for Pleasant & Healthy Air-Distribution ISO 9001:2000 Linear Slot Diffusers Product Bulletin 133-D
|
|
- Thomas Johns
- 5 years ago
- Views:
Transcription
1 for Pleasant & Healthy Air-Distribution ISO 9001:2000 Product Bulletin 133-D Linear Slot Diffusers
2 Pleasant.. Serene.. YOU & DASCO... Since 1964 Partners for good health
3 INTRODUCTION Linear slot diffusers are always considered as the most attractive air distribution devices. They are specially designed for ceiling mounting in a wide range of applications in heating, ventilation and air conditionin systems. At a perfect setting, linear slot diffusers provide a stable pattern of diffusion to produce an optimum performance for both supply and return air in addition to their pleasant appearance. To satisfy both architectural and engineering needs, curved slot diffusers have been also developed and designed. Whether it requires a continuous linear run, ellipse, complete circle orserpentine curve,. LINEAR/CURVED SLOT DIFFUSERS CAN ALWAYS BE IORPORATED INTO ANY DESIGN. 1 Introduction
4 LINEAR SLOT DIFFUSERS GENERAL Dasco linear slot diffusers for both supply and return applications DLD-C(S/R) are designed to give unobstrusive continuous air diffusion with a pleasing aesthetic appearance. Hairline joints ensure clean continuous runs of linear slot diffusers for both active and dummy sections. They are normally connected to the main ducting system by means of connection boxes (Plenums), and are adjustable in height for accurate lining-up with the ceiling. Linear Slot Diffuser ( 3 Slots) Linear Slot Diffuser ( 2 Slots) In general, DLD-C(S/R) linear slot diffuser is considered as a unique type of an air distribution device, dispenses proper air quantities, controls air pattern for ultimate human comfort and adapts to any design concept perceived by architect / design engineer. Mitered Corner ( 90º ) 2 Linear Slot Diffusers
5 DESCRIPTION Dasco linear slot diffusers DLD-C(S/R) are designed to give a comprehensive and full range of air flow patterns and volumes. Their deflector blades and volume control dampers give a full flexibility in air patternand volume control. These are fully adjustable from the face of the diffuser. Single or multiple slot arrangements can provide any combinations of horizontal, vertical or any intermediate setting of air flow pattern over a full range of 180º adjustment, as each slot is individually adjustable. Volume control dampers consist of two strips of extruded aluminium profiles, one fixed and one movable. They can be also usedas equalizing grids. Mitered Corners (Different angles) SINGLE SLOT ADJUSTMENTS Horizontal right Horizontal left Fully Vertical Dampered Horizontal Fully Closed MULTIPLE SLOT ADJUSTMENTS (TWO TO EIGHT SLOTS ) Horizontal one-way Horizontal two-way Fully Vertical Horizontal two-way Dampered(unequal flow) Vertical Horizontal 3 Linear Slot Diffusers
6 Two types of linear slot diffusers are available: Linear slot diffusers with 3 / 4 slot width. Linear slot diffusers with 1 slot width. Both are manufactured in one up to eight slots with a maximum one piece length of 6 meters as a standard, permitting complete control of flow rate without disturbing the selected air pattern. Linear slot diffusers with other lengths and /or number of slots can also be provided on request. End caps on both sides are supplied on one piece linear slot diffusers, and on one side of end sections of continuous units. Sections are connected by using alignment strips. MATERIAL & FINISH High quality and heavy gauge extruded aluminium profiles. They are available in white polyester powder coated finish. However, any other RAL standard colours are also available upon customer s request. Deflector blades and dampers are also made from extruded aluminium profiles normally in black colour. Plenum boxes are made from galvanized steel. LINEAR DIFFUSER (3-SLOTS) WITH DAMPERS 4 Linear Slot Diffusers
7 Linear Slot Diffuser (Hexagonal Shape) Linear Slot Diffuser (T-Shape) Linear Slot Diffusers (2Slots) Special Geometric Shapes Vertical outside Mitered corner section 2 Slots Diffuser Circular Shape Vertical inside Mitered corner section Vertical inside Mitered corner section Chamfered type 5 Linear Slot Diffusers
8 ACCESSORIES A complete variety of accessories and options are always available for DLD-C(S/R) 1. MOUNTING BRACKETS Are used normally for ceiling installations. They are made from Z-27(gauge 20 ) galvanized steel and are arranged with holes for easy installations. Mounting Brackets 2. ALIGNMENT STRIPS Are used for continuous sections and are made from aluminium sheets. Alignment strips 3. END CAPS L-Shape flanges, manufactured from aluminium extruded profiles and are available in different lengths to match different number of slots and widths. They are usually fixed at the end of linear slot diffusers and are very easy to install and remove. Alignment strips End caps Without end caps End cap (left or right) End caps (both sides) 6 Accessories
9 4. DUMMY SECTIONS With exactly the same construction of supply air linear slot diffusers but with blank off damper sheets. Are used along with continuation sections of supply and /or return linear slot diffusers for decoration purposes. Linear Diffuser (3 Slots) - Dummy Type 5. MITERED CORNERS Are usually used when slot diffusers are designed to form closed loops. They are available in one to eight slots and can have any combination of L1, L2 and angle ø. Mitered Corners 7 Accessories
10 PLENUM BOXES DESCRIPTION It is designed to ensure even air distribution along the associated linear slot diffusers, and therefore maintaining correct performance characteristics. Plenum boxes, are available with or without internal lining of thermal and acoustic insulation and are available for single or continuous installations. All joints are sealed for a perfect tightness and in most cases are Lock formed, which adds to maintain rigidity. INSULATION Fiberglass 25 mm thick (16kg/m3) with black tissue face for acoustic and thermal insulation (Available as optional) Plenum Box with insulation MATERIAL Galvanized sheet steel Z-27 (Gauge 24 ) Plenum Box without insulation 8 Plenum Boxes
11 SIZES Available in various neck openings (5 to12 ) suitable for fixing linear slot diffusers (1 to 8 slots). Maximum plenum length is 240 cm per piece. Longer lengths are provided with special joints to fit continuous shape. Insulated Plenum Plenum without Insulation Single Installation DLD-C with Plenum box DPB-C Table 1. Dimensions of plenum boxes ( with /without ) insulation 9 Plenum Boxes
12 ORDERING CODE Dasco Linear Slot Diffuser a =Version b =Number of slots c =Slot width d =Length,cm e =Number of end caps Dasco Plenum Box S :Supply R :Return RD :Return with volume control damper D :Dummy 1,2,3,4,5,6,7,8 1 :3/4 slot width 2 :1 slot width (Maximum 600) 0 : Without 1 : One end cap 2 : Two end caps DLD-C a - b - c - d - e DPB-C a - b - c - d - e a =Installation b =Number of slots c = Slot width d =Length, cm e =Thermal insulation S I :Single Unit :In - Line 1,2,3,4,5,6,7,8 1 : 3 / 4 slot width 2 :1 slot width (Maximum 240) 0 : Without thermal insulation 1 : With thermal insulation 10 Ordering Code
13 DIMENSIONAL DATA Linear slot diffuser with 3 / 4 slot width Linear slot diffuser with 1 slot width 11 Dimensional Data
14 DIMENSIONS OF LISTED SIZES: a) Linear slot diffusers with 3/4 slot width Table 2. Dimensions of linear slot diffusers with 3/4 slot width a) Linear slot diffusers with 1 slot width Table 3. Dimensions of linear slot diffusers with 1 slot width Woodall Colour Curved Diffusers Arched Shape 12 Dimensional Data
15 ENGINEERING DATA DEFINITIONS Throw (T) : Throw of an outlet, in m (feet), is the distance from the center of the outlet to a point in the mixed air stream where the highest sustained velocity of the mixed air stream has been reduced to a specified level, i. e, 100 and 50 FPM. CFM : Is the air flow rate in cubic feet per minute. Velocity (Vk) : Discharge or intake velocity of an outlet or inlet, in m/s (FPM) measured with an approved calibrated velometer at specified locations relative to the face of the outlet or inlet. Sometimes referred to as jet velocity. Terminal velocity (Vt) : Terminal velocity from an outlet, in m/s (FPM), is the highest sustained velocity in the mixed air stream arbitrarily specified and used to determine throw. Area factor (Ak) : Is the area factor of an outlet or inlet which is also a flow factor determined from the discharge or intake velocity ( V k ), and the volume flow rate (CFM). A CFM k = V k Static Pressure (Ps) : The outward force within a duct measured in mm (inch) W.G. Velocity pressure (Pd) : The forward moving force of an air stream within a duct measured in (Dynamic pressure) mm ( inch) W.G. Total pressure (Pt) : The sum of the velocity pressure and static pressure measured in mm (inch) W.G. The following table could be helpful before starting the selection of a linear slot diffuser. Table 4. CFM range for supply linear slot diffusers (1 to 8 slots). 13 Engineering Data
16 NOISE CRITERIA Noise criteria : The sound pressure level of 8 octave bands acceptable to human ears and are estimated from table 5. The sound caused by an air outlet is directly proportional to the velocity of the air passing through it. Ambient sounds a) b) c) ENVIRONMENTAL SOUND Existing within the space with air conditioning Equipment off EXTERNAL SOUND Entering a space from outdoors. INTRUDING SOUND Entering from adjacent spaces. Prior to selection of level from table 5, the three ambient sounds above must be considered. The room effect : Is the difference between the sound power level of a terminal and the sound pressure level sensed by human ears in the room, and is affected by room size, sound absorption characteristic of the room surfaces, ceiling height, space volume, distance of listener to terminal, terminal location and number of terminals. Curved Slot Diffuser Concave Shape Curved Slot Diffusers Convex Shape 14 Noise Criteria
17 RECOMMENDED NOISE CRITERIA FOR ROOMS Table 5. Recommended range of noise criteria from ASHRAE GUIDE. 15 Noise Criteria
18 BASIC PERFORMAE DATA FOR DLD-CS A. Supply linear slot diffusers with 3/4 slot width Note Number of slots Throw (Ft) <20 <20 < 20 <20 <20 <20 < 20 < Throw (Ft) <20 <20 < Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Table 6. Performance data for supply linear slot diffusers with 3 / 4 Slot width Throw data (Ft) is based on terminal velocities of 100 & 50 FPM for horizontal discharge. values are for horizontal discharge. For vertical discharge subtract(5) from values. values are for 4 Ft long unit and assume room attenuation 10 db Performance Data
19 Number of Slots Supply P.D. W.G Curve 1. Static pressure drop Vs. Air flow for DLD-CS ( 3 / 4 Slot width) Note Static pressure drop in inch W.G. for horizontal discharge. For vertical discharge multiply by 0.6 EFFECTIVE FREE AREA (A k ) Table 7. Effective free area A k (Ft 2 /Ft run) for DLC-CS ( 3 / 4 Slot width) 17 Performance Data
20 BASIC PERFORMAE DATA FOR DLD-CS B. Supply linear slot diffusers with 1 slot width Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Throw (Ft) Number of slots <20 <20 < 20 <20 <20 <20 < < 20 < 20 < 20 < < < Note Table 8. Performance data for supply linear slot diffusers with 1 slot width Throw data (Ft) is based on terminal velocities of 100 & 50 FPM for horizontal discharge. values are for horizontal discharge. For vertical discharge subtract(5) from values. values are for 4 Ft long unit and assume room attenuation 10 db. 18 Performance Data
21 Supply P.D. W.G. Number of Slots Curve 2. Static pressure drop Vs. Air flow for DLD-CS ( 1 slot width) Note Static pressure drop in inch W.G. for horizontal discharge. For vertical discharge multiply by 0.6 EFFECTIVE FREE AREA (A k ) Table 9. Effective free area A k (Ft 2 /Ft run) for DLC-CS (1 Slot width) 19 Performance Data
22 BASIC PERFORMAE DATA FOR DLD-CR A. Return linear slot diffusers with 3/4 slot width Static Pressure Drop W.G Number of slots < 20 < 20 <20 <20 < 20 < 20 < 20 < <20 < Table 10. Performance data for return linear slot diffusers with 3 / 4 slot width Note Performance data are for return linear slot diffusers with deflection blades. values are for 4 Ft long unit and assume room attenuation 10 db. Static pressure values are in inches W.G. EFFECTIVE FREE AREA (A k ) 8 Table 11. Effective free area A k (Ft 2 /Ft run) for DLC-CR ( 3 / 4 Slot width) 20 Performance Data
23 BASIC PERFORMAE DATA FOR DLD-CR B. Return linear slot diffusers with 1 slot width Static Pressure Drop W.G Number of slots < 20 < 20 < 20 <20 < 20 < 20 < <20 <20 < < Table 12. Performance data for return linear slot diffusers with 1 slot width Note Performance data are for return linear slot diffusers with deflection blades. values are for 4 Ft long unit and assume room attenuation 10 db. Static pressure values are in inches W.G. EFFECTIVE FREE AREA (A k ) Table 13. Effective free area A k (Ft 2 /Ft run) for DLC-CR (1 slot width) 21 Performance Data
24 CORRECTION FACTORS A) Supply Linear slot diffusers Throw and values in performance tables are based on supply linear slot diffusers with active length of 4 Ft. To determine throw and values for other lengths, use the correction factors in the following table : Table 14. Correction factors for throw and values at different active lengths of supply linear slot diffusers Static pressure drop and values in performance table/curves are based on 100% damper opening. Use the following correction factors for different damper adjustments. Table 15. Correction factors for static pressure drop and values at different damper adjustments B) Return linear slot diffusers values in performance tables are based on return linear slot diffusers with active length of 4 Ft. To determine values for other lengths, use the correction factors in the following table: Table 16. Correction factors for values at different active lengths of return linear slot diffusers. 22 Correction Factors
25 AIR BALAING ADJUSTMENT To determine the CFM, follow up the following procedure: 1) Use measuring tools for air velocity like ALNOR 2220 A or 2220 probe, or anemotherm air meter model 60. 2) Take number of measuring points ( should be not less than 4)based on 4 Ft long linear difffuser, and probe should be located and adjusted as to measure the maximum air velocity by facing the probe to the air flow direction on the face of the linear slot diffuser as shown. 3) Take the arithmetic average of velocity readings to obtain the Vk (average) as follows: V k ( average ( V1+V2+...+V ) = k ) K 4) 5) Determine the area factor (Ak) from previous tables considering the linear diffuser length and number of slots. Calculate the air volume ( CFM ) with the following formula : CFM = V k (average) x Ak Note Right Flow Left Flow Vertical Flow Return If the air volume calculated from above procedure is not satisfactory, repeat the same proceddure after adjusting the deflector angle. DEFLECTOR SETTING The deflector blades of the supply linear slot diffusers can be fully adjusted to give either a horizzontal / vertical air pattern, or any combination of them. The horizontal air flow adjustment may be set for either left or right hand throw. 23 Air Balancing
26 STANDARD FIXING METHOD Linear Diffuser (2 slots) with end cap from one side Linear Diffuser (2 slots) without end caps 24 Fixing Method
27 CONVERSION TABLE Quantity Imperial Unit Metric Unit From Imperial To From Metric To Metric Multiply By Imperial Multiply By Area Square foot Square meter (m 2 ) Square inch Square millimeter (mm 2 ) Density Pounds per cubic foot Kilograms per cubic meter (kg/m 3 ) Length inch millimeter (mm) foot millimeter (mm) foot meter (m) yard meter (m) Pressure inch of water column Kilopascal (kpa) foot of water column inch of mercury column ounces per square inch pounds per square inch Kilopascal (kpa) Kilopascal (kpa) Kilopascal (kpa) Kilopascal (kpa) Temperature fahrenheit celcius (ºC ) 5/9 (ºF-32) (9/5 ºC ) + 32 Velocity feet per second meters per second (m/s) feet per minute ( fpm) meters per second (m/s) miles per hour meters per second (m/s) Volume Flow Cubic feet per minute (cfm) Liters per second (L/s) Cubic feet per minute (cfm) Cubic meters per second (m 3 /s) Cubic feet per hour ( cfh) Milliliters per second( ml/s) Gallons per minute(u.s.) Liters per second( L/s) Gallons per minute(imperial) Liters per second( L/s) Table 17. Metric guide conversion factors. 25 Conversion Table
28 TESTING AND APPROVAL Different samples from DASCO air terminal devices (Linear Slot Diffusers) were tested at ITS (Intertek Testing Services) labs in accordance with: Air diffusion council test code for grilles, registers and diffusers No. ADC 1062: GRD-84. ISO 5219 Air distribution and air diffusion laboratory aerodynamic testing and rating of air terminal devices. ANSI/ASHRAE , Method of testing for rating the performance of air outlets and inlets. LINEAR SLOT DIFFUSERS WERE TESTED FOR: a. b. c. d. Sound ( Noise Criteria). Static pressure in inches W.G. Throw, feet. Ak (Area factor). 26 Testing & Approval
29 COATING WITH POWDER NOW YOU CAN ACHIEVE OPTIMAL COATING PERFORMAE ON ALL PRODUCTS YOU PAINT! DASCO offers a first class service by introducing a wide range of perfect polyester powder coating on all of its aluminium products of air terminal devices. The best quality of polyester powder Corro-Coat are used in according to the internnational standards (BS,ISO,DIN,ASTM). PE-F architectural grade polyester powders are used perfectly with pre-treatment, electrostatic spray and curing in accordance with the above standards recommendations. A complete range of RAL-Standard colours are always available in addition to a vast range of special compound colours as per our customers request. RAL Standard Colour Chart Swatch 27
30 28
31 29
32 Since 1962 P.O. Box: 6192 Hawalli Kuwait. Tel: Fax: Product Bulletin 133-D
-4.~1~ S L 0 T D I F F U S E R S
\ I R DISTR I BUTION SPECIALIST -4.~~ S L 0 T D I F F U S E R S SLSD RLSD Supply Linear Slot Diffuser with hit & miss damper, and with deflectors. Return Linear Slot Diffuser with hit and miss damper,
More informationHCD HIGH CAPACITY DRUM LOUVER
HIGH CAPACITY DRUM LOUVER The s (HCD) consist of extruded aluminum blades mounted inside a rotatable drum to produce long air throws with a high degree of directional control. Rotateable drum provides
More informationAdjustable swirl diffuser ODZA TECHNICAL DATA
Adjustable swirl diffuser ODZA TECHNICAL DATA 2 Adjustable swirl diffuser ODZA Adjustable ceiling swirl diffuser ODZA is intended for commercial and industrial buildings with a large room volume and high
More informationCEILING DIFFUSERS technical CONTROL THE AIR YOU BREATHE. types -CD, CAB. Europair Africa a division of Performancair Products Africa (Pty) Ltd
CEILING DIFFUSERS technical types -CD, CAB Europair Africa a division of Performancair Products Africa (Pty) Ltd tel +27 11 974 2425 fax +27 11 974 7251 web www.europair-africa.com email: info@europair-africa.com
More informationEXTRUDED ALUMINUM SQUARE AND RECTANGULAR DIFFUSERS
INDUSTRIAL REGISTRATION NO.353 EXTRUDED ALUMINUM SQUARE AND RECTANGULAR DIFFUSERS SQUARE AND RECTANGULAR FLUSH CEILING DIFFUSERS OUTSTANDING FEATURES: Extruded aluminum construction 1-2-3-4 way throw patterns.
More informationSupply air diffuser ROFB, RPFB
Supply air diffuser ROFB, RPFB ROFB and RPFB are supply air diffusers with an integrated plenum box for freely suspended installation in a ceiling. The diffuser ROFB comes with an unperforated and RPFB
More informationvento specification sheet
type purpose application linear diffuser 18mm diffuser for air distribution for false ceiling the diffuser is used for the supply and exhaust of cooled or heated air in facilities such as offices, shopping
More informationCLB 3 ATTRACTIVE JOINABLE LINEAR PROFILE EASILY ACCESIBLE VOLUME ADJUSTMENT INCLUDED FLEX CLAMP HEATING AND COOLING TERMINAL REHEAT AVAILABLE
CONSTANT VOLUME LINEAR BAR CEILING DIFFUSER CLB 3 ATTRACTIVE JOINABLE LINEAR PROFILE EASILY ACCESIBLE VOLUME ADJUSTMENT INCLUDED FLEX CLAMP HEATING AND COOLING TERMINAL REHEAT AVAILABLE CONTROL THE PERIMETER
More informationC O L M A N. Air Distribution SWIRL DIFFUSERS DRS SERIES DRS SERIES
C O L M N ir Distribution E N G I N E E R E D I R P R O D U C T S SWIRL DIFFUSERS DRS SERIES DRS SERIES D SERIES SWIRL DIFFUSERS pplication The DRS, DQS, DCS and DSS series of fixed circular swirl diffusers
More informationCADENZA
---------------------------------------------- ---------------------------------------------------------------------- Attenuator with aerodynamically shaped splitters for rectangular ducts GENERAL has
More informationCALMO
---------------------------------------------------- Sound attenuator with recessed connection for rectangular ducts ---------------------------------------------------------------------- GENERAL is, due
More informationCHILLED BEAM FLEXICOOL IQID
CHILLED BEAM FLEXICOOL IQID TECHNICAL CATALOGUE 2 Flexicool IQID Chilled beam - Technical catalogue CHILLED BEAM FLEXICOOL IQID The chilled beam Flexicool IQID is an integrated system for ventilation,
More informationAIR DIFFUSION INDUCTIVE MICRO-PERFORATED DUCTS
cop1 SISTEMI INNOVATIVI TRATTAMENTO ARIA AMBIENTE AIR DIFFUSION INDUCTIVE MICRO-PERFORATED DUCTS SELECTION CATALOGUE JULY 2012 EDITION INTRODUCTION The DLD air diffusion perforated ducts are born with
More informationfor Asia / Pacific Radial outlet RA-N3... DS 4134 AUS /
for Asia / Pacific Radial outlet RA-N... DS AUS./ Radial outlet RA-N Preliary remarks KRANTZ KOMPONENTEN radial outlets of type RA-N have fixed radial vanes. They generate high-quality, diffuse supply
More informationRound duct nozzle jet diffuser Model DSA-RR
Round duct nozzle jet diffuser Model DSA-RR Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3
More informationQuick Reference Technical Data
Bulletin 127C 2 Quick Reference Technical Data For over 100 years, The Spencer Turbine Company has specialized in innovative solutions to air and gas handling problems. Spencer's product line includes
More informationGENERAL OVERVIEW GENERAL OVERVIEW
GENERAL OVERVIEW A GENERAL OVERVIEW Traditional HVAC systems in most commercial buildings today employ Overhead Mixing (Mixed Ventilation, MV) to meet both outdoor air ventilation and space conditioning
More informationenclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets)
enclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets) Stainless steel and plastic enclosures for use in potentially explosive environments R Rittal system partners Perfect
More informationTECHNICAL DESCRIPTION
TECHNICAL DESCRIPTION Exhaust Hose Reel ser. 865, electric motor driven No. 981118101 Description Limit switches, for hose coiling and uncoiling integrated in drive unit. Motor turns drum via a planetary
More informationLindabSolus. Supply air beam. lindab we simplify construction
lindab we simplify construction Lindab 03.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,
More informationFuel Filters DN15 DN25. elektrogas.com DE
FF Fuel Filters DN15 DN25 elektrogas.com DE180 0914 FF Fuel Filters Contents Description.. 2 Features.. 2 Functioning and application. 3 Accessories and optionals 4 Technical specifications 4 Gas flow
More informationTechnical Documentation Linear diffusers series LDB
Technical Documentation Linear diffusers series 70435 Stuttgart, Grenzstraße 7, Germany Tel. +49 711 81-0, Fax +49 711 81-7 info@ltg-ag.de www.ltg-ag.com LTG Incorporated 105 Corporate Drive, Suite E Spartanburg
More informationLindabPremum. Supply air beam. lindab we simplify construction
lindab we simplify construction Lindab 03.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,
More informationLindabPremax. Supply air beam. lindab we simplify construction
lindab we simplify construction Lindab 03.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,
More informationenclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets)
lri030784900.eps lri031083400.eps enclosures to ATEX and enclosures for special custom design (EEx p and NEMA cabinets) fri040466500.eps Stainless steel and plastic enclosures for use in potentially explosive
More informationSIZING THE EXTROL DIAPHRAGM-TYPE HYDRO-PNEUMATIC TANK
SIZING THE EXTROL DIAPHRAGM-TYPE HYDRO-PNEUMATIC TANK 1400 Division Road, West Warwick, RI 02893 T: 401.884.6300 F: 401.885.2567 www.amtrol.com Sizing the ExTrol Diaphragm-Type Hydro-Pneumatic Tank For
More informationHorizontal Bladder Tanks
DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationSafidDampers. Class 1A & Class 1 Low Leakage Volume Control Damper ( Flange Type ) SPK Standard Construction. Description SPK
( Flange Type ) SPK 30 400 Standard Construction FRAME: 60mm x 30mm x.5mm (6 Ga.) galvanized steel formed channel for flange connection. BLADES: 00mm, 5mm and 50mm wide airfoil shaped blades extruded aluminum.
More informationDry Plant Measurement Information
Dry Plant Measurement Information Fertilizer - Information Pages DRY PLANT MEASUREMENT Basic Formula: Pounds of Product = Cubic Feet x Product Weight Area A: 14' x 28' x width = cubic feet x product weight
More informationModel MTB-ASME Horizontal Bladder Tanks
DATA SHEET Model MTB-ASME Horizontal Bladder Tanks Features n UL Listed and FM Approved for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationThe most common terms rating air flow capacity are ICFM, FAD, ANR, SCFM or nl/min
Rating of Air Compressors and Air Equipment The most common terms rating air flow capacity are ICFM, FAD, ANR, SCFM or nl/min There is no universal standard for rating air compressors, air equipment and
More informationSizes JNŽ-6, ANŽ-3, ANŽ-4
JNŽ-6, ANŽ-3, ANŽ-4 Application are used in all kinds of low pressure air conditioning, air heating ind ventilation, where it is necesary to equalise the pressure between adjacent rooms. They can be applied
More informationTESTING APPLICATION STANDARD (TAS)
TESTING APPLICATION STANDARD (TAS) No. 00(A)-9 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE AND/OR INCREASED WINDSPEED RESISTANCE OF SOFFIT VENTILATION STRIP AND CONTINUOUS OR INTERMITTENT VENTILATION
More informationRELIEF CAPACITY CURVES
E (800) 910-4295 www.hawk-eye.com TANKAGE VENTING RELIEF CAPACITY CURVES SERIES 6000 PVRV SERIES 4000 MARSH HAWK TRV SERIES 5000 EPRV RE SERIES 200 & 300 TVTH RE INTRODUCTION INTRODUCTION A relief capacity
More informationPrecision Duct Systems 4570 Commerce Cir SW Atlanta, GA Phone (404)
Project Name: Engineer: Contractor: Section Number: Date Submitted: Date Approved: Pressure Class: Material Type: Connections: 2005 Up to 10 wg 1995 2 wg pos 1995 4 wg pos 1995 10 wg 2005 neg WG: 1995
More informationVertical Bladder Tanks
DATA SHEET Vertical Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationVENTILATOR OPTIONS. Please visit our web page to view all the available options and for a specification.
Seefire Natural Louvred Ventilator Seefire is a natural louvred ventilator that is available in a wide range of sizes, louvre options and control options. Seefire has been exhaustively tested and certified
More informationPART 3 MODULE 6 GEOMETRY: UNITS OF GEOMETRIC MEASURE
PART 3 MODULE 6 GEOMETRY: UNITS OF GEOMETRIC MEASURE LINEAR MEASURE In geometry, linear measure is the measure of distance. For instance, lengths, heights, and widths of geometric figures are distances,
More informationMedium Heavy Vehicle Safety and Foundation 1
Medium Heavy Vehicle Safety and Foundation Student/intern information: Name Class Vehicle used for this activity: Year Make Model Odometer VIN Learning Objective / Task General Safety Identify tools and
More informationBERMAD Waterworks. Level Control Valve with Altitude Pilot. 700 Series. Model X. Features and Benefits. Major Additional Features
Level Control Valve with Altitude Pilot High level reservoirs & water towers Energy cost critical systems Systems with poor water quality Inherent refreshing Level sustaining at reservoir outlet The Level
More informationRadiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G
Data sheet Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G EN 215 Application RA2000 013G2910 Built-in sensor RA2000 013G2920 tamperproof RA2000 013G5062 remote temperature
More informationGas Filters DN15 DN300. elektrogas.com EE151 06/13
FG Gas Filters DN15 DN300 elektrogas.com EE151 06/13 FG Gas Filters Contents Description.. 2 Features.. 2 Functioning and application. 3 Accessories and optionals 4 Technical specifications 4 Gas flow
More information94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work?
94270 What is Tank Blanketing? blanketing systems are used to prevent the escape of liquid vapors into the atmosphere or to prevent moisture from entering a tank and contaminating its contents. A tank
More informationEvolution. Radiant Panels. Radiant panel system LPHW up to 90 C Suspended ceiling grid or sofit mounting Vertical wall surface mounting
Evolution Radiant Panels Radiant panel system LPHW up to 90 C Suspended ceiling grid or sofit mounting Vertical wall surface mounting Contents IDENTIFICATION DESCRIPTION Page STYLE CG 3-7 STYLE CS, FC
More informationME 449/549 Lab Assignment 2 Spring 2006 due 25 April Background. 2 Apparatus
ME 9/59 Lab Assignment Spring due 5 April 1 Background The thermal management laborator has three small wind tunnels used for heat transfer experiments. The wind tunnels provide air velocities from to
More informationVibration isolated tables. Individually tailored to your requirements.
68 Vibration isolated tables Individually tailored to your requirements. LTH laboratory table Particularly robust and resistant n Adjustable leveling mounts n Rigid, welded steel subframe n BiAir membrane
More informationVARIABLE ORIFICE BALANCING VALVE PN 25 TECHNICAL DATA SHEET. Approved by*: Main features:
VARIABLE ORIFICE BALANCING VALVE PN 787 Main features: Technical data: Cim 787 is used for balancing the flow in cooling, heating and domestic water systems. Cim 787 is a combined manual presetting valve
More informationCLEANROOM GEL GRID CEILING SYSTEM PRODUCT DATA Division
5023 HAZEL JONES ROAD, BOSSIER CITY, LA 71111 888.315.1561 800.877.8746 FAX SALES@GORDONCLEANROOM.COM GORDONCLEANROOM.COM AN EMPLOYEE OWNED COMPANY CLEANROOM GEL GRID CEILING SYSTEM PRODUCT DATA Division
More informationMANAGEMENT PROCEDURE FOR LABORATORY VENTILATION
UNIVERSITY OF ALASKA FAIRBANKS SAFETY SYSTEM POLICY AND PROCEDURE DOCUMENT NUMBER: 508 ISSUE DATE: SEPTEMBER 1996 SUBJECT: Management Procedure for Laboratory Ventilation MANAGEMENT PROCEDURE FOR LABORATORY
More informationRadiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G
Data sheet Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G Application RA2000 013G2910 Built-in sensor RA2000 013G2920 tamperproof RA2000 013G5062 remote temperature adjuster
More informationFLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN
FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN George Feng, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga, Ontario Vadim Akishin, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga,
More informationGood News From the Doctor
Good News From the Doctor Understanding Temperature and Altitude Corrections The most common influences on air density are the effects of temperature other than 70 F and barometric pressures other than
More informationAutomatic extractor outlet
L-07-2-01e Automatic extractor outlet Type HFA Contents Application Realisation Operation Safety instructions Contents Application Realisation Operation Safety instructions 2 Connection diagram Dimensions
More informationBULLETIN FA-300. February 1999 AXIAD II. Adjustable Pitch Airfoil Axial Flow Fan
BULLETIN FA-300 February 1999 AXIAD II Adjustable Pitch Airfoil Axial Flow Fan AXIAD II The axial flow fan with: High efficiency Low sound level Adjustable pitch blades Complete range of accessories Axial
More informationSizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios
Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Yunlong (Jason) Liu, PhD, PE HNTB Corporation Sean Cassady, FPE HNTB Corporation Abstract Extraction
More informationINSTALLATION & OPERATION MANUAL AORCS ATLAS OPERATING ROOM CEILING SYSTEM. Redefine your comfort zone.
INSTALLATION & OPERATION MANUAL AORCS ATLAS OPERATING ROOM CEILING SYSTEM IOM AORCS ATLAS OPERATING ROOM CEILING SYSTEM Table of Contents Inspection...3 Examination...3 Preparation...3 Installation...4
More informationASX 176 Axial Pressure regulator
ASX 176 Axial Pressure regulator ASX 176 Classification and Area of Application ASX 176 is a downstream pressure regulator, pilot controlled, for medium and high pressure applications. It is particularly
More informationK13.12 FACE FIXED PANIC EXIT DEVICE K13 DOORS
K13 DOORS K13.12 FACE FIXED PANIC EXIT DEVICE 01.03.2018 Waregemstraat 5-9870 Zulte - Belgium - T. +32 9 388 88 81 - F. +32 9 388 88 21 - commercial@sobinco.com - www.sobinco.com CONTENTS 1. Base set n
More informationGas Filters DN15 DN300. delta-elektrogas.com EE151 03/17
FG Gas Filters DN15 DN300 delta-elektrogas.com EE151 03/17 FG Gas Filters Contents Description.. 2 Features.. 2 Functioning and application. 3 Technical specifications 4 Gas flow chart (pressure drop)
More informationRA-N radiator valves with integrated presetting and self-sealing tailpiece
Data sheet RA-N radiator valves with integrated presetting and self-sealing tailpiece EN 215 Application Straight version Angle version Horizontal angle version All RA-N valve bodies can be used together
More informationCR Series. Special doors for clean room application
CR Series Special doors for clean room application The CR Series: Special doors for clean rooms An increasing number of defined standards require reliable special doors for clean room application, for
More informationGRAND OPENINGS. By UDI, Inc. Manufacturers of Elliptical and Radius Cased Opening Jamb Systems
GRAND OPENINGS By UDI, Inc Manufacturers of Elliptical and Radius Cased Jamb Systems GRAND OPENINGS BY UDI, INC Manufacturers of Elliptical and Radius Cased Jamb Systems Table of Contents Steps to Ordering
More informationTurbo Blowers. Combustion Excellence Since Features. Benefits
Turbo Blowers Features Integral molded scroll design Turbine bladed impeller Steel inlet guard Precisely balanced impellers eliminate vibration Complete line of available accessories for adapting to any
More informationChilled beam iq Star WEGA II
Chilled beam iq Star WEGA II Key features Ventilation Water Heating and cooling Adjustable induction Flow Pattern Control In option: Demand Controlled Ventilation, Pressure independent, Electrical heating,
More informationV5434T/H THREE-WAY ROTARY VALVE PN10 AND H-EXTENSION
V544T/H THREE-WAY ROTARY VALVE PN10 AND H-EXTENSION FEATURES PRODUCT DATA Chrome-plated plug for long life-span Optimized characteristics for supply water temperature control All around changeable rotary
More informationOperating Instructions for Cobra and Lynx Duct Leakage Testers
Operating Instructions for Cobra and Lynx Duct Leakage Testers Table of Contents Introduction Introduction... 2 Safety Precautions Safety Precautions.. 2 Prior to Testing System Preparation.. 4 Power Requirements...
More informationEstimating Highway Maintenance Work 2008
Purdue University Purdue e-pubs Indiana Local Technical Assistance Program (LTAP) Publications Indiana Local Technical Assistance Program (LTAP) 5-2008 Estimating Highway Maintenance Work 2008 Ohio Department
More informationSizing Enclosures for SCR Power Controllers
INTRODUCTION Application Note 1002 Sizing Enclosures for SCR Power Controllers Author - George A. Sites, AMETEK HDR Power Systems Most applications for SCR Power Controllers require some type of enclosure.
More informationMass Flow Controller (MFC) for Gases
Mass Flow Controller (MFC) for Gases Type 8713 can be combined with... Direct flow measurement by MEMS- Technology for nominal flow rates from 1 ml N /min to 8 l N /min (N 2 ) High accuracy and repeatability
More informationCentriflow Plus High-pressure plug fan - Technical Data
Centriflow Plus 3 High-pressure plug fan - Technical Data Contents General description...3 General survey chart...4 Design description Fan Impeller...5 Fan Inlet...5 base with base frame...5 Hub...5 Air
More informationSIZING AND CAPACITIES OF GAS PIPING
APPENDIX A (IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is adopted as part of the code.) A.1 General. To determine the size of piping used in a gas piping system, the following factors must
More informationTex-616-J, Construction Fabrics
Contents: Section 1 Overview... Section s...3 Section 3 Archived Versions...10 Texas Department of Transportation 1 06/00 1/07 Section 1 Overview Effective dates: June 000 December 007. Section 1 Overview
More informationKrantz Components. Multifunction Sail AVACS. Cooling and Heating Systems
Multifunction Sail AVACS Cooling and Heating Systems 2 AVACS Air Ventilation And Cooling System 3 System design Air diffuser box Air connection Sound absorbers (optional) Cooling element with heat conducting
More informationEclipse Extern-A-Therm Recuperators
Design Guide 540 3/9/2009 Eclipse Extern-A-Therm Recuperators Models 300 MA - 2500 MA Copyright Copyright 2007 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation
More informationHVAC Air Duct Leakage. Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA
HVAC Air Duct Leakage Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA Learning Objectives Understand the difference between System leakage and Duct leakage Understand
More informationAXIAL FLOW FANS GENERAL INFORMATION
ELTA IMPELLER RANGE AXIAL INTRODUTION TEST STANDARDS The Elta impeller ranges included in this catalogue have harnessed the latest technology in axial impeller design, resulting in enhanced pressure development,
More informationPressure Independent Control Series
Document No. 155-522 Pressure Independent Control Series Two-Way Cast Iron Flanged Bodies, ANSI 125 and 250 Description Siemens Pressure Independent Control Valves integrate three functions into a single
More informationBarcol-Air BRM Radiant Module
Barcol-Air BRM Radiant Module General The high capacity Radiant Cooling Module BRM is based on the principles of the radiant cooling technology. Due to the purpose designed profile and the geometry of
More informationGas Cylinder Cabinets
The fire resistant Maximum safety. Temperature increase of less than 50 K on the cylinder after 90 minutes according to EN 14470-2. G90 EN 14470-2 90 minutes max. 50 k increase of temperature FIRE CHAMBER
More informationDICTATOR Spring Rope Pulleys for the Closing of Sliding Doors
DICTATOR for the Closing of Sliding Doors Spring rope pulleys are a simple, efficient and cost-effective closing device for sliding doors. During the opening of the door the internal spring is tensioned
More informationBaffles and Traps Cryotrap
Baffles and Traps 362-6 Cryotrap Varian Low-Profile Water-Cooled Baffles combine 100% optical density with high conductance and unusually low overall height. They are especially useful in applications
More informationHow to specify a product. Process Sensors and Mechanical Instruments
How to specify a product Process Sensors and Mechanical Instruments Keep the overview. Here is some guideline information on how to specify our products. Intended as supplementary help to specification
More informationPRODUCT CONFIGURATOR AT mcr Monsun. smoke extraction and air supply axial-flow fans
PRODUCT CONFIGURATOR AT WWW.MERCOR.COM.P mcr Monsun smoke extraction and air supply axial-flow fans APPICATION mcr Monsun fans are designed to extract hot air, smoke and exhaust gases from fire-exposed
More informationACCESSORIES AND FLASHINGS FOR SANDWICH PANELS
CCESSORIES ND FLSHINGS FOR SNDWICH PNELS TECHNICL CTLOGUE www.balex.eu CCESSORIES and FLSHINGS for sandwich panels February 2014 The content of this folder does not constitute a commercial offer in the
More informationHorizontal Gratings. Pressure Locked and Electrofused Products. t:
Horizontal Gratings Pressure Locked and Electrofused Products t: 0131 441 1255 sales@langandfulton.co.uk www.langandfulton.co.uk D B A E GLOSSARY OF TERMS A - pitch of bearing bars (centre-to-centre distance
More informationPressure Reducing Valve DMV 755 set range: 1,0-9,0 bar
Pressure Reducing Valve DMV 755 set range:,0-9,0 bar Advantage pressure setting possible at any time, also during operation high reproducibility of the set pressure high level of operating safety and long
More informationKestrel Aluminium Systems Limited. Product Manual Section 10 Thermal Framing System. Manual Version
Kestrel luminium Systems Limited Product Manual Section 10 Manual Version 23.0.1 Kestrel luminium Systems Section 10.01 Product Specification 10.01.01 sheet 1 Product specification 10.01.01 sheet 2 Product
More informationA.M. The time between 12:00 midnight and 12:00 noon. Houghton Mifflin Co. 1 Grade 4 Unit 5
A.M. The time between 12:00 midnight and 12:00 noon. Houghton Mifflin Co. 1 Grade 4 Unit 5 bar graph A graph in which information is shown by means of rectangular bars. Favorite Sea Creature Sea Creature
More informationMeasuring range Δp (span = 100%) Pa
4.4/ RLE 5: Volume-flow controller, continuous How energy efficiency is improved Enables demand-led volume flow control for the optimisation of energy consumption in ventilation systems. Areas of application
More informationE 328 E 498 Tank top mounting Connection up to G1½ / -24 SAE and SAE 2 Nominal flow rate up to 600 l/min / gpm
Return-Suction Filters E 8 E 98 Tank top mounting Connection up to G½ / - SE and SE Nominal flow rate up to 6 l/min / 8. gpm Description pplication For operation in units with hydrostatic drives, when
More informationMass Flow Meter (MFM) for gases
Mass Flow Meter (MFM) for gases Type can be combined with Inline MFM for nominal flow rates from 25 l N /min to 1,500 l N /min; 1/4 to 3/4 High accuracy Fast settling time Fieldbus option Special version
More informationTable of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1
Table of contents A1 Design criteria 1 A1.1 Local thermal discomfort indices........................... 1 A2 Experiment set-up 3 A2.1 Equipment....................................... 3 A2.2 Test cases.......................................
More informationHydraulic Optimization Worksheet for MS Excel All Versions subsequent to 5.0
Hydraulic Optimization Worksheet for MS Excel All Versions subsequent to 5.0 1. Introduction. 2. Data Input. Header. Bit Information. Mud Information. Casing Program. P.D.M./Turbine. Drill String Design.
More informationThese products are available only in packs of 100 pieces
NYLON CABLE TIES SPECIFICATION Kompress Cable Ties are produced to comply with the requirements of Military Specification MIL-S 23190E and supplied in accordance with our ISO 9001 accreditation. They have
More informationCTG Certification Protocol -- Version 3.0 SUMMARY
Date of Test: Test Report Number: SUMMARY Date of Prior Certification: Certified by: Re-certification Due Date: Unit Description: Make : Model: Serial Number: Location: CERTIFIER INFORMATION Name: Client
More informationSIZING AND CAPACITIES OF GAS PIPING
APPENDIX A (IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is informative and is not part of the code. This appendix is an excerpt from the 2003 International Fuel Gas Code, coordinated with
More informationPROVIDING QUALITY SOLUTIONS FOR THE AUDIOMETRIC INDUSTRY
PROVIDING QUALITY SOLUTIONS FOR THE AUDIOMETRIC INDUSTRY PRODUCT OPTIONS AMB Portable Series: Booths consist of 2 or 3 inch panels with integrated ventilation in the roof and floor. AMB 410: Consists
More informationAutomatic balancing valves ASV
Automatic balancing valves ASV ASV-P ASV-PV ASV-PV ASV-PV ASV-I ASV-M 15-40 15-40 50 65-100 15-50 15-50 Description / Application ASV balancing valves are used for dynamic hydronic balance in heating and
More information