Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

Size: px
Start display at page:

Download "Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION"

Transcription

1 Exercise 2-2 Second-Order Interacting Processes EXERCISE OBJECTIVE Familiarize yourself with second-order interacting processes and experiment with the finer points of controller tuning to gain a deeper understanding of interacting processes. DISCUSSION OUTLINE The Discussion of this exercise covers the following point: The actual setup DISCUSSION The actual setup In this exercise, you will set up and control a second-order interacting level process similar to the one described in Figure 2-4, except that an additional drain line will be connected to the first tank, as shown in Figure This introduces a new flow rate,, and an additional resistance,, in the process. This causes the overall transfer function of the process to become: (2-27) Vent tube Figure The interacting second-order system. Festo Didactic

2 Outline The final height of liquid in the second column can be found using the final-value theorem. The calculations assume the incoming flow to be constant during the experiment so that. (2-28) The resistance,, which controls the output flow,, will be adjusted with a hand valve and will be taken in a first time to be so large as to make. Equation (2-27) reduces to the previously obtained equation in such a case and we obtain: (2-29) and (2-30) PROCEDURE OUTLINE The Procedure is divided into the following sections: Setup and connections Adjusting the differential-pressure transmitter Adjusting and characterizing the system Controlling the process PROCEDURE Setup and connections 1. Connect the equipment according to the piping and instrumentation diagram (P&ID) shown in Figure 2-12 and use Figure 2-13 to position the equipment correctly on the frame of the training system. Table 2-3. Material to add to the basic setup for this exercise. Name Model Identification Column (small diameter) Differential-pressure transmitter (low-pressure range) LIT 1 Color paperless recorder UR Controller * LIC 1 70 Festo Didactic

3 Vent tube Open to the atmosphere Figure P&ID - Second-order interacting process. Festo Didactic

4 Air from the pneumatic unit (140 kpa (20 psi)) Figure Setup - Second-order interacting process. 2. Connect the control valve to the pneumatic unit. 3. Connect the pneumatic unit to a dry-air source with an output pressure of at least 700 kpa (100 psi). 4. Wire the emergency push-button so that you can cut power in case of emergency. 5. Do not power up the instrumentation workstation yet. You should not turn the electrical panel on before your instructor has validated your setup that is not before step Festo Didactic

5 6. Connect the controller to the control valve and to the differential-pressure transmitter. You must also include the recorder in your connections. On channel 1 of the recorder, plot the output signal from the controller, on channel 2, plot the signal from the transmitter. Be sure to use the analog input of your controller to connect the differential-pressure transmitter. 7. Figure 2-14 shows how to connect the different devices together. Analog input Analog output In1 Out1 Ch1 Ch2 24 V Figure Connecting the equipment to the recorder. 8. Before proceeding further, complete the following checklist to make sure you have set up the system properly. The points on this checklist are crucial elements to the proper completion of this exercise. This checklist is not exhaustive, so be sure to follow the instructions in the Familiarization with the Training System manual as well. f All unused ports of the two tanks are closed with a cap. The hand valves are in the positions shown in the P&ID. The control valve is fully open. The pneumatic connections are correct. The controller is properly connected to the differential-pressure transmitter and to the control valve. The paperless recorder is connected correctly to plot the appropriate signals on channel 1 and channel Ask your instructor to check and approve your setup. Festo Didactic

6 10. Power up the electrical unit, this starts all electrical devices as well as the pneumatic unit. Activate the control valve of the pneumatic unit to power the devices requiring compressed air. 11. With the controller in manual mode, set the output of the controller to 0%. The control valve should be fully open. If it is not, revise the electrical and pneumatic connections and be sure the calibration of the I/P converter is appropriate. 12. Test your system for leaks. Use the drive to make the pump run at low speed to produce a small flow rate. Gradually increase the flow rate, up to 50% of the maximum flow rate that the pumping unit can deliver (i.e., set the drive speed to 30 Hz). Repair any leaks and stop the pump. Adjusting the differential-pressure transmitter 13. Connect the impulse line leading to the high-pressure port of the differentialpressure transmitter to the pressure port at the base of the column. Leave the low-pressure port open to atmospheric pressure. Bleed the impulse lines and configure the transmitter for level measurement. Adjust the zero of the differential-pressure transmitter. Set the transmitter parameters so that a 4 ma signal is sent for a level of 5 cm (2 inches) and a 20 ma signal for a level of 50 cm (20 inches). Adjusting and characterizing the system The adjustment of the different parameters is delicate and requires some trial and error over a few minutes. The following steps will guide you through the process of adjusting the resistance at the output of the small-diameter column. 14. With the controller in manual mode (or with a calibrator), send a signal of about 40% (about 10 ma) to the control valve. The control valve should be partly closed. Start the drive at a speed of 25 Hz. Valve HV4 should be fully open and valve HV5 should be fully closed. The flow, as measured by the rotameter, should be close to 12 L/min (3.2 gal/min). Adjust the opening of the control valve to match this value. Write down the control signal used to obtain the required flow rate: Control signal: % (or ma) 15. The resistance,, must now be adjusted in order to obtain an appropriate level in the small-diameter column when the system reaches equilibrium. Turn valve HV4 about halfway through its full course to increase the resistance and let the level of water increase in both columns. 74 Festo Didactic

7 16. Adjust valve HV4 to obtain, at equilibrium, a level of about 43 cm (17 inches) in the small-diameter column. Aim for the specified level within a ± 3 cm (± 1 inch) range. This step takes time, but is crucial to the proper completion of the exercise. Once valve HV4 is properly adjusted, do not modify its opening for the remainder of the exercise. Record the measured levels below: Level measured in the small column: Level measured in the large column: 17. The system is to be characterized in this step. Configure the trend recorder correctly to record the step change in the controller output. Perform a step change by increasing the output of the controller by 5.0% (or increasing the output current of the calibrator by 0.8 ma). Wait until the level in the small column stabilizes (about 10 minutes), transfer the data to a computer, and note the following information: Flow rate: Control output: % or ma Level in the small-diameter column: Level in the large-diameter column: 18. Assuming you can approximate the resultant process as a first-order process, analyze your results and write down the process parameters obtained: Use these parameters to calculate : 19. From the process characteristics you just obtained, you can now calculate the PID coefficients prescribed by the open-loop Ziegler-Nichols method. Write your results in Table 2-4. Table 2-4. Calculated control parameters for the Ziegler-Nichols method. Mode Proportional Gain Integral Time Derivative Time PI PID a Be on the lookout with units. Your controller might use units different from those you used in Table 2-4. Festo Didactic

8 Ex. 2-2 Second-Order Interacting Processes Conclusion Controlling the process 20. Set the controller to operate in PID mode with the parameters you just calculated. Optimize your parameters if possible. 21. Create a 40-60% step change in set point and observe the evolution of the system. Record and transfer the data to a computer. Plot a graph of your results. 22. Stop the system, turn off the power, and store the equipment. CONCLUSION This experiment allowed you to work with a second-order system where two tanks were interacting. Approximating the system to a first-order process made it possible to obtain process characteristics, which were used to calculate PID parameters with the Ziegler-Nichols method. Finally, control was exerted upon the process. REVIEW QUESTIONS 1. What is the difference between a second-order non-interacting process and a second-order interacting process? 2. Is the mathematical representation of a second-order non-interacting process simpler if two identical tanks are used? Why? 76 Festo Didactic

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring

More information

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler. Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure

More information

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps Exercise 4-2 Centrifugal Pumps EXERCISE OBJECTIVE Familiarize yourself with the basics of liquid pumps, specifically with the basics of centrifugal pumps. DISCUSSION OUTLINE The Discussion of this exercise

More information

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range Exercise 4-3 Zero Suppression and Zero Elevation EXERCISE OBJECTIVE In this exercise, you will learn the effect that mounting a pressure transmitter above or below the reference level has on the hydrostatic

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-2 Orifice Plates EXERCISE OBJECTIVE In this exercise, you will study how differential pressure flowmeters operate. You will describe the relationship between the flow rate and the pressure drop

More information

Heat Pump Connections and Interior Piping

Heat Pump Connections and Interior Piping Job Sheet 3 Heat Pump Connections and Interior Piping OBJECTIVES In this job sheet, you will observe how the presence of air in the ground loop affects the geothermal heat pump performance. You will also

More information

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump. Exercise 2-3 Centrifugal Pumps EXERCISE OBJECTIVE In this exercise, you will become familiar with the operation of a centrifugal pump and read its performance chart. You will also observe the effect that

More information

Process Control Measurement Pressure, Flow, and Level Courseware Sample

Process Control Measurement Pressure, Flow, and Level Courseware Sample Process Control Measurement Pressure, Flow, and Level Courseware Sample 85981-F0 Order no.: 85981-10 First Edition Revision level: 07/2015 By the staff of Festo Didactic Festo Didactic Ltée/Ltd, Quebec,

More information

Multi-Process Station

Multi-Process Station Process Control Multi-Process Station Courseware Sample 85629-F0 Order no.: 85629-00 First Edition Revision level: 06/2015 By the staff of Festo Didactic Festo Didactic Ltée/Ltd, Quebec, Canada 2009 Internet:

More information

CONTROL and INSTRUMENTATION

CONTROL and INSTRUMENTATION CONTROL and INSTRUMENTATION COURSE 500: 5 DAYS: Max 8 Candidates This course covers the key aspects of current instrumentation and process control technology and is designed to enable maintenance personnel

More information

Armfield Distillation Column Operation Guidelines

Armfield Distillation Column Operation Guidelines Armfield Distillation Column Operation Guidelines 11-2016 R.Cox Safety SAFETY GLASSES ARE REQUIRED WHEN OPERATING THE DISTILLATION COLUMN Wear gloves when mixing alcohol feedstock The column will become

More information

Cover Page for Lab Report Group Portion. Pump Performance

Cover Page for Lab Report Group Portion. Pump Performance Cover Page for Lab Report Group Portion Pump Performance Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 March 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section number:

More information

Lab 1c Isentropic Blow-down Process and Discharge Coefficient

Lab 1c Isentropic Blow-down Process and Discharge Coefficient 058:080 Experimental Engineering Lab 1c Isentropic Blow-down Process and Discharge Coefficient OBJECTIVES - To study the transient discharge of a rigid pressurized tank; To determine the discharge coefficients

More information

Cover Page for Lab Report Group Portion. Head Losses in Pipes

Cover Page for Lab Report Group Portion. Head Losses in Pipes Cover Page for Lab Report Group Portion Head Losses in Pipes Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 February 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section

More information

P-5215 Differential Pressure Transmitter

P-5215 Differential Pressure Transmitter P-5215 Differential Pressure Transmitter Pneumatic Control Manual 717.1 Pressure Section Product Bulletin P-5215 Issue Date 0891 Features and Benefits Ultra Sensitive Feedback Circuit - Enhances System

More information

EXPERIMENT 2 LEVEL CONTROL SYSTEM

EXPERIMENT 2 LEVEL CONTROL SYSTEM EXPERIMENT 2 LEVEL CONTROL SYSTEM 1.0 OBJECTIVE To study the response of level control process in open tank using the PID controller. 2.0 INTRODUCTION TO THE APPARATUS (MODEL WLF922). a) The process consists

More information

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller CHEMICAL ENGINEERING LABORATORY CHEG 239W Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller Objective The experiment involves tuning a commercial process controller for temperature

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

Job Sheet 1. Geothermal Energy

Job Sheet 1. Geothermal Energy Job Sheet 1 Geothermal Energy OBJECTIVES In this job sheet, you will become familiar with the training system components. You will operate your training system in heating and cooling mode and observe the

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE Exercise 8 Closed-Loop Pressure Control, EXERCISE OBJECTIVE To understand open and closed-loop pressure control; To learn how to sense the pressure in a pneumatic circuit; To control the pressure in a

More information

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6

More information

Bubble Tube Installations

Bubble Tube Installations Instruction MI 020-328 September 2013 Bubble Tube Installations For Liquid Level, Density, and Interface Level Measurements 2 Contents Introduction... 5 Abbreviations... 5 Principle of Operation... 5 Alternative

More information

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels 12.09 product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels Introduction: This manual covers the installation and operation of Humboldt FlexPanels for Triaxial and Permeability

More information

DPC-30 DPC-100. Reference Manual

DPC-30 DPC-100. Reference Manual DPC-30 DPC-100 Reference Manual 1. Introduction 1.1 Description The Martel DPC Digital Pneumatic Calibrator improves upon traditional dial gauge pneumatic calibrators. The Martel DPC improves accuracy,

More information

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW AC 2010-2145: MEASUREMENT OF HYDROGEN IN HELIUM FLOW Randy Buchanan, University of Southern Mississippi Christopher Winstead, University of Southern Mississippi Anton Netchaev, University of Southern Mississippi

More information

Mitos Fluika Pressure and Vacuum Pumps Datasheet

Mitos Fluika Pressure and Vacuum Pumps Datasheet Unit 1, Anglian Business Park, Orchard Road, Royston, Hertfordshire, SG8 5TW, UK T: +44 (0)1763 242491 F: +44 (0)1763 246125 E: sales@dolomite-microfluidics.com W: www.dolomite-microfluidics.com Dolomite

More information

Lab #1 Pressure: Bubblers and Water Balloons CEE 331 Fall 2003

Lab #1 Pressure: Bubblers and Water Balloons CEE 331 Fall 2003 CEE 331 Lab 1 Page 1 of 9 SAFETY Lab #1 Pressure: Bubblers and Water Balloons CEE 331 Fall 2003 Laboratory exercise based on an exercise developed by Dr. Monroe Weber-Shirk The major safety hazard in this

More information

Fluid Flow. Link. Flow» P 1 P 2 Figure 1. Flow Model

Fluid Flow. Link. Flow» P 1 P 2 Figure 1. Flow Model Fluid Flow Equipment: Water reservoir, output tubes of various dimensions (length, diameter), beaker, electronic scale for each table. Computer and Logger Pro software. Lots of ice.temperature probe on

More information

INSTRUMENTS A THERMAL MASS FLOW SENSOR USING A CONSTANT DIFFERENTIAL TEMPERATURE ABOVE THE AMBIENT GAS TEMPERATURE

INSTRUMENTS A THERMAL MASS FLOW SENSOR USING A CONSTANT DIFFERENTIAL TEMPERATURE ABOVE THE AMBIENT GAS TEMPERATURE TELEDYNE HASTINGS TECHNICAL PAPERS INSTRUMENTS A THERMAL MASS FLOW SENSOR USING A CONSTANT DIFFERENTIAL TEMPERATURE ABOVE THE AMBIENT GAS TEMPERATURE Proceedings of FEDSM 98 1998 ASME Fluids Engineering

More information

Exploring the Properties of Gases

Exploring the Properties of Gases Computer 30 The purpose of this investigation is to conduct a series of experiments, each of which illustrates a different gas law. You will be given a list of equipment and materials and some general

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Level Measurement Basics of DP Level Measurement Level the parameters that exist in virtually every industrial process, there are many ways to measure the level,

More information

Exploring the Properties of Gases. Evaluation copy. 10 cm in diameter and 25 cm high)

Exploring the Properties of Gases. Evaluation copy. 10 cm in diameter and 25 cm high) Exploring the Properties of Gases Computer 30 The purpose of this investigation is to conduct a series of experiments, each of which illustrates a different gas law. You will be given a list of equipment

More information

ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING

ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING Blair Chalpin Charles A. Matthews Mechanical Design Engineer Product Support Manager Scanivalve Corp Scanivalve Corp Liberty Lake, WA

More information

1.2 Example 1: A simple hydraulic system

1.2 Example 1: A simple hydraulic system Note: It is possible to use more than one fluid in the Hydraulic library. This is important because you can model combined cooling and lubrication systems of a library. The hydraulic library assumes a

More information

RC 195 Receiver-Controller

RC 195 Receiver-Controller Document No. 129-082 RC 195 Receiver-Controller Product Description The POWERS RC 195 Receiver-Controller is a pneumatic instrument that receives one, two or three pneumatic inputs. It produces a pneumatic

More information

Gerald D. Anderson. Education Technical Specialist

Gerald D. Anderson. Education Technical Specialist Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions

More information

Exploring the Properties of Gases

Exploring the Properties of Gases Exploring the Properties of Gases LabQuest 30 The purpose of this investigation is to conduct a series of experiments, each of which illustrates a different gas law. You will be given a list of equipment

More information

Manual for continuous distillation

Manual for continuous distillation Manual for continuous distillation 1. Week 1: Objectives: Run the column at total reflux. When steady state is reached, take the sample from the top and bottom of the column in order to determine the overall

More information

Boyle s law Verifying the relation between air pressure and volume measuring air pressure in a closed container.

Boyle s law Verifying the relation between air pressure and volume measuring air pressure in a closed container. Objective The purpose of this activity is to analyze the relationship between the pressure and volume of a confined gas at constant temperature, create a hypothesis and proceed to test it using the Labdisc

More information

Ultrasonic Level Transmitter

Ultrasonic Level Transmitter Process Control Ultrasonic Level Transmitter Courseware Sample 85991-F0 Order no.: 85991-10 First Edition Revision level: 10/2017 By the staff of Festo Didactic Festo Didactic Ltée/Ltd, Quebec, Canada

More information

Cover Page for Lab Report Group Portion. Drag on Spheres

Cover Page for Lab Report Group Portion. Drag on Spheres Cover Page for Lab Report Group Portion Drag on Spheres Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 29 September 2017 Name 1: Name 2: Name 3: [Name 4: ] Date: Section number:

More information

The Ins and Outs of I/P Transducers

The Ins and Outs of I/P Transducers The Ins and Outs of I/P Transducers By Mark B. Levine, ControlAir Inc. General description I/P transducers are versatile instruments that use an electrical control signal to proportionally regulate gas

More information

Installation and Operation Manual

Installation and Operation Manual Manual Static pressure transducer with controller Differential static pressure transducer with analog output and optional PI control mode Large diaphragm element with differential transformer Transducer

More information

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes. Piping Tutorial A piping network represents the flow of fluids through several pieces of equipment. If sufficient variables (flow rate and pressure) are specified on the piping network, CHEMCAD calculates

More information

HEATEC TEC-NOTE. Setting Siemens Pressure Transmitter. Used on Heatec Vertical Asphalt Tanks. Publication No , Revised

HEATEC TEC-NOTE. Setting Siemens Pressure Transmitter. Used on Heatec Vertical Asphalt Tanks. Publication No , Revised HEATEC TEC-NOTE, Revised 1-5-15 Setting Siemens Pressure Transmitter Used on Heatec Vertical Asphalt Tanks This document provides information on setting Siemens pressure transmitters used on Heatec vertical

More information

Lab 4: Root Locus Based Control Design

Lab 4: Root Locus Based Control Design Lab 4: Root Locus Based Control Design References: Franklin, Powell and Emami-Naeini. Feedback Control of Dynamic Systems, 3 rd ed. Addison-Wesley, Massachusetts: 1994. Ogata, Katsuhiko. Modern Control

More information

Electronic gas volume corrector model DGVC-04

Electronic gas volume corrector model DGVC-04 Electronic gas volume corrector model DGVC-04 1. Introduction The following user s manual gives information about the installation, configuration, usage and storage of the electronic gas volume corrector

More information

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control Introduction This experiment offers a look into the broad field of process control. This area of

More information

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C Exercise 2-3 EXERCISE OBJECTIVE C C C To describe the operation of a flow control valve; To establish the relationship between flow rate and velocity; To operate meter-in, meter-out, and bypass flow control

More information

PRESSURE CONTROL TRAINER

PRESSURE CONTROL TRAINER PRESSURE CONTROL TRAINER Product Code 314A (PCT version) (With Ethernet communication) Instruction manual Contents 1 Description 2 Specifications 3 Packing slip 4 Installation requirements 5 Installation

More information

Exercise 3. Power Versus Wind Speed EXERCISE OBJECTIVE DISCUSSION OUTLINE. Air density DISCUSSION

Exercise 3. Power Versus Wind Speed EXERCISE OBJECTIVE DISCUSSION OUTLINE. Air density DISCUSSION Exercise 3 Power Versus Wind Speed EXERCISE OBJECTIVE When you have completed this exercise, you will know how to calculate the power contained in the wind, and how wind power varies with wind speed. You

More information

TR Electronic Pressure Regulator. User s Manual

TR Electronic Pressure Regulator. User s Manual TR Electronic Pressure Regulator Page 2 of 13 Table of Contents Warnings, Cautions & Notices... 3 Factory Default Setting... 4 Quick Start Procedure... 5 Configuration Tab... 8 Setup Tab... 9 Internal

More information

Instruction and Maintenance Manual

Instruction and Maintenance Manual Instruction and Maintenance Manual GRYF OXY ZM 02/100/2 E Contact GRYF HB, spol. s r.o. Cechova 314 Havlickuv Brod 580 01 tel.: +420 569 426 627 fax: +420 569 426 627 www.gryf.eu ver.: 11.2.2015 OEM module

More information

Applying Hooke s Law to Multiple Bungee Cords. Introduction

Applying Hooke s Law to Multiple Bungee Cords. Introduction Applying Hooke s Law to Multiple Bungee Cords Introduction Hooke s Law declares that the force exerted on a spring is proportional to the amount of stretch or compression on the spring, is always directed

More information

CHAPTER 7: THE FEEDBACK LOOP

CHAPTER 7: THE FEEDBACK LOOP When I complete this chapter, I want to be able to do the following. Identify the major elements in the feedback loop Select appropriate candidate variables to be controlled and manipulated Evaluate the

More information

Operating Instructions

Operating Instructions Operating Instructions Note: 1. Never let the centrifugal pump run dry. 2. Make sure that there is at least one open path for water flow in the pipe network before turning the pump on. Never run the pump

More information

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity

More information

Introductory Lab: Vacuum Methods

Introductory Lab: Vacuum Methods Introductory Lab: Vacuum Methods Experiments in Modern Physics (P451) In this lab you will become familiar with the various components of the lab vacuum system. There are many books on this topic one of

More information

BAPI Pressure Line of Products - FAQs

BAPI Pressure Line of Products - FAQs Table of Contents 1. Several manufacturers produce pressure transmitters, why should I purchase from BAPI?... p. 2 2. BAPI makes several styles of pressure transmitters. What are the features of each?...

More information

FX134, FX1234, FX3030 Problem and Solutions

FX134, FX1234, FX3030 Problem and Solutions FX134, FX1234, FX3030 Problem and Solutions Unit Will Not Power Up Turn the power switch on. The unit LCD will display revision program and filter life within 3 to 5 seconds after turning on unit. If this

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

Single Pressure/ vacuum decay leak rate, loss, rate of loss, or occlusion tests with standard Cv valves.

Single Pressure/ vacuum decay leak rate, loss, rate of loss, or occlusion tests with standard Cv valves. Application Bulletin: #167 Date: November 2009 BLACKBELT PRINCIPALS OF OPERATION INSTRUMENT CONFIGURATIONS Depending on the types of tests required and resolution and repeatability desired, the Sentinel

More information

How to specify a product. Process Sensors and Mechanical Instruments

How to specify a product. Process Sensors and Mechanical Instruments How to specify a product Process Sensors and Mechanical Instruments Keep the overview. Here is some guideline information on how to specify our products. Intended as supplementary help to specification

More information

AMT-Ex Dewpoint Transmitter

AMT-Ex Dewpoint Transmitter AMT-Ex Dewpoint Transmitter Instruction Manual Alpha Moisture Systems Alpha House 96 City Road Bradford BD8 8ES England Tel: +44 1274 733100 Fax: +44 1274 733200 email: mail@amsytems.co.uk web: www.amsystems.co.uk

More information

Gas Diluter Portable Gas Dilution System User s Manual

Gas Diluter Portable Gas Dilution System User s Manual Gas Diluter Portable Gas Dilution System User s Manual Defiant Technologies, Inc. 2015 Vol.1 This page is intentionally left blank. Gas Diluter Portable Gas Dilution System User s Manual Defiant Technologies,

More information

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021-PR Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021-PR For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4

More information

Model GFC 7000T CO 2 Analyzer (Addendum to GFC 7000TA Manual, PN 07272)

Model GFC 7000T CO 2 Analyzer (Addendum to GFC 7000TA Manual, PN 07272) Manual Addendum Model GFC 7000T CO 2 Analyzer (Addendum to GFC 7000TA Manual, PN 07272) P/N M07273 DATE 06/11/13 TELEDYNE ELECTRONIC TECHNOLOGIES Analytical Instruments 16830 Chestnut Street City of Industry,

More information

NATIONAL UNIVERSITY OF SINGAPORE. EE3302/EE3302E Industrial Control Systems E1: ADVANCED CONTROL SYSTEMS

NATIONAL UNIVERSITY OF SINGAPORE. EE3302/EE3302E Industrial Control Systems E1: ADVANCED CONTROL SYSTEMS NATIONAL UNIVERSITY OF SINGAPORE EE3302/EE3302E Industrial Control Systems E1:. OBJECTIVES: Before embarking on this hands-on session, you should have been introduced to the concepts of cascade and feedforward

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition Siemens AG 07 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure

More information

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid Volumetric flow Compressed Air Mass flow Gas Net volumetric flow Steam Liquid Universal compact orifice flow meter combines a compact orifice flow sensor and sotiphicated converter One-piece flow sensor,

More information

Introduction. Part one: Identify the Hydraulic Trainer Components

Introduction. Part one: Identify the Hydraulic Trainer Components The University Of Jordan School of Engineering Mechatronics Engineering Department Fluid Power Engineering Lab Experiments No.4 Introduction to Hydraulic Trainer Objective: Students will be able to identify

More information

Modeling Diffusion Rates of a Gas in an Enclosed Space

Modeling Diffusion Rates of a Gas in an Enclosed Space Modeling Diffusion Rates of a Gas in an Enclosed Space By: Chirag Kulkarni, Haoran Fei, Henry Friedlander Abstract: This research attempts to identify the relationship between pressure of a certain gas

More information

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters Instruction Manual Form 5177 March 1999 4150K and 4160K Series 4150K and 4160K Series Wizard II Pressure Controllers and Transmitters Contents Introduction.............................. 2 Scope of Manual.............................

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM

More information

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features ANALOG MASS FLOW CONTROLLERS Model AF mass fl ow controllers are designed to indicate fl ow rates and control set fl ow rates of gases. Each of these units incorporates an advanced straight tube sensor

More information

INSTALLATION & MAINTENANCE INSTRUCTIONS

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The QBX series valve uses Proportion-Air closed loop technology for Pressure control. It gives an output pressure proportional to an electrical command signal input. The QB1X

More information

UNIVERSITY OF WATERLOO

UNIVERSITY OF WATERLOO UNIVERSITY OF WATERLOO Department of Chemical Engineering ChE 524 Process Control Laboratory Instruction Manual January, 2001 Revised: May, 2009 1 Experiment # 2 - Double Pipe Heat Exchanger Experimental

More information

Instruction and Maintenance Manual

Instruction and Maintenance Manual Instruction and Maintenance Manual GRYF OXY Z 02/100/2 E Contact GRYF HB, spol. s r.o. Cechova 314 Havlickuv Brod 580 01 tel.: +420 569 426 627 fax: +420 569 426 627 Czech Republic www.gryf.eu Technical

More information

Application Worksheet

Application Worksheet Application Worksheet All dimensions are nominal. Dimensions in [ ] are in millimeters. Service Conditions Medium Through Valve: Required C v : Temperature Maximum: Minimum: Normal: Flow Maximum: Minimum:

More information

Agilent ICP-MS Interactive Troubleshooting tool for Low sensitivity

Agilent ICP-MS Interactive Troubleshooting tool for Low sensitivity Agilent ICP-MS Interactive Troubleshooting tool for Low sensitivity Rev. B 2017,Janyary,20 Next > Preconditions 7900, 7800, 7700, or 8800 ICP-MS is used. Sample introduction type is PeriPump. If you are

More information

Boyle s Law VC 09. Experiment 9: Gas Laws. Abstract

Boyle s Law VC 09. Experiment 9: Gas Laws. Abstract Experiment 9: Gas Laws VC 09 Abstract In this laboratory activity, you will experimentally confirm Boyle s Law, determine absolute zero from Gay-Lussac's Law, and determine the molecular weight of acetone,

More information

Level Process Control. Penn State Chemical Engineering

Level Process Control. Penn State Chemical Engineering Level Process Control Penn State Chemical Engineering Revised Spring 2015 1 Table of Contents LEARNING OBJECTIVES... 3 EXPERIMENTAL OBJECTIVES AND OVERVIEW... 3 Pre-lab study... 3 Experiments in the lab...

More information

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve Test Report # 30016558 Rev 0 Adiabatic Compression With Constant Bleed Valve Scope: This test report contains test data on the effects of adiabatic compression in nitrogen service on AP3600 diaphragm valves,

More information

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM 1.0 OBJECTIVE To study the response of gas pressure control using PID controller. 2.0 INTRODUCTION TO THE APPARATUS a) The process plant consists of two air vessels

More information

GP1 & GP2. Electropneumatic Regulators FOR PRESSURE CONTROL TO 1,000 PSI

GP1 & GP2. Electropneumatic Regulators FOR PRESSURE CONTROL TO 1,000 PSI GP1 & GP2 Electropneumatic Regulators FOR PRESSURE CONTROL TO 1, PSI GP1 & GP2 Functional Description The GP series control valve is an electronic pressure regulator designed to precisely control the pressure

More information

CASCADE CONTROL TRAINER

CASCADE CONTROL TRAINER CASCADE CONTROL TRAINER Product Code 315A (PCT version) Instruction manual Contents 1 Description 2 Specifications 3 Installation requirements 4 Installation Commissioning 5 Troubleshooting 6 Components

More information

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments Pegas 4000 MF Gas Mixer InstructionManual Contents I Table of Contents Foreword Part I Introduction 1 2 1 System overview... 2 2 Specifications... 3 Part II Installation 4 1 Rear panel connections...

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI Siemens AG 06 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure

More information

PROCESS DYNAMIC AND CONTROL MODIFIED II QUADRUPLE TANK ON LABVIEW APPLICATION

PROCESS DYNAMIC AND CONTROL MODIFIED II QUADRUPLE TANK ON LABVIEW APPLICATION PROCESS DYNAMIC AND CONTROL MODIFIED II QUADRUPLE TANK ON LABVIEW APPLICATION Gumelar Ahmad Muhlis 1, Nia Fauziah Lestari 1, Juwari Purwo Sutikno 1, Renanto Handogo 1 and Anwaruddin Hisyam 2 1 Chemical

More information

SomnoSuite FAQ. Setup. Calibration 4. What are the calibration requirements for the SomnoSuite? Settings

SomnoSuite FAQ. Setup. Calibration 4. What are the calibration requirements for the SomnoSuite? Settings SomnoSuite FAQ V1.3 January 2015 Setup 1. How do I connect the SomnoSuite to my oxygen source? 2. Is there a way to speed up the downward movement of the pusher block when setting the empty position? 3.

More information

Code Basic module and level control complete with optionals code

Code Basic module and level control complete with optionals code AUTOMATION AND PROCESS CONTROL MPCT - Modular Process Control Trainer Code 916960 Basic module and level control complete with optionals code 916961-916962-916963-916964-916965 1. General Didacta proposes

More information

Appendix D: SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor. Description and Principle of Operation

Appendix D: SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor. Description and Principle of Operation Page 1 of 19 : SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor Description and Principle of Operation The photoacoustic multi-gas monitor (INNOVA 1412, Innova AirTech Instruments, Denmark) is a highly

More information

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12 LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/ This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the rates with which selected

More information

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. .

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. . User Manual Capacitance Continuous Level Indicator Comprehensive User s Manual. Introduction. General Description. Principle of Operation. Specifications. Connection Diagrams. Quick Calibration Chart.

More information

Title: Standard Operating Procedure for R&R Environmental Devices Model MFC201 Gas Dilution Calibrator

Title: Standard Operating Procedure for R&R Environmental Devices Model MFC201 Gas Dilution Calibrator Procedure No: SOP-029 Revision No: 1.1 (December 29, 2010) Page No.: 1 of 7 1. INTRODUCTION AND SCOPE To obtain timely data for the purpose of air quality assessment, air quality trend reporting, air quality

More information

EN00 Pre-Instructional Survey

EN00 Pre-Instructional Survey EN00 Pre-Instructional Survey Name: Date: 1. At 433 degrees F, a type J thermocouple with a 3 degree F reference junction will produce an output in millivolts that is most nearly to: a. 9.04 b. 10.51 c.

More information

Additel761 Series Firmware Updates

Additel761 Series Firmware Updates Additel761 Series Firmware Updates 2018-09-03 APC V01.XX Vertions before APC V01.03(Included) APC V01.04 APC V01.05 APC V01.06 APC V01.07 APC V01.08 APC V01.09 APC V01.10 APC V01.11 APC V01.12 APC V01.13

More information