1 Flexcon M-P Pump automat 0664 Flex MP-eps GB Installation and operating instructions 1999, Flamco

2 2

3 Installation and operating instructions Flexcon M-P pump automat Dear customer, GB With the purchase of the Flexcon M-P pump automat, you are now the owner of a high quality product from Flamco. The Flexcon M-P pump automat offers trusted technique, operational reliability and simplicity with installation and operation. This manual is intended for siting and placing, and for the commissioning. The manual also contains a description of the operation of the Flexcon M-P pump automat. We are convinced that you will quickly become acquainted with the technique of this Flexcon M-P pump automat. Should you have any questions about the Flexcon M-P pump automat that are not answered in the manual, we will be very pleased to answer them. Contents page 1.General 4 2.Function and operation 5 3.Different versions 6 4.Siting and placing 8 5.The Easycontrol automat 11 6.The Flexcon control automat 16 7.Commissioning and operation 22 8.Maintenance - periodic inspections 23 Appendices I - VI 24 3

4 1.General Flexcon M-P pump automats are used in closed heating installations, cooling and air conditioning installations with large water contents. The automats absorb the expansion volume that arises through heating in the installation. When the temperature falls, the required amount of water is again made available. Here, a servo-magnet valve is used to feed the expansion water into the diaphragm of the expansion vessel, and a pump is used to return the water to the installation. Flexcon M-P pump automats provide a considerably better solution than the pressure dictation systems that are known with installations for hot water production. The reason is that the expansion water is not connected to the atmosphere and, in this way, damage through corrosion is avoided. Thus, the Flexcon M-P pump automats ensure an accurate setting and maintenance of the pressure required in the installation. 1.1 Fields of application The Flexcon M-P pump automats can be used in closed heating installations, according to DIN 4751, Part 2, with water supply temperatures to a maximum of 120 C and also in closed cooling and air conditioning installations. The Flexcon M-P pump automats are designed for: Maximum allowed water supply temperature of the heating installation: 120 C Maximum continuous temperature loading of the diaphragms, according to DIN 4751, Part 3: 70 C Maximum allowed working pressure: 10 bar Special versions over 10 bar, on request. With a temperature > 70 C in the expansion pipe-work between the heating installation and the Flexcon M-P pump automat, a cooling vessel* is connected in front of the expansion vessel to cool the expansion water. The Flexcon M-P pump automats can be supplied in series with sizes of 200 to 5200 litres. * Flexcon V-B cooling vessels: volumes from 180 to 2000 litres maximum allowed working pressure: 5.0 to 10.0 bar 1.2 Specifications and regulations The diaphragm expansion vessels are pressure-less in the state for use. The vessels are designed for installations according to DIN 4751 part 2 after TRD 702. The test certificates (factory declaration) are included in the delivery and must be given to the locally responsible authorities for viewing. The installation and operating manual and the test certificates are kept in the cabinet of the automat! The test that must be carried out after the installation at the operational site must be organised by the exploitant. 1.3 Advantages of using the Flexcon M-P pump automat complete programme in size, design and pressure stages. broad applicability as a result of flexible possibilities of use. small placement surface - large expansion volume in a small space. use of low-noise pumps with high capacity to produce pressure, with automatic venting of the pump. storage of expansion water in pressure-less operating vessels with solid diaphragm made of high-quality butyl rubber. the pressure in the system is kept constant within tight limits, which means minimum pressure variations, independent of the state of the system. minimisation of pressure shocks and reduction of switching frequency of the pump and solenoid valve as a result of an integrated pressure control vessel. freely programmable control with a microprocessor, whereby the actual values in use and all operational states are shown on a display. connection to a personal computer or combination with a building control system possible. connection to a general fault indication present. safe operation through many years of experience and high manufacturing quality. 4

5 2. Function and operation Functional diagram of a Flexcon M-P pump automat Figure recommended on-site assembly from M-P 1000 l Steuerautomat 8 15 plug Steel vessel 2 Exchangeable diaphragm made from butyl rubber, according to DIN 4807, Part 3 3 Control automat 4 Heavy duty pump 5 Overflow valve 6 Pressure sensor 7 Contents sensor 8 Safety valve 9 Non-return valve 10 Dirt catcher 11 Pressure control vessel expansion pipe-work system connection 12 Ball valve 13 Floatvent 14 Aerator and de-aerator 15 Earth connection 16 Connecting pipe between diaphragm 17 Filling-drain cock 18 Pump vent (valve, floating vent) 19 Flexible hose connection 20 Safety valve - fit on site! Figure 1 shows the Flexcon M-P pump automat. In the standard version, the pump automat consists of the following two components: - Flexcon M-P diaphragm expansion vessel - Flexcon M-P automatic control of the pump The essential constructional parts of the two components are: - Flexcon M-P diaphragm expansion vessel vessel (1) diaphragm (2) - Flexcon M-P automatic pump control control automat (3) heavy duty pump (4) overflow valve (5) The diaphragm (2), which is in the expansion vessel (1), absorbs the expansion volume and functions as a separation wall between air and water. The control automat (3) guarantees that the system pressure which is set in the control is kept constant within tight limits. The signal that is necessary for this is sent to the automat by the pressure sensor (6). When the temperature rises, the pressure in the system increases. The overflow valve (5) opens and lets the expansion water flow into the Flexcon M-P diaphragm expansion vessel. When the temperature drops, the pressure in the system decreases. If the pressure falls below the set system pressure, the pump (4) switches on, and is switched off when the system pressure is reached. A check and a continuous indication of the filling level in the display (3) prevents the pump (4) from running dry or the vessel (1) from being filled to an unallowably high level. The Flexcon M-P pump automat can be fitted with the following microprocessor controls: Easycontrol automat The Easycontrol automat is designed for single installations (a Flexcon M-P expansion automat with coupling vessel). For operation, see pages 11 to 15. Flexcon control automat The Flexcon control automat is prepared for single installations, and for failure change-over operation by two pumps. For operation, see pages 16 to 21. 5

6 A solid diaphragm of butyl rubber divides the Flexcon M-P diaphragm expansion vessel into a water and gas space. The diaphragm prevents contact between the expansion water and atmospheric oxygen. Via a floating aerator and vent (13), air that is released from the heating water is optimally separated and prevents an enrichment of the heating water with air from the atmosphere. The safety valve (8) protects the pressure-less vessel (1) from unpermitted overpressure in the case of a failure. The supply and removal of expansion water to and from the diaphragm is done by the flexible high pressure hose (19) between the diaphragm expansion vessel and the automatic pump. The pressure control vessel (11) thus reduces the pressure shocks when the pump and the servo solenoid valve switch. 3. Different versions The different versions that are described in the following can be supplied for the varied requirements that the heating installations place on the expansion automats. If you wish to realise other versions, please contact your local Flamco representative. The design can be effectively realised with the help of the Flamco calculation diskette* for expansion vessels. * Available on request from the Sales Office of Flamco. 3.1 Flexcon M-P pump automat The standard version of the Flexcon M-P pump automat is supplied in two components: - Flexcon M-P diaphragm expansion vessel in the sizes 200 to 5000 litres (upright) with flexible high pressure hose - Flexcon M-P automatic control including a pump Figure Expansion pipe-work 3.2 Flexcon M-P pump automat with auxiliary vessel Figure Install on site Expansion pipe-work With a battery or series circuit of Flexcon M-P pump automats with an automatic pump (Flexcon M-P pump automat with auxiliary vessel), care must be taken that the expansion vessel is of the same size. The automats can be supplied with both control automats (Flexcon control automat or Easycontrol automat). 6

7 3.3 Parallel operation or failure change-over operation by two pumps* Figure Steuerautomat Plug Expansion pipe-work With the Flexcon M-P pump automat with one M-P control and two pumps, only one of the two pumps works during failure change-over operation. In the case of a fault (the motor protection switch becomes active), the system automatically switches over to the other pump. This is also done after expiry of the set change time, which serves to load the pumps evenly. * Only with Flexcon control automat - see page 16. 7

8 Steuerautomat Flamco 4. Siting and placing The Flexcon M-P pump automat is supplied as standard version in two packages. Appendix VI gives the main dimensions and weights. 1. Diaphragm expansion vessel 2. Automatic pump control The Flexcon M-P pump automat must be placed in closed spaces with a temperature between 5 C and 40 C. Here, the floor must be sufficiently sturdy and flat. Caution: The expansion vessel and the control must be installed at the same height. If this is not structurally possible, the expansion vessels may be placed higher than the control. The control is not allowed to be higher than the expansion vessels! Flexcon M-P pump automats must be so placed that they can operate without problems and can be maintained at all times. The following sketch and table contain the minimum distances ab c c Vessel size a b c (l) (cm) (cm) (cm) = > Note: Depending on the structural situation, the automatic pump control can be placed next to the vessel as required, by turning the vessel connection. Above the top inspection opening, there must be a free space of: - min. 650 mm for vessel sizes Flexcon M-P l - min mm for vessel sizes Flexcon M-P l Caution: To be able to safeguard a contents measurement according to regulations, attention must be paid to the following points: The diaphragm expansion vessel must be upright and free! The transport protection of the measurement foot must be removed after placing, so that the contents sensor can stand freely on a flat base. Steps 1 and 2 of the removal of the transport protection! 1.) 2.) 6557 Support points of the spirit level Removed transport protection (bent steel plate with fixing bolt) The foot height adjustment of the two other vessel feet makes the required safe upright placing of the Flexcon M-P diaphragm expansion vessel possible. The vertical placing must be done according to the sketch with a spirit level on the indicated axes. The required flexible hydraulic connection between the diaphragm expansion reservoir and the automatic pump control is provided by a metal high pressure hose that belongs to the delivery. 8

9 The zero level setting of the vessel contents may only take place with an empty and exactly vertical vessel! Before the commissioning of the expansion automat (see also chapter 7), no water may be added and the vessel must be kept separated from the mains (safety valve closed). After the components of the Flexcon M-P pump automat are placed, the following connections can be made: a) Hydraulic connections The connection of the installation to the automatic pump control can be stiff or flexible, but must be fitted with a shut-off valve. The connections are dependent on the chosen expansion pump, as follows: Pump type System connection M-P/1.0 G 1!/4 /DN 32 M-P/2.0 G 2 /DN 50 M-P/3.0 G 2 /DN 60 The connection between the control and the expansion vessel must be flexible. Here, the following must be taken into account: - It must be possible to shut the pump automat off from the installation. This valve must be protected against unintended closing (for example, a valve with a seal). - Welding activities must be so carried out that no welding material can fall on or enter the pump automat. - The maximum working temperature at the system connection may not exceed 70 C (generally speaking, the system connection must be coupled into the return pipe-work of the boiler). b) Electrical connection The control must be connected to 400 V, 50 Hz, 16 A. Here, attention must be paid to the following: - The voltage and the frequency values must correspond with the DIN VDE recommendations. - The connection must be made with a 400 V CEE wall socket (according to IEC 309-2). - The earth connection (zero earth potential difference) must be made to an earth leakage connection (according to DIN VDE 0100, part 540) through the central earthing bolt of the control automat (see figure 1, item number 13). c) Connection of the contents sensor for the contents level measurement The electrical connection of the contents sensor to the measurement foot of the diaphragm expansion vessel must be made on site with the cable which is supplied with the delivery (this is connected to the control in the factory). Here, the 5-pole round plug must be connected to with the measurement probe. Both the Flexcon M-P expansion automat in the standard version (chapter 3.1 figure 2) and the Flexcon M-P expansion automat with M-P automatic pump control in the version with two pumps (point 3.3 figure 4) are delivered ready for use in two components. Assembly recommendation: Flexcon M-P expansion automat Directly heated installation (Connection through protected shut-off valve) Figure Flexcon M-P expansion automat 2 Valve (with wire and lead seal) 3 Filling-drain cock (included in delivery) 4 Flexcon diaphragm expansion vessel 5 Safety valve 6 Flamco low water level protection 7 Pressure meter 8 Flexvent floating vent 9 Air separator 9

10 Assembly recommendation for the Flamco-Fill STA or PA automatic water replenisher The hydraulic coupling of a automatic water replenisher must be made according to figure 6. Figure Replenisher connection Coupling Pump type Coupling* M-P/1.0 Double nipple 1!/4 + T-piece 1!/4 -!/2-1!/4 M-P/2.0 Double nipple 2 + M-P/3.0 T-piece 2 -!/2-2 * is not part of the delivery 10

11 5. The Easycontrol automat To commission and/or operate the Flexcon M-P pump automat, knowledge is required of the operation of the control automat. The user is guaranteed an easy check and operation as a result of the design of the Easycontrol automat with modern building elements, such as microprocessor, 2-digit display and Status LEDs for the display: - of the actual operational parameters - of the possible operational faults - of the desired parameter changes Input data that is not permitted is not accepted. Figure Technical data control - power supply voltage : 400 V 3/N/PE - own consumption : roughly 20 W - loadability of the relay : 8 A, 230 V contents sensor - power supply voltage : DC V - type of protection : IP 65 pressure sensor - measurement range : 0-16 bar overflow valve (servo solenoid valve) - operating range (standard) : 0-10 bar 5.2 Setting and commissioning The control automat is supplied with the system or operating pressure that you have ordered, plus the settings for an automatic water replenisher (ON and OFF). If you did not indicate the system pressure with the order, then the control automat is ready for use with the standard values that are set in the factory (see point 5.2.1). By pressing the relevant key after the main switch is set to "ON", the following actual operational values appear on the display: LED operational parameters water level (%) or working pressure (bar) 11

12 If you did indicate the working parameters with your order, you only need to carry out the zero level setting (fourth operational step) in the programming mode (see chapter 5.2.1) for: - working pressure (bar) - automatic water replenisher "ON" (%) - automatic water replenisher "OFF" (%) If no working parameters were entered beforehand or if the set working parameters must be changed, you must carry out the relevant operational steps in the following section Changing the operational parameters To change the operational parameters, the following operational steps are required: - main switch : OFF - control automat : OPEN - sliding switch (colour red) on the control panel : OPERATE SWITCH - control automat : CLOSE - main switch : ON The programming mode LED is lit! Figure 8 Easycontrol (open) Sliding switch (red) operate programming 6634 In the programming mode, the display shows the following: 00 First operational step Operate the. working pressure (bar) or automatic water replenisher "ON" (%) or automatic water replenisher (OFF) (%) key for three seconds. The relevant LED will light. The display will show the value that was entered in the factory or that was saved last! Values of parameters that the factory enters (without previous values!) working pressure values Flexcon M-P 10 bar 5.5 bar automatic water replenisher "ON" 15 % automatic water replenisher "OFF" 25 % 12

13 Example: Working pressure (bar) The following appears in the display: the figure after the decimal point "flashes" Second operational step: Correct the "flashing figure" by operating the keys - or + and confirm with the "Working pressure" key If the displayed value has to remain unchanged, you can confirm this by only operating the "working pressure" key the figure in front of the decimal point "flashes" Third operational step: Repeat the second operational step! The operational steps are analogous to the "working pressure example" for the indication and if necessary the desired change of the entered values for: automatic water replenisher "ON" and automatic water replenisher "OFF" Note! The values can only be changed within the range limits that are previously set in the factory. If the set value is within the range limits, the relevant LED goes out after about five seconds. If the value is outside the range limits, the entry must be repeated with plausible values. If a change of the parameters is desired, the values can be changed within the following range limits: working pressure Flexcon M-P 10 bar automatic water replenisher "ON" automatic water replenisher "OFF" - range 0.5 to 8.7 bar - range 5 % to 49 % - range replenisher "On" + 2 % to replenisher "On" + 20 % Example - automatic water replenisher "ON" : 06 % - automatic water replenisher "OFF" : 12 % Note: The values for the minimum and maximum permitted water level are programmed as fixed values. min. water level : 05 % max. water level : 94 % If these values become too high or low during operation, this will cause a fault report (see also point 5.3 "Reporting - operational faults"). 13

14 Contents level - zero level setting Caution: The "operational zeroing", i.e. the zero level setting of the filling level may only take place with an empty vessel and with the transport protection removed (see also chapter 4 - Siting and placing). Fourth operational step Key zero level setting operate for three seconds. The zero level setting is finished when the appropriate LED goes out after about five seconds. If the LED flashes eight times, the operational step must be repeated. Caution! After finishing the value change, the equipment must be switched to the "operation" mode because the control cannot otherwise operate (operational mode LED)! The switch-over to the "operation" mode after the earlier set parameters are changed must be carried out as follows: Operational steps: - main switch : OFF - control automat : OPEN - sliding switch (colour red) on the control panel (fig. 9) : OPERATE SWITCH - control automat : CLOSE - main switch : ON Note! The following LED is lit because the vessel of the Flexcon M-P expansion automat is empty: Minimum water level/alarm for minimum working pressure The minimum water level fault serves as a protection against the pump running dry. The pump is blocked and switches off! The Flexcon M-P expansion automat of the expansion installation must be filled with water (see also chapter 7 "Commissioning - operation"). 5.3 Reporting - operational faults The control automat is equipped with a detailed fault indication. A possible fault report is given by the relevant "operational fault LED" lighting, in combination with the "operational parameter LED". To leave the fault reports after clearing the faults, operate the relevant key. Caution! With a motor protection fault, the contact for too high current has activated. This fault must be cleared by a qualified person! If you cannot clear the general or other faults, please contact our customer service department. 5.4 Connection of a general fault indication ("Fehler") Faults in the heating installation or the control are reported by the potential-free changeover contact. The contacts are connected to terminals x 1-11, 12 and 13 of the control automat (see "terminal plan" appendix I). Warning! Even with a switched off control, there can be voltage on the connections of the fault relay (external power supply). 5.5 Connection of an automatic water replenisher - Flamco-Fill Type STA or PA A potential-free contact is available on terminals x 1-9 and 10 to control the automatic water replenisher. The contact closes at the water replenish command from the control (see "terminal plan" appendix I). Warning! Even with a switched off control, there can be voltage on the connections of the fault relay (external power supply). 14

15 Flamco 5.6 Automatic leakage detection The Flexcon M-P pump automat can be supplied with a "leakage probe" to detect possible damage to the diaphragm. With damage to the diaphragm, whereby water penetrates the air space of the diaphragm expansion vessel and especially air enters the installation, there is an immediate alarm on the display of the Flexcon control automat. 5.7 Connection to a personal computer of a building control system The Easycontrol automat is so prepared that an uninterrupted remote transfer is possible of relevant control data, on request. In this way, a remote visualisation through a personal computer or a combination with a building control system is possible. - Connection to a personal computer Figure Easycontrol control automat RS 485 Max. 1.2 km PC Interface RS Combination with a building control system You will receive the data that is necessary for this when you order this option. 15

16 6. The Flexcon control automat To commission or operate the Flexcon M-P pump automat, knowledge is required of the operation of the control automat. The design of the Flexcon control automat with modern components such as microprocessors and a digital display make it possible for the user to change the system settings and the user parameters in dialogue with the control. Input data that is not permitted is provided with commentary in the display, just as system faults. For the operation, a foil keyboard is fitted on the door of the control automat. Figure 10 Display Keyboard 5577 Flamco Control automat Main switch 6.1 Technical data General fault indication control - power supply voltage : 400 V 3/N/PE - own consumption : roughly 20 W - loadability of the relay : 2 A, 230 V pressure sensor - measurement range (standard) : 0-10 bar contents sensor - power supply voltage : DC V - type of protection : IP 65 overflow valve (servo solenoid valve) - operating range (standard) : 0-10 bar 6.2 Setting and commissioning The control automat is supplied with the system pressure that you have ordered. If you did not indicate the system pressure with the order, then you can set it yourself. You can read the programmed values and their setting ranges on the display by scrolling through the menu points. 16

17 Flamco After the main switch is set to "ON", the following appears on the display: Pressure Level 00.0 bar 000 % 01.7 Pump. 005 % 02.3 Vent. 095 % (Here, the system pressure was set to 2.0.) By pressing the <RET> key, you can call further menus: Operating hours Pump hours Pump hours Options Leakage probe : - (*) Parallel operation : - Failure change-over operation : - - = not present * = present Installation : M-P Working pressure : 10 bar Contents : XXXX L X = nominal vessel contents To change the operational parameters that are set in the factory, the control must be switched from the "BETRIEBS-Modus" (operational mode) to the "PROGRAMMIER- Modus" (programming mode). Switching to the programming mode operational steps - Main switch : OFF - Control automat : OPEN - Sliding switch (colour red) on the inside of the door : OPERATE SWITCH - Control automat : CLOSE - Main switch : ON Figure 11 Flexcon control automat (opened) On Programming 6559 Sliding switch (red) Caution! Automat operation is not possible in the programming mode. The programming mode is indicated by a flashing report "Fehler". 17

18 The display is as follows: Programming mode further with "RET" or switch on Operate <RET> key, the display now becomes: - Menu point 1 System pressure : 02.0 Allowed : bar Confirmation : "RET" The value can be changed within the indicated range limits. Each time the <RET> key is operated, the next menu point appears. - Menu point 2 Min. water level : 05 % Allowed : 5 % to 50 % Confirmation : "RET" (standard: 5 %) - Menu point 3 Max. water level : 95 % Allowed : 50 % to 95 % Confirmation : "RET" (standard: 95 %) - Menu point 4 Min. pressure : 00.5 Allowed : X.X - XX.X bar Confirmation : "RET" Value can be changed within the indicated range limits "X.X to XX.X". - Menu point 5 Max. pressure : 04.5 Allowed : XX.X - XX.X bar Confirmation : "RET" Value can be changed within the indicated limits "XX.X to XX.X". - Menu point 6 Water make-up level Switches on at : 04 % Allowed : 04 to 49 % Confirmation : "RET" - Menu point 7 Water make-up level Switches off at : 10 % Allowed : XX to XX % Confirmation : "RET" Value can be changed within the indicated range limits "XX to XX". - Menu point 8 Maximum pump running time Allowed Confirmation : 10 min : 10 to 240 min : "RET" Value can be changed within the indicated range limits. 18

19 - Menu point 9 (Optional) Parallel operation 1: present 2: not present (for this, see point 3) - Menu point 10 Zero level setting of the contents sensor operate : "ESC" further : "RET" Caution! The zero level setting of the vessel contents may only take place with an empty vessel and removed transport protection! (See also chapter 4 "Siting and placing".) The zero level setting may only be carried out if the electronics are at working temperature (roughly ten minutes after switching on). After the preset operational parameters are changed, the change-over to the operational mode must be carried out as follows: Operational steps: - main switch : OFF - control automat : OPEN - sliding switch on the inside of the door (figure 9) : ON - control automat : CLOSE - main switch : ON The Flexcon M-P pump automat is ready for use! Note: The general fault lamp is on because the vessel or the expansion installation is "empty" and for that reason the "minimum water level" fault is reported. You must now fill the diaphragm expansion vessel of the Flexcon M-P pump automat (for this, see chapter 7: "Commissioning - operation". 6.3 Fault reports The control automat is equipped with a general fault indication. The alarm relay is deenergised when a fault occurs. The <Fehler> (Fault) lamp at the bottom of the display (figure 10) lights continuously. The faults are given separately in the display. With more than one fault at a time, the separate fault reports can be displayed by operating the <RET> key. After this, the following displays are possible: FAULT min. water level clear fault! This means that the entered minimum water level (point menu point 2) has not been reached. CAUTION: The min. water level fault serves as a protection against the pump running dry. The pump is blocked and switches off! In this case, it is necessary to refill the installation. FAULT max. water level clear fault! Here, the preset maximum water level has apparently been exceeded. You can let water drain away with the aid of the drain devices that are fitted in the installation. FAULT min. pressure alarm clear fault! 19

20 FAULT max. pressure alarm clear fault! FAULT running time of the pump clear fault! The fault reports for the minimum pressure and maximum pressure alarms, and also running time of the pump can have several causes. Therefore, please contact our Customer service department when one of these faults occurs. FAULT motor protection clear fault! With this fault, the relay for a too high current is activated. To clear this fault, the following steps must be carried out by a suitably qualified person: - main switch : OFF - control automat : OPEN - operate the motor protection reset - control automat : CLOSE - main switch : ON To leave the fault reports after clearing the faults, operate the <ESC> key. If you cannot clear the displayed faults or other faults, please contact our Customer service department. 6.4 Connection of a general fault indication ("Fehler") Faults in the heating installation or the control are reported by the potential-free changeover contact. The contacts are connected to terminals 17, 18 and 19 of the Flexcon control automat. Terminal 17 is the common connection. The relay is used inversely. This means that the relay is energised when there are no faults (contact to terminal 19) and is de-energised when a fault occurs (contact to terminal 18). In this way, the reporting of a mains failure is also possible. The fault relay is also energised in the programming mode (see "terminal plan" appendices III - V). Warning! Even with a switched off control, there can be voltage on the connections of the fault relay (external power supply). 6.5 Connection of an automatic water replenisher - Flamco-Fill Type STA or PA A potential-free contact is available on terminals 7 and 8 to control the automatic water replenisher. The contact closes at the water replenish command from the control (see "terminal plan" appendices III - V). Warning! Even with a switched off control, there can be voltage on the connections of the fault relay (external power supply). 6.6 Failure change-over operation The different versions that can be supplied for failure change-over operation are described under point 3.3. The setting of the failure change-over operation in the Flexcon control automat requires special measures that can be obtained from the manufacturer. 6.7 Automatic leakage detection The Flexcon M-P pump automat can be supplied with a "leakage probe" to detect possible damage to the diaphragm. With damage to the diaphragm, whereby water penetrates the air space of the vessel and especially air enters the installation, there is an immediate alarm indication on the display of the Flexcon control automat. 20

21 6.8 Connection to a personal computer or a building control system The Flexcon control automat is so prepared that an uninterrupted remote transfer is possible of relevant control data, on request. In this way, a remote visualisation through a personal computer or a combination with a building control system is possible. Figure Flexcon control automat Master Flexcon control automat Slave Flexcon control automat Slave RS 485 PC max. 1,2 km Interface RS Combination with a building control system You will receive the data that is necessary for this when you order this option. 21

22 7. Commissioning and operation 7.1 Commissioning with a cold heating installation Valve closed, check the system pressure. Carry out a zero level setting of the operation while the vessel is empty. Check the pressure of the pressure control vessel and adjust if necessary and then open the shut-off valve. The setting of the pressure must be carried out as follows: In the state as supplied by the factory, the pressure control vessel has a pressure of 4 bar, the ball valve to the Flexcon M-P station (at the bottom of the vessel) is closed. The pressure of the pressure control vessel must locally be adjusted as follows: Pressure of control vessel* = system pressure bar Next, the ball valve must be opened. * If the pressure that is required for the operation in the pressure control vessel is above the pressure in the delivery state (4 bar), then this pressure must accordingly be raised for the commissioning with nitrogen! While the valve between the vessel and the installation is closed, fill the heating installation and vent Open vent shut-off of the floating vent ("red knob") on the vessel by turning it one full turn. Fill the Flexcon M-P pump automat (diaphragm expansion vessel) with the planned amount of water through the filling-drain cock in the expansion pipe-work. Vent expansion pipe-work Vent the automatic pump (see figure 8) commissioning system in operation Open valve to the installation : manually vent with the aid of valve or nipple : automatically vent Flexvent floating vent (during commissioning, open by turning the red knob one full turn!) 7.2 Commissioning with a heated installation With the valve between the vessel and the installation closed, check the set system pressure Carry out a zero level setting of the operation while the vessel is empty. Set pressure of the pressure control vessel DSB as follows: see point 7.1. Open vent shut-off of the floating vent ("red knob") on the vessel by turning it one full turn! Fill the vessel of the Flexcon M-P pump automat through the filling-drain cock. The filling level must correspond with the amount of water that is calculated for the actual expansion volume of the operational situation. Vent the automatic pump (see point 7.1). Open valve to the installation. Figure 13 Pump type: M-P/1.0 M-P/2.0 floating vent vent valve Pump type: M-P/3.0 floating vent with aerator valve vent nipple

23 8. Maintenance - periodic inspections The DIN 4807/2 standard requires an annual maintenance and inspection for diaphragm expansion vessels. Besides the external condition of the vessel and the correct operation of the control, the pump and overflow valve must be checked for leakage and the dirt catcher must be checked and cleaned if required. Moreover, the connecting pipes must be checked for leakage. If the diaphragm expansion automat is a component of a boiler installation with boilers of group II with a water content of more than 2000 litres that must be inspected for the first time by an expert, then a supplementary annual external inspection by an expert must be prescribed, according to paragraph 16 of the Boiler Regulation (DampfV). In the other case, this check must be carried out by an expert. The intervals of the periodic inspections have been set as follows, independently of the Boiler Regulation, paragraph 16: - external check yearly - internal check every five years - water pressure check every ten years The checks must be carried out by an expert. We advise you to contract the customer service department of Flamco for the maintenance. (The test of the pressure of the pressure control vessel must take place at least once per year, in combination with cleaning the dirt catcher). This manual must be handed over to the owner and must be kept in the vicinity of the vessel. 23

24 Appendix I Easycontrol automat Control panel Option Leakage probe Pressure Filling quantity Motor protection fault Fault Water make up Protection K 1 Solenoid valve Power supply 5580 Appendix II 5581 Control panel IEB connections Pump/compressor 24

25 Appendix III Flexcon control automat 5583 Motor protection 1 Motor protection 2 Protection 1 Protection 2 Power supply Compressor 1 Compressor 2 Terminal block Printed circuit board terminals I/O 25

26 Appendix IV 3-Phase one compressor Mains 3/N/PE 50 Hz 400 V/230 V Compressor 1 Valve 1 Valve 2 Valve 3 Water make up Fault Parallel operation Contents Pressure Leakage probe PE PE PE Terminal block Printed circuit board terminals I/O Appendix V 3-Phase two compressors Mains 3/N/PE 50 Hz 400 V/230 V Compressor 1 Compressor 2 Valve 1 Valve 2 Valve 3 Water make up Fault Parallel operation Contents Pressure Leakage probe PE PE PE Terminal block Printed circuit board terminals I/O 26

27 Appendix VI Main dimensions and weights for Flexcon M-P pump automats - Flexcon M-P diaphragm expansion vessel (lying on pallet) Type Dimensions mm Weight l x w x h kg M-P x 0550 x M-P x 0750 x M-P x 0750 x M-P x 0750 x M-P x 0750 x M-P x 1000 x M-P x 1000 x M-P x 1200 x M-P x 1200 x M-P x 1200 x M-P x 1500 x Flexcon M-P pump automat Type Dimensions mm Weigth l x w x h kg M-P/ x 500 x M-P/ x 590 x M-P/ x 590 x

Flamco Flexcon M-K Compressor - automat expansion vessel

Flamco Flexcon M-K Compressor - automat expansion vessel Flexcon M-K Compressor - automat expansion vessel M-K EPS GB Installation and operating instructions 1999, Flamco 2 Flamco UK Limited P.O. Box 9, Washway Lane, St. Helens, Merseyside WA10 6FE United Kingdom

More information

Flamco Flamco-Fill STA Flamco-Fill STM

Flamco Flamco-Fill STA Flamco-Fill STM STA STM Typ STA 5936 Typ STM 5937 GB Installation and operating instructions 1999, 2 Contents GB UK Limited P.O. Box 9, Washway Lane, St. Helens, Merseyside WA10 6FE United Kingdom Telephone: 01744 744744

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

Airfix D-E-B Installation and operating instructions

Airfix D-E-B Installation and operating instructions www.flamco.nt-rt.ru Airfix D-E-B Installation and operating instructions Dear Customer, With the Airfix D-E-B membrane expansion vessel you have acquired a Flamco quality product. This expansion vessel

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Models: DS 126 Single Pump / Single System DT 126 Twin Pump / Single System DS 160

More information

Flamco Airfix D-E. Installation and operating instructions. 1999, Flamco eps

Flamco Airfix D-E. Installation and operating instructions. 1999, Flamco eps Airfix D-E 6442.eps GB Installation and operating instructions 1999, Exclusion of liability All operation and maintenance related technical information, data and instructions contained in these installation

More information

SPIROVENT VACUUM DEGASSERS

SPIROVENT VACUUM DEGASSERS SPIROVENT VACUUM DEGASSERS S P I R O V E N T A I R S U P E R I O R FLUID AND GAS There are always a certain amount of gasses in a fluid, dependent on pressure and temperature. The British physicist William

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

ENA. Flamco. Installation, maintenance and operating instructions. This manual must be passed to the end-user, and stored with the ENA.

ENA. Flamco. Installation, maintenance and operating instructions. This manual must be passed to the end-user, and stored with the ENA. VENT/TOP-UP APPLIANCE ENA This manual must be passed to the end-user, and stored with the ENA. VEN2302 Dear customer, In purchasing the ENA, you have chosen a quality product. This patented vent/top-up

More information

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz GRUNDFOS DATA BOOKLET Complete pressure boosting systems 5/6 z Contents Product data Performance range 3 Operating conditions Inlet pressure Type key Product range 5 Construction 5 Installation 5 Mechanical

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Micro-S / Micro-S Digital Wall Hung Unit Please fulfil all listed requirements prior to and during

More information

PressVal Pressurisation Units. Packaged Pressurisation Units with expansion vessels for heating systems.

PressVal Pressurisation Units. Packaged Pressurisation Units with expansion vessels for heating systems. PressVal Packaged with expansion s for heating systems. lamco Basepak LEXILLER lamco Basepak LEXILLER POWER AULT MUTE/ RESET SYSTEM OK lamco ON / O lamco Basepak LEXILLER PressVal SM skid mounted units

More information

Tightness controls TC 1 3 and TC 4

Tightness controls TC 1 3 and TC 4 Tightness controls TC 1 3 and TC 4 Test of both safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted to different systems

More information

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Healthcare and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

SCAM T.P.E. WATER TREATMENT SYSTEM SWT- AP AUTOMATIC PURGE

SCAM T.P.E. WATER TREATMENT SYSTEM SWT- AP AUTOMATIC PURGE SCAM T.P.E. WATER TREATMENT SYSTEM SWT- AP AUTOMATIC PURGE 1 TABLE OF CONTENTS 1. PURPOSE OF SUPPLY... 3 2. SYSTEM FUNCTIONING... 3 3. SYSTEM COMPONENTS... 4 4. BATTERY LIMITATIONS... 6 5. DOCUMENTATION...

More information

CENTRAL GAS SUPPLY SYSTEMS : CYLINDER BATTERIES AND HIGH PRESSURE HOSES

CENTRAL GAS SUPPLY SYSTEMS : CYLINDER BATTERIES AND HIGH PRESSURE HOSES P0170E-1.DOCX/08.16/MG CENTRAL GAS SUPPLY SYSTEMS : CYLINDER BATTERIES AND HIGH PRESSURE HOSES With a Central Gas Supply System, individual work places or gas take-off stations are supplied with gas through

More information

WE SAY: REFILL PLEASE!

WE SAY: REFILL PLEASE! multicontrol autofill MCA WE SAY: REFILL PLEASE! MULTICONTROL AUTOFILL SOLO MCA-S Ver.03/208-en OPERATING PRINCIPLE Operating principle Make-up Losses within the system are mostly unavoidable. To ensure

More information

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation. Quality Products at Competitive Prices Gas Check Automatic testing of the down-stream installation to check that all valves are closed and that pipework and fittings are gas tight before each system start-up.

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

Reverse Osmosis System Installation Guide and Operation Manual.

Reverse Osmosis System Installation Guide and Operation Manual. Reverse Osmosis System Installation Guide and Operation Manual. Table of Contents 1 Introduction...2 2 Installation...3 2.1 Feed water connection...3 2.2 Permeate and concentrate plumbing...3 2.3 Electrical

More information

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION 1 INFORMATION and TECNICAL DESCRIPTION 14 2 AIRLEADER Professional Compressor Management + Compressed Air Visualisation + Alarm Service Management + AIRLEADER - has been the effective answer for compressed

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module: FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS This work covers part of outcome 2 of the Edexcel standard module: UNIT 21746P APPLIED PNEUMATICS AND HYDRAULICS The material needed for outcome

More information

Automatic Control Unit. Controlmatic E.2. Type Series Booklet

Automatic Control Unit. Controlmatic E.2. Type Series Booklet Automatic Control Unit Controlmatic E.2 Type Series Booklet Legal information/copyright Type Series Booklet Controlmatic E.2 All rights reserved. The contents provided herein must neither be distributed,

More information

Automatic Valve Proving Control

Automatic Valve Proving Control ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Automotive and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

Electronic Single and Twin Pump System Pressure Managers

Electronic Single and Twin Pump System Pressure Managers Electronic Single and Twin Pump System Pressure Managers Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING, OPERATING

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

Expansion Vessels for Potable Installations

Expansion Vessels for Potable Installations 4. Expansion Vessels for Potable Installations Domestic installations lose millions of litres of potable water due to expansion water leaking from the vent and expansion pipe. Flamco s Airfix diaphragm

More information

Pressure independent control valve (PICV) FLOWMATIC

Pressure independent control valve (PICV) FLOWMATIC Pressure independent control valve (PICV) FLOWMATIC 145 series FM 21654 003 01262/19 GB replaces dp 01262/17 GB Function The pressure independent control valve is a device composed of an automatic flow

More information

Multiple Pressure Booster Systems With Variable Speed Controller Type BL

Multiple Pressure Booster Systems With Variable Speed Controller Type BL Multiple Pressure Booster Systems With Variable Speed Controller Type BL General Characteristics - Single or multistage pumps - Horizontal or vertical mounting - Total head 30m ~ 250m - Material construction:

More information

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S06* Valve Proving System VDK 200 A S06* Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S02 Valve Proving System VDK 200 A S02 Valve proving system with the following approvals. UL Recognized File # MH17004 CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

Pneumatic Outflow Control

Pneumatic Outflow Control Technical Bulletin Pneumatic Outflow Control Pneumatically powered controls for the precise limitation of the volumes of waste water and rain water Contents Applications... 3 Success features... 4 Technical

More information

Operating instructions Electrical switching facility pco

Operating instructions Electrical switching facility pco Operating instructions Electrical switching facility pco from software version V1.33 on TABLE OF CONTENTS 1. Before you start... 4 1.1 Brief description... 4 1.2 Using this manual... 4 2. pco integrated

More information

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly. Components preparation and pressure adjustment ABP Overview ABP is a component that enables boosting by s only up to twice primary pressure (.0MPa max.) in combination with using air tank but not using

More information

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119 Pressure switch type CS December 2001 DKACT.PD.P10.A2.02 520B1119 Introduction Pressure switch type CS is part of the Danfoss pressure control range. All CS pressure switches have a built-in pressure-operated,

More information

KGW - ISOTHERM. Operating Instructions. Level controlling device for liquid nitrogen LEVEL CONTROL LN2

KGW - ISOTHERM. Operating Instructions. Level controlling device for liquid nitrogen LEVEL CONTROL LN2 KGW - ISOTHERM Germany 76185 Karlsruhe Gablonzer Straße 6 Tel. 0049 / 721 / 95897-0 Fax. 0049 / 721 / 95897-77 email:info@kgw-isotherm.de Internet: www.kgw-isotherm.de Operating Instructions Level controlling

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

1 Notes on the operating manual Liability and guarantee Safety Description of the device... 9

1 Notes on the operating manual Liability and guarantee Safety Description of the device... 9 Reflexomat with Touch controller with one compressor: RS 150/1, RS 300/1, RS 400/1, RS 580/1 with two compressors: RS 90/2, RS 150/2, RS 300/2, RS 400/2, RS 580/2 01.06.2014 GB Operating manual Original

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 9 ACCUMULATORS The material needed for outcome 2 is very extensive so there are

More information

OEM Manual. MODEL ½ Digit DRUM SCALE

OEM Manual. MODEL ½ Digit DRUM SCALE OEM Manual MODEL 4020-3 ½ Digit DRUM SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA & Canada) Phone:

More information

RAM 4021 Operation Manual

RAM 4021 Operation Manual RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For your safety...3 Description...3 Set-up mode...4 Annunciator lights/alarms...4 Operation...5 Calibration...6

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

Vacuum spray degassing

Vacuum spray degassing Vacuum spray degassing Servitec 35-95 01.04.2014 GB Operating manual Original operating manual Contents English Contents 1 Notes on the operating manual... 5 2 Liability and guarantee... 5 3 Safety...

More information

RAM 4021-DPX Operation Manual

RAM 4021-DPX Operation Manual RAM 4021-DPX Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS ABL 4021-DPX / RAM 4021-DPX For Your Safety... 3 Description... 3 Setup Mode... 4 Lights/Alarms... 4 Operation...

More information

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES I N S T R U C T I O N - M A N U A L CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES FUNCTION: Conductivity level limit switches are based on the principle of measuring level through the electrical

More information

Experiment Instructions. Circulating Pumps Training Panel

Experiment Instructions. Circulating Pumps Training Panel Experiment Instructions Circulating Pumps Training Panel Experiment Instructions This manual must be kept by the unit. Before operating the unit: - Read this manual. - All participants must be instructed

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) 42047 Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 45052 Constant Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor

More information

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG33KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG33KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) ENGLISH ENGLISH ENGLISH ENGLISH Installation user s manual Warning! electrical scheme modified JANUARY 2005 version 3.3 JOLLY2 DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) 6 different operating modes

More information

AUTROL 217 Expansion and pressurization Systems

AUTROL 217 Expansion and pressurization Systems Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE15C150, VE18C150, VE25C150 PART NO: 2226010, 2226020, 2226025 OPERATION & MAINTENANCE INSTRUCTIONS LS0715 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Arrow Valves Ltd Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Tel 01442 823 123 Fax 01442 823 234 www.arrowvalves.co.uk Model shown

More information

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For Your Safety... 2 Description.... 2 Setup Mode.... 2 Lights/Alarms.... 3 Operation.... 4 Calibration....

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

Differential pressure controls, Type MP 54, 55 and 55A

Differential pressure controls, Type MP 54, 55 and 55A MAKING MODERN LIVING POSSIBLE Technical brochure Differential pressure controls, Type MP 54, 55 and 55A MP 54 and oil pressure controls are used as safety switches to protect refrigeration compressors

More information

Differential Pressure Control Types MP 54, MP 55 and MP 55A

Differential Pressure Control Types MP 54, MP 55 and MP 55A MAKING MODERN LIVING POSSIBLE Data sheet Differential Pressure Control Types MP 54, MP 55 and MP 55A MP 54 and MP 55 oil differential pressure controls are used as safety switches to protect refrigeration

More information

Hydro Dome GRUNDFOS INSTRUCTIONS

Hydro Dome GRUNDFOS INSTRUCTIONS GRUNDFOS INSTRUCTIONS Hydro Dome Installation and operating instructions Montage- und Betriebsanleitung Notice d installation et d entretien Istruzioni di installazione e funzionamento Instrucciones de

More information

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. LTB013EN Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. to IECEx scheme Subject to technical modification Bachofen AG Ackerstrasse 42

More information

INNOVATIVE PRESSURE COMPETENCE Pressure holding & degassing equipment

INNOVATIVE PRESSURE COMPETENCE Pressure holding & degassing equipment Technomat Duo Plus Pressure holding Degassing Topping up Excess drain off Temperature measurement Oxygen measurement Pressure holding & degassing equipment Advantage! Certified quality ade in Germany 2

More information

Instruction Manual Dräger MSI P7 and MSI P7 plus

Instruction Manual Dräger MSI P7 and MSI P7 plus Dräger MSI GmbH Rohrstraße 32 58093 Hagen Tel.: +49-2331 / 9584-0 Fax: +49-2331 / 9584-29 e-mail: info@draeger-msi.de D 923; Edition 2011-01-01 Content 1. General Hints Page 4 2. The Instrument 2.1 Front

More information

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013 Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release

More information

Remotely-installed Hydraulic Module

Remotely-installed Hydraulic Module Remotely-installed Hydraulic Module HDM 1.1-2.2 Single or twin pump ACC-PRC001E-GB Table of Contents Application Considerations Unit sizing...4 Unit placement... 4 Minimum water volume... 4 Selection Procedure...5

More information

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM

More information

GV Standard X-Vent. Setup, Commissioning & Installation Guide

GV Standard X-Vent. Setup, Commissioning & Installation Guide GV Standard X-Vent Setup, Commissioning & Installation Guide Technical experts in the design, manufacture and supply of precision engineered, architectural rooflights for residential and commercial buildings.

More information

HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION

HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION Introduction: Hypoxic Air Fire Prevention System is a revolutionary fire prevention technology. It has the unique ability to create a breathable

More information

ELADOS EDP L Diaphragm Metering Pump Type

ELADOS EDP L Diaphragm Metering Pump Type ELADOS EDP L Diaphragm Metering Pump Type 04800-06700 Motor-driven diaphragm pump with integrated frequency converter High reserves due to a powerful asynchronous motor High flexibility due to variably

More information

V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS

V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS V10K GAS FEED SYSTEM WALLACE & TIERNAN PRODUCTS V10K SYSTEM: PROVEN TECHNOLOGY WORLDWIDE IN USE Since Charles F. Wallace and Martin F. Tiernan discovered the first chlorine gas feed system in 1913 the

More information

USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH

USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH THIS MANUAL IS INTENDED FOR TECHNICAL STAFF IN CHARGE OF THE INSTALLATION, THE OPERATION AND THE MAINTENANCE OF THIS PRODUCT

More information

Expert Hydrostatic Level Transmitters

Expert Hydrostatic Level Transmitters Expert Hydrostatic s General Features MJK Expert hydrostatic level transmitters are designed for level measurement by submerging the transmitter in open channels, drains and tanks. Expert hydrostatic level

More information

Pressure switch Type BCP

Pressure switch Type BCP Data sheet Pressure switch Type BCP The BCP type is a series of dedicated switches for safety and monitoring of steam and hot water boilers. The BCP incorporates a single-pole changeover microswitch where

More information

Flexcon. Flamco. Flamco. Diaphragm pressure expansion vessels FLEXCON C 2-80 FLEXCON CE FLEXCON M FLEXCON V-B FLEXCON EXPANSION VESSELS

Flexcon. Flamco. Flamco. Diaphragm pressure expansion vessels FLEXCON C 2-80 FLEXCON CE FLEXCON M FLEXCON V-B FLEXCON EXPANSION VESSELS FLEXCON EXPANSION VESSELS Flexcon Diaphragm pressure expansion vessels FLEXCON C 2-80 FLEXCON CE 110 1000 FLEXCON M FLEXCON V-B 2005 edition / EXP Choose quality choose a Flexcon the choice of a satisfied

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

Pressure switches for air and water CS

Pressure switches for air and water CS Data sheet Pressure switches for air and water CS CS pressure switches have a built-in pressure operated, three-pole switch. The contact position of which depends on the pressure in the connector and the

More information

Electronic gas volume corrector model DGVC-04

Electronic gas volume corrector model DGVC-04 Electronic gas volume corrector model DGVC-04 1. Introduction The following user s manual gives information about the installation, configuration, usage and storage of the electronic gas volume corrector

More information

reflex gigamat Pressure-maintaining station Assembly, operating and maintenance instructions Status 03/07

reflex gigamat Pressure-maintaining station Assembly, operating and maintenance instructions Status 03/07 Pressure-maintaining station Assembly, operating and maintenance instructions Status 03/07 Table of contents General Assembly Overview 3 Type key for control unit, control panel 4 General safety instructions

More information

Flamco

Flamco EN 7-30 Flamco www.flamcogroup.com EN 7-30 INSTLLTION ND OPERTING INSTRUCTIONS Contents Page 1 General 3 1.1 bout this manual 3 1.2 Other supplied documentation 3 1.3 Use of Flamco products 3 1.4 Further

More information

CALEFFI. Ball zone valves. series /03 GB

CALEFFI. Ball zone valves. series /03 GB all zone valves series cert. n ISO / Function Zone valves are used to automatically shut-off the flow of carrier fluid distributed to a system. Specifically: -In central heating systems, they support the

More information

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013 September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking

More information

Mobile High Pressure Compressor Unit for Compressing Air and Breathing Air. PE 250-TE with compressor control (optional equipment)

Mobile High Pressure Compressor Unit for Compressing Air and Breathing Air. PE 250-TE with compressor control (optional equipment) Mobile High Pressure Compressor Unit for Compressing Air and Breathing Air Types: PE 200-TE PE 250-TE PE 300-TE Production status: F02 PE 250-TE with compressor control (optional equipment) General Medium

More information

Airfix. Flamco. Flamco. Pressure expansion vessels for sanitary appliances and potable water systems AIRFIX A AIRFIX D AIRFIX D-E

Airfix. Flamco. Flamco. Pressure expansion vessels for sanitary appliances and potable water systems AIRFIX A AIRFIX D AIRFIX D-E AIRFIX EXPANSION VESSELS Flamco Airfix Pressure expansion vessels for sanitary appliances and potable water systems AIRFIX A AIRFIX AIRFIX -E Flamco Edition 2005 / EXP Flamco Flamco offers you a wide choice

More information

Columbus Instruments

Columbus Instruments 0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011

More information

Pressurisation Systems. Variomat. Pump Controlled Pressurisation Systems. Pressure maintenance Deaeration Water make-up. For Control Touch:

Pressurisation Systems. Variomat. Pump Controlled Pressurisation Systems. Pressure maintenance Deaeration Water make-up. For Control Touch: Variomat Pump Controlled Pressurisation Systems Pressure maintenance Deaeration Water make-up For Control Touch: 17 Control Unit Control Basic Control Basic S Control Touch 2-line LCD display 8 control

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013 October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve

More information

INDUSTRIAS IBAIONDO, HYDROPNEUMATIC TANKS

INDUSTRIAS IBAIONDO, HYDROPNEUMATIC TANKS IBAIONDO, HYDROPNEUMATIC TANKS IBAIONDO, INTRODUCTION Hydropneumatic tanks are designed to be used in potable water supply installations as a part of the pressure booster set in order to ensure the adequate

More information

4/2 way Pneumatic Solenoid Valve

4/2 way Pneumatic Solenoid Valve 4/2 way Pneumatic Solenoid Valve Compact design Push-over solenoid coil Exhaust air can be regulated Tube, threaded and sub-base connections Type combined with Seat valve version Type 2508 Type 2510/11

More information

EnerVal. Technical data litre storage capacity. Buffer storage vessels

EnerVal. Technical data litre storage capacity. Buffer storage vessels EnerVal Buffer storage vessels Technical data 200-10000 litre storage capacity Contents Title Page number EnerVal (200-2000) Description 3 Part No. 4 Technical data 6 Dimensions 7 EnerVal G (1000-10000)

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

AUTOMATIC HOSE TEST UNIT, TYPE SPU

AUTOMATIC HOSE TEST UNIT, TYPE SPU VALVES AND FITTINGS UP TO 14,000 BAR TEST AND CONTROL EQUIPMENT H IGH PRESSURE TECHNOLOGY AUTOMATIC HOSE TEST UNIT, TYPE SPU Pressure range from 1 up to 10,000 bar User-friendly touch panel operation HIGH-PRESSURE

More information

AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE

AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE AIR COMPRESSOR MANUAL INSTALLATION, OPERATION AND MAINTENANCE GUIDE 1. DESCRIPTION The compressor is a reciprocating air pump mounted on and driven by an electric induction motor. Mounted on a sturdy frame

More information