penn State Chemical Engineering Revised Spring 2015 1 Table of Contents LEARNING OBJECTIVES... 3 EXPERIMENTAL OBJECTIVES AND OVERVIEW... 3 Pre-lab study... 3 Experiments in the lab...

More information

V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS

V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS V10K SYSTEM: PROVEN TECHNOLOGY WORLDWIDE IN USE Since Charles F. Wallace and Martin F. Tiernan discovered the first chlorine gas feed system in 1913 the

More information

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE Exercise 8 Closed-Loop Pressure Control, EXERCISE OBJECTIVE To understand open and closed-loop pressure control; To learn how to sense the pressure in a pneumatic circuit; To control the pressure in a

More information

Pressure on Demand. Air Pressure Amplifiers

Pressure on Demand. Air Pressure Amplifiers Pressure on Demand Air Pressure Amplifiers Introduction Haskel air pressure amplifiers offer the most comprehensive range in the industry combining simple principles of operation with rugged construction

More information

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve Test Report # 30016558 Rev 0 Adiabatic Compression With Constant Bleed Valve Scope: This test report contains test data on the effects of adiabatic compression in nitrogen service on AP3600 diaphragm valves,

More information

Fisher DSA Steam-Atomized Desuperheater

Fisher DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Fisher DSA Steam-Atomized Desuperheater Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 2 Operating Instructions...

More information

Design DSA Steam-Atomized Desuperheater

Design DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Design DSA Steam-Atomized Desuperheater Contents Introduction............................... 1 Scope of Manual......................... 1 Description..............................

More information

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control Introduction This experiment offers a look into the broad field of process control. This area of

More information

Service Test Unit for ROSS Proportional Valves RESK

Service Test Unit for ROSS Proportional Valves RESK Service Unit for Proportional Valves Page 1 Technical Description ROSS 04.08.2015 Service Test Unit for ROSS Proportional Valves Technical Description V 1.0 / 2015 RESK 4591.40 For all Prop Valve Models

More information

Characterizers for control loops

Characterizers for control loops Characterizers for control loops By: F. G. Shinskey (May 1999) Introduction Commercial controllers such as the PID series (proportional, integral, derivative, and their combinations) are linear devices

More information

Fisher DVI Desuperheater Venturi Inline

Fisher DVI Desuperheater Venturi Inline Instruction Manual DVI Desuperheater Fisher DVI Desuperheater Venturi Inline Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 3 Operating Instructions...

More information

Time-Delay Electropneumatic Applications

Time-Delay Electropneumatic Applications Exercise 3-4 EXERCISE OBJECTIVE & & & To introduce time delays; To describe the operation of a time-delay valve; To describe the operation of a time-delay relay. DISCUSSION Time-Delays Time delays are

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION Exercise 2-2 Second-Order Interacting Processes EXERCISE OBJECTIVE Familiarize yourself with second-order interacting processes and experiment with the finer points of controller tuning to gain a deeper

More information

Valve Communication Solutions Axiom

Valve Communication Solutions Axiom Axiom Detect automated valve problems... before they shut down your process Reasons for Automated On/Off Valve Failures Monitor Fail Solenoid Fail Actuator Fail Coupling Break Too Slow Leaking Sticking

More information

SB AXIAL FLOW VALVES

SB AXIAL FLOW VALVES SB9509.3 AXIAL FLOW VALVES The improved technology for pressure regulation The American Axial Flow Valve provides pressure and flow control in high capacity pipelines. It can be used for pressure regulation,

More information

Operating Instructions EB EN. Series 373x Electropneumatic Positioner Type 373x-5 EXPERT + with FOUNDATION fieldbus communication

Operating Instructions EB EN. Series 373x Electropneumatic Positioner Type 373x-5 EXPERT + with FOUNDATION fieldbus communication Series 373x Electropneumatic Positioner Type 373x-5 EXPERT + with FOUNDATION fieldbus communication Fig. 1 Valve diagnostics with TROVIS-VIEW Operator Interface Operating Instructions EB 8388-5 EN Firmware

More information

Unit 55: Instrumentation and Control Principles

Unit 55: Instrumentation and Control Principles Unit 55: Instrumentation and Control Principles Unit code: J/601/1417 QCF level: 4 Credit value: 15 OUTCOME 2 PROCESS CONTROL SYSTEMS AND CONTROLLERS 2 Understand process control systems and controllers

More information

T e l N o : F a x N o : E m a i l : a i s h c m c - m e. c o m w w w. c m c - m e.

T e l N o : F a x N o : E m a i l : a i s h c m c - m e. c o m w w w. c m c - m e. MU047: Practical Valve Technology: Selection, Installation, Upgrading, Inspection & Troubleshooting MU047 Rev.002 CMCT COURSE OUTLINE Page 1 of 7 Training Description: This five-day intensive course covers

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

Four common PRESSURE CALIBRATION PAIN POINTS

Four common PRESSURE CALIBRATION PAIN POINTS Four common PRESSURE CALIBRATION PAIN POINTS Pressure calibration is often critical to process control systems, helping to optimize operations and ensure plant safety. While pressure instrumentation can

More information

How to Combat Process Disturbances and Interactions

How to Combat Process Disturbances and Interactions How to Combat Process Disturbances and Interactions Henri A. (Hank) Brittain, Ph.D., Jean-François Dubé, P.Eng. BBA - Top Control Inc. KEYWORDS Decoupling, First-Order Plus DeadTime (FOPDT) Feedforward,

More information

The Ins and Outs of I/P Transducers

The Ins and Outs of I/P Transducers The Ins and Outs of I/P Transducers By Mark B. Levine, ControlAir Inc. General description I/P transducers are versatile instruments that use an electrical control signal to proportionally regulate gas

More information

NATIONAL UNIVERSITY OF SINGAPORE. EE3302/EE3302E Industrial Control Systems E1: ADVANCED CONTROL SYSTEMS

NATIONAL UNIVERSITY OF SINGAPORE. EE3302/EE3302E Industrial Control Systems E1: ADVANCED CONTROL SYSTEMS NATIONAL UNIVERSITY OF SINGAPORE EE3302/EE3302E Industrial Control Systems E1:. OBJECTIVES: Before embarking on this hands-on session, you should have been introduced to the concepts of cascade and feedforward

More information

NOTICE. Issued: February 12, 2010 AO# Dundas Street West, Oakville, ON CANADA Phone: (905) Fax: (905)

NOTICE. Issued: February 12, 2010 AO# Dundas Street West, Oakville, ON CANADA Phone: (905) Fax: (905) NOTICE The enclosed materials are considered proprietary property of GE Water & Process Technologies. No assignments, either implied or expressed, of intellectual property rights, data, know how, trade

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

MODEL LW74E, LW76E. Unit of Total Plate Front Cover Fitting HEX Soc. Bolt TAG (Ratings Shown) Register Front Cover

MODEL LW74E, LW76E. Unit of Total Plate Front Cover Fitting HEX Soc. Bolt TAG (Ratings Shown) Register Front Cover Total-counter type Register ULTRA OVAL with BATCH CONTROLLER MODEL LW74E, LW76E GENERAL SPECIFICATION GS.No.GBC201E 5 GENERAL This unit is designed specifically to mount integrally on the ULTRA OVAL, a

More information

Data Sheet T 8389 EN. Series 3730 and 3731 Types , , , and. EXPERTplus Valve Diagnostic

Data Sheet T 8389 EN. Series 3730 and 3731 Types , , , and. EXPERTplus Valve Diagnostic Data Sheet T 8389 EN Series 3730 and 3731 Types 3730-2, 3730-3, 3730-4, 3730-5 and Type 3731-3 Electropneumatic Positioners EXPERTplus Valve Diagnostic Application Positioner firmware to detect potential

More information

GP1 & GP2. Electropneumatic Regulators FOR PRESSURE CONTROL TO 1,000 PSI

GP1 & GP2. Electropneumatic Regulators FOR PRESSURE CONTROL TO 1,000 PSI GP1 & GP2 Electropneumatic Regulators FOR PRESSURE CONTROL TO 1, PSI GP1 & GP2 Functional Description The GP series control valve is an electronic pressure regulator designed to precisely control the pressure

More information

REASONS FOR THE DEVELOPMENT

REASONS FOR THE DEVELOPMENT 7 Series 7 Series +24VDC VDC OUTPUT MICROPROCESS. E P IN EXH OUT 7 Series 7 ø,8 8 7 Series 9 5 8 9 7 Series Display features The proportional regulator has a 3 /2 digit display and a three-pushbutton

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

SECTION P4 SEPARATION SYSTEMS

SECTION P4 SEPARATION SYSTEMS SEPARATION SYSTEMS The H.P. Separation System begins with the H.P. Production Header (GAY-1000). This header directs flow to the H.P. Production Separator (MBD-1000). Gases from the H.P. Production Separator

More information

C1 Series Pneumatic Controllers and Transmitters

C1 Series Pneumatic Controllers and Transmitters Instruction Manual C1 Controllers and Transmitters C1 Series Pneumatic Controllers and Transmitters Contents Introduction............................... 2 Scope of Manual......................... 2 Description..............................

More information

CP3R Quick Start Manual

CP3R Quick Start Manual RUN MON PRM PU EXT NET RUN D700 3 200V RUN MON PRM PU EXT NET RUN D700 3 200V CP3R Quick Start Manual for Constant Pressure Applications This CP3R Drive has been factory pre-programmed for your specific

More information

Modelling of the Separated Geothermal Water Flow between Te Mihi flash plants

Modelling of the Separated Geothermal Water Flow between Te Mihi flash plants Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Modelling of the Separated Geothermal Water Flow between Te Mihi flash plants Kevin Koorey, Kim Harwood and Norman Lawgun

More information

CPN1 Quick Start Manual

CPN1 Quick Start Manual RUN MON PRM PU EXT NET RUN RUN MON PRM PU EXT NET RUN CPN1 Quick Start Manual for Constant Pressure Applications This CPN1 Drive has been factory pre-programmed for your specific pressure control application.

More information

APPS-160 Gen 2 User Manual

APPS-160 Gen 2 User Manual APPS-160 Gen 2 User Manual Applicable Products: PN 11914406 - APPS-160 10 to 50 PSIG operating pressure PN 11918618 - APPS-160 40 to 85 PSIG operating pressure Rev 9/16/2004 Chart Ind. www-chart-ind.com

More information

STICTION: THE HIDDEN MENACE

STICTION: THE HIDDEN MENACE STICTION: THE HIDDEN MENACE How to Recognize This Most Difficult Cause of Loop Cycling By Michel Ruel Reprinted with permission from Control Magazine, November 2000. (Most figures courtesy of ExperTune

More information

Richards Industries Basic Siemens PS2 Positioner Functions

Richards Industries Basic Siemens PS2 Positioner Functions Basic Siemens PS2 Positioner Functions Wiring 1 Supply Pressure Use clean, dry instrument air for the supply pressure. In general, on valves that are normally closed, you need 35-40 psi of supply pressure

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring

More information

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters Instruction Manual Form 5177 March 1999 4150K and 4160K Series 4150K and 4160K Series Wizard II Pressure Controllers and Transmitters Contents Introduction.............................. 2 Scope of Manual.............................

More information

QuickHeat TM Packaged Heat Exchanger Solutions

QuickHeat TM Packaged Heat Exchanger Solutions 4831999/1 IM-P483-03 CH Issue 1 QuickHeat TM Packaged Heat Exchanger Solutions Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

SERVICE MANUAL No. I-0043

SERVICE MANUAL No. I-0043 Bettis Canada Ltd. 4112 91A Street Edmonton, Alberta, Canada T6E 5V2 Tel: (403) 450-3600 Fax: (403) 450-1400 SERVICE MANUAL No. I-0043 Edmonton GAS/HYDRAULIC ADDITIONAL COMPONENTS CUSTOMER: P.O.#: W.O.#:

More information

LABORATORY EXERCISE 1 CONTROL VALVE CHARACTERISTICS

LABORATORY EXERCISE 1 CONTROL VALVE CHARACTERISTICS Date: Name: LABORATORY EXERCISE 1 CONTROL VALVE CHARACTERISTICS OBJECTIVE: To demonstrate the relation between valve stem position and the fluid flow through a control valve, for both linear and equal

More information

SSL. Smart Valve Positioner.

SSL. Smart Valve Positioner. Smart Valve Positioner Smartest valve control device meeting a dynamic performance and a precise setting with a piezoelectric technology and an optimized auto-calibration program Features Auto-Calibration

More information

CASCADE CONTROL TRAINER

CASCADE CONTROL TRAINER CASCADE CONTROL TRAINER Product Code 315A (PCT version) Instruction manual Contents 1 Description 2 Specifications 3 Installation requirements 4 Installation Commissioning 5 Troubleshooting 6 Components

More information

RC 195 Receiver-Controller

RC 195 Receiver-Controller Document No. 129-082 RC 195 Receiver-Controller Product Description The POWERS RC 195 Receiver-Controller is a pneumatic instrument that receives one, two or three pneumatic inputs. It produces a pneumatic

More information

Temperature Controllers

Temperature Controllers IM0004 April 2013 CONTENTS T-12 Thermostat PAGE Introduction 1 Scope 1 Description 1 Specification 1 Temperature Controllers 2 INTRODUCTION CAUTION Prior to installing, the instructions provided herein

More information

EDUCATION DEPARTMENT ACCU-TEST

EDUCATION DEPARTMENT ACCU-TEST ABN 17 100 208 964 EDUCATION DEPARTMENT ACCU-TEST GAS SAFETY SHUT OFF SYSTEM Operating & Installation Manual Head Office (Melbourne) Sydney Brisbane (Distributor) 1/5 Samantha Court 2/14 Welder Road 17

More information

FUEL GAS FIRING CONTROL RJ (Dick) Perry Safety Systems Consultant 6 June 2016

FUEL GAS FIRING CONTROL RJ (Dick) Perry Safety Systems Consultant 6 June 2016 INTRODUCTION Fired equipment such as Heaters and Boilers, normally have to comply with either NFPA 85/86 or API 556 for North America and some other countries which apply such standards, or EN 746-2 for

More information

Fisher C1 Pneumatic Controllers and Transmitters

Fisher C1 Pneumatic Controllers and Transmitters Instruction Manual C1 Controllers and Transmitters Fisher C1 Pneumatic Controllers and Transmitters Contents Introduction... 2 Scope of Manual... 2 Description... 2 Specifications... 2 Educational Services...

More information

SEPARATION SYSTEMS. The Separation Systems consists of the Test Header (GAY-0302) and the Test Separator (MBD-4501).

SEPARATION SYSTEMS. The Separation Systems consists of the Test Header (GAY-0302) and the Test Separator (MBD-4501). SEPARATION SYSTEMS The Separation Systems consists of the Test Header (GAY-0302) and the Test Separator (MBD-4501). The Header System is designed to collect and direct the well stream to the corresponding

More information

Becker Precision Equipment

Becker Precision Equipment Becker Precision Equipment VRP-B-CH Series Valve Regulation Pilot VRP-B-CH Valve Regulator Pilot Provides Low-Bleed Pressure Control When Combined with Double-Acting Pneumatic Control Valve Actuators Description

More information

Vacuum Pumpdown and Venting Procedure, CRaTER Thermal Vacuum System. Dwg. No

Vacuum Pumpdown and Venting Procedure, CRaTER Thermal Vacuum System. Dwg. No Rev. ECO Description Checked Approval Date 01 32- Release M. Smith Vacuum Pumpdown and Venting Procedure, CRaTER Thermal Vacuum System Dwg. No. 32-06003.05 Revision 01 June 18, 2007 1 1. Introduction 1.1.

More information

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100 107 W. Main Street Worthington, PA 16262 Phone: 724.297.3416 Fax: 724.297.5189 http://www.airtak.com OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100 12-2007 TABLE OF CONTENTS PAGE

More information

Considering Control Valve EFFICIENCY

Considering Control Valve EFFICIENCY Considering Control Valve EFFICIENCY Strategies for optimizing the energy requirement for control valves in plant systems The discussions revolving around the scarcity of fossil fuels and increasing energy

More information

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA. Dry 132a. October 1, 2008 October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.

More information

Operating Instructions

Operating Instructions Operating Instructions Before operating the thin film evaporator, please be aware of all safety concerns associated with this experiment: Burn hazard from the column and steam lines, Chemical hazards associated

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

Model: 43T. Bermad Pressure Relief Valve

Model: 43T. Bermad Pressure Relief Valve Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment

More information

WW-730. Pressure Sustaining/Relief Control Valve

WW-730. Pressure Sustaining/Relief Control Valve WW-730 Pressure Sustaining/Relief Control Valve Installation Operation & Maintenance Page 1 of 6 1. DESCRIPTION The Model 730 Pressure Relief / Sustaining Valve is an automatic control valve designed to

More information

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions

More information

my SYSTEM A guide to common applications in water distribution systems

my SYSTEM A guide to common applications in water distribution systems my SYSTEM A guide to common applications in water distribution systems WWW.SINGERVALVE.COM INDEX This short guide is intended to offer guidance on some of the common problems, applications and questions

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

Plasma Asher: March PX-500 User guide (May-30, 2017)

Plasma Asher: March PX-500 User guide (May-30, 2017) Plasma Asher: March PX-500 User guide (May-30, 2017) This is a highly versatile plasma etch tool that can etch using a direct plasma configuration (Oxygen plasma cleaner), a downstream plasma (Remote plasma),

More information

WW-720. Pressure Reducing Control Valve

WW-720. Pressure Reducing Control Valve WW-720 Pressure Reducing Control Valve (Size Ranges: 2-4 and 6-14 ) Installation Operation & Maintenance Page 1 of 6 1. DESCRIPTION The Model 720 Pressure Reducing is an automatic control valve (powered

More information

Calibration and Switching Module

Calibration and Switching Module Calibration and Switching Module Application Guide A Swagelok Pre-Engineered Subsystem Pre-engineered subsystems available in weeks, not months. Field-tested design ensures optimum system performance.

More information

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. Supplied with an electric input signal of 4 to 20

More information

NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab Torque Calculation & Actuator Mounting Data tab... 21

NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab Torque Calculation & Actuator Mounting Data tab... 21 NORDCALC User Guide Table of Contents NORDCALC Introduction... 2 Registration... 2 Flow Calculations tab... 5 Calculating the gas flow rate for gaseous medium... 6 Calculating the pressure drop for gaseous

More information

OFI MODEL 20 CONSTANT SPEED BLENDER INSTRUCTIONAL MANUAL

OFI MODEL 20 CONSTANT SPEED BLENDER INSTRUCTIONAL MANUAL OFI MODEL 20 CONSTANT SPEED BLENDER INSTRUCTIONAL MANUAL OPERATING INSTRUCTIONS OFI MODEL 20 CONSTANT SPEED BLENDER GENERAL OFI's Model 20 Constant Speed Blender was designed to prepare well cements for

More information

Experimental Investigation on Transient Response of Two Stage Pressure Relief Valve

Experimental Investigation on Transient Response of Two Stage Pressure Relief Valve Experimental Investigation on Transient Response of Two Stage Pressure Relief Valve Prof. Basavaraj V.HUBBALLI 1, Dr. Vilas B.SONDUR 2 1 Jain College of Engineering, Belagavi Karnataka, India, bvhubliabhi@gmail.com

More information

Modeling a Pressure Safety Valve

Modeling a Pressure Safety Valve Modeling a Pressure Safety Valve Pressure Safety Valves (PSV), Pressure Relief Valves (PRV), and other pressure relieving devices offer protection against overpressure in many types of hydraulic systems.

More information

Controlling the prefeeder

Controlling the prefeeder Controlling the prefeeder A prefeeder is a modulating device of some kind, controlling the material flow into the belt feeder infeed. You need it for three reasons: 1. The material can not be sheared at

More information

SSR. Smart Valve Positioner.

SSR. Smart Valve Positioner. Smart Valve Positioner Smartest valve control device meeting a dynamic performance and a precise setting with a piezoelectric technology and an optimized auto-calibration program Features Auto-Calibration

More information

Modeling Case Study: Surge Tanks, Valves, Level sensors, and modeling

Modeling Case Study: Surge Tanks, Valves, Level sensors, and modeling Modeling Case Study: Surge Tanks, Valves, Level sensors, and modeling By Peter Woolf (pwoolf@umich.edu) University of Michigan Michigan Chemical Process Dynamics and Controls Open Textbook version 1.0

More information

CONTROL and INSTRUMENTATION

CONTROL and INSTRUMENTATION CONTROL and INSTRUMENTATION COURSE 500: 5 DAYS: Max 8 Candidates This course covers the key aspects of current instrumentation and process control technology and is designed to enable maintenance personnel

More information

Model 4000 Pressure Controller

Model 4000 Pressure Controller FEATURES Multiple Configurations The 4000 series pressure controller can be configured into either proportional only or proportional plus reset mode with a minimum of parts. Rugged Design Die cast aluminum

More information

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE ractical Guide The following article was published in ASHRAE Journal, March 2003. Copyright 2003 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational

More information

Specifications and information are subject to change without notice. Up-to-date address information is available on our website.

Specifications and information are subject to change without notice. Up-to-date address information is available on our website. www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp FY302 AssetView IHM FY302 -

More information

NGP-250/500 Nitrogen Generator Quick Start Guide

NGP-250/500 Nitrogen Generator Quick Start Guide NGP-250/500 Nitrogen Generator Quick Start Guide Version: A July 2013 Potter Electric Signal Company, LLC 5757 Phantom Dr., Suite 125 P. O. Box 42037 Hazelwood, MO 63042 Phone: (314) 595-6900 Document

More information

Burner Management System DEMO Operating instructions

Burner Management System DEMO Operating instructions Burner Management System DEMO Operating instructions Burner Management System DEMO Operating Instructions Startup Summary - Normal startup is accomplished in four basic steps: 1. Leak Test a. Safety Valve

More information

Recovery from a Process Saturation Condition. Benefits of Using DeltaV PIDPlus

Recovery from a Process Saturation Condition. Benefits of Using DeltaV PIDPlus Recovery from a Process Saturation Condition Benefits of Using DeltaV PIDPlus Presenters Daniel Coyne Terry Blevins Introduction The PIDPlus option in DeltaV v11 provides improved the control response

More information

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18 The Bray Simple Set Max is a flanged pressure independent control (PIC) valve designed for a wide variety of hot water and chilled water control applications. The SSM Series combines high rangeability

More information

MWEA MAINTENANCE SEMINAR SPECIALTY VALVES POWER GLOBES

MWEA MAINTENANCE SEMINAR SPECIALTY VALVES POWER GLOBES MWEA MAINTENANCE SEMINAR SPECIALTY VALVES POWER GLOBES J O H N G. H U N T E R Types of Valves P A U L M A R C H I Accessories Principals of Operation Maintenance Control Valve Types Common Problems Key

More information

H.T.S.T. EQUIPMENT TEST PROCEDURES. Field Reference. Sequence of Testing. Pasteurizer Not Operating 3, 1, 4, 2, 7, 10, 8, 5B, 5E, 5C (dual stem), 9

H.T.S.T. EQUIPMENT TEST PROCEDURES. Field Reference. Sequence of Testing. Pasteurizer Not Operating 3, 1, 4, 2, 7, 10, 8, 5B, 5E, 5C (dual stem), 9 H.T.S.T. EQUIPMENT TEST PROCEDURES Field Reference Sequence of Testing Equipment testing should be conducted in the following sequence to minimize equipment run times. Pasteurizer Not Operating 3, 1, 4,

More information

CMC IMPLEMENTATION IN OBSOLETE ISKAMATIC TG CONTROL SYSTEM

CMC IMPLEMENTATION IN OBSOLETE ISKAMATIC TG CONTROL SYSTEM UNCHAHAR CMC IMPLEMENTATION IN OBSOLETE ISKAMATIC TG CONTROL SYSTEM NTPC UNCHAHAR Parsuram Saha, DGM(C&I) Neeraj Agarwal, Sr. Supdt.(C&I) A.K.Goel, Sr. Supdt. (C&I) 1 2 FUEL SECURING FUEL SUPPLIES SOARING

More information