1 PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1 SUPPLEMENT HIGH PRESSURE FIRE HYDRANT SYSTEM The High Pressure fire hydrant system was constructed approximately one hundred years ago. The purpose of the system is to supply large volumes of water under high pressure from hydrants directly to the scene of a fire without the use of pumpers. The system utilizes two independent pumping stations that supply more than 1,000 hydrants through approximately 64 miles of supply piping. The system can be divided into two districts by closing two sectional stops. The high pressure system is independent of the domestic low pressure fire hydrant system. The two systems should never be interconnected. A connection could result in the contamination of the city's potable water supply. Pumpers should not be directly connected to a high pressure fire hydrant 1 ( See O.P. 16, Addendum 1, guidelines for high pressure hydrant to pumper operation.) NEVER CONNECT THE DOMESTIC AND HIGH PRESSURE SYSTEMS HIGH PRESSURE PUMPING STATION #1 (DELAWARE AVE. & RACE STREET) Pumping station # 1 is equipped with six (6) 2,500 gallon per minute Worthington electric centrifugal pumps capable of pumping a total of 15,000 gallons of water per minute into the system. This station is an unmanned back-up station and is put in operation only upon request from the incident commander when sufficient pressure or water is unavailable from pumping station # 2. HIGH PRESSURE PUMPING STATION # 2 (7TH STREET & LEHIGH AVENUE) Pumping station # 2 is equipped with six (6) 2,000 gallon per minute Worthington electric centrifugal pumps capable of pumping a total of 12,000 gallons of water per minute. Pumping station #2 is now also unmanned and is the primary pumping station. Both stations are controlled remotely from the Water Department s Load Control Center. The two distribution systems are connected by two OPEN 20" valves and are operated as one unit. One of the valves is located at New Market and Poplar Streets, the other is at Broad and Spring Garden Streets. The two high pressure pumping stations can be separated by CLOSING the valves at BOTH of the locations. Each of these valves has a 4" bypass pipe. A pressure of 35 pounds per square inch (PSI) is maintained on the Delaware Avenue and Race Street system from the water level in the reservoir at 7th and Somerset Streets due to the elevation of the reservoir. The reservoir has a capacity of 4,692,000 gallons of water. The water used at fires and also system leakage is automatically replaced from a 30" filtered water supply main running along Lehigh Avenue. 1 Under special circumstances, a connection is permitted with the use of a gate valve. REV. 4/01/
2 SUPPLEMENT 101 PAGE 2 PFD TRAINING MANUAL SUPPLEMENT Figure Map of High Pressure System BULKHEAD CONNECTION SECONDARY OR EMERGENCY METHOD TO SUPPLY THE HIGH PRESSURE FIRE HYDRANT SYSTEM. Should these pumps become unserviceable, there is a bulkhead connection at the foot of Race Street and the Delaware River. The connection is equipped with (8) eight, 3½" male intake fittings, to which fireboats or pumpers can connect and augment the water supply in the high pressure water mains. Adapters for these connections are carried on the Marine Units. Figure Bulkhead Connection 101_RFH.DOC REV. 4/01/99
3 PFD TRAINING MANUAL SUPPLEMENT SUPPLEMENT 101 PAGE 3 THE STREET VALVE Whenever the bulkhead connection is to be utilized for service or training, a line valve (street valve) is to be opened before and closed after each service. The street valve (20 ft. in front of the bulkhead connection) will be kept in the CLOSED position when the connection is not being used. The street valve key is onboard the Marine Units. The drain valve on the bottom of the bulkhead connection will be closed before opening the street valve. To OPEN the street valve turn it clockwise 44 turns. When the operation is to be terminated, the street valve is to be shut down first, 44 turns counterclockwise. The drain valve on the bottom of the connection will be opened before disconnecting the lines. The drain valve will be left FULLY OPEN. HIGH PRESSURE FIRE HYDRANT High pressure fire hydrants are RED in color and are fitted with three (3) stems. Figure Bulkhead Connection (Diagram) Figure Street Valve Cover The center stem controls a compression type valve that admits water from the main into the barrel of the hydrant. The two outer stems control the side outlet gates. Water for this type of hydrant is supplied via the high pressure pumping stations in mains ranging from 8 inches to 20 inches. A static pressure of 35 to 43 PSI is maintained on the system. High pressure hydrants are Figure High Pressure Hydrant fitted with (2) 4" male threaded side outlets. These hydrants are capable of supplying more than 1,000 gallons per minute. PRACTICAL TEST OF USABLE FLOWS In late 1993, limited practical tests were conducted on the high pressure fire hydrant system to determine the feasibility of pipeline companies connecting large diameter hose line (LDH) directly from high pressure hydrants. The results of the tests demonstrated the practicality of using LDH directly from high pressure hydrants. REV. 4/01/
4 SUPPLEMENT 101 PAGE 4 PFD TRAINING MANUAL SUPPLEMENT LDH was connected to both sides of the hydrant, stretched 200 and connected to two manifolds. During the tests, deluge guns were added to the manifolds via dual 100 stretches of 3 hose line, until usable streams were no longer produced, with four guns being the average when using smaller tips. The tests were repeated for different system pressures and different tip sizes. In most cases, acceptable streams were produced. PRESSURIZATION OF THE HIGH PRESSURE SYSTEM 1. If the activation of the high pressure system is required on the 1st alarm, it must be requested by the incident commander. The Water Department will then pressurize the system to 100 PSI. 2. Activation of the high pressure system is automatic on the 2nd alarm for fires occurring within the high pressure district. The system will initially be pressurized to 100 PSI. 3. Once activated, it will take approximately 10 minutes for the 64 miles of high pressure water main system to be fully charged. The incident commander should wait at least 10 minutes for the system to become fully charged before requesting an increase in pressure. 4. Increases in pressure will be applied by load control in increments of 10 PSI PSI at the pumping station at 7th Street and Lehigh Avenue will result in 140 PSI in center city because of gravity. 6. The maximum normal pressure at pumping station #2 is 140 PSI. However, the Water Department has the capacity to deliver more than 140 PSI if requested by the incident commander. 7. A request for more than 140 PSI entails shutting-down a pressure relief valve in center city which is set at 180 PSI. A shut-down of this valve will allow greater pressure on the system. 8. Pressures higher than 140 PSI at the pumping station may result in a water main break in the high pressure system. The Water Department is willing to deliver pressures greater than 140 PSI in extreme emergencies when requested by the incident commander. 9. If the fire is on the outside perimeter of the high pressure district, the Fire Communications Center (FCC) will contact the incident commander to determine if the high pressure system should be activated. HIGH PRESSURE HYDRANT OUT-OF-SERVICE Lock nuts are utilized to denote that a particular hydrant or side outlet is unserviceable. A lock nut on the center stem denotes that the hydrant is out-of-service. If the lock nut is found on either side stem, it denotes that only that discharge gate is out of service. Whenever a high pressure hydrant is placed out-of-service or returned to service, it is announced over the P. A. System. These announcements are to be brought to the officer's attention and a running record is to be placed in the Status of Hydrant Report that is kept in the rear of the watch desk log book _RFH.DOC REV. 4/01/99
5 PFD TRAINING MANUAL SUPPLEMENT SUPPLEMENT 101 PAGE 5 TOOLS NECESSARY TO PLACE A HIGH PRESSURE HYDRANT IN SERVICE FIRE HYDRANT WRENCH Any of the wrenches pictured below will operate a high pressure fire hydrant. STANDARD ENGINE COMPANY Hydrant wrench, 3½ gate valve, 3-way, two high pressure hydrant reducers (4" female x 3½" male), two 3½" all-purpose spanners and one high pressure fire hydrant template. PIPELINE COMPANY In addition to the above equipment, with the exception of the 3-way, a pipeline company requires an adapter (4 female Phila. thread to 5 Storz sexless), a 5 gate valve w/storz fittings, 5 hoseline, a manifold and two LDH spanners. HIGH PRESSURE FIRE HYDRANT TEMPLATE The high pressure hydrant template shows the number of half turns necessary to fully open the valves on a high pressure hydrant and the direction in which the valves must be turned to open. The template is placed on the high pressure hydrant and left there while the hydrant is in service. Figure Hydrant Wrenches HIGH PRESSURE HYDRANT REDUCER A high pressure fire hydrant reducer is a reducing fitting that allows 3½" (NST) equipment to be connected to an outlet that is 4" Philadelphia thread, such as high pressure or domestic low pressure fire hydrants. The fitting consists of a 4" Philadelphia threaded female side and a 3½" NST male side. Figure High Pressure Template The template acts as a guide for the person operating the hydrant so that there will be no mistake in turning the stem in the wrong direction and causing damage to the side outlet valve stem or replaceable nut. Figure High Pressure Hydrant Reducer REV. 4/01/
6 SUPPLEMENT 101 PAGE 6 PFD TRAINING MANUAL SUPPLEMENT PLACING A HIGH PRESSURE HYDRANT IN SERVICE IF IT WERE YOUR DUTY TO PLACE A HIGH PRESSURE HYDRANT IN SERVICE Place the template over the hydrant nuts, place the hydrant wrench on the center stem, which controls the flow of the water from the main. Now pull with the left hand to make sure the valve is CLOSED. Remove both side outlet caps, check that the side outlets are closed, open the side discharge valves all the way. Thirty-five (35) half-turns are required to open the side outlets. Visually inspect the outlets to insure that they are fully open. STANDARD ENGINE COMPANY The hydrant can then be placed in service in the following manner (Fig.101-9): Figure HP Hydrant In Service (Standard Engine Company) 101_RFH.DOC REV. 4/01/99
7 PFD TRAINING MANUAL SUPPLEMENT SUPPLEMENT 101 PAGE 7 1. Place a high pressure hydrant reducer on each side outlet. 2. Place a 3-way on the outlet nearest the fire, then place one 3½" gate valve on the outlet facing away from the fire. 3. When the water is ordered, open the center stem all the way, thirty-nine (39) half-turns clockwise. This will service both sides of the hydrant. Water supply will then be controlled by members operating the 3-way and the 3½" gate valve. 4. To shut down a high pressure hydrant, close the center stem, bleed appliances then remove the 3-way, the 3½" gate valve and hydrant reducers. Close the side outlets thirty-five (35) half-turns, counter clockwise. Replace the outlet caps. 5. When a high pressure fire hydrant is placed in service, the following information will be given to the member in charge of the company: A. The location of the hydrant. B. Which numbered outlets on the 3-way are being used and is the 3½" gate valve being used by the company. PIPELINE COMPANIES The hydrant can be placed in service in the following manner (Fig ): 1. On the side of the hydrant going toward the fire - place a Storz hydrant adapter (4" female, Phila. thread x Storz 5" sexless fitting), attach to that a 5" gate. Additional 5" line will then be attached and will most likely terminate in a 5" manifold. 2. On the opposite side of the hydrant, place a high pressure hydrant reducer and then attach a 3½" gate valve. As an option, if additional hardware of the same type as mentioned in step one is available, it may be used also on this side of the hydrant. 3. When the water is ordered, open the center stem all the way, thirty-nine (39) half-turns clockwise. This will service both sides of the hydrant. Water supply will then be controlled by members operating the 5" gate valve and the 3½" gate valve. 4. To shut down a high pressure hydrant, close the center stem, bleed appliances, then remove the Storz hydrant adapter, the 3½" gate valve and the hydrant reducer. Close the side outlets thirty-five (35) halfturns, counter clockwise. Replace the outlet caps. 5. When a high pressure fire hydrant is placed in service, the following information will be given to the member in charge of the company: A. Location of the hydrant. B. The location of the manifold, which numbered outlets are being used on the manifold and is the 3½" gate valve being used by the company. Members assigned to operate high pressure fire hydrants should keep in mind some of the possible causes for damaging the valve stems and replaceable nuts: 1. Attempting to turn the stem in the wrong direction when the valve is in the closed position. REV. 4/01/
8 SUPPLEMENT 101 PAGE 8 PFD TRAINING MANUAL SUPPLEMENT Figure HP Hydrant In Service (Pipeline Company) 2. Forgetting to count the number of halfturns when opening and closing the valves. NOTE: It is important that the member assigned to operate the hydrant remain calm and think before acting. Companies outside the high pressure district must continually review the operation of the high pressure hydrant, so that they will be familiar with the operation when responding on alarms of fire in the high pressure districts. DUE TO THE POSSIBILITY OF DEBRIS IN THE HIGH PRESSURE SYSTEM, IT IS RECOMMENDED THAT ONLY SMOOTH BORE TIPS BE USED _RFH.DOC REV. 4/01/99
Des Plaines Fire Dept. Engineer Program
Des Plaines Fire Dept. Engineer Program Lieutenants Palenik, Gross, Owen, Butenschoen, Engineer Felde New Developments 1. Laminated fluid specs on the rigs 2. Maintenance repair request updates 3. Locations
More informationINSTRUCTOR GUIDE REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST EDITION, IFSTA
TOPIC: RELAY PUMPING OPERATIONS LEVEL OF INSTRUCTION: TIME REQUIRED: ONE HOUR INSTRUCTOR GUIDE MATERIALS: APPROPRIATE AUDIO VISUAL SUPPORT REFERENCES: PUMPING APPARATUS DRIVER/OPERATOR HANDBOOK, FIRST
More informationINSTRUCTOR GUIDE MATERIALS: TWO FULLY EQUIPPED PUMPERS STATIC AND PRESSURIZED WATER SOURCES
COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 5 TOPIC: SUPPLY LINES AND SALVAGE LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS INSTRUCTOR GUIDE MATERIALS: TWO FULLY EQUIPPED PUMPERS STATIC AND PRESSURIZED
More informationTurboDraft Fire Eductor
TurboDraft Fire Eductor Operating Manual Introduction The TurboDraft is designed to be used for rural water supply operations. Many of us take for granted that there is a fire hydrant on every corner.
More informationESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised
DRIVER OPERATOR Page 1 of 14 HYDRAULICS Hydraulics applied in the dynamic fire ground environment is an art that comes with study and experience. The following describes the factors that must be mastered
More information3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289
3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for
More informationEssentials of Fire Fighting
Essentials of Fire Fighting 6 th Edition Certified Volunteer Firefighter Chapter 14 Water Supply Learning Objectives Explain the ways water supply system components are used by firefighters. Describe types
More informationInstallation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series
Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator
More informationExercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C
Exercise 2-3 EXERCISE OBJECTIVE C C C To describe the operation of a flow control valve; To establish the relationship between flow rate and velocity; To operate meter-in, meter-out, and bypass flow control
More informationVarying pump capacity affects the required hoseline diameter
Slide 1 Rural Fire Command by Larry Davis Issue #34 October 2005 H 2 O On The Go Varying pump capacity affects the required hoseline diameter 1 Slide 2 Training America s Rural Fire & Emergency Responders
More informationTurboDraft. Fire Eductor Operating Instructions.
TurboDraft Fire Eductor Operating Instructions 1234djfkjldfjlkdjfklsdjlkjfdslkjfsd Table of Contents Description Page Introduction........ 1 Safety Guidelines... 2 Care and Maintenance... 3 TurboDraft
More informationAir Operated Hydraulic Pumping Systems to 50,000 psi
High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air
More informationSECTION FIVE: OP-1B (XLDS) HIGH PRESSURE AIR STORAGE SYSTEM (HPASS) 02/17/2012
HIGH PRESSURE AIR STORAGE SYSTEM (HPASS) 02/17/2012 CAUTION: BEFORE STARTING THIS PROCEDURE ENSURE THE SUPPLY REGULATORS ARE BACKED OFF COUNTER CLOCKWISE UNTIL THE KNOBS SPIN FREELY AND THE DIVERS PNEUMOFATHOMETER
More information22. Specialty Valves.
22. Specialty Valves. a. Types of Specialty Valves. 1) Use of the following specialty valves is covered in this section: Altitude Valve, Pressure Reducing Valve, Pressure Relief Valve, Swing Check Valve,
More informationChapter 14 Water Shuttle Operations
1. Which of the following statements about water shuttle operations is TRUE? A. Water shuttle operations may create a dramatic hose failure B. Water shuttle operations are safer than relay pumping operations
More informationDesign Requirements for Eyewash and Safety Shower Units
Design Requirements for Eyewash and Safety Shower Units Application: Eyewash Stations must be provided in the following areas. Laboratories Plumbed emergency eyewash equipment shall be installed in every
More informationMODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve) 1¼", 1½", 2", 2½", 76.1mm, 3", 4", 6",165.1mm, 8"
4077 Airpark Dr. Standish, MI 48658 989-846-4583 www.globesprinkler.com Technical Support 989-414-2600 techservice@globesprinkler.com MODEL UM UNIVERSAL MANIFOLD ASSEMBLY (With or Without Control Valve)
More informationModel PSI Compressor with 3-Gallon Air Tank 12VDC
Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing
More informationFOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM
IMI CORNELIUS INC One Cornelius Place Anoka, MN 55303-623 Telephone (800) 238-3600 Facsimile (612) 22-326 INSTALLATION INSTRUCTIONS FOR INSTALLING CO 2 BLENDER KIT (P/N 111612000 IN BEER SYSTEM SECONDARY
More informationFIREGROUND HYDRAULICS
INTRODUCTION This section is designed to give pump operators a quick and fairly easy process for determining fire ground hydraulics. Supplying water is a critical part of the control, and the efficient
More informationPortable Hydrostatic Pneumatic Test Pump. Procedure Manual
Portable Hydrostatic Pneumatic Test Pump Procedure Manual Dixon Valve & Coupling Company 800 High Street Chestertown, MD 21620 800-355-1991 Fax: 800-283-4966 Specifications Dixon Portable Pneumatic Hydrostatic
More informationWater Thiefs APPLIANCES APPLIANCES WATER THIEFS
WATER THIEFS Water Thiefs A Water Thief allows the fire professional to extend attack lines from a main supply line. Elkhart s selection of Water Thief options includes Storz connectors which, when combined
More informationDBML-60/80 Squeeze Tool
DBML-60/80 Squeeze Tool OPERATORS MANUAL Description The Mustang Model DBML-60/80 Hydraulic squeeze tool has been manufactured since 1995. A Mustang 3 3/4 bore doubleacting cylinder producing 41,000 lbs
More informationMANUAL BE SERIES Test Benches
The CustomCrimp Manual BE Series Test Benches are designed with features that make proof and burst testing of hydraulic hose assemblies a quick and easy procedure. CUSTOMIZED AND SPECIAL DESIGN BENCHES
More informationPressure Differential Automatic Manifold For LPG. PDH1000 Series. LPG Installation & Operations Instructions
Pressure Differential Automatic Manifold For LPG PDH1000 Series LPG Installation & Operations Instructions Precise Equipment Company 3822 Market St., STE 101 Denton, Texas Phone : 800.795.8388 Precise
More informationOperation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve
Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve Model CYCLE GARD II, CI & CNA YOUR PRODUCT INFORMATION: Model Number: Date: Serial Number:
More informationTypes 749B and R130 Changeover Manifolds
Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies
More informationSECTION PRESSURE TESTING OF PIPING
SECTION 15044 PRESSURE TESTING OF PIPING PART 1 - GENERAL 1.01 DESCRIPTION A. Scope of Work: This section specifies the leakage and pressure testing of piping. B. Testing Records: PART 2 - PRODUCTS 2.01
More informationFIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program
FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program Welcome & Introductions Identify emergency exits to all participants. Identify location of restroom facilities. Cover any other related
More information!!!! SERVICE MANUAL PRESSURE POT 2 GALLON. Service Manual: LT Washington St 931 Progress Ave., #7
EXEL North America, Inc. EXEL Industrial Canada, Inc. 1310 Washington St 931 Progress Ave., #7 West Chicago, IL 60185 Scarborough ONT, M1G 3V5 Ph : (800) 573 5554 Ph : (800) 450 0655 Fx : (800) 664 1511
More informationAIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL
00, 0, 000 00, 000, 00 A. TECHNICAL INFORMATION Model 00 Inlet/Outlet " Air Inlet /" 0 / 000 /" /" 00 /" /" 000 /" /" 00 /" /" Flow Rate GPM/ 0LPM GPM/ 0LPM GPM/ LPM GPM/ LPM GPM/ 0LPM GPM/ 0LPM Maximum
More informationBermad Pressure Reducing. Model: 42T
Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel
More informationPortable Hydrostatic Electric Test Pump. Procedure Manual. Dixon 800 High Street Chestertown, MD Fax: dixonvalve.
Portable Hydrostatic Electric Test Pump Procedure Manual Dixon 800 High Street Chestertown, MD 21620 800-355-1991 Fax: 800-283-4966 dixonvalve.com Dixon's Portable Electric Hydrostatic Test Pump (E.T.P.)
More informationHYDRANT/WATER POINT INSPECTION AND MAINTENANCE
HYDRANT/WATER POINT INSPECTION AND MAINTENANCE SCOPE This guideline shall apply to all members of the Stoney Point Fire Department (SPFD) and shall be adhered to by all members. Stoney Point Fire Department
More informationCozumel Turbodraft. Operational Considerations
Cozumel Turbodraft Operational Considerations Safety Guidelines Safety Guidelines 1. Carefully read and follow all operating instructions before putting the TurboDraft unit into service. 2. Be sure all
More informationDESIGN DATA. Dry 105a. September 5, 2008
September 5, 2008 Dry 105a 1. Description Dry and Preaction Systems require a dependable source of clean dry air under the proper pressure. The air supply must be adequate to restore normal air pressure
More informationINSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y
INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50 Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y OFFICE: (507) 843-4700 P.O. BOX 7079 Toll
More informationFlow Material Length. Weight GPM LPM. Style 3095
Akron Municipal Eductors feature a large, easy to read, and removable metering dial with infinite settings between 0% and 6%. Detents at 1 4, 1 2, 1, 3 and 6%. The Eductors are rated to flow at 200 psi
More informationIdaho Fire Service Technology Fire Fighter II
ICS Skill Requirements Skill Sheet: 1 STANDARD: 6.1.2 TASK: Organize, coordinate, and function within an incident management system. PERFORMANCE OUTCOME: The candidate shall be able to determine the need
More informationMANUAL: Jumbo Gate Valve
MANUAL: Jumbo Gate Valve INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE Read instruction manual before use. Operation of this device without understanding the manual and receiving proper training is a
More informationDS05C,D,G Dial Set Pressure Regulating Valves
DS05C,D,G Dial Set Pressure Regulating Valves APPLICATION The Honeywell DS05C,D,G Dial Set Pressure Regulating Valve is a high quality pressure regulating valve that maintains a constant outlet pressure
More informationPerforma Cv Twin Alternating and High Flow Systems. Manual Supplement
Performa Cv Twin Alternating and High Flow Systems Manual Supplement Table of Contents 1.0 Installation and Start-Up.............. 3 Water Line Connection Brine Tank Turbine Connection Connecting Manifold
More informationMarschalk Model # 94000
Marschalk Model # 94000 12-volt DC Portable oil-less Air Compressor Operation Manual 27250006 REV 1 9/13/05 Table of Contents CHAPTER 1: SYSTEM DESCRIPTION... 5 FUNCTION AND THEORY... 5 SYSTEM COMPONENTS...
More informationMedical Gas Control Panel
Medical Gas Control Panel INSTALLATION & MAINTENANCE MANUAL 255105 (Rev. 6) 2018-04 2 255105 (Rev. 6) 2018-04 1.0 User Responsibilities The information contained in this installation and operation maintenance
More informationBuild Your Own Flamethrower Step-by-step Manual
Build Your Own Flamethrower Step-by-step Manual Table of Contents: Parts List.. page 1 Operation...page 6 Diagrams. pages 7-9 Parts list: Required: Air tank (large) Pressure washer gun with high-pressure
More informationWater Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware
57007-88 Introduction Safety Precautions This instruction sheet describes how to set up and use the Hach (Figure 1). A water weir is a device that raises or diverts water to regulate the flow. Hach s water
More informationIntroduction. Part one: Identify the Hydraulic Trainer Components
The University Of Jordan School of Engineering Mechatronics Engineering Department Fluid Power Engineering Lab Experiments No.4 Introduction to Hydraulic Trainer Objective: Students will be able to identify
More informationButton style shirt and firefighting gloves are not required. (This will be a requirement in 2019.)
Firefighting (FF) Public Safety Skilled and Technical Sciences Contests Contest Information State Qualifying Exam: Yes National Contest: Yes Participation: Individual Update April 2, 2018 Contest Description
More informationBlue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION
Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Install your Blue River Technologies Port-A-Poly mixing system in a clean dry area.
More informationInstruction Manual Updated 7/26/2011 Ver. 2.2
4-Unit Model MB HTHP Filter Press #171-50-4: 115-Volt #171-51-4: 230-Volt Instruction Manual Updated 7/26/2011 Ver. 2.2 OFI Testing Equipment, Inc. 11302 Steeplecrest Dr. Houston, Texas 77065 U.S.A. Tele:
More informationApparatus Operator/Pumper
Skill Number: AOP-1 Operate Fixed Systems Objective: 4.3.7 (A) (B) 1. The candidate shall be provided with the equipment to complete this objective including apparatus. 2. The candidate uses safety precautions.
More informationHYDRAULIC CYLINDER TEST
In the event that a coach equipped with hydraulic slide-outs begins to experience room drift, whether the room drifts out after retract, or drifting in after extension, a test of the hydraulic cylinders
More informationUpon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system.
Water Supply - 1 UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: 1. Identify the parts of a water distribution system. 2. Identify the causes of increased resistance
More informationApparatus Operator Refresher Training Program
Division of Training In-Service Training Program Apparatus Operator Refresher Training Program 1 Single Engine / Single Line Operation Refresher Evolution #1 Objective: Charging single handlines at correct
More informationaccidents which arise due to non-observance of these instructions and the safety information herein.
3 GALLON PANCAKE COMPRESSOR Model: 50959 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement, or other masonry.
More informationINSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION
INSTALLATION INSTRUCTIONS CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION The CVS Controls 67CFR Filter regulator is a pressure reducing supply regulator typically used for pneumatic
More informationLaboratory Safety Guideline Emergency Eyewash and Safety Showers
Introduction The purpose of this program is to ensure that all safety eyewashes and showers supply clean, potable water and are in proper working order. This program describes procedures for emergency
More informationPROPERTY INSURANCE ASSOCIATION OF LOUISIANA
PROPERTY INSURANCE ASSOCIATION OF LOUISIANA WATER HAULING GUIDELINES NOTE: Effective immediately, Fire Departments in Louisiana who receive credit for water hauling will receive their credit through a
More informationTABLE OF CONTENTS. Solution Mixing...pg. 2 Components...pg. 3 Set-Up...pg. 4 Operation...pg. 5 Toubleshooting...pg. 6
Manual Thank you for your purchase of the Transmate DeChlorinator. Please read and understand this short operation manual. Our goal is to serve you, our customer. If you have any questions or improvement
More informationInstallation Operating Instructions for Duplex Manual Manifolds PX-TMD Series
Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator
More informationESCONDIDO FIRE DEPARTMENT TRAINING MANUAL ENGINE MODULE HOSE PAGE 1 OF 24 Attack Hose Lays Revised
HOSE 12-01-16 PAGE 1 OF 24 To effectively attack and extinguish a fire, hose lines must be removed from the apparatus and advanced to the location of the fire. The techniques used to advance hose lines
More informationTECHNICAL DATA. Q = C v P S
Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationInstallation and operating manual. Pneumatic control station LK product no: PCS 1-10
LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory
More informationDischarge Relief Valve Operation & Maint.
Relief Valve Operation & Maint. CZ Series Centrifugal Fire Relief svalve Operation and Maintenance Instructions 1410 Operation and Maintenance Form No. F-1031 Section 2302.6 2111 Issue Date 04/90 11/95
More informationStandard Operating and Maintenance Instructions for Pumping System Model PS-90
Standard Operating and Maintenance Instructions for Pumping System Model PS-90 High Pressure Equipment Company 2955 West 17th Street, Suite 6 PO Box 8248 Erie, PA 16505 USA 814-838-2028 (phone) 814-838-6075
More informationOperating Manual. Model BAC-30RT30/BAC-30DC
Model BAC-30RT30/BAC-30DC Manual No. BAC012 (Rev 1 October 2002) Operating Manual AIR SYSTEMS INTERNATIONAL, INC. 829 Juniper Crescent, Chesapeake, Va., 23320 Telephone (757) 424-3967 Toll Free 1-800-866-8100
More informationTECHNICAL DATA. Q= Cv S
Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationOperating Instructions Model and Hydrostatic Test Pump
Operating Instructions Model 29200 and 2920 Hydrostatic Test Pump Dimension Weight Pump Pressure for 29200 Pump Pressure for 2920 Gauge for 29200 Gauge for 2920 Inlet Connection Outlet Connection Hose
More informationAdjustable. Unloader Valve. O&M Manual. Part #
Adjustable Unloader Valve O&M Manual Unloader Valve Part #60-020-361 ADVANCED PRESSURE SYSTEMS 701 S. Persimmon St., Suite 85 - Tomball, TX 77375 Toll Free in North America: (877) 290-4277 Phone: (281)
More informationIrrigation System Winterization and Pressurization Procedures
Irrigation System Winterization and Pressurization Procedures Introduction Any time that an irrigation system is filled and pressurized, or when the system is drained and water flushed from the system,
More informationSERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL
SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL WARNING: Do not attempt to operate this equipment without first reading and understanding the service manual enclosed with this device. 2/05 GENERAL
More informationFiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual
Fiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual 27.75 23.75 25.50 20.75 Specifications: 8-13 GPM 100 strand fiber - Bubbler 75 strand fiber - Spillway Light Bar 45 ft. fiber tail
More informationEvaluating 2-1/2 Direct Fill Lines Colton, New York
www.gotbigwater.com Tanker Fill Tests Evaluating 2-1/2 Direct Fill Lines Colton, New York August 24, 2008 Overview On August 23 rd and 24 th, 2008, the Colton (NY) Fire District hosted a Rural Water Supply
More informationCable Pressurization Buffering
Cable Pressurization Buffering What This Practice Is About Introduction This practice describes the various buffering practices that are used to protect the integrity of the pressurized cable network during
More informationPortable Oil Lube Air Compressors
Portable Oil Lube Air Compressors 8003631 8003632 0410149 8018968 8018940 Owner s Manual Read and understand operating instructions before use Safety definitions The information listed below should be
More informationLARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual
LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual 002694 IntroductIon 8-1-11 Page 1 ForEWord This manual is intended for use with
More informationKJ4000 Operating Instructions & Parts Manual NSN
KJ4000 Operating Instructions & Parts Manual NSN 1025-01-473-7710 Mandus Group Ltd. KJ4000 Operators Manual Date: 3 Jan. 2002 TABLE OF CONTENTS General Safety Instructions...Page 1 Operator Instructions...Page
More informationIMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS
Warrior D.E. Filter Operating Procedures IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Table of Contents SECTION I. FILTER INSTALLATION... 1 SECTION II. FILTER
More informationMANUAL: Jumbo Siamese and Jumbo Wye
TASK FORCE TIPS FIRE FIGHTING EQUIPMENT MANUAL: Jumbo Siamese and Jumbo Wye INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE Read instruction manual before use. Operation of this device without understanding
More informationMODEL MN-PWV PRESSURIZED WATER VESSEL ASSEMBLY OPERATING MANUAL
MODEL MN-PWV PRESSURIZED WATER VESSEL ASSEMBLY OPERATING MANUAL Prepared by CR Manning Edited by SC Woidtke Rev August 22, 2011 PRESSURIZED WATER VESSEL OPERATING MANUAL 1. Background 1.1 The Pressurized
More informationELKHART BRASS MANUFACTURING COMPANY
ELKHART BRASS MANUFACTURING COMPANY INSTALLATION and OPERATING INSTRUCTIONS for MODEL UP PRESSURE RESTRICTING HOSE VALVES I. Models and Sizes Covered: UP-20, 1-1/2" size UP-25, 1-1/2" size UP-20, 2-1/2"
More informationModel: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering
Bermad Pressure Reducing Valve Model: 720-UL INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working with and around our equipment
More informationFIRE FIGHTER II SKILL PERFORMANCE CHECK SHEETS NFPA FIRE FIGHTER II SKILL STATION MENU
FIRE FIGHTER II SKILL STATION MENU STATION TASK(S) A FIREGROUND OPERATIONS/FIRE COMMUNICATIONS MANDATORY B SPRINKLER DRAIN/PRESSURES RANDOM C PITOT GAUGE USE RANDOM D INSPECTION/MAINTENANCE: GENERATOR,
More informationIMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS
Clean & Clear Plus Cartridge Filters Owner's Manual IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Table of Contents SECTION I. FILTER INSTALLATION... 1 SECTION
More informationTri-Tech Medical Inc.
Introduction Tri-Tech Medical manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists
More informationUBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions
Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM
More informationOPERATION MANUAL NTF-60 Plus
OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)
More informationOPERATION MANUAL NTF-15
OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE
More informationModel: 43T. Bermad Pressure Relief Valve
Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment
More informationInstallation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.
Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow Model: FP 450-80 Installation Operation Maintenance PAGE 1 OF 5 1. Safety First BERMAD believes that the safety of personnel
More informationENGINE COMPANY OPERATIONS CHAPTER 12 February 15, 2006 WATER LOSS PROCEDURES
CHAPTER 12 February 15, 2006 WATER LOSS PROCEDURES 1. WATER LOSS PROCEDURES 1.1 The loss of water on the fire ground is a very serious situation, and something all members should strive to prevent. The
More information4-W GAS ODORIZER WITH POSITIVE ACTION INDICATOR GAUGE (300 PSIG) 2014 INFORMATION MANUAL SUBMITTED BY:
4-W GAS ODORIZER WITH POSITIVE ACTION INDICATOR GAUGE (300 PSIG) 2014 INFORMATION MANUAL SUBMITTED BY: #3, 1470 28 Street NE Calgary, Alberta Canada, T2A 7W6 Phone: (403) 569-8566 Fax: (403) 207-5110 Submitted
More informationWater Supply for Suburban and Rural Firefighting
FIRE AND RESCUE DEPARTMENTS OF NORTHERN VIRGINIA FIREFIGHTING AND EMERGENCY OPERATIONS MANUAL Water Supply for Suburban and Rural Firefighting Second Edition Issued: 2003 Revised: November 2017 ACKNOWLEDGEMENTS
More informationInstallation, Operation and Maintenance Manual for Back Pressure Regulator
Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN
More informationDeveloped by Lt. Randy Stuart Eng. Ben Wynkoop, and FF. Alex Klinger in Sept 2011
W A T E R S U P P L Y O P E R A T I O N S R U R A L ( 2. 1 ) Developed by Lt. Randy Stuart Eng. Ben Wynkoop, and FF. Alex Klinger in Sept 2011 Revised by Lt. Greg Van Heel, Eng. Chris Wining, and FF. Uriel
More informationHPIC D Hydrostatic Test Pump PRODUCT INFORMATION AND OPERATING INSTRUCTIONS
WIDDER TOOLS HPIC-10000-D Hydrostatic Test Pump PRODUCT INFORMATION AND OPERATING INSTRUCTIONS Description: The WIDDER Hydrostatic Test Systems C Series is a portable, selfcontained, air driven hydrostatic
More informationTECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1
Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a
More informationMaster Control Systems, Inc. Variable Speed Fire Pump Controllers
Master Control Systems, Inc. Variable Speed Fire Pump Controllers Meets NFPA 20-2019 UL/FM Listed and Approved for fire protections * Pressure Limiting Control * Suction Limiting Control Why Variable Speed?
More informationI T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL I-867-4T 867-4T Pressure Reducing Valve HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR FUTURE REFERENCE WARNING Read and understand all instructions
More informationOperating Manual. Models PAK-4 & PAK-4R Manual No. PAK002 (Rev 6 February 1999)
Models PAK-4 & PAK-4R Manual No. PAK002 (Rev 6 February 1999) Operating Manual AIR SYSTEMS INTERNATIONAL, INC. 829 Juniper Crescent, Chesapeake, Va., 23320 Telephone (757) 424-3967 Toll Free 1-800-866-8100
More information