Keywords: Chilled beam, Thermal plume, Air diffusion, Draught risk

Size: px
Start display at page:

Download "Keywords: Chilled beam, Thermal plume, Air diffusion, Draught risk"

Transcription

1 Topic 6. Ventilation, infiltration and air distribution Impact of Heat Load Location and Strength on Air Flow Pattern with a Passie Chilled Beam System Risto Kosonen 1,*,Pekka Saarinen 2, Alex Hole 3 and Hannu Koskela 2 1 Halton Oy, Vantaa, Finland 2 Finnish Institute of Occupational Health, Turku, Finland 3 Arup, Sydney, Australia * Corresponding risto.kosonen@halton.com Keywords: Chilled beam, Thermal plume, Air diffusion, Draught risk SUMMARY A chilled beam is a source of natural conection, creating a flow of cold air directly into the occupied zone. Experiments hae been conducted in a mock up of an office room to study the air elocities in the occupied spaces. In addition, elocity profiles of a passie beam are registered with underneath heat loads when the cool and warm air flows interact. Experimental laboratory study shows that the underneath heat gains, een when no upward plume is generated and the dummy only affects as a flow obstacle, hae a significant effect on the elocity profile. Furthermore in an actual occupied office enironment, the thermal plumes and the supply air diffuser mix effectiely the whole air olume. The maximum air elocity measured was still below 0.25 m/s with the high heat gain of 16 W/m². The results demonstrate that a simplified analysis of an undisturbed conection flow can not accurately describe air moement and draught risk. INTRODUCTION The maximum elocities inside the occupied zone increase with a rising thermal load (Muller et al. 200) and the location and strength of the heat gain has a significant effect on air flow pattern (Kosonen et al. 2007). Thus, elocity profiles together with thermal comfort should be analyzed using heat load higher than 60 W/m 2. There are seeral international and local standards and guidelines that gie recommendations and propose design criteria for achieing good indoor enironment (ISO , EN , ASHRAE , CEN CR , etc.). Recommended alues for the mean air elocity, air temperature, relatie humidity, ertical temperature gradient and mean radiant temperature both for winter and summer conditions are listed in these documents. A model for local discomfort that predicts the percentage of dissatisfied due to draught was introduced by Fanger et al. (1988). An index called draught rating () index was deried as a function of mean air elocity, air temperature and turbulence intensity. The chilled beam system is an attractie solution to achiee good indoor air conditions in an energy efficient manner. A common design encompasses a combination of entilation air, distributed by mechanical means to a ceiling or floor diffuser, and mechanical cooling ia the passie chilled beam element integrated into a suspended ceiling. The passie battery type element itself is essentially a series of water tubes with fins. Cooled water circulation through the coil generates airflow across the beam by the natural buoyancy. Under undisturbed conditions, a flow of cold air is directly falling down in the occupied zone.

2 Experimental study of the elocity field generated by passie beams has been conducted in undisturbed conditions (Fredrikson el al. 2001). The study indicated that the air elocity can create draught with the specific cooling capacity higher than 200 W per linear metre of beam. As a rule of thumb, the REHVA guide (REHVA 2006) recommends a specific cooling capacity to be lower than 150 W/m when the beam is in an occupied zone, and up to 250 W/m when installed in the non-occupied zone. During the design phase, howeer, the location of the passie beam should be carefully considered. Basic principle is to aoid installation oer the working places. Neertheless, in many cases when the layout changes, it is possible that someone is sitting just below a passie beam. Therefore, more information is required about the actual air flow pattern in the occupied offices. In this paper, the results of the laboratory study on the effect of the underneath heat gains on the elocity profile of a passie beam are presented. Furthermore in a mock-up office, the air elocities are studied when thermal plumes and a supply air diffuser are introduced in the room space. METHODS The heat load used in the measurements comprised a PC and a human dummy, simulating an office situation. This load was supplemented by underfloor heating, if necessary, to attain the cooling power required. The heated floor then coered a much larger area than the load below the beam. The basic arrangement is shown in Fig. 1. (Saarinen et al. 2006). Two additional arrangements were also used. In one of them the heat load was shifted 0.5 m aside from the beam centre line, and in the other it was remoed altogether. The human dummy was constructed according to the standard DIN (DIN 1995), containing a description of a cooling load simulator. The dummy was heated electrically with the power of 90 W, whereupon, depending on the cooling power, of the heat loss was through conection. Moreoer, the dummy used in the experiments originally had three large holes on its flank, near the top surface. They had to be blocked, since the warm air blew horizontally out of them, when the dummy was under the chilled beam. Figure 1. Basic arrangement obeyed in most experimental setups. All measures are in millimeters. Vertical middle line (red) marks the position of the beam centre point.

3 A list of all the experimental setups measured is gien in Table 1. In the setups with a B affixed to the setup number, the load has been shifted 0.5 m aside (to the left in the scheme of Fig. 1), and an A tells that the load was in its normal position, but unheated. In setups 3, 9, and the load was remoed from under the beam. The dimensions of the beam were mm and of the heat exchanger mm. The difference between the cooling and heating powers is due to the leakage of heat through the surfaces of the test room. Table 1. Test setups measured in the research. A = load unheated, B = load shifted by 0.5 m. setup cooling cooling additional balance power PC + dummy power load (underfloor of passie display (cylinder) per linear m heating) beam [W] [W] [W] [W] [W] B A B A The flow field was measured on four horizontal planes at different heights between the beam and the load, and on a ertical plane below the beam centre line. The density of the measuring grid on each plane was cm cm. The elocity measurements were carried out by two direction sensitie ultrasonic anemometers, and the temperature field was always measured simultaneously, enabling calculation of the distribution of the draught rating. The measurement planes were scanned using a computerized measurement robot, coneying the sensors through the points of measurement. In each point there was a s waiting period to allow the swinging to damp out, followed by a measurement period of 60 s. Another test room (L x W x H = 3.6m x 3.6m x 3.3/2.8m) was used to simulate a real office (Hole and Kosonen 2006). In this test room, two passie beams (CPT /200) were installed aboe the perforated false ceiling (3195 mm from the floor leel). Three light fittings (each: 2x28 W/T5) and a swirl diffuser (TSR-160) were installed in the false ceiling at the leel of 2800 mm from the floor leel. The gross free area of the ceiling panels was 37 and the diameters of the perforation holes were 5mm. Close to the window wall, there was arranged an additional opening (300 mm) to improe the buoyancy effect, Fig. 2. In the basic case of 122 W/m 2, the heat loads were: two computers (260 W), two dummies (150 W), light fittings (168 W), warm window surface (35.0 o C and ~ 600 W) and an electrical foil (00 W) (size of 3.6 m x 1.5 m close to the window) on the floor. The used airflow rate and supply air temperature of the swirl diffuser were 35 L/s (2.7 L/s per m 2 ) at 13 o C. The inlet water temperature of the chilled beams was 15 o C. The requested cooling

4 capacity was arranged by modulating water flow rate of the chilled beams. The room air temperature was in the test cases between o C. Figure 2. Simulated office (workplace layout 1) and the cross-section of the room space. Two higher cooling capacity 153 W/m 2 and 16 W/m 2 were also studied. In the case of 153 W/m 2, two extra computers and dummies were installed. The highest cooling capacity (16 W/m 2 ) was arranged from the case of 153 W/m 2 by increasing the heat gain of the dummies. In this study, the effect of the location of the workplaces on the performance of the passie chilled beam system was also analyzed. One additional case without false ceiling was also measured to analyze the effect of the perforated ceiling panels on the air distribution. The cooling capacities and office layouts in the test cases are shown in Table 2. Table 2. Studied heat load and workplace layout cases. Case Room Water flow Heat loads Workplace (WP) layout: air rate (l/s) (W/m 2 ) :WP in the middle :WP close to the side wall :WP close to the window :WP in the middle 23. (no ceiling panels) :WP in the middle :WP in the middle Mean air elocity, air temperature and turbulence intensity were measured within the occupied zone at the locations of 0.1m, 0.2m, 0.5m, 1.1m, 1.5m and 1.8m aboe the floor. The measurement grid consisted altogether of 16 locations at each height (96 points in total), Fig. 2. Air flow elocities were measured with elocity sensor type Sensor HT 12 haing an accuracy of ± 1. The room air temperature, inlet water temperature, supply and exhaust air temperatures were measured with temperature sensors of type PT0 class A. The temperature sensors were shielded against radiation. Instantaneous alues of elocity and temperature were measured simultaneously. Measurements of elocity and temperature were time aeraged oer a period of 180 s.

5 RESULTS Contrary to the expectations, the plumes from the heat loads were not powerful enough to fight the downward flow from the beam. Instead the heated air was captured by the downward flow from the beam and no significant upward buoyancy force was generated. This was true een with low cooling powers, as can be seen from Fig. 3, showing the horizontal cross sections of z for the cooling power of 223 W. Only when the load was shifted (setups 1B and B), or when an extra load was added (setup 2), did an upward plume build up. 2.1 m 1.8 m 1.5 m 1.2 m ertical flow speed z setup No cooling power: W dummy: 90 W PC+dspl: 95 W Figure 3. Vertical component of the flow field at different heights in setup No... The positions of the dummy, PC, display, and the table hae been marked on the lowermost measurement plane (height 1.2 m). On the uppermost plane (height 2.1 m), the beam is outlined. The centre point of the beam has been marked by a red cross on each plane. Measurement grid ( cm cm) is also displayed

6 Figure shows that in the absence of the dummy the downward air elocity below the beam, 0.1 m aboe the default position of dummy top surface, was m/s with cooling powers W ( W/m). In the presence of the dummy the obtained z and alues were considerably smaller. When the dummy is present, it reduces the downward flow elocity cm aboe its top surface by m/s regardless of whether it is heated or not. Howeer, since the effect of the dummy on the flow seems to be based on its geometry rather than on its plume, its shape becomes important. Therefore, replacing the dummy by a real human, or a manikin, might result in considerably different results Air elocity z at cylinder axis, height 1.2 m warm load cold load shifted load load absent cooling power [W] Figure. Vertical air elocity [m/s] cm aboe the dummy top surface as a function of the cooling power. In case of shifted load (yellow triangles), the point of measurement is not shifted. In Fig 5, there are listings of the measured air elocity, temperature, turbulence intensity and draft rate profiles in the mock-up test case 1. The elocity profile reeals that the air is well mixed oer the whole occupied zone. Een with a heat gain of 122 W/m 2, the maximum air elocity was only 0.20 m/s. Also, the draft rate alues were at an acceptable leel. Changes in office layout had no effect on the performance of the air distribution. This is seen from the results of cases 2 and 3. The maximum air elocity was 0.20 m/s when the workplaces were located in the middle of the room, close to the side wall or close to the window. Also when the false ceiling was remoed (case ), the air elocities did not increase. In fact, the maximum elocity slightly reduced. When the cooling capacity was increased from 122 W/m 2 to W/m 2, the maximum air elocity was increased up to the alue of 0.23 m/s. Still, the draft rate alues were at acceptable leel: only in a couple of points - index was higher than 15. It should be noted that the typical limit of air elocity is set to 0.25 m/s during cooling season. Thus, the chilled beam concept studied does not exceed this international standard threshold for the air elocity een with the cooling capacities as high as W/m 2.

7 Height (m) () () () () () () Height (m) () () () () Height (m) () Figure 5. Measured air elocity, temperature, turbulence intensity and draft rate in case 1. The numbers on the top rows refer to the horizontal locations listed in Fig. 2. Table3. Measured air elocity and draft rate () in the test cases. Case Heat gain (W/m 2 ) Workplace location Middle Side Window Middle Middle Middle max ag max () ag () Number of point > Number of lines > DISCUSSION () () The draught rating is designed to be measured without the presence of human beings. Howeer, the occupants constitute a significant heat load, affecting the cooling power of the beam and the flow field in the room. The question then arises whether this heat load should be present during the measurement, and how far from the load surface the elocity measurements should be made. The results of this study suggest that when a cooled downward air flow dominates, it is distorted if measured less than cm away from the surface. Seeral tests were performed in order to establish the draught and heat gain performance of a mock up passie chilled beam installation under a number of scenarios. The results identify that within the range of these tests the draught rate () could be maintained below 20 een with relatiely high heat gains ( W/m 2 ). The measurement indicates that the influence of the mechanically introduced air supply ia swirl outlet diffusers together with thermal plumes has a profound effect on the air flow within the space. Similarly, adjustments to the internal layout of equipment produced little effect on the air moement. In all cases, the whole olume is fully mixed as demonstrated by the elocitiy measurements and smoke tests. There was no location in the occupied zone that exhibited excessiely high () () ()

8 elocities. The maximum elocity was approximately two times higher than aerage elocity in all cases. CONCLUSIONS It is apparent that the total performance is a combination of the influence of the cooling elements, air diffusion and thermal plumes of heat gains. Focusing on the performance of a chilled beam element in empty space will not gie the total iew. When the dummy is present, it reduces the downward flow elocity cm aboe its top surface by m/s. These tests found that under certain conditions a combination of cooled air supply through swirl outlet diffusers, and battery type passie chilled beams can proide room sensible cooling capacities of 120 W/m² and potentially up to 16 W/m² without exceeding the requirements of ISO7730. It is belieed that a mechanically introduced air supply together with thermal plumes plays a significant role in the deelopment of the elocity field within the space. ACKNOWLEDGEMENT The study is supported by Technology Agency of Finland (TEKES). REFERENCES ASHRAE Thermal Enironmental Conditions for Human Occupancy, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. CEN CR 1752, Ventilation for Buildings: Design Criteria for the Indoor Enironment. Brussels. European Committee for Standardization. DIN Chilled surfaces for rooms Part 1: Measuring of the performance with free flow Test rules (English ersion). Deutsche Institut für Normung. EN Indoor enironmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal enironment, lighting and acoustics. Fanger P. O., Meliko A. K., Hanzawa H., Ring J Air turbulence and sensation of draught, Energy and buildings, 12, pp Hole A and Kosonen, R. An experimental inestigation of a passie chilled beam system in sub-tropical conditions. WellBeing Indoors Clima June Helsinki Finland. Proceedings of Clima 2007 ISO Ergonomics of the thermal enironment- Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Fredriksen, J, Sandberg M and Moshfegh Experimental inestigation of the elocity field and airflow pattern generated by cooling ceiling beams. Building and Enironment 36 (2001) Kosonen R, Meliko A, Yordonoa B and Bozkho L. Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams. RoomVent 2007 th International Conference on Air Distribution in Rooms. Proceedings of Rooment 2007 Helsinki June REHVA.2006 Guidebook no.5. Chilled Beam Cooling. Federation of European Heating and Air-conditioning Associations. Saarinen P, Kosonen, R and Koskela H. Interaction of a passie chilled beam and underneath heat load. RoomVent 2007 th International Conference on Air Distribution in Rooms. Proceedings of Rooment 2007 Helsinki June 2007.

Thermal Conditions in a Simulated Office Environment with Convective and Radiant Cooling Systems

Thermal Conditions in a Simulated Office Environment with Convective and Radiant Cooling Systems Thermal Conditions in a Simulated Office Environment with Convective and Radiant Cooling Systems Panu Mustakallio #1, Zhecho Bolashikov *2, Kalin Kostov *3, Arsen Melikov *4, Risto Kosonen #5 # Halton

More information

Effect of airflow direction on human perception of draught

Effect of airflow direction on human perception of draught Effect of airflow direction on human perception of draught J. Toftum, G. Zhou, A. Melikov Laboratory of Indoor Environment and Energy Department of Energy Engineering Technical University of Denmark Abstract

More information

Interacting Turbulent Plumes in a Naturally Ventilated Enclosure

Interacting Turbulent Plumes in a Naturally Ventilated Enclosure International Journal of Ventilation ISSN 473-33 Volume 4 No 4 Interacting Turbulent Plumes in a Naturally Ventilated Enclosure P. F. Linden and N. B. Kaye Department of Mechanical and erospace Engineering,

More information

THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM

THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM P Jacobs *, WF de Gids Department of Building Physics Indoor Environment and Energy TNO Environment and Geosciences Delft, 2600 AA,

More information

CFD BENCHMARKING: HAMER HALL AUDITORIUM CASE STUDY

CFD BENCHMARKING: HAMER HALL AUDITORIUM CASE STUDY CFD BENCHMARKING: HAMER HALL AUDITORIUM CASE STUDY Anthony Scanlon and Anthony Calderone Aurecon, Australia anthony.scanlon@aurecongroup.com anthony.calderone@aurecongroup.com ABSTRACT This paper presents

More information

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1 Table of contents A1 Design criteria 1 A1.1 Local thermal discomfort indices........................... 1 A2 Experiment set-up 3 A2.1 Equipment....................................... 3 A2.2 Test cases.......................................

More information

Universities of Leeds, Sheffield and York

Universities of Leeds, Sheffield and York promoting access to White Rose research papers Universities of Leeds, Sheffield and York http://eprints.whiterose.ac.uk/ White Rose Research Online URL for this paper: http://eprints.whiterose.ac.uk/7819/

More information

Occupant body movement and seat occupancy rate for design of desk microenvironment

Occupant body movement and seat occupancy rate for design of desk microenvironment Downloaded from orbit.dtu.dk on: Dec 04, 2017 Occupant body movement and seat occupancy rate for design of desk microenvironment Melikov, Arsen Krikor; Pokora, Petr Published in: Proceedings of ROOMVENT

More information

vento specification sheet

vento specification sheet type purpose application linear diffuser 18mm diffuser for air distribution for false ceiling the diffuser is used for the supply and exhaust of cooled or heated air in facilities such as offices, shopping

More information

CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test

CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test Håkan O. Nilsson 1, Henrik Brohus 2 and Peter V. Nielsen 2 1 Department of Technology and Built Environment, University

More information

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT - 277 - NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT Iseler J., Heiser W. EAS GmbH, Karlsruhe, Germany ABSTRACT A numerical study of the flow behaviour

More information

E. Agu, M. Kasperski Ruhr-University Bochum Department of Civil and Environmental Engineering Sciences

E. Agu, M. Kasperski Ruhr-University Bochum Department of Civil and Environmental Engineering Sciences EACWE 5 Florence, Italy 19 th 23 rd July 29 Flying Sphere image Museo Ideale L. Da Vinci Chasing gust fronts - wind measurements at the airport Munich, Germany E. Agu, M. Kasperski Ruhr-University Bochum

More information

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood Statesville, NC Results of AM ASHRAE 11 Laboratory Fume Hood Performance Evaluations Venturi Hood January, 217 Prepared By: Exposure Control Technologies Inc. 231-C East Johnson Street Cary, NC 27513 Phone:

More information

EXTENDING THE PRINCIPLES OF IMPULSE VENTILATION IN TUNNELS TO APPLY TO SMOKE CONTROL IN CAR PARKS

EXTENDING THE PRINCIPLES OF IMPULSE VENTILATION IN TUNNELS TO APPLY TO SMOKE CONTROL IN CAR PARKS , Volume 6, Number, p.53-7, 004 EXTENDING THE PRINCIPLES OF IMPULSE VENTILATION IN TUNNELS TO APPLY TO SMOKE CONTROL IN CAR PARKS H.P. Morgan International Fire Consultants Ltd, UK B. Vanhoe and J-C. De

More information

AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES

AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES Andrea Frisque* Stantec Consulting, Vancouver BC V6B6A3, Canada Rowan, Williams, Davies & Irwin (RWDI), Vancouver, BC, V5Z 1K5, Canada**

More information

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM D Faulkner *, WJ Fisk, DP Sullivan and SM Lee Indoor Environment Dept., Lawrence Berkeley National Lab, Berkeley, CA, USA ABSTRACT

More information

Methods The experiments were carried out in the wind tunnel in the Air physics laboratory at the Engineering Centre Bygholm as shown in figure 1.

Methods The experiments were carried out in the wind tunnel in the Air physics laboratory at the Engineering Centre Bygholm as shown in figure 1. 1 Standardisation of test method for salt spreader: Air flow experiments Report 2: Visualization of airflow patterns by Jan S. Strøm, Consultant Aarhus University, Engineering Centre Bygholm, Test and

More information

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Grzegorz Kubicki, Ph.D. Department of Environmental Engineering, Warsaw University of Technology

More information

Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols

Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols Aalborg Universitet Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols Published in: Proceedings III The th international

More information

Krantz Components. Multifunction Sail AVACS. Cooling and Heating Systems

Krantz Components. Multifunction Sail AVACS. Cooling and Heating Systems Multifunction Sail AVACS Cooling and Heating Systems 2 AVACS Air Ventilation And Cooling System 3 System design Air diffuser box Air connection Sound absorbers (optional) Cooling element with heat conducting

More information

Development of virtual 3D human manikin with integrated breathing functionality

Development of virtual 3D human manikin with integrated breathing functionality SAT-9.2-2-HT-06 Development of virtual 3D human manikin with integrated breathing functionality Martin Ivanov Development of virtual 3D human manikin with integrated breathing functionality: The presented

More information

Barcol-Air BRM Radiant Module

Barcol-Air BRM Radiant Module Barcol-Air BRM Radiant Module General The high capacity Radiant Cooling Module BRM is based on the principles of the radiant cooling technology. Due to the purpose designed profile and the geometry of

More information

Influence of Persons' Movements on Ventilation Effectiveness Brohus, Henrik; Hyldig, Mikkel; Kamper, Simon; Vachek, Ulla Maria

Influence of Persons' Movements on Ventilation Effectiveness Brohus, Henrik; Hyldig, Mikkel; Kamper, Simon; Vachek, Ulla Maria Aalborg Universitet Influence of Persons' Movements on Ventilation Effectiveness rohus, Henrik; Hyldig, Mikkel; Kamper, Simon; Vachek, Ulla Maria Published in: Proceedings of Indoor Air 2008 Publication

More information

Development of a load model for men-induced loads on stairs

Development of a load model for men-induced loads on stairs Porto, Portugal, 30 June - 2 July 2014 A. Cunha, E. Caetano, P. Ribeiro, G. Müller (eds.) ISSN: 2311-9020; ISBN: 978-972-752-165-4 Development of a load model for men-induced loads on stairs Benjamin Czwikla

More information

ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL

ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL ANALYSIS OF HEAT TRANSFER THROUGH EXTERNAL FINS USING CFD TOOL B. Usha Rani 1 and M.E Thermal 2 1,2 Asst.Professor, Dadi Institute of Engineering and Technology, India Abstract-The rate of heat transfer

More information

Installation Effects on Ultrasonic Flow Meters for Liquids. Jan Drenthen - Krohne

Installation Effects on Ultrasonic Flow Meters for Liquids. Jan Drenthen - Krohne Installation Effects on Ultrasonic Flow Meters for Liquids Jan Drenthen - Krohne Jan G. Drenthen & Pico Brand ALTOSONIC 5 Installation effects on ultrasonic flow meters for liquids 1. Introduction 2. Meter

More information

Study on Fire Plume in Large Spaces Using Ground Heating

Study on Fire Plume in Large Spaces Using Ground Heating Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 226 232 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Study on Fire Plume in Large Spaces Using

More information

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR - 9 - AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR O Gorman S., Nuttall R., Purchase A. Parsons Brinckerhoff, Australia ABSTRACT Recent fire tests for tunnels

More information

Valve Lift Measurement for the Validation of a Compressor Simulation Model

Valve Lift Measurement for the Validation of a Compressor Simulation Model Purdue Uniersity Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 8 Vale Lift Measurement for the Validation of a Compressor Simulation Model Daniel Nagy Graz

More information

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012 Natural Ventilation using Ventilation shafts Multiple Interconnected Openings in a Ventilation Shaft Reduce the Overall Height of the Shaft While Maintaining the Effectiveness of Natural Ventilation ABHAY

More information

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE - 247 - AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE J D Castro a, C W Pope a and R D Matthews b a Mott MacDonald Ltd, St Anne House,

More information

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS 3 rd International Conference on Energy Systems and Technologies 16 19 Feb. 2015, Cairo, Egypt ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

More information

Bio-Effluents Tracing in Ventilated Aircraft Cabins

Bio-Effluents Tracing in Ventilated Aircraft Cabins Excerpt from the Proceedings of the COMSOL Conference 2009 Milan Bio-Effluents Tracing in Ventilated Aircraft Cabins Petrone G. *, Cammarata L., Cammarata G. Department of Industrial and Mechanical Engineering,

More information

Technical Note. Determining the surface tension of liquids by measurements on pendant drops

Technical Note. Determining the surface tension of liquids by measurements on pendant drops Technical Note Pendant Drop Measurements Technical note: TN316e Industry section: all Author: FT, TW Date: 12/2010 Method: Drop Shape Analyzer DSA100 Keywords: Methods, surface tension, interfacial tension,

More information

Technical Requirements for Rotor Blades Operating in Cold Climate

Technical Requirements for Rotor Blades Operating in Cold Climate Technical Requirements for Rotor Blades Operating in Cold Climate H. Seifert, DEWI Wilhelmshaen 1. Introduction Wind turbines are increasingly erected at inland sites with their cold climate conditions

More information

Air distribution systems Circular displacement outlet with adjustable damper VA-ZD...

Air distribution systems Circular displacement outlet with adjustable damper VA-ZD... Air distribution systems Circular displacement outlet with adjustable damper VA-ZD... DS 059 E 05.010/1 Construction design and function Preliminary remarks Displacement air outlets enable to extract pollutants

More information

Experimental Determination of Temperature and Pressure Profile of Oil Film of Elliptical Journal Bearing

Experimental Determination of Temperature and Pressure Profile of Oil Film of Elliptical Journal Bearing International Journal of Advanced Mechanical Engineering. ISSN 2250-3234 Volume 4, Number 5 (2014), pp. 469-474 Research India Publications http://www.ripublication.com Experimental Determination of Temperature

More information

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS Presented By: Sandra Dedesko University of Toronto Contributing Authors: Caleb Parker Kim Pressnail Marianne Touchie Dave DeRose Multi-Unit Residential

More information

SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG A SCALE MODEL OF THE LHC TUNNEL

SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG A SCALE MODEL OF THE LHC TUNNEL EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH European Laboratory for Particle Physics Large Hadron Collider Project LHC Project Report 684 SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG

More information

for Asia / Pacific Radial outlet RA-N3... DS 4134 AUS /

for Asia / Pacific Radial outlet RA-N3... DS 4134 AUS / for Asia / Pacific Radial outlet RA-N... DS AUS./ Radial outlet RA-N Preliary remarks KRANTZ KOMPONENTEN radial outlets of type RA-N have fixed radial vanes. They generate high-quality, diffuse supply

More information

An Indian Journal FULL PAPER. Trade Science Inc. Research on free throw shooting skills in basketball games ABSTRACT KEYWORDS

An Indian Journal FULL PAPER. Trade Science Inc. Research on free throw shooting skills in basketball games ABSTRACT KEYWORDS [Type text] [Type text] [Type text] ISSN : 0974-7435 Volume 10 Issue 0 BioTechnology 014 An Indian Journal FULL PAPER BTAIJ, 10(0), 014 [11799-11805] Research on free throw shooting skills in basketball

More information

WP2 Fire test for toxicity of fire effluents

WP2 Fire test for toxicity of fire effluents Pagina 3 di 89 TRA SFEU VTT 22.6.2009 v.2 WP2 Fire test for toxicity of fire effluents Task 2.1.2 Development of small-scale test method for fire effluents Step 1: Use of modeling Plans according to DoW:

More information

Fire ventilation Not any panacea

Fire ventilation Not any panacea /4/7 ire entilation Not any panacea Stefan Sensson /4/7 nd best moie eer? But, which is the best moie? /4/7 What is a fire and rescue operation? phenomenon in which one or more actions are initiated, coordinated

More information

XERO 8 ASSEMBLY AND OPERATING INSTRUCTIONS

XERO 8 ASSEMBLY AND OPERATING INSTRUCTIONS XERO 8 ASSEMBLY AND OPERATING INSTRUCTIONS General Instructions Vitra products are manufactured according to the latest technology and comply with alid rules and regulations. Neertheless, these products

More information

Different Air Distribution Principles in an Aircraft Cabin

Different Air Distribution Principles in an Aircraft Cabin Different Air Distribution Principles in an Aircraft Cabin Peter V. Nielsen Aalborg University pvn@civil.aau.dk 1 Different Air Distribution Principles in an Aircraft Cabin Introduction Mixing ventilation

More information

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage William M. Pitts, Jiann C. Yang, Kuldeep Prasad, and Marco Fernandez National Institute of Standards

More information

COST COMPARISON OF FSW AND MIG WELDED ALUMINIUM PANELS

COST COMPARISON OF FSW AND MIG WELDED ALUMINIUM PANELS COST COMPARISON OF FSW AND MIG WELDED ALUMINIUM PANELS Jukka Mononen 1 Mika Sirén 2 Hannu Hänninen 1 jukka.t.mononen@hut.fi mika.siren@vtt.fi hannu.hanninen@hut.fi 1) Helsinki University of Technology

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0081 ISBN: 978-83-7947-232-1 Effectiveness of an integrated air flow unit for an instrument table in an operating theatre Frank Behnke,

More information

Autodesk Moldflow Communicator Process settings

Autodesk Moldflow Communicator Process settings Autodesk Moldflow Communicator 212 Process settings Revision 1, 3 March 211. Contents Chapter 1 Process settings....................................... 1 Profiles.................................................

More information

Snowboard Course: The Optimization of the Halfpipe Shape. Abstract. Team # 10061

Snowboard Course: The Optimization of the Halfpipe Shape. Abstract. Team # 10061 Snowboard Course: 1 / 16 The Optimization of the Halfpipe Shape Abstract We determine the shape of the snowboard course, also known as halfpipe, to get the production of the maximum ertical air and the

More information

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage Experimental Study of Hydrogen Release Accidents in a Vehicle Garage Erik Merilo Mark Groethe James Colton Seiki Chiba Poulter Laboratory SRI International 3rd International Conference on Hydrogen Safety

More information

Use of Equivalent Building Dimensions (EBD) to Characterize Upwind Terrain Wake Effects for AERMOD

Use of Equivalent Building Dimensions (EBD) to Characterize Upwind Terrain Wake Effects for AERMOD Use of Equivalent Building Dimensions (EBD) to Characterize Upwind Terrain Wake Effects for AERMOD Paper # 425 100 th Annual Meeting of the Air & Waste Management Association June 2007 Ronald Petersen

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BYAENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2017 June 11(8): pages 408-415 Open Access Journal Design of Absorptive

More information

Free Surface Flow Simulation with ACUSIM in the Water Industry

Free Surface Flow Simulation with ACUSIM in the Water Industry Free Surface Flow Simulation with ACUSIM in the Water Industry Tuan Ta Research Scientist, Innovation, Thames Water Kempton Water Treatment Works, Innovation, Feltham Hill Road, Hanworth, TW13 6XH, UK.

More information

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration M. Burak Şamşul ITU AYOC 2014 - Milper Pervane Teknolojileri Company Profile MILPER is established in 2011 as a Research and Development

More information

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK ABSTRACT Ventilation stacks are becoming increasingly common in the design of naturally

More information

Hydrodynamics for Ocean Engineers Prof. A.H. Techet

Hydrodynamics for Ocean Engineers Prof. A.H. Techet 13.012 Hydrodynamics for Ocean Engineers Prof. A.H. Techet Archimedes s Principle and tatic tability I. Archimedes s Principle: The force on a body due to pressure alone (in the absence of iscous forces)

More information

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION Mads Mysen* 1, Axel Cablé 1, Peter G. Schild 1, and Kari Thunshelle 1 1 SINTEF Building and Infrastructure Forskningsveien

More information

FUNNELLING WINDOW: EXPERIMENTAL STUDY OF VENTILATION PERFORMANCE

FUNNELLING WINDOW: EXPERIMENTAL STUDY OF VENTILATION PERFORMANCE FUNNELLING WINDOW: EXPERIMENTAL STUDY OF VENTILATION PERFORMANCE Adolfo Gomez-Amador - Universidad de Colima Marcos Gonzalez-Trevizo - Universidad Michoacana de San Nicolas de Hidalgo Gonzalo Bojorquez-Morales

More information

A numerical Euler-Lagrange method for bubble tower CO2 dissolution modeling

A numerical Euler-Lagrange method for bubble tower CO2 dissolution modeling A numerical Euler-Lagrange method for bubble tower CO2 dissolution modeling Author: Daniel Legendre & Prof. Ron Zevenhoven Åbo Akademi University Thermal and Flow Engineering Laboratory Turku, Finland

More information

Figure 1. Outer dimensions of the model trucks.

Figure 1. Outer dimensions of the model trucks. 1 Standardisation of test method for salt spreader: Air flow experiments Report 3: Simulations of airflow patterns by Jan S. Strøm, Consultant Aarhus University, Engineering Centre Bygholm, Test and Development

More information

VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES

VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES Proceedings: Indoor Air 005 A SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES PH Zhang * Jacobs Civil, Inc. 60 Madison Avenue, 1 th Floor, NYC, NY10016, USA ABSTRACT This paper discusses indoor

More information

Sprinkler Protection for Cloud Ceilings. SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013

Sprinkler Protection for Cloud Ceilings. SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013 Sprinkler Protection for Cloud Ceilings SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013 Background Cloud ceilings are a popular architectural feature Lack of clear guidance in the code for sprinkler installation

More information

COMPUTATIONAL FLOW MODEL OF WESTFALL'S LEADING TAB FLOW CONDITIONER AGM-09-R-08 Rev. B. By Kimbal A. Hall, PE

COMPUTATIONAL FLOW MODEL OF WESTFALL'S LEADING TAB FLOW CONDITIONER AGM-09-R-08 Rev. B. By Kimbal A. Hall, PE COMPUTATIONAL FLOW MODEL OF WESTFALL'S LEADING TAB FLOW CONDITIONER AGM-09-R-08 Rev. B By Kimbal A. Hall, PE Submitted to: WESTFALL MANUFACTURING COMPANY September 2009 ALDEN RESEARCH LABORATORY, INC.

More information

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet:

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet: OXY Integral INTERCON ENTERPRISES INC Tel: 800 665 6655 Fax: 604 946 5340 E-Mail: sales@intercononline.com Internet: www.intercononline.com Manual Integral 2006 1 INDEX 2-3 PREFACE 4 INTRODUCTION 5 Principle

More information

Akasison Flow phenomena of a siphonic roof outlet

Akasison Flow phenomena of a siphonic roof outlet Akasison Flow phenomena of a siphonic roof outlet Ir. Marc Buitenhuis MTD Hydraulic research engineer Akatherm BV, Panningen, The Netherlands 06-01-2011 Abstract So far the investigations on siphonic roof

More information

Fire test of ventilated and unventilated wooden façades

Fire test of ventilated and unventilated wooden façades Fire test of ventilated and unventilated wooden façades Lars Boström, Charlotta Skarin, Mathieu Duny, Robert McNamee SP Technical Research Institute of Sweden SP Report 216:16 Fire test of ventilated and

More information

Improving the Effectiveness of LEV A HSL perspective

Improving the Effectiveness of LEV A HSL perspective Improving the Effectiveness of LEV A HSL perspective C J Saunders Health and Safety Laboratory Crown copyright 2013 www.hsl.gov.uk www.hsl.gov.uk An An Agency Agency of the of Health the Health and Safety

More information

Development of High-speed Gas Dissolution Device

Development of High-speed Gas Dissolution Device Development of High-speed Gas Dissolution Device Yoichi Nakano*, Atsushi Suehiro**, Tetsuhiko Fujisato***, Jun Ma**** Kesayoshi Hadano****, Masayuki Fukagawa***** *Ube National College of Technology, Tokiwadai

More information

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Analysis of Pressure Rise During Internal Arc Faults in Switchgear Analysis of Pressure Rise During Internal Arc Faults in Switchgear ASANUMA, Gaku ONCHI, Toshiyuki TOYAMA, Kentaro ABSTRACT Switchgear include devices that play an important role in operations such as electric

More information

Using the Models TA-460, PVM610, and PVM620 to Measure Pressure

Using the Models TA-460, PVM610, and PVM620 to Measure Pressure Using the Models TA-460, PVM610, and PVM620 to Measure Pressure Application Note AF-107 Models TA-460, PVM 610 and PVM 620 measure differential pressure, or in other words, the pressure difference between

More information

Krantz Components. Multifunction sail AVACS. Cooling and heating systems

Krantz Components. Multifunction sail AVACS. Cooling and heating systems Multifunction sail AVACS Cooling and heating systems DS 4170 E 01.2014 Preliminary remarks and construction design Preliminary remarks The multifunction sail AVACS is designed for use with plane metal

More information

excavation work and necessary for the exhalation of workers. After conducting the ventilation network analysis, the result should be checked whether t

excavation work and necessary for the exhalation of workers. After conducting the ventilation network analysis, the result should be checked whether t Abstract FEASIBILITY STUDY OF VENTILATION DESIGN FOR UNDERGROUND FACILITIES Naoki Katsumata 1, Ryoji Yahagi 2, Hiromi Kurosaki 2, Shigeru Kubota 1 Nuclear Waste Management Organization of Japan (NUMO)

More information

Procedure Instruction of program Pressurized Enclosure - Test Round 2017

Procedure Instruction of program Pressurized Enclosure - Test Round 2017 Procedure Instruction of program Pressurized Enclosure - Test Round 2017 Provider: Physikalisch-Technische Bundesanstalt Address: Bundesallee 100 38116 Braunschweig Country: Germany Place, date Braunschweig,

More information

Yasuyuki Hirose 1. Abstract

Yasuyuki Hirose 1. Abstract Study on Tsunami force for PC box girder Yasuyuki Hirose 1 Abstract In this study, a waterway experiment was performed in order to understand the influence of tsunami forms on tsunami forces acting on

More information

Design, Building and Teaching with a Hydrostatic and Buoyancy Apparatus

Design, Building and Teaching with a Hydrostatic and Buoyancy Apparatus Design, Building and Teaching with a Hydrostatic and Buoyancy Apparatus Mir M. Atiqullah and Norman Russell Southern Polytechnic State University Marietta, GA. ABSTRACT A typical Fluid Mechanics laboratory

More information

Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure

Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure Norbert Jendzelovsky 1,*, Roland Antal 1 and Lenka Konecna 1 1 STU in Bratislava, Faculty

More information

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars. Simply a question of better measurement SCHMIDT Flow Sensor SS 20.261 The cost-effective alternative in pressurised systems up to 10 bars. Compressed air technology Industrial processes A cost analysis

More information

Pulsation and Vibration Control Requirements in the Design of Reciprocating Compressorand Pump Installations

Pulsation and Vibration Control Requirements in the Design of Reciprocating Compressorand Pump Installations Purdue Uniersity Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1982 Pulsation and Vibration Control equirements in the Design of eciprocating Compressorand

More information

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental identification of thermal-moisture conditions in the indoor swimming pool

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental identification of thermal-moisture conditions in the indoor swimming pool Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0261 ISBN: 978-83-7947-232-1 Experimental identification of thermal-moisture conditions in the indoor swimming pool Piotr Ciuman 1,

More information

Postprint.

Postprint. http://www.diva-portal.org Postprint This is the accepted version of a paper presented at ASHRAE and AIVC IAQ 2016 Defining Indoor Air Quality: Policy, Standards and Best Practices, 12 14 September 2016,

More information

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS Chapter 65 EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS Ch.D. Taylor NIOSH/Pittsburgh Research Laboratory Pittsburgh, PA J.A. Zimmer NIOSH/Pittsburgh Research Laboratory

More information

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India)

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India) IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN(e) : 2278-1684, ISSN(p) : 2320 334X, PP : 45-49 www.iosrjournals.org Modeling, Optimization & Manufacturing of Vortex Tube and Application

More information

Experiment P18: Buoyant Force (Force Sensor)

Experiment P18: Buoyant Force (Force Sensor) PASCO scientific Physics Lab Manual: P18-1 Experiment P18: (Force Sensor) Concept Time SW Interface Macintosh file Windows file Newton's Laws 45 m 300/500/700 P18 P18_BUOY.SWS EQUIPMENT NEEDED CONSUMABLES

More information

Effect of clothing ventilation on thermal insulation and vapor resistance

Effect of clothing ventilation on thermal insulation and vapor resistance Effect of clothing ventilation on thermal insulation and vapor resistance Xiaoqun Dai 1 and George Havenith 2 1 Soochow University, College of Textile and Clothing Engineering, Suzhou, 2156, P. R. China

More information

Pendant Drop Measurements

Pendant Drop Measurements KRÜSS pplication Note TN316d Page 1 Pendant Drop Measurements pplication note: TN316d Industry section: all uthor: Dr. Tobias Winkler Date: December 2010 Method: Drop Shape nalysis System DS100 Drop Shape

More information

Sound scattering by hydrodynamic wakes of sea animals

Sound scattering by hydrodynamic wakes of sea animals ICES Journal of Marine Science, 53: 377 381. 1996 Sound scattering by hydrodynamic wakes of sea animals Dmitry A. Selivanovsky and Alexander B. Ezersky Selivanovsky, D. A. and Ezersky, A. B. 1996. Sound

More information

Lab # 03: Visualization of Shock Waves by using Schlieren Technique

Lab # 03: Visualization of Shock Waves by using Schlieren Technique AerE545 Lab # 03: Visualization of Shock Waves by using Schlieren Technique Objectives: 1. To get hands-on experiences about Schlieren technique for flow visualization. 2. To learn how to do the optics

More information

Development of Biomimicry Wind Louver Surface Design

Development of Biomimicry Wind Louver Surface Design International Proceedings of Chemical, Biological and Environmental Engineering, V0l. 93 (2016) DOI: 10.7763/IPCBEE. 2016. V93. 6 Development of Biomimicry Wind Louver Surface Design Jaepil Choi 1, Donghwa

More information

THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM

THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM Piotr Grzelecki Master Thesis on Indoor Environmental Engineering Aalborg University The Faculty of Engineering and Science

More information

TS1. Ultrasonic Tank Sender. Installation and Operating Instructions. For TS1 Firmware v3.8. Page 1 INST-TS1-V13 18/11/10

TS1. Ultrasonic Tank Sender. Installation and Operating Instructions. For TS1 Firmware v3.8. Page 1 INST-TS1-V13 18/11/10 TS1 Ultrasonic Tank Sender Installation and Operating Instructions For TS1 Firmware v3.8 Page 1 Table of Contents 1. FEATURES... 3 2. SPECIFICATIONS... 3 3. DIMENSIONS... 4 4. MOUNTING AND INSTALLATION...

More information

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS T. Gélain, C. Prévost Institut de Radioprotection et de Sûreté Nucléaire (IRSN), Saclay, France Abstract In order to better understand the risks due

More information

METRO System Design. Witt&Sohn AG Aug-11

METRO System Design. Witt&Sohn AG Aug-11 METRO System Design Content Purpose Comparison Metro Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary Purpose Presentation: Degree of Complexity of Metro Systems No

More information

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction Introduction A key task in commercial building HVAC design is determining outdoor ventilation airflow rates. In most jurisdictions in the United States, ventilation airflow rates must comply with local

More information

Workshop 1: Bubbly Flow in a Rectangular Bubble Column. Multiphase Flow Modeling In ANSYS CFX Release ANSYS, Inc. WS1-1 Release 14.

Workshop 1: Bubbly Flow in a Rectangular Bubble Column. Multiphase Flow Modeling In ANSYS CFX Release ANSYS, Inc. WS1-1 Release 14. Workshop 1: Bubbly Flow in a Rectangular Bubble Column 14. 5 Release Multiphase Flow Modeling In ANSYS CFX 2013 ANSYS, Inc. WS1-1 Release 14.5 Introduction This workshop models the dispersion of air bubbles

More information

THEORETICAL EVALUATION OF FLOW THROUGH CENTRIFUGAL COMPRESSOR STAGE

THEORETICAL EVALUATION OF FLOW THROUGH CENTRIFUGAL COMPRESSOR STAGE THEORETICAL EVALUATION OF FLOW THROUGH CENTRIFUGAL COMPRESSOR STAGE S.Ramamurthy 1, R.Rajendran 1, R. S. Dileep Kumar 2 1 Scientist, Propulsion Division, National Aerospace Laboratories, Bangalore-560017,ramamurthy_srm@yahoo.com

More information

Division of Occupational Safety and Health (Cal/OSHA) HEAT ILLNESS PREVENTION TRAINING

Division of Occupational Safety and Health (Cal/OSHA) HEAT ILLNESS PREVENTION TRAINING Diision of Occupational Safety and Health (Cal/OSHA) 2015 HEAT ILLNESS PREVENTION TRAINING 2015 Training Goals Reiew the regulatory language and heat illness preentie measures. Increase awareness and commitment

More information

Paper #: POWER

Paper #: POWER Proceedings of POWER2008 ASME Power 2008 July 22-24, 2008, Orlando, Florida, USA Paper #: POWER2008-60061 THE USE OF AN EDDY CURRENT INSPECTION OF BRASS TUBES IN A SURFACE CONDENSER TO PROVIDE A CONDITION

More information

An Experimental Performance Study of Vortex Tube Refrigeration System

An Experimental Performance Study of Vortex Tube Refrigeration System An Experimental Performance Study of Vortex Tube Refrigeration System Sankar Ram T. Department Of Industrial Refrigeration and Cryogenics T. K. M. College of Engineering Karicode, Kollam, Kerala sankarram9@gmail.com

More information