Designing a Pond Loop using. Alan Watts, CGD, IAI AWEB Supply Baton Rouge, LA
|
|
- Karen Mason
- 6 years ago
- Views:
Transcription
1 Designing a Pond Loop using Alan Watts, CGD, IAI AWEB Supply Baton Rouge, LA
2 The POWER of WATER ¾ of the Earth Surface is covered by WATER
3 Some See A Pond... We See a Fuel Free, Emission Free, Power Plant created through demand reduction when used in conjunction with geo-exchange heat pumps
4 Ability of Water to Handle Energy Example: 1 acre pond, 10 deep average 208 x 208 = 43,264 ft². 43,264 x 10 = 432,640 cubic feet 432,640 x 7.5 gal. cubic feet = 3,244,800 gal. 3,236,372 x 8.34 = 27,061,632 lbs... 27,061,632 lbs... or Btu s 1 Btu raises 1 lb. water 1 degree in 1 hour
5 Example- Small Pond Midwest A 10 ton (150,000 Btu/hr) heat pump system connected to a pond loop SLIM JIM Geo Lake Plate exchanger. Question: What effect does this system have on the temperature of the pond?
6 Small Pond Midwest Answer: Remember it would require approximately 27,000,000 Btu s to raise the temperature of the pond 1 Deg. F. Now, lets assume the impossible, no wind or evaporation to dissipate heat, no spring to replenish the pond water, and one 10 ton unit is running at full speed for 10 hours in cooling adding 150,000 Btu/hr into the pond. That would be a total of 150,000* 10 = 1,500,000 Btu s.
7 Small Pond Midwest This could change the pond temp F per day. This is insignificant when you consider a steady 5 MPH wind blowing for 3 days can lower the pond temperature by as much as 5 Deg F.
8 Pond Temperature Change Calculator AWEB SUPPLY 7350 Tom Drive, Baton Rouge, LA Phone: Fax: /17/2010 HR Pond/Lake Calculations Project: Example Location: Midwest Heat of Rejection (HR): 150,000 Btu/Hr 10 Tons (HR) 1 Ton (HR): 15,000 Btu/Hr Length: 208 ft Width: 208 ft Surface Area:.99 Acre Surface Area: 43,264 sq. ft. Cu. Ft of Water: 432,640 cu. ft. Gal. of Water: 3,236,372 Gal. Lbs of Water: 26,991,344 Lbs Full Speed Run Time in 24 hours: 10 Hr Temp change per hour:.0056 F Temp change per day:.0556 F Btu's Required to Raise the Water Temp 1 F in 1 day: 2,699,134 Btu/Hr Ton(s) Required to Raise the Water Temp 1 F in 1 day: 180 Tons (HR) Pond Dimensions AVG Depth: 10 ft Temp. F : Water influx: Gal/Day Lbs Influx Water Temp: These basic calculation are done without taking into account for the gains or losses from incoming solar radiation, net advected energy, the energy in evaporation and condensation, the conduction of sensible heat from the water to the atmosphere, or vice versa, etc YELLOW = YELLOW CELL IS USER INPUT Version GREEN = GREEN FIELD IS CALCULATED
9 What is a Slim Jim Geo Lake Plate It is a simple, labor-friendly alternative to polyethylene pipe (lake loops) for fluid to fluid heat transfer in any water cooled refrigeration or heat pump equipment in (ponds/lakes/rivers/oceans). Easy to install (labor friendly) Easy to flush No limit to job size - single to multiple units
10 Family of Slim Jim & Geo Lake Plates
11 Size Does Matter By grouping like Slim Jim Geo Lake Plates in parallel they can accommodate almost any load 200 Ton Preassembled Bank 8 Ton Preassembled Bank 5 Ton Single Plate
12 Just Add Water (3) 8SJ040TCAMT3F3 40 Ton Preassemblies Banks
13 Project Information Sheet
14 HVAC Project 1 Equipment Type Equipment: WaterFurnace Envision TM NXW540 Source Water Temperatures: Summer: 81 F (Warmest at installation depth) Winter: 39 F (Coldest at installation depth)
15 Temperature Pond Depth vs. Temperature Copyright 1997, American Society Of Heating, Air-conditioning and Refrigeration Engineers Inc.,
16 The Summer condition is circled in RED Capacity Data sheet WaterFurnace Envision NXW540
17 Capacity Data sheet WaterFurnace Envision NXW540 The Winter condition is circled in BLUE We need to extrapolate the data to find a EST = 35 F EST = 30 F with a HE of MBTUH EST = 50 F with a HE of MBTUH The EST spread from 30 to 50 is 20 ( ) = = = = EST = 35 F with a HE of MBTUH
18 HVAC Project 1 Project Information Sheet Us the Envision NXW540 data sheets and the pond data to complete the Project Information Sheet
19 HVAC Project 1 Sizing Using the Slim Jim Geo Lake Plate design selection software, the Summer & Winter data is entered. The size and configuration of the Slim Jim Geo Lake Plate required for this project is displayed. Water = W Brine = B Summer Cooling Condition Cooling HR / Calculate Equipment LWT EWT F LWT F HR (kbtu) GPM/T Winter Heating Condition Heating HE / Calculate Equipment LWT EWT F LWT F Pond/Lake Temp (C1) F (Enter the Warmest temperature) Pond/Lake Temp (H1) F (Enter the Coldest temperature) Water = W Brine = B HE (kbtu) GPM/T Equipment EWT (H1) Equipment LWT (H2) 0.0 F Equipment EWT (C1) 0.0 F F Equipment LWT (C2) F T1 T2 0.0 LMTD T1 T2 0.0 LMTD Summer Duty Load "U" Value * Suggested SLIM JIM Geo Lake Plate surface ºF LMTD Winter ºF LMTD kbtu/hr Duty Load 0.0 kbtu/hr Btu/hr. ft2 ºF * 100 is default "U" Value * 80 Btu/hr. ft2 ºF ft² Suggested SLIM JIM Geo Lake Plate surface ft² SLIM JIM Geo Lake Plate Sizes GPM/SJ ft²/sj SJ Plates Suggested SJ Plates Suggested For SJ Plates Suggested SJ Plates Suggested For SLIM JIM Geo Lake Plate Sizes GPM/SJ ft² for Surface Area Application for Surface Area Application SJ-02T 24 in X 72 in ###### 24 SJ-02T 24 in X 72 in ####### 24 SJ-03T 48 in X 60 in ###### 40 SJ-03T 48 in X 60 in ####### 40 SJ-04T 48 in X 72 in ###### 48 SJ-04T 48 in X 72 in ####### 48 SJ-05T 48 in X 96 in ###### 64 SJ-05T 48 in X 96 in ####### 64 SJ-05TC 24 in X 180 in ###### 60 SJ-05TC 24 in X 180 in ####### 60 SJ-08T 48 in X 144 in ###### 96 SJ-08T 48 in X 144 in ####### 96 SJ-10T 48 in X 180 in ###### 120 SJ-10T 48 in X 180 in ####### 120 LEGEND LEGEND #### Version Brine / B = water with a freeze inhibiting solution WARNING POSSIBLE INPUT ERROR EWT = equipment entering water temperature Select Units of Measurement EWT IS BELOW FREEZING - PLEASE CONSULT AWEB SUPPLY FOR SUPPORT US UNITS GPM/SJ = gallon per minute / Slim Jim Plate GPM/T = gallon per minute / System requirement HE = heat extracted in kbtu/hr HR = heat rejected in kbtu/hr LMTD = Logarithmic Mean Temperature Difference LWT = equipment leaving water temperature SJ = Slim Jim User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H1-C2= T1 & H2-C1= T2 Abbreviations and Definitions U = overall coefficient of heat transfer. Btu/hr. ft 2 ºF Water / W = water with no freeze inhibiting solution Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H1-C2= T1 & H2-C1= T2 * 100 is default Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply APPROACH TEMP IS TOO LOW - PLEASE CONSULT AWEB SUPPLY FOR SUPPORT You may use this program to obtain preliminary design selection of a SLIM JIM Geo Lake Plate for your application. Your use of this service is subject to the limitations set forth below. This program is provided as a convenience to our customers solely to assist them in design and selection of SLIM JIM Geo Lake Plate for their applications. We offer this service only as a preliminary design tool for use in selection of the SLIM JIM Geo Lake Plate. It is to be used for no other purpose. The validity and value of the results you achieve depend critically upon the accuracy of the information you provide. AWEB Supply disclaims any liability for the results you obtain using this program, and SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. You are encouraged to contact AWEB Supply at to obtain assistance in making your final selection
20 HVAC Project 1 Using the Slim Jim data is entered. The data from the specification sheet is entered in the Yellow cells Summer Design Geo Lake Plate design selection software, the Summer Water = W Brine = B B Pond/Lake Temp (C 1 ) Equipment EWT (H1) Equipment LWT (H2) Summer Cooling Condition Cooling HR / Calculate Equipment LWT EWT F LWT F HR (kbtu) F (Enter the Warmest temperature) F F GPM/T T 1 T LMTD 13.4 Summer Duty Load "U" Value * Suggested SLIM JIM Geo Lake Plate surface ºF LMTD kbtu/hr Btu/hr. ft2 ºF f t² * 100 is default SLIM JIM Geo Lake Plate Sizes GPM/SJ ft²/sj SJ-02T 24 in X 72 in 6 24 SJ-03T 48 in X 60 in SJ-04T 48 in X 72 in SJ-05T 48 in X 96 in SJ-05TC 24 in X 180 in SJ-08T 48 in X 144 in SJ-10T 48 in X 180 in LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 SJ Plates Suggested for Surface Area SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
21 HVAC Project 1 Winter Design Using the Slim Jim data is entered. The data from the specification sheet is entered in the Yellow cells Geo Lake Plate design selection software, the Winter Water = W Brine = B B Heating HE / Calculate Equipment LWT EWT F LWT F HE (kbtu) 35.0 Pond/Lake Temp (H 1 ) Equipment EWT (C1) Equipment LWT (C2) Winter Heating Condition GPM/TOTAL F (Enter the Coldest temperature) F WARNING FREEZE F INHIBITING SOLUTION REQUIRED T 1 T LMTD 6.2 Winter Duty Load "U" Value * Suggested SLIM JIM Geo Lake Plate surface SLIM JIM Geo Lake Plate Sizes GPM/SJ SJ-02T 24 X SJ-03T 48 X SJ-04T 48 X SJ-05T 48 X SJ-05TC 24 X SJ-08T 48 X SJ-10T 48 X LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 ft² ºF LMTD kbtu/hr Btu/hr. ft2 ºF ft² SJ Plates Suggested for Surface Area * 100 is default SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
22 HVAC Project 1 Dominate Condition Using the Slim Jim Geo Lake Plate design selection software allows you to design for the dominate condition for the size and configuration for the Slim Jim Geo Lake Plate required for this project. Suggested SLIM JIM Geo Lake Plate surface ft²/sj SLIM JIM Geo Lake Plate Sizes GPM/SJ ft²/sj SJ-02T 24 in X 72 in SJ-03T 48 in X 60 in SJ-04T 48 in X 72 in SJ-05T 48 in X 96 in SJ-05TC 24 in X 180 in SJ-08T 48 in X 144 in SJ-10T 48 in X 180 in LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 SJ Plates Suggested for Surface Area SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply Summer Condition Winter Condition Suggested SLIM JIM Geo Lake Plate surface SLIM JIM Geo Lake Plate Sizes GPM/SJ SJ-02T 24 X SJ-03T 48 X SJ-04T 48 X SJ-05T 48 X SJ-05TC 24 X SJ-08T 48 X SJ-10T 48 X LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 ft² ft² SJ Plates Suggested for Surface Area SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
23 HVAC Project 1 Selection Option 1 SLIM JIM Geo Lake Plate Sizes SJ-02T 24 X SJ-03T 48 X SJ-04T 48 X SJ-05T 48 X SJ-05TC 24 X SJ-08T 48 X SJ-10T 48 X Winter Heating Condition SJ Plates Suggested GPM/SJ ft² for Surface Area SJ Plates Suggested For Application SJ060TAM3F3
24 Installation Suggested list of items used for this type of installation: (1) - 3" Back Up Flange kit (To connect 3" Flange to 3" HDPE Pipe) (2) - 3" PE Fusion Elbow 90 Adapter 3" PE Pipe Misc. Nylon wire ties to secure the rebar to the HDPE pipe from the shore to the Slim Jim plate Misc. Rebar cut to short lengths to overcome the buoyancy and allow the liquid filled HDPE pipe to sink to the bottom from the shore to the Slim Jim plate Note: PVC pipe with caped ends can be added to allow the assembly to float at the surface of the water. This will allow the Slim Jim assembly to be placed into position before the system is flushed with fluid. Once the Slim Jim assembly is positioned and flushing of the loop system has started the PVC pipe will allow the Slim Jim assembly to submerge in the upright position and sink to the bottom as the air in the Slim Jim assembly is displaced with the fluid used in the loop system. Once the Slim Jim assembly skid plates have settled on the bottom and all the air is removed from the assembly the PVC pipe can remain in place.
25 4SJ040TAM3F3 Installation Photos Picture Perfect
26 Flushing The fluid flow from the Heat Pump equipment must enter the lowest connection on the Slim Jim assembly. The fluid flow returning to the Heat Pump equipment must exit the highest connection on the Slim Jim assembly. This will insure any remaining air in the system will not be trapped in the Slim Jim assembly. For proper operation and maximum performance, follow the Slim Jim or Geo Lake Plate SUGGESTED INSTRUCTIONS FOR INSTALLATION.
27 Auxiliary Heat Systems on any earth/lake loop in extreme conditions may call for auxiliary heat. When this happens and the return water to the unit is 32 F or less and the unit calls for auxiliary heat, it should be designed to stay engaged until the thermostat(s) are fully satisfied and the system shuts down. This will allow for down time and loop regeneration regardless of loop type In most applications a relay will need to be added to keep the supplemental heat engaged until the thermostat(s) are fully satisfied.
28 HVAC Project 2 Equipment Type Equipment: WaterFurnace Envision TM NS060-ECM Source Water Temperatures: Summer: 81 F (Warmest at installation depth) Winter: 39 F (Coldest at installation depth)
29 The Summer condition is circled in RED Capacity Data sheet WaterFurnace Envision NS060
30 Capacity Data sheet WaterFurnace Envision NS060 The Winter condition is circled in BLUE We need to extrapolate the data to find a EWT = 35 F EWT = 30 F with a HE of 31.8 kbtu/h EWT = 40 F with a HE of 39.2 kbtu/h The EWT spread from 30 to 40 is 10 ( ) = = = = 35.5 EWT = 35 F with a HE of 35.5 kbtu/h
31 HVAC Project 2 Summer Design Using the Slim Jim Geo Lake Plate design selection software, the Summer data is entered. Summer Cooling Condition The data from the specification sheet is entered in the Yellow cells Water = W Brine = B B Pond/Lake Temp (C 1 ) Cooling HR / Calculate Equipment LWT EWT F LWT F HR (kbtu) 90.0 Equipment EWT (H1) Equipment LWT (H2) F (Enter the Warmest temperature) F F 77.7 GPM/T T 1 T LMTD 13.5 Summer Duty Load "U" Value * Suggested SLIM JIM Geo Lake Plate surface ºF LMTD kbtu/hr Btu/hr. ft2 ºF ft²/sj * 100 is default SLIM JIM Geo Lake Plate Sizes GPM/SJ ft²/sj SJ-02T 24 in X 72 in SJ-03T 48 in X 60 in SJ-04T 48 in X 72 in SJ-05T 48 in X 96 in SJ-05TC 24 in X 180 in SJ-08T 48 in X 144 in SJ-10T 48 in X 180 in LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 SJ Plates Suggested for Surface Area SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
32 HVAC Project 2 Winter Design Using the Slim Jim Geo Lake Plate design selection software, the Winter data is entered. Winter Heating Condition The data from the specification sheet is entered in the Yellow cells Water = W Brine = B B Heating HE / Calculate Equipment LWT EWT F LWT F HE (kbtu) 35.0 Pond/Lake Temp (H 1 ) Equipment EWT (C1) Equipment LWT (C2) GPM/TOTAL F (Enter the Coldest temperature) F WARNING FREEZE F INHIBITING SOLUTION REQUIRED T 1 T LMTD 6.1 Winter Duty Load "U" Value * Suggested SLIM JIM Geo Lake Plate surface SLIM JIM Geo Lake Plate Sizes GPM/SJ SJ-02T 24 X SJ-03T 48 X SJ-04T 48 X SJ-05T 48 X SJ-05TC 24 X SJ-08T 48 X SJ-10T 48 X LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 ft² ºF LMTD kbtu/hr Btu/hr. ft2 ºF ft² SJ Plates Suggested for Surface Area * 100 is default SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
33 HVAC Project 2 Dominate Condition Using the Slim Jim Geo Lake Plate design selection software allows you to design for the dominate condition for the size and configuration for the Slim Jim Geo Lake Plate required for this project. Suggested SLIM JIM Geo Lake Plate surface 57.4 ft²/sj SLIM JIM Geo Lake Plate Sizes GPM/SJ ft²/sj SJ-02T 24 in X 72 in SJ-03T 48 in X 60 in SJ-04T 48 in X 72 in SJ-05T 48 in X 96 in SJ-05TC 24 in X 180 in SJ-08T 48 in X 144 in SJ-10T 48 in X 180 in LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 SJ Plates Suggested for Surface Area SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply Summer Condition Winter Condition Suggested SLIM JIM Geo Lake Plate surface SLIM JIM Geo Lake Plate Sizes GPM/SJ SJ-02T 24 X SJ-03T 48 X SJ-04T 48 X SJ-05T 48 X SJ-05TC 24 X SJ-08T 48 X SJ-10T 48 X LEGEND User Input: User to input their data in yellow fields 73.2 Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 ft² ft² SJ Plates Suggested for Surface Area 3.05 SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
34 HVAC Project 2 Shallow Water 38 F Winter Design Using the Slim Jim Geo Lake Plate design selection software, the Winter data is entered. Winter Heating Condition The data from the specification sheet is entered in the Yellow cells Water = W Brine = B B Heating HE / Calculate Equipment LWT EWT F LWT F HE (kbtu) 35.0 Pond/Lake Temp (H 1 ) Equipment EWT (C1) Equipment LWT (C2) GPM/TOTAL F (Enter the Coldest temperature) F WARNING FREEZE F INHIBITING SOLUTION REQUIRED T 1 T LMTD 5.0 Winter Duty Load "U" Value * Suggested SLIM JIM Geo Lake Plate surface SLIM JIM Geo Lake Plate Sizes GPM/SJ SJ-02T 24 X SJ-03T 48 X SJ-04T 48 X SJ-05T 48 X SJ-05TC 24 X SJ-08T 48 X SJ-10T 48 X LEGEND User Input: User to input their data in yellow fields Calculated Values: These are formula and cannot be changed by user Information Only: H 1 -C 2 = T 1 & H 2 -C 1 = T 2 ft² ºF LMTD kbtu/hr Btu/hr. ft2 ºF ft² SJ Plates Suggested for Surface Area * 100 is default SJ Plates Suggested For Application Flow Is BELOW Specs: Consult AWEB Supply Flow Is ABOVE Specs: Consult AWEB Supply
35 The Power of WATER Our Future
36 Thank You
The Hoffman Specialty Series 2000 consists of main
Pressure and/or Temperature Pilot Operated Steam Series 2000 The Hoffman Specialty Series 2000 consists of main valves, pilot valves, wells and hardware kits. They are designed to meet a wide range of
More informationHill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide
Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide Secondary Coolant System Start-Up Procedures June 2006 Produced by the Hill PHOENIX Learning Center DISCLAIMER This
More informationBrazed Heat Exchangers
Brazed Heat Exchangers The Brazed Heat Exchanger less is more The brazed plate heat exchanger is the most compact heat exchanger on the market today. Its high heat transfer efficiency in combination with
More informationENGINEERING DATA. Engineering Data
ENGINEERING DATA Engeerg Data 599 Average Depth 3.5 ft. ESTIMATING TOTAL GALLONS IN A POOL OR SPA Length 24 ft. Dia. Width Depth (deep) Depth (shallow) Radius 2 x 3.14 x A.D. x 7.5 = Gallons 12 x 12 x
More informationWARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only
Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)
More informationDISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES THIS REPORT WAS PREPARED BY THE ORGANIZATION(S) NAMED BELOW. NEITHRE THE ORGANIZATION(S) BELOW, NOR ANY PERSON ACTING ON BEHALF OF THEM: (A) MAKES
More informationFMU4X, FMC4X FMU4P, FMC4P
ENVIRONMENTALLY SOUND REFRIGERANT FMU4X, FMC4X FMU4P, FMC4P Product Specifications HORIZONTAL FAN COILS FMU4P and FMC4P 1 1/2, 2, 2 1/2, and 3 Tons FMU4X and FMC4X 1 1/2, 2 and 2 1/2 Tons ALL MODELS Horizontal
More informationBrazed Heat Exchangers - Edition 2. Click Anywhere to enter
Brazed Heat Exchangers - Edition 2 Click Anywhere to enter Brazed Heat Exchangers Menu - Edition 2 Introduction DX Evaporators/Chillers Water-Cooled Condensers Economizers/ Subscoolers Desuperheaters/
More informationPump On Demand. Skimmer System
Pump On Demand Skimmer System POD (Pump on Demand) Skimmer System Application Out-of-the-box LNAPL recovery in 2-inch and larger-diameter wells. The POD Skimmer model TR-610 recovers light-end hydrocarbons
More informationModel 26.5 WEAU242AA WEAU244BA 29.0 WEAU242BA 29.0 WEAU304AA 33.0 WEAU302AA WEAU304BA 33.0 WEAU302BA 33.
EVAPORATOR COILS A COIL UNCASED R 22 or R 410A SYSTEMS 1 5 Tons WEAU Certification applies only when the complete system is listed with ARI ISO 9001:2000 REGISTERED R 410A R 22 Size Shipping Weight Size
More informationProduct Data CAPVP, CARVP, CAPVU, CARVU EVAPORATOR COIL A COIL - CASED AND UNCASED UPFLOW, DOWNFLOW DESIGN FEATURES
CAPVP, CARVP, CAPVU, CARVU EVAPORATOR COIL A COIL - CASED AND UNCASED UPFLOW, DOWNFLOW Product Data CAPVP / CARVP A06001 A06002 CAPVU / CARVU The CAPVP, CARVP, CAPVU, and CARVU evaporator coils incorporate
More informationiphone Application Slurry Pump System Calculator Instructions
iphone Application Slurry Pump System Calculator Instructions Press + to start a New Calculation Enter in Title of the Calculation. Press on saved calculation to open and start calculation. Select U.S.
More informationBaffles and Traps Cryotrap
Baffles and Traps 362-6 Cryotrap Varian Low-Profile Water-Cooled Baffles combine 100% optical density with high conductance and unusually low overall height. They are especially useful in applications
More information4 IN. BALL LAUNCHER Engine Mounted / PTO Driven
4 IN. BALL LAUNCHER Engine Mounted / PTO Driven OPERATOR S PARTS and MAINTENANCE MANUAL 2006 EDITION BL-MAN-4EN Creation Revision date: 10MAR06 date: by: Ivon LeBlanc by: Table of Contents Table of Contents...
More informationProduct Data CAPMP, CARMP EVAPORATOR COIL A COIL - CASED MULTIPOISE CAPMP / CARMP CAPMP / CARMP (3619, 4823, 6025)
CAPMP, CARMP EVAPORATOR COIL A COIL - CASED MULTIPOISE Product Data (3619, 4823, 6025) A06009 A07904 The CAPMP and CARMP evaporator coils incorporate proven standards for reliable system operation and
More informationUser's Manual. Heavy Duty Dissolved Oxygen Meter. Model
User's Manual Heavy Duty Dissolved Oxygen Meter Model 407510 Introduction Congratulations on your purchase of Extech's Heavy Duty Dissolved Oxygen / Temperature Meter which simultaneously displays Dissolved
More informationTAZGO DIVISION. Available Services: Shearing, Plate Burning, Saw Cutting, Drilling
TAZGO DIVISION STEEL~STAINLESS~ALUMINUM Beams ~ Channel ~ Flat bar ~ HR Rounds ~ CR Rounds Angle ~ Square Tube ~ Rectangle Tube Pipe~ DOM~ Plate~ HR sheets ~ CR sheets~ Galvanized Sheets ~ Cross Members
More informationGAS SUPPLY DESIGN GUIDE
GAS SUPPLY DESIGN GUIDE Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers BENCHMARK Series Gas-Fired Boilers For models: BMK750 to BMK6000 Last Update: 06/20/2014 PR1 06/20/14
More informationENERGY BLADE 3K4. Energy Blade Installation Instructions
ENERGY BLADE 3K4 Energy Blade Installation Instructions 1 Contents General information 2 Scope of these instructions 2 Product information 2 Designated use 3 Warranty 3 Safety instructions 4 Assembly and
More informationEclipse Extern-A-Therm Recuperators
Design Guide 540 3/9/2009 Eclipse Extern-A-Therm Recuperators Models 300 MA - 2500 MA Copyright Copyright 2007 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation
More informationAir Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
More informationGerald D. Anderson. Education Technical Specialist
Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions
More informationLesson 27: Real-World Volume Problems
Student Outcomes Students use the volume formula for a right prism ( ) to solve volume problems involving rate of flow. Lesson Notes Students apply their knowledge of volume to real-world contexts, specifically
More informationCoils Designed to Fit Your Requirements. Temtrol Manufacturing OEM & Replacement Coils Since 1955
Temtrol Manufacturing OEM & Replacement Coils Since 1955 Coils Designed to Fit Your Requirements Chilled & Hot Water Direct Expansion Steam Distributing Condenser Standard Steam Quick Ship Program with
More informationExpansion Tank Design (Chilled Water)
Expansion Tank Design (Chilled Water) Table of Contents 1.0 Introduction... 2 1.1 Units... 2 2.0 Disclaimer... 2 3.0 Expansion Tank Types... 2 3.1 Open Tank... 2 3.2 Closed Tank with No Bladder... 3 3.3
More informationProduct Data. CAPVP, CARVP, CAPVU, CARVU Evaporator Coil A Coil --- Cased and Uncased Upflow, Downflow CAPVP / CARVP
CAPVP, CARVP, CAPVU, CARVU Evaporator Coil A Coil Cased and Uncased Upflow, Downflow Product Data CAPVP / CARVP A06001 A06002 CAPVU / CARVU The CAPVP, CARVP, CAPVU, and CARVU evaporator coils incorporate
More informationEvaporator (DX) Freon Applications 1 12 Tons MHF
Evaporator (DX) Freon Applications 1 12 Tons > > Used For small to medium freon applications The Global Leader In Heat Exchange Technology With seven decades of experience and commitment to total client
More informationAppalachian Basin Gas Well. Marietta College, Marietta, Ohio June 7-8, Development. Robert McKee, P.E. Design Engineer Multi Products Company
Appalachian Basin Gas Well Marietta College, Marietta, Ohio June 7-8, 2010 Casing Plunger Applications & Development Robert McKee, P.E. Design Engineer Multi Products Company Casing Plunger A.L. Lift Without
More informationNatural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)
Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please
More informationThis loop is filled with an antifreeze solution such
Solar Panel expansion Tank Sizing: Getting It right Part I The most common type of solar thermal system uses a closed piping loop between the collector array and storage tank heat exchanger. BY JOhN SIeGeNThAler
More informationSeptic Tank Buoyancy Control 101. David Lentz, P.E.
Septic Tank Buoyancy Control 101 David Lentz, P.E. Archimedes Principle https://physics.weber.edu/carroll/archimedes/principle.htm Archimedes Principle: The buoyant force is equal to the weight of the
More informationHOT SERIES (High Output Temperature) Geothermal Water to Water Heat Pump R-134A Refrigerant 2 Ton to 20 Ton Single Speed
Customer Manual HOT SERIES (High Output Temperature) Geothermal Water to Water Heat Pump R-134A Refrigerant 2 Ton to 20 Ton Single Speed 2 Customer Manual 5.2.3 Change is in the Air You are about to experience
More informationGas-Lift Test Facility for High- Pressure and High-Temperature Gas Flow Testing
40 th Gas-Lift Workshop Houston, Texas, USA Oct. 23 27, 2017 Gas-Lift Test Facility for High- Pressure and High-Temperature Gas Flow Testing Angel Wileman, Senior Research Engineer Southwest Research Institute
More informationV248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants
V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants Product Code No. LIT-12011515 Issued June 19, 2009 The V248 Series 3-Way Pressure-Actuated Water-Regulating Valves
More informationGeotech 1.66 Auto-Reclaimer Installation and Operation
Geotech 1.66 Auto-Reclaimer Installation and Operation Rev 10/19/12 Part # 16600165 TABLE OF CONTENTS CHAPTER 1: SYSTEM DESCRIPTION... 3 FUNCTION AND THEORY... 3 SYSTEM COMPONENTS... 4 CHAPTER 2: SYSTEM
More informationDRS4-RM Manual. Set Up Instructions for DRS4 Series Single Tank
Set Up Instructions for DRS4 Series Single Tank Inspect the packaging of the equipment to confirm that nothing was damaged during shipping. (Figure 1) Remove the resin tank(s) and valve(s) from the packaging.
More informationV248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure
V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants The V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants regulate water
More informationFloWash. Industrial Filter Cart
OPERATION AND MAINTENANCE MANUAL FloWash Industrial Filter Cart Read all instructions before installation or operation of equipment. Failure to comply with these instructions could result in bodily injury
More informationANALOG ULTRASOUND WATTMETER USP-30
ANALOG ULTRASOUND WATTMETER USP-30 USER MANUAL BC BIOMEDICAL USP-30 ULTRASOUND WATTMETER TABLE OF CONTENTS WARNINGS, CAUTIONS, NOTICES... ii DESCRIPTION... 1 TEST SETUP... 2 TESTING... 5 MANUAL REVISIONS...
More informationProduct Data. CK5A, CK5B, CK5P Furnace N-Coils. Sizes A018 thru A060
Product Data CK5A, CK5B, CK5P Furnace N-Coils Sizes A018 thru A060 This vertical design N-coil is a furnace coil designed to provide the highest standards of reliability and durability. The coils are offered
More informationCustomer Responsibilities. Important Customer Information. Cary 4000/5000/6000i UV-Vis spectrophotometer Site Preparation Checklist
Thank you for purchasing an Agilent instrument. To get you started and to assure a successful and timely installation, please refer to this specification or set of requirements. Correct site preparation
More informationLPS Product Guide. LPS Series Nitrogen Generators. N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved
LPS Product Guide N2-GEN LPSTM LPS Series Nitrogen Generators N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved - 2014 p 888 526 6284 e info@southteksystems.com w www.southteksystems.com
More informationTECHNICAL ACCESSORIES
A.R.I. VALVES S-050P AIR PLASTIC RELEASE 16 BAR Automatic Component A.R.I patent, Rolling Seal Mechanism: Dramatically reduces the possibility of obstruction by debris. Discharges high air flow rates upto
More information1 Exam Prep State Pool Contractor Feedback Questions and Answers
1 Exam Prep State Pool Contractor Feedback Questions and Answers 1. What valves are not part of the pool recirculation system? a. Rotary Valve b. Butterfly Valve c. Ball valves d. Hydrostatic Valves 2.
More informationApplication Worksheet
Application Worksheet All dimensions are nominal. Dimensions in [ ] are in millimeters. Service Conditions Medium Through Valve: Required C v : Temperature Maximum: Minimum: Normal: Flow Maximum: Minimum:
More informationSeparation of Acetone-Water with Aspen HYSYS V8.0
Separation of Acetone-Water with Aspen HYSYS V8.0 Liquid-Liquid Extraction with 3-Methylhexane as the Solvent 1. Lesson Objectives Learn how to build an extraction and solvent recovery flowsheet. Learn
More informationShell & Tube. JATCO Inc. Operating Manual
Shell & Tube JATCO Inc. Operating Manual 1 System Operation Operating Instructions System P&ID System Drawing Starting Procedure Shutting Down Service & Maintenance Trouble Shooting Guide Recommended Spare
More informationAPI Piping Plan 62: A Reliable Quench System
MAY05PUMPS&SYSp24-33 4/19/05 4:04 PM Page 24 It s one of the few methods you have to control the environment outside a mechanical seal. By Keith Schindler, PE, Schindler Engineering, Inc., and Paul McMahan,
More informationA Basic Approach to the Installation of Small Movement Expansion Joints. Peter Weykamp, P.E.
A Basic Approach to the Installation of Small Movement Expansion Joints Peter Weykamp, P.E. OBJECTIVE Avoid failures Share practices Simplify Guide Dialog NYSDOT TRANSITION Armor to Elastomeric Systems
More informationDan Johnson, CBP Swim, Incorporated Lead Dog Aquatic Consulting
Dan Johnson, CBP Swim, Incorporated Lead Dog Aquatic Consulting APSP/ANSI-7 Writing Committee APSP/ANSI/ICC-15 Writing Committee APSP/ANSI/ICC-5 Writing Committee (Chairman) International Swimming Pool
More informationMILE POINT TRAINING WALL JACKSONVILLE, FL. Geotextile Tube Installation
MILE POINT TRAINING WALL JACKSONVILLE, FL Geotextile Tube Installation PROJECT DESIGN Remove portion of existing training wall Construct new eastern and western training walls Deepen new flow improvement
More informationTroubleshooting Guide. Pg. 1
Troubleshooting Guide Pg. 1 Introduction to Automotive HVAC: Introduction to an AC System Review of AC System and components. Pg. 2 Troubleshooting: AC system Components AC System and its Components Receiver/
More informationType 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator
January 2009 Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator Introduction The Type 310A pilot-operated high-pressure regulator (Figure 1) is used where high capacity
More informationV246 Series 2-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants
Code No. LIT-19575 Issued January 1, 1 V46 Series -Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants Description The V46 Series -Way Pressure-Actuated Water-Regulating Valves
More informationCash Valve. Type G-4. Pilot Operated Pressure Reducing Regulator for Steam, Air and Gases. Flow Control
Cash Valve Type G-4 Pilot Operated Pressure Reducing Regulator for Steam, Air and Gases Issued - March 2001 CAVMC-0512-US-0609 ISO 9001 Certified Flow Control Description FIG 2042 - Bronze FIG 2043 - Bronze
More informationOVERVIEW. Flow Coefficient C v. Operating Conditions. Specific Gravity
VERVIEW This valve sizing software program is based on the use of nomenclature and sizing equations from ISA Standard S75.01 and IEC Standard 534-2. The sizing equations are based on equations for predicting
More informationIrrigation System Winterization and Pressurization Procedures
Irrigation System Winterization and Pressurization Procedures Introduction Any time that an irrigation system is filled and pressurized, or when the system is drained and water flushed from the system,
More informationSIZING AND CAPACITIES OF GAS PIPING
(IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is informative and is not part of the code. This appendix is an excerpt from the 2006 International Fuel Gas Code, coordinated with the section
More informationGas Lift Valve Testing
36 th Gas-Lift Workshop Stavanger, Norway February 4 8, 2013 Gas Lift Valve Testing Angel Wileman, Research Engineer Southwest Research Institute, Fluid Dynamics Feb. 4 8, 2013 2013 Gas-Lift Workshop 1
More informationInstallation and Operation 370ESP (Electric Single-Point Purger) & 370ESPR (Retrofit Purger)
IB-77 Installation and Operation 370ESP (Electric Single-Point Purger) & 370ESPR (Retrofit Purger) These installation, operation and technical instructions should be used by experienced personnel as a
More informationSHOP WELDED TANKS STANDARD CONNECTIONS
STEEL WELDED TANKS Tanks are constructed using 3/16 and ¼ inch A36 material. Welding and testing are performed according to API 12F specifications. Shop welded tanks are also available in special sizes
More informationSPECIFICATION // DATA SHEET WATER DRAIN VALVE AM SENSORS LTD AMS-S-084/DS/ (ISSUE 1)
SPECIFICATION // DATA SHEET WATER DRAIN VALVE 1 Introduction The Water Drain Valve was developed for a major oil company to detect the presence of fuel when discharging water through the drain line of
More informationDewatering Landfill Gas Wells to Maximize LFG Collection
Dewatering Landfill Gas Wells to Maximize LFG Collection QED Environmental Systems Inc. Ann Arbor, Michigan - San Leandro, California Copyright QED Environmental Systems, Inc. 2013; all rights reserved.
More informationHAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
HAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING HAYWARD TFS SERIES FLOW METERS. FAILURE
More informationNAVIGATOR PROP BUILDING INSTRUCTIONS & PHOTOS
NAVIGATOR PROP BUILDING INSTRUCTIONS & PHOTOS Science under the ice Ice sheet At regional competitions the ice is simulated by 8 ft x 4 ft ½-inch foam sheeting (Home Depot part #703990 [in store only],
More informationGeotech 1.66 Auto-Reclaimer
Geotech 1.66 Auto-Reclaimer Installation and Operation Rev 9 8/31/06 Part # 16600165 TABLE OF CONTENTS CHAPTER 1: SYSTEM DESCRIPTION... 3 FUNCTION AND THEORY... 3 SYSTEM COMPONENTS... 4 CHAPTER 2: SYSTEM
More informationModel Series 62 Constant Differential Relay
Siemens Industry, Inc. INSTALLATION AND SERVICE INSTRUCTION INTRODUCTION Model Series 62 Constant Differential Relay Rev 11 March 2011 Supersedes Rev 10 The Constant Differential Relay maintains a constant
More informationRecirculating Coolers
(Chillers) - Basic type Low Temp. - General Type Low Temp. - Intelligent type Selection Guide Recirculating Cooler Basic type General type (Low temp.) Intelligent type (Low temp.) Working Temp. Range (
More informationPractical Guide. By Steven T. Taylor, P.E., Member ASHRAE
ractical Guide The following article was published in ASHRAE Journal, March 2003. Copyright 2003 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational
More informationTANKS 4.0.9d Emissions Report - Detail Format Tank Indentification and Physical Characteristics
Page 1 of 5 Tank Indentification and Physical Characteristics Identification User Identification: City: State: Company: Type of Tank: Description: SRX-T-101 San Francisco AP California Mobius Vertical
More informationFlow Sensors & Hydrometers Specification Sheet
Baseline Flow s and Hydrometers Baseline s smart flow sensors and hydrometers are two-wire ready flow measurement and control devices that are pre-programmed with the correct K and Offset values. In addition,
More informationGas Furnaces 95AF2V. Warranty Heat Exchanger - 20 Year Limited Parts - 5 Year Limited
PRODUCT SPECIFICATIONS INSTALLATION OPTIONS Available in Upflow/Horizontal and Counterflow models HEAT EXCHANGER Aluminized steel primary heat exchanger with crimped non-welded construction Stainless steel
More informationThe density of a substance is the same for all samples of that substance.
8.8.a Density and Buoyancy Students know density is mass per unit volume. P71 Wood Steel The density of a substance is the same for all samples of that substance. 1. The two blocks shown have the same
More informationCCT-7320/ROC-2313 Reverse Osmosis Controller
CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation
More information829S1 Series Flexflo Pilot
REDQ Regulators The Model 829S1 Provides Versatile Pressure Regulation At An Economical Price. The Model 829S1 Flexflo Pilot is a reversible pressure control regulator (seat & nozzle) that is used in conjunction
More informationPressure is defined as force per unit area. Any fluid can exert a force
Physics Notes Chapter 9 Fluid Mechanics Fluids Fluids are materials that flow, which include both liquids and gases. Liquids have a definite volume but gases do not. In our analysis of fluids it is necessary
More informationBest Practices Pneumatics Machine & Design. Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016
Pneumatics Machine & Design Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016 Contents at Atmospheric Air The air at a compressor s intake contains about 78% nitrogen,
More informationMODEL 1329 Tank Gauge
SERVICE INSTRUCTIONS FOR PETRO-METER 1329 GAUGE SERVICE INSTRUCTIONS MODEL 1329 Tank Gauge www.petro-meter.com Petro-Meter 1329 series Service Instructions HOW TO DETERMINE IF A PETRO-METER IS IN GOOD
More informationV248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants
Code No. LIT-19576 Issued June 22, 21 V248 Series -Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants Description The V248 Series -Way Pressure-Actuated Water-Regulating Valves
More informationNHR Powder Feed Hopper
Instruction Sheet P/N 0804A0 NHR-8-50 Powder Feed Hopper Description This instruction sheet provides specifications, installation and operation instructions, and parts lists for the NHR-8-50 powder feed
More informationAnother convenient term is gauge pressure, which is a pressure measured above barometric pressure.
VACUUM Theory and Applications Vacuum may be defined as the complete emptiness of a given volume. It is impossible to obtain a perfect vacuum, but it is possible to obtain a level of vacuum, defined as
More informationNorth American Orifice Metering System
Combustion North American Orifice Metering System 8697 and M8697 Metering Orifices accurately measure gas flows to industrial burners. They are compact, inexpensive, and can be installed in individual
More informationNatural Gas to L.P. Gas Conversion Kit
Natural Gas to L.P. Gas Conversion Kit For Bosch 80% AFUE Gas Furnace, BGS80 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change
More informationCatalina 36 Onyenma. Number:
Catalina 36 Onyenma Make: Model: 36 Length: Catalina 36 ft Price: $ 42,995 Year: 1988 Condition: Used Location: Kemah, TX, United States Boat Name: Hull Material: Draft: Number of Engines: 1 Fuel Type:
More informationWinter Culture of Caged Rainbow Trout in the South.
Winter Culture of Caged Rainbow Trout in the South. Forrest Wynne, State Extension Specialist for Aquaculture, Kentucky State University Cooperative Extension Program, Graves County Extension Office, 251
More informationGAS SUPPLY APPLICATION GUIDE
GAS SUPPLY APPLICATION GUIDE Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters This document applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B Gas-Fired Boilers
More informationInstruction Manual VCG-6
Specifications Amps / Volts requirements 400 ma @ 24 VDC Propane pressure (VCG-6LP) 11 WC / 2.8 kpa Natural Gas pressure (VCG-6NG) 4.5 WC / 1.15 kpa Cu ft per hour / CO2 3-6 SCFH BTU Rating (Variable)
More informationSIZING AND CAPACITIES OF GAS PIPING
SIZING AND CAPACITIES OF GAS PIPING A.1 General piping considerations. The first goal of determining the pipe sizing for a fuel gas piping system is to make sure that there is sufficient gas pressure at
More informationOffice Use Only Fee Paid
WASHOE COUNTY HEALTH DISTRICT ENVIRONMENTAL HEALTH SERVICES DIVISION 1001 East Ninth Street PO Box 11130 Reno, Nevada 89520 Telephone (775) 328-2434 Fax (775) 328-6176 www.washoecounty.us/health APPLICATION
More informationPhysics 7b Midterm Exam #1 Fall Name: Disc. Section SID
Physics 7b Midterm Exam #1 Fall 2004 Name: Disc. Section SID #1 #2 #3 #4 #5 Total M w of O 2 = 32 g/mol, k b =1.38x10-23 J/K, N A =6x10 23 The weight of a 1kg mass on the Earth s surface is 2.2pounds.
More informationCustomer Responsibilities. Important Customer Information Series Q-TOF LC/MS Systems Site Preparation Checklist
Thank you for purchasing an Agilent system. To get you started and to assure a successful and timely installation, please refer to this specification or set of requirements. Correct site preparation is
More informationINSTALLATION & START-UP INSTRUCTIONS. Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS
INSTALLATION & START-UP INSTRUCTIONS Clack WS1 & WS1.25 METER WATER SOFTENER SYSTEMS 1999-2009 QualityWaterForLess.com - 1 - info@qualitywaterforless.com Preface: Thank you for your purchase of a new Water
More informationGeotech 3.5 Auto-Reclaimer
Geotech 3.5 Auto-Reclaimer Installation and Operation Manual Rev 6/20/12 Part # 16600115 Table of Contents Section 1: System Description... 3 Function and Theory.. 3 Section 2: System Installation. 6
More informationUn-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs
Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini
More informationIRC 2011 All Rights Reserved
1 2 3 The enthalpy of saturated vapor and the enthalpy of saturated liquid is evaluated at the fully accumulated relief device set pressure (P=P set * 1.1 + 14.7). Set Pressure (psig) h fg (Btu/lbm) 150
More informationKörting Liquid Jet Vacuum Ejectors
Körting iquid Jet Vacuum Ejectors Körting iquid Jet Vacuum Ejectors iquid jet vacuum ejectors convey and compress gases or vapours with the aid of a liquid motive fluid. During this action vapours - corresponding
More informationMy Website:
PH202 Recitation Week 06 Problem Set Winter 2015 Ryan Scheirer Email: scheirer@onid.orst.edu My Website: http://people.oregonstate.edu/~scheirer/ph202_rec.html Problem 01 If you double the speed of molecules
More informationPE 2708 CTS & IPS GAS PIPE
Specifications: Resin Chevron Phillips TR418Q PE 2708 Resin formulation listed in PPI TR4 Hydrostatic Design Basis: 1250 psi @ 73 F, 800 psi @ 140 F Cell Classification per ASTM D3350 = 234373E or 234375E
More informationFisher L2sj Low Emission Liquid Level Controller
L2sj Controller Product Bulletin Fisher L2sj Low Emission Liquid Level Controller The rugged Fisher L2sj low emission liquid level controller uses a displacer type sensor to detect liquid level. This controller
More informationUSER GUIDE. Fog Generator. ATMOSPHERE APS TM Series Haze Generator. MAX APS TM Series. No: , Revision A/a
ATMOSPHERE APS TM Series Haze Generator MAX APS TM Series Fog Generator USER GUIDE No: 120815, Revision A/a MADE IN CANADA FABRIQUÉ AU CANADA Les Générateurs de Brouillard Ltée / Fog Generators Ltd 10301
More information