THE A10-TAUERN TUNNEL VENTILATION SYSTEM FROM A CONTRACTOR S PERSPECTIVE. (Experiences and lessons learned)

Size: px
Start display at page:

Download "THE A10-TAUERN TUNNEL VENTILATION SYSTEM FROM A CONTRACTOR S PERSPECTIVE. (Experiences and lessons learned)"

Transcription

1 THE A10-TAUERN TUNNEL VENTILATION SYSTEM FROM A CONTRACTOR S PERSPECTIVE. (Experiences and lessons learned) Van Vemden F, Hofstede W. Zitron Nederland B.V. 6 th Conference Tunnel Safety and Ventilation Graz April

2 Contents 1. Introduction 2. Design review of the ventilation system 3. Room- and installation limitations 4. Acceptance tests 5. Cross passage ventilation 6. Fan stall prevention 7. Contractual aspects 8. Local participation 9. Conclusions and recommendations 6 th Conference Tunnel Safety and Ventilation Graz April

3 Parties involved Customer: ASFINAG Bau Management GmbH Ventilation system design: FVT - Forschungsgesellschaft für Verbrennungskraftmaschinen und Thermodynamik m.b.h. Site supervision (Örtliche Bauaufsicht, ÖBA): IDS Beratende Ingenieure GmbH Contract supervision (Begleitende Kontrolle BK): Hopferwieser Consult Ziviltechniker GmbH Ventilation System review: ILF Beratende Ingenieure m.b.h. 6 th Conference Tunnel Safety and Ventilation Graz April

4 Ventilation system South Portal Cavern North Portal AS01 ZS01 AS02 AS03 AS04 ZS01 ZS03 ZS04 Title Q m3/s P Pa Pmot. KW AS AS AS AS ZS Fresh air impulse damper Fire damper Fresh air throttle opening Vertical duct damper ZS ZS ZS Switch over damper 6 th Conference Tunnel Safety and Ventilation Graz April

5 Design review Elements for discussion: 1. Installation of additional Fresh air impulse damper 2. Ventilation - and design concept in case of fire 3. Cross passage ventilation 6 th Conference Tunnel Safety and Ventilation Graz April

6 Fresh air impulse ventilation Percentile value Processing of the Pressure differences at the portals Processing of the Shaft Natural Draught 95- Percentile ZAMG Design (Planer) NP SP SP NP Shaft-Draught Up Shaft-Draught Down Pa Pa Pa Pa = 71 Pa x 48 (Traffic Area) = 3400 N Thrust (120 kw Jet fan Power) 6 th Conference Tunnel Safety and Ventilation Graz April

7 Room- and installation limitations 6000 AS-01 Exhaust 2140x2140 ø x 2140 Wire mesh (FMU) Exhaust 3000x3000 ø2522 Wire mesh 6 th Conference Tunnel Safety and Ventilation Graz April

8 Room- and installation limitations 6000 AS-01 Exhaust 2140x2140 ø x 2140 Wire mesh CFD calculations to optimize inlet and outlet shape (ILF) 6 th Conference Tunnel Safety and Ventilation Graz April

9 Room- and installation limitations (FMU) 2140x2140 ø x x3000 ø2522 Tauern Exhaust Fan AS01 (Impellerdiameter 2510 mm.) Volume Duct v P-dyn. Component m3/s m2. m/s Pa ζ [ - ] P Pa Optimum Duct lay-out Duct v P-dyn. m2. m/s Pa Inlet part: Screen 160 4,84 33,06 639,30 0,10 63,93 9,00 17,78 184,89 0,10 18,49 Inlet piece 160 4,84 33,06 639,30 0,05 31,97 9,00 17,78 184,89 0,09 16,64 Discharge duct / Diffuser: Inlet 160 3,38 47, ,22 3,38 47, ,22 Outlet 160 3,27 48, ,25 4,61 34,67 703,26 Efficiency / factor 160 0,15 12,90 0,15 91,34 Impuls losses 3>4 With innerpipe 160 3,71 43, ,28 5,05 31,67 586,87 Without innerpipe 160 4,84 33,06 639,30 60,89 6,18 25,88 391,87 20,13 Fan isolation dampe 160 3,71 43, ,28 0,25 272,07 9,00 17,78 184,89 0,25 46,22 Total Fan pressure losses 441,76 192,82 In- and outlet concrete duct losses (based on assumption of 1,5 x dynamic loss) 958,95 277,33 Total losses 1400,71 470,15 Fan Power at 85% efficiency 263,66 88,50 ζ [ - ] P Pa 6 th Conference Tunnel Safety and Ventilation Graz April

10 Room- and installation limitations CAVERN DIRECTION SALZBURG 6 th Conference Tunnel Safety and Ventilation Graz April

11 Room- and installation limitations CAVERN DIRECTION VILLACH 6 th Conference Tunnel Safety and Ventilation Graz April

12 Room- and installation limitations Cooling air ducts Tunnel Tube Sbg. Hydraulic & air measurement piping 6 th Conference Tunnel Safety and Ventilation Graz April

13 Acceptance tests 1. Leakage test 2. Flow measurements at different fire scenarios 3. Fire test 6 th Conference Tunnel Safety and Ventilation Graz April

14 Acceptance tests LEAKAGE TEST FAN M1 M2 V1 V2 Leakage Duct (v-duct) = v1 - v2 FAN M1 M2 V1 V2 Leakage Fire Dampers = v1 - v2 - v.duct Damper in open position Damper in closed position with foil closure M1 = Measuring section 1 >> V1 = Air flow M1 [m³/s] M2 = Measuring section 2 >> V2 = Air flow M2 [m³/s] Damper in closed position without foil closure 6 th Conference Tunnel Safety and Ventilation Graz April

15 Acceptance tests CAVERN FIRE TEST SOUTH PORTAL AL ZL Ventilation section 3 Ventilation section 4 A Duct damper, closed position Wall Natural draught A View A-A 6 th Conference Tunnel Safety and Ventilation Graz April

16 Acceptance tests Fire test Tunnel tube Sbg.: Block 142 & 354 Tunnel Tube Vil.: Block 150 & th Conference Tunnel Safety and Ventilation Graz April

17 Das Bild kann zurzeit nicht angezeigt werden. Cross passage ventilation Design Options 1. Speed control with pressure sensor and door switches (Tauern) 2. Overpressure damper 3. Overpressure opening or fire damper 6 th Conference Tunnel Safety and Ventilation Graz April

18 Cross passage ventilation Cross Passage AL ZL Cross passage fan in operation ZL AL RFB Salzburg Air supply RFB Villach Escape route Escape door Design data 1. Overpressure in the cross passage with both escape-doors closed: 50 Pa. 2. In case of one escape-door open (ca. 2 m2 open area) Airflow 5 m3/s (velocity 2,5 m/s.) 6 th Conference Tunnel Safety and Ventilation Graz April

19 Das Bild kann zurzeit nicht angezeigt werden. Cross passage ventilation Speed control of the fan(s) Pressure sensor and Door switches Advantage: - No overpressure damper Disadvantages - Accelerating and decelerating fans takes time - Control system necessary 6 th Conference Tunnel Safety and Ventilation Graz April

20 Cross passage ventilation System with overpressure damper 6 th Conference Tunnel Safety and Ventilation Graz April

21 Cross passage ventilation System with overpressure damper 6 th Conference Tunnel Safety and Ventilation Graz April

22 Cross passage ventilation System with overpressure damper 6 th Conference Tunnel Safety and Ventilation Graz April

23 Cross passage ventilation System with overpressure damper 6 th Conference Tunnel Safety and Ventilation Graz April

24 Cross passage ventilation System with overpressure damper 6 th Conference Tunnel Safety and Ventilation Graz April

25 Cross passage ventilation System with pressure relief opening or fire damper 6 th Conference Tunnel Safety and Ventilation Graz April

26 Cross passage ventilation System with pressure relief opening or fire damper 6 th Conference Tunnel Safety and Ventilation Graz April

27 Cross passage ventilation System with small (0,5 m2) overpressure damper and slide doors (Pmax=120 Pa) 6 th Conference Tunnel Safety and Ventilation Graz April

28 Fan stall prevention 6 th Conference Tunnel Safety and Ventilation Graz April

29 Fan stall prevention 6 th Conference Tunnel Safety and Ventilation Graz April

30 Commercial aspects Price escalation (ÖNORM B2111) Indices Labour: Baukostenindex Baunebengewerbe Split-up Lüftung und Klima 100% Product: Labour: Baukostenindex für Lüftung und Klima 60% Material: Großhandelspreisindex Eisen und Stahl 40% 6 th Conference Tunnel Safety and Ventilation Graz April

31 Commercial aspects Entwicklung Großhandelspreisindex Eisen und Stahl Großhandelspreisindex Jun 08 Jul 08 Aug 08 Sep 08 Oct 08 Nov 08 Dec 08 Jan 09 Feb 09 Monat Mar 09 Apr 09 May 09 Jun 09 Jul 09 Aug 09 Sep Eisen und Stahl Sonstiges Lohn 6 th Conference Tunnel Safety and Ventilation Graz April

32 Commercial aspects Example: Price basis 0-date June 2008 Due date Sept Labour: 127,78 132,69 Others: Labour: 130,02 138,5 Material: 174,6 94,2 Price Splitup Po without Lo / Mo Ldd / Mdd Price factor Pdd with % esc. % esc. % labour Product: 80 Product split-up Labour Material th Conference Tunnel Safety and Ventilation Graz April

33 Local Participation 1. Facilitating and assisting in local assembly. 2. Supply of steel construction work. 3. Education of local employees / staff. 4. Local handling of service- and maintenance work. 5. A quick response time in case of failure or damage. 6 th Conference Tunnel Safety and Ventilation Graz April

34 Local Participation 6 th Conference Tunnel Safety and Ventilation Graz April

35 Conclusions, Recommendations 1. Design review The design review has to take place immediately after contract award to cover for possible consequences in time. 2. Fan room and duct dimensions Allowing for sufficient space for fans and ventilation components will reduce capital cost and energy consumption. 3. Acceptance tests Carrying out site tests is not only required to prove system performance but can also reveal further optimisation possibilities. 4. Cross passage ventilation More attention should be given to the response time for pressurizing cross passages and the control thereof. 5. Price escalation Customers may, in co-operation with contractors, allow for limits in price variation to limit overall economic risk for longer term contracts. 6. Local Participation Local participation contributes to local interest and substantial reduction of cost for travelling and lodging. 6 th Conference Tunnel Safety and Ventilation Graz April

THE A10-TAUERN TUNNEL VENTILATION SYSTEM FROM A CONTRACTOR S PERSPECTIVE.

THE A10-TAUERN TUNNEL VENTILATION SYSTEM FROM A CONTRACTOR S PERSPECTIVE. - 236 - THE A10-TAUERN TUNNEL VENTILATION SYSTEM FROM A CONTRACTOR S PERSPECTIVE. (Experiences and lessons learned) Van Vemden F, Hofstede W. Zitron Nederland B.V. ABSTRACT In recent years, numerous existing

More information

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS* COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun Jul

More information

OPTIMISATION OF VENTILATION IN THE CASE OF A FIRE IN ROAD TUNNELS

OPTIMISATION OF VENTILATION IN THE CASE OF A FIRE IN ROAD TUNNELS - 51 - OPTIMISATION OF VENTILATION IN THE CASE OF A FIRE IN ROAD TUNNELS ABSTRACT Stosch R. 1, Wehner M. 1, Brandt R. 2 HBI HAERTER AG, Tunnel Ventilation Heidenheim 1, D and Zurich 2, CH The control of

More information

THE TÚNEL LA LÍNEA - A CHALLENGE FOR VENTILATION AND SAFETY

THE TÚNEL LA LÍNEA - A CHALLENGE FOR VENTILATION AND SAFETY - 263 THE TÚNEL LA LÍNEA - A CHALLENGE FOR VENTILATION AND SAFETY Mario Glessig, Gerhard Plank, Geoconsult, Salzburg, Austria, Karl Pucher, Technische Universität Graz, Institut für VKM und Thermodynamik,

More information

THE TUNNELS IN GUADARRAMA FOR THE HIGH SPEED RAILWAY

THE TUNNELS IN GUADARRAMA FOR THE HIGH SPEED RAILWAY THE TUNNELS IN GUADARRAMA FOR THE HIGH SPEED RAILWAY MAP GUADARRAMA TUNNELS THE TUNNELS IN GUADARRAMA FOR THE HIGH SPEED RAILWAY The tunnels in Guadarrama for the high speed train (AVE) entered into service

More information

VENTILATION OF PROTECTED AREAS IN ROAD TUNNELS

VENTILATION OF PROTECTED AREAS IN ROAD TUNNELS - 187 - VENTILATION OF PROTECTED AREAS IN ROAD TUNNELS ABSTRACT Zumsteg F., Steinemann U. US+FZ Beratende Ingenieure, CH-5600 Lenzburg P. Wildi Civil Eng. Dept. Canton Grisons, CH-7000 Chur During the

More information

FROM THE CLASSICAL FIRE FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE GAS COOLING TAKING GLEINALMTUNNEL AS AN EXAMPLE; PART II

FROM THE CLASSICAL FIRE FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE GAS COOLING TAKING GLEINALMTUNNEL AS AN EXAMPLE; PART II - 131 - FROM THE CLASSICAL FIRE FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE GAS COOLING TAKING GLEINALMTUNNEL AS AN EXAMPLE; PART II Kern H. AQUASYS Technik GmbH, Linz Austria ABSTRACT Traditionally fire

More information

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT - 277 - NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT Iseler J., Heiser W. EAS GmbH, Karlsruhe, Germany ABSTRACT A numerical study of the flow behaviour

More information

vento specification sheet

vento specification sheet type purpose application linear diffuser 18mm diffuser for air distribution for false ceiling the diffuser is used for the supply and exhaust of cooled or heated air in facilities such as offices, shopping

More information

Appendix FRANCE Lyon Croix-Rousse Tunnel

Appendix FRANCE Lyon Croix-Rousse Tunnel Appendix 2.9 - FRANCE Lyon Croix-Rousse Tunnel 1. SUMMARY A NEW MULTIMODAL TUNNEL The Croix-Rousse tunnel is located in Lyons (France). The City of Lyons has about 475.000 inhabitants with 1,31 million

More information

2018 HR & PAYROLL Deadlines

2018 HR & PAYROLL Deadlines th (by payment date) EPAF 3rd PARTY FEEDS WTE Approval 2018 HR & PAYROLL s Normal Payroll day s 2017 B1-26 3 * 13-Dec-17 15-Dec-17 n/a n/a n/a 28-Dec-17 29-Dec-17 11:00 AM 16-Dec-2017 29-Dec-2017 JAN 2018

More information

Utility Debt Securitization Authority 2013 T/TE Billed Revenues Tracking Report

Utility Debt Securitization Authority 2013 T/TE Billed Revenues Tracking Report Utility Debt Securitization Authority 2013 T/TE Billed Revenues Tracking Report Billing Budgeted Billed Dollar Percent Month Revenues Revenues Variance Variance Jan 2018 11,943,180.68 12,697,662.47 754,481.79

More information

THE INFLUENCE OF PRESSURE GRADIENTS ON VENTILATION DESIGN SPECIAL FOCUS ON UPGRADING LONG TUNNELS

THE INFLUENCE OF PRESSURE GRADIENTS ON VENTILATION DESIGN SPECIAL FOCUS ON UPGRADING LONG TUNNELS - 90 - THE INFLUENCE OF PRESSURE GRADIENTS ON VENTILATION DESIGN SPECIAL FOCUS ON UPGRADING LONG TUNNELS Sturm P.J., Beyer M., Bacher M., Schmölzer G. Graz University of Technology, Austria ABSTRACT In

More information

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1 OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL Rehan Yousaf 1, Oliver Scherer 1 1 Pöyry Infra Ltd, Zürich, Switzerland ABSTRACT Gotthard Base Tunnel with its 57 km

More information

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Yunlong (Jason) Liu, PhD, PE HNTB Corporation Sean Cassady, FPE HNTB Corporation Abstract Extraction

More information

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN George Feng, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga, Ontario Vadim Akishin, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga,

More information

SGA REDUCTION OF PA & ID FAN LOADING

SGA REDUCTION OF PA & ID FAN LOADING SGA REDUCTION OF PA & ID FAN LOADING Project: Reduction of PA and ID fan loading Baseline: 1. PA Fan 1265 KW 2.ID Fan 1844 KW Target: 1. PA Fan 1215 KW 2.ID Fan 1800 KW Resources - Team Members Name Role

More information

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS - 56 - CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS Gloth O., Rudolf A. ILF Consulting Engineers Zürich, Switzerland ABSTRACT This article investigates the

More information

VENTILATION AND ESCAPE FACILITIES FOR SHORT CUT-AND- COVER URBAN TUNNELS

VENTILATION AND ESCAPE FACILITIES FOR SHORT CUT-AND- COVER URBAN TUNNELS - 213 - VENTILATION AND ESCAPE FACILITIES FOR SHORT CUT-AND- COVER URBAN TUNNELS M. Bettelini, S. Rigert Amberg Engineering Ltd., Regensdorf-Watt, Switzerland ABSTRACT Cut and cover tunnels or enclosures

More information

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars. Simply a question of better measurement SCHMIDT Flow Sensor SS 20.261 The cost-effective alternative in pressurised systems up to 10 bars. Compressed air technology Industrial processes A cost analysis

More information

METRO System Design. Witt&Sohn AG Aug-11

METRO System Design. Witt&Sohn AG Aug-11 METRO System Design Content Purpose Comparison Metro Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary Purpose Presentation: Degree of Complexity of Metro Systems No

More information

Farm Energy IQ. Wind Energy on Farms. Objectives of this Module. How windy is it? How windy is it? How windy is it? 2/16/2015

Farm Energy IQ. Wind Energy on Farms. Objectives of this Module. How windy is it? How windy is it? How windy is it? 2/16/2015 Farms Today Securing Our Energy Future Ed Johnstonbaugh, Penn State Extension Objectives of this Module At the conclusion of this module, you should: Understand wind requirements for power generation Be

More information

INNCOM SYSTEM MONITORING MARRIOT HOTEL DOWNTOWN PHILADELPHIA, PA. Report 9. July 2, CH2M HILL Project No

INNCOM SYSTEM MONITORING MARRIOT HOTEL DOWNTOWN PHILADELPHIA, PA. Report 9. July 2, CH2M HILL Project No INNCOM SYSTEM MONITORING MARRIOT HOTEL DOWNTOWN PHILADELPHIA, PA Report 9 CH2M HILL Project No. 421631 1. PURPOSE The purpose of this report is to present observations of the Inncom system operation in

More information

COMPLEX COMMISSIONING AND QUANTITATIVE TESTING OF THE GOTTHARD BASE TUNNEL VENTILATION SYSTEM

COMPLEX COMMISSIONING AND QUANTITATIVE TESTING OF THE GOTTHARD BASE TUNNEL VENTILATION SYSTEM - 323 - COMPLEX COMMISSIONING AND QUANTITATIVE TESTING OF THE GOTTHARD BASE TUNNEL VENTILATION SYSTEM M. Viertel, Ch. Brander, J. Badde, M. Poloni Pöyry Switzerland Ltd., Switzerland ABSTRACT The new Gotthard

More information

A COMPARATIVE STUDY OF MIX FLOW PUMP IMPELLER CFD ANALYSIS AND EXPERIMENTAL DATA OF SUBMERSIBLE PUMP

A COMPARATIVE STUDY OF MIX FLOW PUMP IMPELLER CFD ANALYSIS AND EXPERIMENTAL DATA OF SUBMERSIBLE PUMP IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN 2321-8843 Vol. 1, Issue 3, Aug 2013, 57-64 Impact Journals A COMPARATIVE STUDY OF MIX FLOW PUMP IMPELLER CFD ANALYSIS

More information

Personnel Benchmarking Author: Ed Rehkopf

Personnel Benchmarking Author: Ed Rehkopf Author: Ed Rehkopf 2009 Club Resources International Table of Contents Background.................................. 1 Purpose.................................... 1 Sources of Information............................

More information

Progress Report on the Design and Planning of an Infrastructure Improvement Project for the Sunnyside TIF District (Phase II)

Progress Report on the Design and Planning of an Infrastructure Improvement Project for the Sunnyside TIF District (Phase II) Presentation to the CNRC Board of Directors Regular Meeting March 11, 2015 1 Agenda Preferred Alternate Refinement for University Avenue, 3rd Street, and Beverly Avenue Intersection Improvements validate

More information

Tunnel Ventilation The Actual State of the Art

Tunnel Ventilation The Actual State of the Art Tunnel Ventilation The Actual State of the Art Design à What has to be installed? à Equipment and its layout à Calculations To a achieve a desired state under defined design conditions à Subject to Guidelines

More information

SWISS reports stable load factors

SWISS reports stable load factors SWISS Corporate Communications Phone: +41 (0)848 773 773 Fax: +41 (0)44 564 2127 communications@swiss.com SWISS.COM Media release Zurich Airport, October 10, 2008 SWISS reports stable load factors SWISS

More information

Evaluation of the optimum conditions for a local ventilation system in connection with the mine ventilation network

Evaluation of the optimum conditions for a local ventilation system in connection with the mine ventilation network Underground Mining Technology 2017 M Hudyma & Y Potvin (eds) 2017 Australian Centre for Geomechanics, Perth, ISBN 978-0-9924810-7-0 https://papers.acg.uwa.edu.au/p/1710_55_lee/ Evaluation of the optimum

More information

1 PEW RESEARCH CENTER

1 PEW RESEARCH CENTER 1 SEPTEMBER 2018 POLITICAL SURVEY FINAL TOPLINE SEPTEMBER 18-24, 2018 N=1,754 QUESTIONS 1-2, 7-8, 11-13, 28 PREVIOUSLY RELEASED NO QUESTIONS 3-6, 9-10, 14-27, 29-32, 34-43, 47-49 QUESTION 33 HELD FOR FUTURE

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES s of the IGF Code CONTENTS GF1 Test for gas fuel tank s high level alarm Rev.1 July 2017 GF2 Ship Steel Protection against Liquefied Gas Fuel (Part

More information

CALMO

CALMO ---------------------------------------------------- Sound attenuator with recessed connection for rectangular ducts ---------------------------------------------------------------------- GENERAL is, due

More information

Financial Project ID No(s).: and ETDM No(s).: and 14181

Financial Project ID No(s).: and ETDM No(s).: and 14181 Palm Beach Metropolitan Planning Organization (MPO) Presentation I-95 at Boynton Beach Boulevard Interchange and I-95 at Gateway Boulevard Interchange Project Development and Environment Study Palm Beach

More information

Performance Evaluation of the Wavestar Prototype

Performance Evaluation of the Wavestar Prototype Performance Evaluation of the Wavestar Prototype Morten Kramer, R&D engineer, Wave Star A/S Laurent Marquis, Head of Development, Wave Star A/S Peter Frigaard, Head of Civil Engineering Department, Aalborg

More information

Wisconsin 511 Traveler Information Annual Usage Summary January 3, Wisconsin 511 Phone Usage ( )

Wisconsin 511 Traveler Information Annual Usage Summary January 3, Wisconsin 511 Phone Usage ( ) Wisconsin 511 Traveler Information 211 Annual Usage Summary January 3, 212 Overall to-date Summary 36 months of operation 1,16,63 total calls the 1 Million mark was passed on December 3, 212 3,627,527

More information

Appendix ITALY Valsassina Tunnel near Lecco (Lombardy)

Appendix ITALY Valsassina Tunnel near Lecco (Lombardy) Appendix 2.12 - ITALY Valsassina Tunnel near Lecco (Lombardy) 1. SUMMARY The Valsassina tunnel is located along the National Road 36 (SS36), from Milan towards Valsassina in the town of Lecco with about

More information

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE - 247 - AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE J D Castro a, C W Pope a and R D Matthews b a Mott MacDonald Ltd, St Anne House,

More information

THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM

THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM P Jacobs *, WF de Gids Department of Building Physics Indoor Environment and Energy TNO Environment and Geosciences Delft, 2600 AA,

More information

TUNNEL KASTELEC - PLANING, REALISATION, TESTING, EXPERIENCES

TUNNEL KASTELEC - PLANING, REALISATION, TESTING, EXPERIENCES - 212 - TUNNEL KASTELEC - PLANING, REALISATION, TESTING, EXPERIENCES ABSTRACT prof.dr. Jurij MODIC dr. S. Muhič, dr. C. Arkar Faculty of Mechanical Engineering Ljubljana, Slovenia Slovenia is among the

More information

Air distribution systems Circular displacement outlet with adjustable damper VA-ZD...

Air distribution systems Circular displacement outlet with adjustable damper VA-ZD... Air distribution systems Circular displacement outlet with adjustable damper VA-ZD... DS 059 E 05.010/1 Construction design and function Preliminary remarks Displacement air outlets enable to extract pollutants

More information

Nasdaq Dubai AED TRADING HOLIDAYS AND SETTLEMENT CALENDAR 2018 For Equities Outsourced to the DFM (T+2)

Nasdaq Dubai AED TRADING HOLIDAYS AND SETTLEMENT CALENDAR 2018 For Equities Outsourced to the DFM (T+2) NasdaqDubai Circular No: 14 /2018 Date of Issue: 13 March 2018 Date of Expiry : Upon issue of replacement Circular Nasdaq Dubai AED TRADING HOLIDAYS AND SETTLEMENT CALENDAR 2018 For Equities Outsourced

More information

TRANSCRITICAL CO 2 IN AUSTRALIAN SUPERMARKETS CONTINUED SUCCESS. Mike Baker Baker Refrigeration M. IE Aust, C P Eng, M. AIRAH

TRANSCRITICAL CO 2 IN AUSTRALIAN SUPERMARKETS CONTINUED SUCCESS. Mike Baker Baker Refrigeration M. IE Aust, C P Eng, M. AIRAH TRANSCRITICAL CO 2 IN AUSTRALIAN SUPERMARKETS CONTINUED SUCCESS Mike Baker Baker Refrigeration M. IE Aust, C P Eng, M. AIRAH Transcritical is here! Transcritical is here! 14 x AJ Baker installs across

More information

Appendix FRANCE Annecy Tunnel Courier

Appendix FRANCE Annecy Tunnel Courier Appendix 2.7 - FRANCE Annecy Tunnel Courier 1. TRANSIT TUNNEL AND ACCESS TO UNDERGROUND PARKING LOTS The Courier tunnel is located in Annecy (France), a city of about 55,000 inhabitants and the centre

More information

The routine maintenance and inspection of local exhaust ventilation (LEV)

The routine maintenance and inspection of local exhaust ventilation (LEV) The routine maintenance and inspection of local exhaust ventilation (LEV) This document details the standards for inspection and maintenance that should be achieved for all local exhaust ventilation owned

More information

Farm Energy IQ. Farms Today Securing Our Energy Future. Wind Energy on Farms

Farm Energy IQ. Farms Today Securing Our Energy Future. Wind Energy on Farms Farm Energy IQ Farms Today Securing Our Energy Future Wind Energy on Farms Farm Energy IQ Wind Energy on Farms Ed Johnstonbaugh, Penn State Extension Objectives of this Module At the conclusion of this

More information

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR - 9 - AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR O Gorman S., Nuttall R., Purchase A. Parsons Brinckerhoff, Australia ABSTRACT Recent fire tests for tunnels

More information

GAZIFÈRE INC. Prime Rate Forecasting Process 2015 Rate Case

GAZIFÈRE INC. Prime Rate Forecasting Process 2015 Rate Case Overview A consensus forecast is used to estimate the prime rate charged by commercial banks. As the prime rate is subject to competitive pressures faced by individual lenders and is set on an individual

More information

A18W35_MASE 130_F_EN MANUAL

A18W35_MASE 130_F_EN MANUAL A18W_MASE 10_F_EN MANUAL CONTENTS 1 Identification 1.1 Manufacturer 1.2 Product name 1. Year of manufacture 1. Area of use 2 Technical specification 2.1 Design 2.2 Function 2. Technical data 2. Security

More information

TUNNEL SAFETY BY VENTILATION AN ILLUSION?

TUNNEL SAFETY BY VENTILATION AN ILLUSION? - 5 - TUNNEL SAFETY BY VENTILATION AN ILLUSION? Zumsteg F. 1, Steinemann U. 1, Joseph C. 2 1 US+FZ Consultant Engineers, Lenzburg, Switzerland 2 Federal Roads Office (FEDRO), Berne, Switzerland ABSTRACT

More information

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations Grzegorz Kubicki, Ph.D. Department of Environmental Engineering, Warsaw University of Technology

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

MODIFICATION OF THE LHC VENTILATION SYSTEM

MODIFICATION OF THE LHC VENTILATION SYSTEM MODIFICATION OF THE LHC VENTILATION SYSTEM M. Nonis EN/CV INTRODUCTION The aim of the present document is to review the current LHC ventilation configuration and evaluate the need to modify part of the

More information

ARCHIVED. Compliance Document for New Zealand Building Code Clause G11 Gas as an Energy Source. Prepared by the Department of Building and Housing

ARCHIVED. Compliance Document for New Zealand Building Code Clause G11 Gas as an Energy Source. Prepared by the Department of Building and Housing Compliance Document for New Zealand Building Code Clause G11 Gas as an Energy Source Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration M. Burak Şamşul ITU AYOC 2014 - Milper Pervane Teknolojileri Company Profile MILPER is established in 2011 as a Research and Development

More information

NASDAQ DUBAI TRADING HOLIDAYS AND SETTLEMENT CALENDAR 2018 For Equities Outsourced to the DFM (T+2)

NASDAQ DUBAI TRADING HOLIDAYS AND SETTLEMENT CALENDAR 2018 For Equities Outsourced to the DFM (T+2) Nasdaq Dubai Circular No : 71/17 Date of Issue : 24 December 2017 Date of Expiry : Upon issue of replacement Circular NASDAQ DUBAI TRADING HOLIDAYS AND SETTLEMENT CALENDAR 2018 For Equities Outsourced

More information

High Performance BSP Dial Up Pattern Pressure Reducing Valve

High Performance BSP Dial Up Pattern Pressure Reducing Valve See our full range online at: www.vip-ltd.co.uk High Performance BSP Dial Up Pattern Pressure Reducing Valve VIP Product Code 31/0103 FUNCTION Pressure reducing valves are devices which, when installed

More information

Gas Pressure Regulator HON 300

Gas Pressure Regulator HON 300 Product information serving the gas industry worldwide Applications, characteristics, technical data Applications direct acting gas pressure regulator, for systems in accordance with DVGW working instruction

More information

On the design and control of complex tunnel ventilation systems applying the HIL tunnel simulator

On the design and control of complex tunnel ventilation systems applying the HIL tunnel simulator On the design and control of complex tunnel ventilation systems applying the HIL tunnel I. R. Riess and P. Altenburger HBI Haerter Ltd Consulting Engineers, Switzerland P. Sahlin Equa Simulation AB, Sweden

More information

Gas Pressure Regulator HON 200

Gas Pressure Regulator HON 200 Product information serving the gas industry worldwide Applications, characteristics, technical data Application Gas supply to municipal, industrial and individual consumers Regulator for low-load rails

More information

UNIVERSITY OF CALIFORNIA Economics 134 DEPARTMENT OF ECONOMICS Spring 2018 Professor David Romer

UNIVERSITY OF CALIFORNIA Economics 134 DEPARTMENT OF ECONOMICS Spring 2018 Professor David Romer UNIVERSITY OF CALIFORNIA Economics 134 DEPARTMENT OF ECONOMICS Spring 2018 Professor David Romer LECTURE 2 OVERVIEW OF THE GREAT DEPRESSION January 22, 2018 I. THE 1920S A. GDP growth and inflation B.

More information

December 25 Christmas Day May 21 Victoria Day December 26 Boxing Day July 1 Canada Day (stat: Mon. July 2)

December 25 Christmas Day May 21 Victoria Day December 26 Boxing Day July 1 Canada Day (stat: Mon. July 2) ACADEMIC SCHEDULE 2017 2018 2017 2018 August 7 BC Day January 1 New Year s Day September 4 Labour Day February 12 Family Day (BC) October 9 Thanksgiving Day March 30 Good Friday November 11 Remembrance

More information

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION Mads Mysen* 1, Axel Cablé 1, Peter G. Schild 1, and Kari Thunshelle 1 1 SINTEF Building and Infrastructure Forskningsveien

More information

Frederick Ross. Real Estate Market Overview. Presented by: Kevin Thomas Senior Vice President. Frederick Ross. Company.

Frederick Ross. Real Estate Market Overview. Presented by: Kevin Thomas Senior Vice President. Frederick Ross. Company. Frederick Ross Real Estate Market Overview Presented by: Kevin Thomas Senior Vice President Frederick Ross Company January 2003 Business Consumers Source: BEA, Ross Research Housing...Bust or Rust? 2001

More information

Shri Krishna Test House, B-70/1, Gali No. 8, New Modern Shahdara, Mansarover Park, Delhi. Discipline Mechanical Testing Issue Date

Shri Krishna Test House, B-70/1, Gali No. 8, New Modern Shahdara, Mansarover Park, Delhi. Discipline Mechanical Testing Issue Date Last Amended on - Page 1 of 14 I. PERFORMANCE TEST 1. Domestic gas Stove for use with L.P.G. General Cl. 4, IS:5116 & Cl.4.1.1 of IS:4246 Material Cl. 5 of IS:5116 Design for Maintenance Cl. 6.2, 6.3,

More information

Gas Pressure Regulator R 51

Gas Pressure Regulator R 51 Gas Pressure Regulator R 51 Product Information Subject to technical modifications! Reprint prohibited! Table of Contents Application, Features, Technical Data 4 Application 4 Features 4 Type of model

More information

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable GEP-6075 Rev. B 101574 Ref. I.D.: 16973 Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable WARNING USER SHOULD READ AND THOROUGHLY UNDERSTAND THESE

More information

Parewanui Road (RP ) 1960 Prog. Mar-18 Prog. May-18

Parewanui Road (RP ) 1960 Prog. Mar-18 Prog. May-18 RDC ROADING REPORT: FEBRUARY 2018 1. MAINTENANCE, OPERATIONS AND RENEWALS This year s resealing programme of 61 km has been completed. Pre-reseal repairs for the 2018/19 year have been programmed. Installing

More information

Instances of 1 Minute or Less Between Buses 4 5% 55% 3.9% 3.5% 3.5% 3.5% 2.9% 2.8% Sep- Sep 07 Oct-07 Nov-07 Dec-07 Jan- Jan 08 Feb- Feb 08 Mar-08

Instances of 1 Minute or Less Between Buses 4 5% 55% 3.9% 3.5% 3.5% 3.5% 2.9% 2.8% Sep- Sep 07 Oct-07 Nov-07 Dec-07 Jan- Jan 08 Feb- Feb 08 Mar-08 President s Report Monthly Performance Matrix Meeting or exceeding target Within 10% of target Missing target by more than 10% Measure does not have target RIDERSHIP Total Ridership p( (in millions) Rail

More information

Integrated Waterway Management of the Danube in Austria

Integrated Waterway Management of the Danube in Austria Integrated Waterway Management of the Danube in Austria Thomas Hartl / Senior Expert Waterway Management via donau Österreichische Wasserstraßen-Gesellschaft mbh Vienna, October 14, 2014 Page 3 Figures

More information

SWISS Traffic Figures May 2004

SWISS Traffic Figures May 2004 SWISS Traffic Figures May 2004 SWISS continues seat load factor improvement in May SWISS s load factor for May was 4.8 percentage points better than for the same period last year. Seat load factor for

More information

LEV Inspection & Test Report

LEV Inspection & Test Report LEV Inspection & Test Report CLIENT: SITE: XXXXXXX LTD XXXXXXX Report Reference: Hinge Room-LEV System Identification: BeCu ESTA Survey Conducted By: Name: Position: Signed: XXXX Environmental Consultant

More information

Pressure surge absorption

Pressure surge absorption Pressure surge absorption Product range for drinking water, waste water and the chemical industry With remote monitoring, everything is fully under control. Willy Zahnd, WARET AG PRESSURE SURGE ABSORPTION

More information

Preston s Edmond Market Report

Preston s Edmond Market Report Preston s Edmond arket Report July 2 Prepared By Brian Preston RE/AX Associates obile: 45-826-5725 Office: 45-359-87 bpreston88@sbcglobal.net www.edmond4sale.com Realtor of the Year 1995 & 22 Lifetime

More information

PROBLEMS ON VENTILATION IN COMPLEX CITY TUNNELS

PROBLEMS ON VENTILATION IN COMPLEX CITY TUNNELS - 15 - PROBLEMS ON VENTILATION IN COMPLEX CITY TUNNELS Sturm P.J. 1, Bacher M. 1, Pretterhofer G. 1 Kalz U., Maier J. 3 1 Graz University of Technology, Austria ASFiNAG Service Gesellschaft Nord; 3 Amt

More information

Implementation of an Asset Management Software for Proactive Management and Optimization of the Collection System Rehabilitation and Renewal Program

Implementation of an Asset Management Software for Proactive Management and Optimization of the Collection System Rehabilitation and Renewal Program Implementation of an Asset Management Software for Proactive Management and Optimization of the Collection System Rehabilitation and Renewal Program P. S. Arora, P.E. Joel Nickerson 2,591,286 linear feet

More information

JULY 2013 RIDERSHIP REPORT MTA METRO-NORTH RAILROAD EXECUTIVE SUMMARY

JULY 2013 RIDERSHIP REPORT MTA METRO-NORTH RAILROAD EXECUTIVE SUMMARY Ridership Report JULY 2013 RIDERSHIP REPORT MTA METRO-NORTH RAILROAD EXECUTIVE SUMMARY July July 2013 Total MNR System Ridership was 7.346 million vs. 7.439 million in July 2012, a decrease of 92,959 passengers

More information

Measuring range Δp (span = 100%) Pa

Measuring range Δp (span = 100%) Pa 4.4/ RLE 5: Volume-flow controller, continuous How energy efficiency is improved Enables demand-led volume flow control for the optimisation of energy consumption in ventilation systems. Areas of application

More information

Safety, ventilation and climate in rail tunnels

Safety, ventilation and climate in rail tunnels INTERNATIONAL SEMINAR LONG TUNNELS Safety, ventilation and climate in long rail tunnels Safety, ventilation and climate in rail tunnels Bernd Hagenah 17, 18 y 19 de Octubre 2012 Santiago, Chile Safety,

More information

CAST IRON SAFETY VALVE TYPE 6301

CAST IRON SAFETY VALVE TYPE 6301 CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 9 ACCUMULATORS The material needed for outcome 2 is very extensive so there are

More information

FIVE YEARS OF OPERATION OF THE FIRST OFFSHORE WIND RESEARCH PLATFORM IN THE GERMAN BIGHT FINO1

FIVE YEARS OF OPERATION OF THE FIRST OFFSHORE WIND RESEARCH PLATFORM IN THE GERMAN BIGHT FINO1 FIVE YEARS OF OPERATION OF THE FIRST OFFSHORE WIND RESEARCH PLATFORM IN THE GERMAN BIGHT FINO1 Andreas Beeken, DEWI GmbH, Ebertstraße 96, D-26382 Wilhelmshaven Thomas Neumann, DEWI GmbH, Ebertstraße 96,

More information

July 2015 Sept Cork City Pedestrian Counter Report

July 2015 Sept Cork City Pedestrian Counter Report July 2015 Sept 2015 Cork City Pedestrian Counter Report Disclaimer Cork City Council has produced this report based on information extracted from our Pedestrian Counter Monitoring System. Although care

More information

Gas Furnaces 95AF2V. Warranty Heat Exchanger - 20 Year Limited Parts - 5 Year Limited

Gas Furnaces 95AF2V. Warranty Heat Exchanger - 20 Year Limited Parts - 5 Year Limited PRODUCT SPECIFICATIONS INSTALLATION OPTIONS Available in Upflow/Horizontal and Counterflow models HEAT EXCHANGER Aluminized steel primary heat exchanger with crimped non-welded construction Stainless steel

More information

Guidance on room integrity testing and its interpretation

Guidance on room integrity testing and its interpretation Guidance Note Guidance on room integrity testing and its interpretation Guidance on room integrity testing and its interpretation 1. SCOPE... 6 2. INTRODUCTION AND BACKGROUND... 6 2.1. DEVELOPMENT OF INTEGRITY

More information

BACK PRESSURE / SUSTAINING

BACK PRESSURE / SUSTAINING SPECIFICATIONS DIMENSIONS In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. This is the function of the 108 Pressure Relief / Back Pressure Series

More information

Supratec. MEMBRANE-PLATE-DIFFUSER For fine bubble aeration of liquids BELÜFTUNGSTECHNIK UMWELT- & VERFAHRENSTECHNIK SERVICE & WARTUNG

Supratec. MEMBRANE-PLATE-DIFFUSER For fine bubble aeration of liquids BELÜFTUNGSTECHNIK UMWELT- & VERFAHRENSTECHNIK SERVICE & WARTUNG BELÜFTUNGSTECHNIK UMWELT- & VERFAHRENSTECHNIK SERVICE & WARTUNG G E N E R A L I N F O R M A T I O N OXYFLEX - MF 1100 For fine bubble aeration of liquids Supratec GESELLSCHAFT FÜR U MWELT- U N D VERFAHRENSTECHNIK

More information

Hard Shoulder Running is a valuable tool July 14, Dean H. Gustafson, PE, PTOE State Operations Engineer VDOT Operations Division

Hard Shoulder Running is a valuable tool July 14, Dean H. Gustafson, PE, PTOE State Operations Engineer VDOT Operations Division Hard Shoulder Running is a valuable tool July 14, 2016 Dean H. Gustafson, PE, PTOE State Operations Engineer VDOT Operations Division Virginia 2 VDOT s Statewide Operations Program Operations Statistics

More information

FREEDOM OF INFORMATION REQUEST

FREEDOM OF INFORMATION REQUEST FREEDOM OF INFORMATION REQUEST REQUEST NUMBER: FOI Request 003905-16 REQUEST DETAILS: As part of my research I am requesting information on the numbers of 'strip searches' that have taken place within

More information

PUBLIC MEETINGS. Please see the City of Geneva Public Meeting Guide for more information regarding City Council and Committee of the Whole meetings.

PUBLIC MEETINGS. Please see the City of Geneva Public Meeting Guide for more information regarding City Council and Committee of the Whole meetings. PUBLIC MEETINGS Citizens are welcome and encouraged to attend all City of Geneva public meetings. Public meeting guests are also urged to participate in any of the City s many public meetings that take

More information

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012 Installation Guide English September 2012 299H Series Introduction This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of

More information

BACK PRESSURE / SUSTAINING

BACK PRESSURE / SUSTAINING In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. This is the function of the 108 Pressure Relief / Back Pressure Series of the OCV control valves.

More information

NCC Cable System Order

NCC Cable System Order Order # 62508883 Flight s 03/13/18-04/01/18 Syscode 2107 Agency Canal Partners Media System Name Spectrum/DISH- I+ Tampa-St. Pete, FL Advertiser Levine For Governor Phone (301) 951-2620 Credit Update 03/13/18

More information

Maintenance Forecast Summary

Maintenance Forecast Summary : 99999 Landings: 99999 : 999999 Forecast : 15-Nov-50 Aircraft : 05 2010-0006 Time Limit / Maintenance Checks. Tail 5755 25.50 833.00 N/A 30 Rotor Pitch-Change Links-Inspection. IAW ASB 05.00.60(AS350)

More information

better measurement Simply a question of

better measurement Simply a question of Simply a question of better measurement SCHMIDT Flow Sensor SS 20.600 The powerful industrial professional for demanding applications involving air and gases. Industrial processes Pneumatic technology

More information

Understanding the Impacts of Culvert Performance on Stream Health

Understanding the Impacts of Culvert Performance on Stream Health Understanding the Impacts of Culvert Performance on Stream Health Kristin Thomas Aquatic Ecologist Michigan Trout Unlimited Transportation and the Environment Conference 12/5/2018 Importance of adequately

More information

INSTRUCTIONS AND MAINTENANCE MANUAL SERIES: RT

INSTRUCTIONS AND MAINTENANCE MANUAL SERIES: RT INSTRUCTIONS AND MAINTENANCE MANUAL 05/11/2015 SERIES: RT cmo @cmo.es http://www.cmo.es page 1 ASSEMBLY THE RT VALVE COMPLIES WITH THE FOLLOWING: Machinery Directive: DIR 2006/42/EC (MACHINERY) Pressure

More information

I 595 Express Corridor Improvements Project. February 2014 Update

I 595 Express Corridor Improvements Project. February 2014 Update I 595 Express Corridor Improvements Project February 2014 Update PROJECT COMPONENTS Reversible Express Lanes Direct Connect to Florida s Turnpike Open Road Tolling SR 84 Continuous Connection Florida s

More information

3. EXCEL FORMULAS & TABLES

3. EXCEL FORMULAS & TABLES Fall 2017 CS130 - Excel Formulas & Tables 1 3. EXCEL FORMULAS & TABLES Fall 2017 Fall 2017 CS130 - Excel Formulas & Tables 2 Cell References Absolute reference - refer to cells by their fixed position.

More information

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module: FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS This work covers part of outcome 2 of the Edexcel standard module: UNIT 21746P APPLIED PNEUMATICS AND HYDRAULICS The material needed for outcome

More information