1 HFC 227 ea AEX Engineered Fire Suppression Systems Design, Installation, Operation and Maintenance Manual V1.0 April 2012

2 2

3 INDEX 1 GENERAL INFORMATION INTRODUCTION SYSTEM DESCRIPTION General Extinguishing Agent Exposure Limitations Toxicity Noise Turbulence Chilling Visibility Pressure OPERATION COMPONENTS FUNCTIONAL DESCRIPTION COMPONENT DESCRIPTION Cylinder / Valve Assembly Control Head Pressure Gauge Actuation Hose Discharge Hose Tees, Elbows and Adapters Check Valve Manifold Discharge Indicator Discharge Nozzle SYSTEM DESIGN DETERMINE HAZARD TYPE DETERMINE CONCENTRATION PERCENTAGE Class A Hazards Class B Flammable Liquids SAFETY RECOMMENDATIONS Normally Unoccupied Areas Unoccupiable Areas General Rules Occupiable Areas DETERMINE AGENT QUANTITY Determine the Hazard Volume Calculate Agent Required Altitude Correction Factors Determine Actual Concentration at Maximum Temperature Leakage CONTAINER SELECTION Container Size and Fill Range Container Location(s) Storage Temperature Limitations NOZZLE SELECTION TEE ORIENTATION INSTALLATION SYSTEM INSTALLATION AGENT STORAGE CONTAINERS CONTAINER MOUNTING FINAL SYSTEM CHECKOUT HAZARD AREA CHECK...35 AEX-MAN V1.0 AGUILERA EXTINCION 3

4 5.5.1 Area Configuration Area Leakage Enclosure Integrity Door Fant Testing SYSTEM MAINTENANCE SYSTEM MAINTENANCE DISCHARGE PIPING DISCHARGE NOZZLES AGENT STORAGE CONTAINERS Valve Reconditioning REMOTE PNEUMATIC ACTUATION CONTAINER TEST AND INSPECTION...38 AEX-MAN V1.0 Mar

5 FOREWORD: This manual is written for those who are installing an AEX Engineered Fire Suppression Systems using HFC 227 ea as extinguishing agent. Aguilera Extinción assumes no responsibility for the application of any systems other than those addressed in this manual. The technical data contained herein is limited strictly for information purposes only. Aguilera Extinción believes this data to be accurate, but it is published and presented without any guarantee or warranty whatsoever. AEX Engineered Fire Suppression Systems are to be designed, installed, inspected, maintained, tested and recharged by qualified, trained personnel in accordance with the following: Standard of the national Fire Protection Association no.2001, titled Clean Agent Fire Extinguishing Systems. European Standard EN , titled Gas Extinguishing Systems, Design, Installation and Maintenance. For any questions regarding the information presented in this manual, please refer to: Aguilera Extincion S.L. Av. Alfonso Peña Boeuf 6 PI Fin de Semana, 28022, Madrid. Phone: Fax: extinción@aguilera.es AEX-MAN V1.0 Mar

6 SAFETY SUMMARY HFC 227 ea fire suppression systems use pressurized equipment; therefore personnel responsible for fire suppression systems must be aware of the risk associated with the improper handling, installation or maintenance of this equipment. All service personnel must be thoroughly trained in the proper handling, installation and service of HFC227 ea equipment and follow the instructions used in this manual. Warnings and cautions are provided within this manual at appropriate locations. These warnings and cautions are to be followed at all times. Failure to do so may result in serious injury to personnel. In addition, Material Safety Data Sheet for HFC 227 ea and nitrogen are provided. Personnel must be familiar with the information contained on these data sheets. WARNING Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of violent discharge which may cause serious body injuries, death and property damage. Read, Understand and always follow the operation and maintenance manuals, owners manuals, service manuals that are provided with the individual systems. AEX-MAN V1.0 Mar

7 1 GENERAL INFORMATION 1.1 INTRODUCTION Aguilera HFC 227 ea AEX Engineered Fire Suppression Systems are designed according to the European Standard EN , titled Gas Extinguishing Systems, Design, Installation and Maintenance. These systems are designed for total flooding. In any situation not covered by this manual, the application and installation of the system must meet the requirement of the standard as stated. In any case, all installations must meet the requirements of the local Authority Having Jurisdiction (AHJ). The complexity of two-phase flow does not allow for any simple method of manual gas HFC 227 ea calculation. Therefore, the flow calculations and design criteria described in this manual have been incorporated into a computer software program. The calculations are based on conserving mass, energy and momentum in the pipe network. The routine calculates the flow in quasi-steady state steps from the initiation of the discharge to the final gas blowdown. 1.2 SYSTEM DESCRIPTION General AEX Engineered Fire Suppression Systems are used to suppress fires in specific hazards or equipment located where an electrically non-conductive agent is required, when agent clean up becomes a problem, where extinguishing capability with low weight is a factor and where the hazard is normally occupied by personnel. AEX Engineered Fire Suppression Systems are designed to protect the following type of class fires: Class A surface type fires. Class B flammable liquids. Class C energized electrical equipment. AEX Engineered Fire Suppression Systems are provided to protect the following type of specific hazards: Telecommunications devices. Process control rooms. Data processing devices. High value facilities (medical, industrial.). Libraries, museums, art galleries. Anechoic chambers. Flammable liquid storage areas. For other hazards beyond the above, the designer must consult with Aguilera Extincion and the Standards NFPA 2001 and EN According to these Standards, HFC 227 ea shall not be used on fires involving the following materials, unless they have been tested to the satisfaction of the Authority Having Jurisdiction (AHJ). Certain chemicals or mixtures of chemicals, such as cellulose nitrate and gunpowder, that are capable of rapid oxidation in the absence of air. Reactive metals such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium and plutonium. Metal hydrides. Chemicals capable of undergoing autothermal decomposition, such as certain organic peroxides and hydrazine. AEX-MAN V1.0 Mar

8 AEX Engineered Fire Suppression Systems are provided to protect the following has a operation temperature range for all its components of 32ºF to 130 ºF (0 ºC to 54 ºC). The program is designed for a temperature of 70 ºF (21 ºC). Therefore, the container operating and storage temperature must be in the range of 60 ºF to 80 ºF (16 ºC to 27 ºC) for a single unbalanced system protecting two or more separate hazards. If the container temperature is outside this range, an insufficient quantity of extinguishing agent may be discharged from one or more discharge nozzles Extinguishing Agent HFC 227 ea (1,1,1,2,3,3,3 heptafluoropropane) is a compound of carbon, fluorine and hydrogen (CF3CHFCF3). It is colorless, odorless and electrically non-conductive. It suppresses fire by a combination of chemical and physical mechanism with a minimal effect on the available oxygen. This allow people to breathe and see, permitting them to leave the fire are safely. HFC-227ea s mechanism of extinguishing fires is considered active. Its primary action is through physically cooling the fire at the molecular level. HFC-227ea belongs to the same class of agents used in the refrigeration industry; therefore, it is an efficient heat transfer agent. HFC-227ea removes the thermal energy from the fire to the extent where the combustion reaction cannot sustain itself. HFC 227 ea is acceptable for use in occupied spaces when used in accordance with the United States Environmental Protection Agency (EPA) Significant New Alternatives Policy (SNAP) program rules. Although HFC 227 ea is considered non toxic for humans in the concentrations required for extinguishing most fires, certain safety considerations should be observed when the agent is applied and handled. The agent discharge may create a hazard to people from the decomposition agent and products, when the agent is exposed to fire or other hot surfaces. The exposure to the agent is generally of less concern than the exposure to the decomposition products. Unnecessary exposure to the agent or its decomposition products should be avoided. For safety considerations, refer to Material Safety Data Sheet. The storage of the agent is in steel containers at 610 PSIG at 70 ºF (42 bar at 21 ºC) as a liquid with dry nitrogen added to improve the discharge flow and characteristics. AEX-MAN V1.0 Mar

9 The HFC 227 ea physical properties are shown in the following table: Chemical Name Heptafluoropro (CF3CHFCF3) Molecular Weight Boiling 760mm Hg o C Freezing Point -131 o C Critical Temperature o C Critical Pressure 29.1 bar Critical Volume (cc/mole) 274 Critical Density (kg/m 3 ) 621 Specific Heat, Liquid 25 o C) Specific Heat, Vapor (kj/kg o constant pressure of 1 25 o C Heat of Vaporization (kj/kg o C) at Boiling Point Thermal Conductivity (W/m o C) of 25 o C Viscosity, 25 o C centipoises Ozone Depletion Potential 0 Estimated Atmospheric Lifetime 31 to 42 years LC50 (Rats; 4 hrs ppm) >800,000 ppm The use and limitations are: Typical hazards that can be protected include the following: Electrical and electronic hazards Computer Cabinets Telecommunications facilities Storage Rooms Flammable liquids Control Panels & Control Rooms Wiring Closets CNC Machinery High Value Assets HFC-227ea systems shall NOT be used on fires involving the following materials. Chemicals or mixtures of chemicals that are capable of rapid oxidation in the absence of air. Examples include Cellulose Nitrate and Gunpowder. Reactive metals such as Lithium, Sodium, Potassium, Magnesium, Titanium, Zirconium, Uranium, and Plutonium Metal hydrides such as Sodium Hydride and Lithium Aluminum Hydride Chemicals capable of undergoing auto-thermal decomposition. Examples include Organic Peroxides and Hydrazine. AEX-MAN V1.0 Mar

10 1.2.3 Exposure Limitations Although HFC-227ea is considered to be non-toxic, limitations to exposure may exist. Consult EN , ISO 14520, NFPA Standard 2001, or the appropriate national standard to determine if such limitations exist. The following definitions are commonly used to describe exposure limitations. NOAEL No Observed Adverse Effect Level. This is the highest concentration at which no adverse toxicological or physiological effect has been observed. For HFC-227ea Systems, the NOAEL concentration is 9% by volume. LOAEL Lowest Observable Adverse Effect Level. This is the lowest concentration at which an adverse toxicological or physiological effect has been observed. For HFC-227ea Systems, the LOAEL concentration is 10.5% by volume. WARNING: The discharge of HFC-227ea Systems to extinguish a fire can result in potential hazards to personnel. These may include the natural form of the agent, or the products of combustion, that result from exposure of the agent to the fire or hot surfaces. Unnecessary exposure of personnel to the natural agent or the products of decomposition from a fire should be avoided. The requirement for pre-discharge alarms and time delays is intended to prevent unnecessary exposure to humans where their presence is not critical to the operation of the area. Suitable safeguards shall be provided to ensure prompt evacuation of [and prevent entry into] all protected areas after discharge Toxicity With a database in excess of seventy toxicity tests, HFC-227ea has been extensively tested and approved by institutions and agencies around the world. The LC50 toxicity rating for HFC-227ea is greater than 800,000ppm. When you consider that most HFC-227ea systems are designed for concentrations providing 105,000ppm or less, it is evident that HFC-227ea is safe to use. HFC-227ea will decompose to form halogen acids when exposed to extremely high temperatures. The formation of these acids is minimized by proper system design and installation of the piping system to deliver the agent quickly. The generation of by-products from the HFC-227ea discharge will be minimal when properly applied Noise The high-pressure discharge from the nozzle(s) of a system can cause noise that is loud enough to be startling, but ordinarily insufficient to cause traumatic injury Turbulence The high velocity discharge from the nozzle(s) can be sufficient enough to dislodge substantial objects located directly in the discharge path. Enough general turbulence may be created within the enclosure to move unsecured paper and light objects Chilling Direct contact with the vaporizing agent being discharged from the nozzle(s) will have a chilling effect on objects and can cause frostbite burns to the skin. The liquid phase vaporizes rapidly when mixed with air, thus limiting the hazard to the immediate vicinity of the discharge nozzle Visibility Although HFC-227ea is odorless, discharging the agent into a humid atmosphere may cause a reduction in visibility for a brief period of time due to condensation of water vapor normally present in the room atmosphere. AEX-MAN V1.0 Mar

11 1.2.9 Pressure The normal operating pressure of AEX Engineered Fire Suppression Systems is o C. This is accomplished by adding a charge of nitrogen to the HFC-227ea after filling the container. Since these are pressurized vessels, care must be observed when handling, filling, and transporting storage containers. Refer to the appropriate transportation requirements for the area in which the system is being installed for guidance regarding marking, transportation methods, etc. AEX-MAN V1.0 Mar

12 2 OPERATION The HFC 227 ea is held in the cylinder compressed by a discharge valve. When the valve is actuated by a control head, the valve closing device is displaced and the compressed liquid escapes through the discharge port of the valve and is directed through the distribution pipe to the nozzles. The nozzles will provide the proper flow rate and distribution of HFC 227 ea. The following operating procedures are considered in a stand-by systems status: Automatic Operation, where the system is operated automatically by means of a detection and control system. Everyone must evacuate the hazard are promptly upon hearing the pre-discharge alarm. Make sure no one enters the hazard area and call the fire department immediately. Local Manual Operation, although is not part of normal system actuation and should only be used in an emergency as a last resort. The following steps are to be taken: 1. To locate the proper cylinder for the hazard to be protected. In case of several cylinders and hazards, appropriate signal must be used. 2. To remove the safety pull pin from the cylinder control head. 3. To operate the manual lever, following the instructions on the lever or control head nameplate. 4. To leave the hazard immediately. 5. To allow no one to enter the hazard area and call the fire department immediately. In case of post-fire operation, the maintenance must be performed by qualified personnel. For cylinder recharge, return all cylinders to an Aguilera official distributor or other qualified refill agency. Both operations must be performed according to the procedures outlined in chapter 5 (Maintenance). AEX-MAN V1.0 Mar

13 3 COMPONENTS 3.1 FUNCTIONAL DESCRIPTION AEX Engineered Fire Suppression System is composed of the following components: Cylinder / Valve assembly. Control head. Pressure gauge. Pressure switch (optional). Actuation hose. Flexible discharge hose. Tees, elbows and adapters. Check valve. Manifold. Discharge indicator (optional) Discharge nozzle. Figure 1: AEX Engineered Fire Suppression System AEX-MAN V1.0 Mar

14 3.2 COMPONENT DESCRIPTION Cylinder / Valve Assembly. The storage of the agent is in steel containers at 610 PSIG at 70 ºF (42 bar at 21 ºC) as a liquid with dry nitrogen added to improve the discharge flow and characteristics. The cylinder valve assembly is equipped with a supervisory pressure switch connection (pressure switch is optional), a pressure gauge and a safety burst disc. In addition, each cylinder valve assembly is provided with a safety cap and a protection cap to prevent uncontrolled and accidental discharge. Figure 2: Cylinder / Valve Assembly CONTAINER SIZE (L) CONTAINER WEIGHT (kg) 4,7 8,6 5,7 6,7 10,3 7,7 13,4 15,5 15,4 26, ,8 40, ,2 50, , Table 1: Container size and weight MAXIMUM WEIGHT OF HFC227-ea (kg) AEX-MAN V1.0 Mar

15 Figure 3: Pilot valve assembly Figure 4: Slave valve assembly AEX-MAN V1.0 Mar

16 3.2.2 Control Head Electric operated control head. The electric control head provides the electric actuation of the cylinder valve. It is operated electrically from a detection and control system or a remote manual station. Figure 5: Electric operated control head (solenoid) Solenoid Data Sheet Coil KT10 (10W) Serie VE 131 VE V DC 100% ED IP Lever operated control head. The lever control head allows the manual operation of the cylinder valve. It is equipped with an operating lever, secured in the closed position by a safety pull pin. When removing the safety pin, the lever can easily be moved to the open position, thereby activating the cylinder valve on which it is installed Figure 6: Lever operated control head AEX-MAN V1.0 Mar

17 Pressure operated control head. The pressure operated control head allows the pressure operation of the cylinder valve through the pilot pressure. It is used in multiple cylinder systems. Pilot pressure is directed to a pressure operated control head on each cylinder valve using a flexible actuation hose. Figure 7: Pressure operated control head Pressure Gauge. It is a pressure indicator provided to indicate the pressure in the agent storage container. Figure 8: Pressure gauge AEX-MAN V1.0 Mar

18 3.2.4 Actuation Hose. The flexible actuation hose is used in multiple cylinder systems to direct the pilot pressure to a pressure operated control head on each cylinder valve. Figure 9: Actuation hose (pilot line) CODE HOSE SIZE CONNECTION SIZE LENGTH (mm) LD LD /16" BSP GAS 1/8" LD18BP 700 LD18BPP 2000 Table 2: Actuation hose (pilot line) Discharge Hose. The HFC 227 ea is routed from the storage cylinders to the discharge piping by a flexible rubbered cover hose with wire braided reinformcements. The hose is connected to the discharge outlet of the cylinder valve and ends at the system piping or discharge manifold. Figure 10: Discharge hose CODE HOSE SIZE CONNECTION SIZE LENGTH (mm) L34 3/4" BSP GAS 3/4" 535 L114N 1 1/4" BSP GAS 1 1/4" 600 L112N 1 1/2" BSP GAS 1 1/2" 690 Table 3: Discharge hose AEX-MAN V1.0 Mar

19 3.2.6 Tees, Elbows and Adapters. Tees, elbows and adapters connect actuation hoses to pressure operated control heads in multiple cylinder system installations. Figure 11: Elbow, tee, adapters (pilot line) Figure 12: Vent valve (pilot line) Figure 13: General assembly of the pilot line AEX-MAN V1.0 Mar

20 3.2.7 Check Valve Check Valves are required for all HFC-227ea Containers connected in a manifold arrangement. NFPA 2001, Section requires all containers connected to a manifold have an automatic, mechanical, means of preventing agent loss from an open leg of a manifold if the system is activated while a container is removed for maintenance. Therefore, the Check Valves are required for each container in a manifold arrangement. Figure 14: Check valve CODE CONNECTION SIZE AEX/VAR12 1/2" AEX/VAR /4" AEX/VAR /2" Table 4: Check valve Manifold The connection manifold is optional. The construction of the manifold is according to the design calculations. The material used is : - Pipe ASTM A106 grade B. - Welded and threaded accessory ANSI B Figure 15: Manifold (standard) AEX-MAN V1.0 Mar

21 3.2.9 Discharge Indicator It is a component, normally mounted on the discharge manifold (our standard manifold has the adapter mounted on it) although it could be mounted on any part of the distribution pipe. It has internally a mechanical device which is moved by the gas pressure when a discharge is activated and then it is activating an electrical connection which send an electric signal to the control panel. Once is activated the reset of the device is only manually. Figure 16: Discharge indicator Discharge Nozzle There are three types of discharge nozzles. The radial type (360 º). With 7 different sizes (1/4 ; 3/8 ; ½ ; ¾ ; 1 ; 1 ¼ ; 1 ½ ). The coverage is 9 x 9 (m) Figure 17: Radial type nozzle (360º) AEX-MAN V1.0 Mar

22 Figure 18: Coverage of the radial type nozzle (360º) The jet type (180 º). With 6 different sizes (3/8 ; ½ ; ¾ ; 1 ; 1 ¼ ; 1 ½ ). The coverage is 7 x 3 (m) Figure 19: Jet type nozzle (180º) Figure 20: Coverage of the jet type nozzle (180º) AEX-MAN V1.0 Mar

23 The window type (90 º). With 6 different sizes (3/8 ; ½ ; ¾ ; 1 ; 1 ¼ ; 1 ½ ). The coverage is 5 x 5 Figure 21: Window type nozzle (90º) Figure 22: Coverage of the window type nozzle (90º) AEX-MAN V1.0 Mar

24 4 SYSTEM DESIGN This section of the manual details the steps necessary to design a AEX Engineered Fire Suppression System. The first part of this chapter will guide the user through the process of analyzing the requirements of the hazard(s) to be protected and determining the amount of agent needed. The balance of the chapter addresses the specific hardware and system design requirements for AEX Engineered Fire Suppression Systems. The design criteria outlined in this chapter are based upon the requirements of EN If the system is being installed in an area governed by another standard such as NFPA Standard 2001, certain design requirements (e.g. concentration, exposure time, etc.) may differ from this document. The design of the system and its associated piping network MUST follow the limitations outlined in this section. If the specified limitations are not maintained, the system may not supply the required quantity of extinguishing agent. 4.1 DETERMINE HAZARD TYPE The Hazard Type generally falls into one of the three following categories, and sometimes a combination thereof. The designer must be aware of the Hazard Type to determine the correct design concentration, agent quantity, etc. The three Hazard Types are: Class A (wood, paper, cloth anything that leaves an ash residue after combustion) Class B (flammable liquids) Class C (electrical) 4.2 DETERMINE CONCENTRATION PERCENTAGE The following is a guideline to be used in determining the proper agent concentration percentage for the hazard(s) being protected. For combinations of fuels (hazard types) the design value for the fuel requiring the greatest concentration MUST be used Class A Hazards Systems protecting hazards containing Class A flammable materials can generally be designed for a 7.9% concentration Class B Flammable Liquids Systems protecting hazards containing Class B Flammable Liquids MUST be designed for the highest concentration required of the specific fuels listed. Therefore, the designer must perform an audit of the hazard space to identify the flammable liquids involved and their associated design concentrations. The fuel that requires the highest concentration shall be the one that determines the design concentration for the hazard. AEX-MAN V1.0 Mar

25 4.3 SAFETY RECOMMENDATIONS The following are safety recommendations as outlined in EN The designer must be aware of the occupancy of the hazard(s) being protected as they complete their evaluation of the project and make adjustments or recommendations as necessary Normally Occupied Areas The minimum safety precautions provided shall be in accordance with the following table. (Reference: ISO ) Table 5: Minimum safety precautions for HFC 227 ea in normally occupied areas Table 6: LOAEL and Exposure time of HFC 227 ea Normally Unoccupied Areas The maximum concentration shall not exceed the LOAEL (10.5%) unless a lock-off valve is provided. (Reference: ISO ) Systems that are designed to exceed the NOAEL (9.0%) should be installed in accordance with NFPA 2001 or ISO Unoccupiable Areas The maximum concentration may exceed the LOAEL (10.5%) without the need for a lock-off valve. (Reference: ISO ) WARNING: Any change to the enclosure volume, or addition or removal of fixed contents not included in the original design will affect the concentration if the system is discharged. AEX-MAN V1.0 Mar

26 4.3.3 General Rules Occupiable Areas Occupiable areas protected by total flooding systems shall be designed in accordance with the following requirements. (Reference: ISO 14520) a) Time delay devices: 1) for applications where a time delay will not significantly increase the threat to life or property from the fire, the system shall incorporate a pre-discharge alarm with a time delay long enough to allow personnel to evacuate the protected are prior to discharge. 2) time delay devices shall only be used for personnel evacuation or to prepare the hazard are for discharge b) Automatic/manual switch, and lock-off devices shall be provided where required in Sections and c) Exit routes shall be kept clear at all times, and travel distances shall be minimized by providing adequate directional signs and emergency lighting. d) Provide outward-swinging doors with automatic closure hardware. The doors shall be capable of being opened from the inside even when locked from the outside. e) Continuously operated visual and audible alarm devices shall be provided inside the protected space at all entrances and designated exits. Similar devices shall be provided outside of the protected space at the same entrances and exits. These devices shall operate until the protected area has been made safe. f) Appropriate warning and instructional signs shall be provided. g) A distinctive pre-discharge alarm shall be provided [where required] upon activation of the time delay prior to system discharge. h) Means for prompt natural or forced-draft ventilation of the agent from the protected space after a discharge. Forced-draft ventilation will be required for most installations. i) Provide adequate training and instructions to all personnel within [or nearby] the protected areas to ensure their correct actions when the system operates. This should include any maintenance, security, and construction personnel who may be brought into the area. 4.4 DETERMINE AGENT QUANTITY The following steps are necessary to determine the amount of HFC-227ea needed to protect the hazard(s) Determine the Hazard Volume The first step in designing the HFC-227ea system is to determine the volume of the space(s) being protected. The volume is calculated by multiplying the length x width x height of the space. Sometimes it is necessary to divide the protected space into smaller segments due to the configuration of the space. Each smaller segment is then added together to determine the total volume. As a general rule, the volume used to calculate the quantity of HFC-227ea required should be based on the empty (gross) volume. Additional considerations include: The volume taken by solid, non-permeable, and non-removable objects can be deducted from the protected volume Any volume that is open to the space being protected must be added (i.e. non-dampered ductwork, uncloseable openings, etc.) NOTE: Any object that can be removed from the protected space CANNOT be deducted from the volume. AEX-MAN V1.0 Mar

27 4.4.2 Calculate Agent Required The next step in designing the HFC-227ea system is to determine the base quantity of agent required to provide the desired concentration within the hazard(s) being protected. This calculation must be based upon two important criteria: the lowest expected ambient temperature, and the design concentration as discussed in Sections 2.2.1, 2.2.2, and To determine the agent quantity needed to produce the design concentration level, the Hazard Volume is multiplied by the factors as determined in the formula below. (Reference: ISO 14520) V C M = -- ( ) S 100 C Where: M = Agent Weight in kg V = Hazard Volume / m 3 C = S = Design Concentration, % by volume Specific Vapor in m 3 /kg S = k 1 + k 2 (t) Where: k 1 = 0,1269 k 2 = 0, t = temperature ( o C) NOTE: The equation to calculate S is an approximation. In ISO should be used to calculate the amount of agent required for a specific volume. NOTE: As an alternative, the table on the next page has been compiled to make it an easier process for the system designer. The information provided is derived from the formulas shown above. AEX-MAN V1.0 Mar

28 (Reference: ISO ) Table 7: Weight requirements (kg/m3) for HFC 227 ea Altitude Correction Factors The design quantity of HFC-227ea shall be adjusted to compensate for ambient pressures that vary more than eleven percent [equivalent to approximately 1000m of elevation change] from standard sea level pressures [1,013 bar absolute]. The amount of agent required must be adjusted using the correction factors shown below to compensate for these effects. (Reference: ISO 14520) AEX-MAN V1.0 Mar

29 The extinguishant quantity is determined by multiplying the quantity determined in by the ratio of the average ambient enclosure pressure to the standard sea level pressure. Table 8: Altitude correction factor for HFC 227 ea Determine Actual Concentration at Maximum Temperature The next step is to determine the expected concentration level at the maximum temperature for the hazard(s). This is a necessary step when designing systems for occupied spaces to properly evaluate the system requirements discussed in Section 2.3. The expected concentration can be determined by applying the following formula. C = (100 x W x S) / (V + V x S) Where: W = Agent Weight in lbs. (kg) M = Agent Weight in kg V = Hazard Volume m 3 C = Design Concentration, % by volume S = Specific Vapor in m 3 /kg S = k 1 + k 2 (t) Where: k 1 = 0,1269 k 2 = 0, t = temperature (ºC) AEX-MAN V1.0 Mar

30 4.4.5 Leakage The physical characteristics of the protected space(s) must be taken into consideration when designing an HFC-227ea system. The area of uncloseable openings must be kept to a minimum to prevent loss of agent into adjacent areas thus reducing the effectiveness of the system to extinguish a fire. Simply adding more agent is neither practical, nor effective. Therefore, all openings must be sealed or equipped with automatic closures. Forced-air ventilating systems shall be shut down or closed automatically where their continued operation would adversely affect the ability of the system to extinguish a fire. Completely self-contained recirculating ventilation systems are not required to be shutdown, but recommended. Dampers should be of the low smoke or 100% closing type to ensure an adequate seal and prevent leakage. Where the ventilation system is not shutdown or dampered, the volume of the associated ductwork and ventilation unit(s) shall be considered as part of the total hazard volume when determining the amount of agent needed. All enclosures must be sealed in order to achieve and maintain the desired concentration for a period of time that is sufficient for emergency personnel to respond. Under normal circumstances, the agent will extinguish the fire rapidly, thereby limiting the potential for fire damage and the creation of dangerous products of decomposition. Therefore, it is critical that the protected space is constructed to prevent any leakage from the protected space(s). The general guidelines for controlling leakage from the hazard are as follows: Doors All doors entering and/or exiting from the perimeter of the protected space(s) should have drop seals on the bottom, weather-stripping around the jams, latching mechanisms and door closure hardware. In addition, double doors should have a weather-stripped astragal to prevent leakage between the doors, and a coordinator to assure the proper sequence of closure. Doors that cannot be kept normally closed shall be equipped with door closure hardware and magnetic door holders that will release the door(s) upon a system alarm. Ductwork All ductwork leading into, or out of, the protected space(s) should be isolated with sealed, low smoke dampers. Dampers should be spring-loaded or motor-operated to provide 100% air shutoff upon activation. Air Handling/Ventilation It is recommended that all air handling/ventilation units be shutdown upon alarm to prevent leakage into other areas. If the air handling unit(s) cannot be shutdown, the volume of the associated ductwork must be added to the total volume of the protected space, and agent must be added to compensate for the additional volume. Penetrations All holes, cracks, gaps or penetrations of the perimeter walls defining the hazard area(s) must be sealed. Less obvious areas of leakage include wire trays, pipe chases, and floor drains. Make certain that floor drains have traps filled with a non-evaporating product to prevent leakage. Walls All perimeter walls that define the hazard area(s) should extend slab-to-slab, and each should be sealed top and bottom on the interior side. Where walls do not extend slab-to-slab, bulkheads will have to be installed to achieve the desired sealing characteristics. Block Walls Porous block walls must be sealed or the HFC-227ea agent will leak through. A room integrity fan pressurization test is an accepted means of determining how long the protected space will hold the agent (concentration) after a discharge. In conjunction with testing the integrity of the room, the test has a program that predicts the performance of the HFC-227ea system so that the Authority Having Jurisdiction can determine if the system has been designed and installed properly. The room integrity fan pressurization test must be performed in accordance with the manufacturer s requirements, and ISO , annex E. AEX-MAN V1.0 Mar

31 4.5 CONTAINER SELECTION Generally, the selection of containers is determined by the amount of HFC-227ea required vs. the approved fill ranges for the various container sizes. However, additional factors such as the System Design Concept, container storage location, and flow calculation limitations may have an impact on this decision as well Container Size and Fill Range All containers must be filled within the allowable fill range mandated by EEC or EN1964, depending on the container type being used. CONTAINER SIZE (L) CONTAINER WEIGHT (kg) 4,7 8,6 5,7 6,7 10,3 7,7 13,4 15,5 15,4 26, ,8 40, ,2 50, , Table 9: Container size and weight MAXIMUM WEIGHT OF HFC227-ea (kg) Container Location(s) The type and location of the storage container is based on several considerations. 1 Agent Quantity The agent storage container(s) selected must have the capacity to store the total quantity of agent required for the system. 2 System Type An area might be protected by several smaller containers with independent nozzles, or it might be protected by a large capacity container that is discharged through a piping network of 2, 4, or more nozzles. 3 Extent of Piping In systems having an unusually large piping system, the pressure drop may be too great for the location or configuration selected. In some cases, it may be necessary to relocate the container(s) closer to the hazard area(s) being protected. It may also be necessary to sub- divide the piping network into smaller configurations with separate containers. 4 Container Type Consideration should be given to the container type required for the installation. 5 Serviceability In general, the larger the container, the more difficult it will be to remove it from the system for maintenance and service. However, smaller containers that are located in a sub-floor space, under a computer bank, or above the ceiling over the same computer bank can be difficult as well. 6 Floor Loading This factor must be considered when selecting a container location. Excessive floor loading may require relocating the container(s) to a more suitable location. 7 Proximity HFC-227ea Containers should be located as close as possible to, or within the hazard that they protect. 8 Environmental Effects DO NOT locate containers where they would be subject to physical damage, exposure to corrosive chemicals, or harsh weather conditions AEX-MAN V1.0 Mar

32 4.5.3 Storage Temperature Limitations AEX Engineered Fire Suppression Systems are approved for a service temperature range of -20 o C to 50 o C. 4.6 NOZZLE SELECTION Nozzle(s) are determined using the following factors: amount of HFC-227ea required (flow rate) vs. the flow rate capabilities of the nozzle(s), area coverage, nozzle placement, discharge path obstructions, etc. all of these factors will have an impact on this decision. Pendant nozzles may be used in all enclosures where overhead ceiling nozzles are preferred or the dimensions restrict the use of an In-Cabinet nozzle. Nozzle Area Coverage must also be considered when designing a FIRERASER System. Each nozzle type (180 o or 360 o ) has been UL listed and FM approved for the maximum area coverage limitations listed below. The maximum area coverage is expressed as a radius ( R ) of coverage along the discharge axis for both nozzle types. Nozzles can be located a maximum of 0.3m below the ceiling. Additionally, 180 o Nozzles can be placed a maximum of 0.3m away from the sidewall. Walls, partitions, dense equipment racks, and tall equipment can make area coverage obstructions for nozzle discharges. For this reason, the discharge path of the nozzles must also be taken into account when determining the quantity of nozzles required. Anytime solid obstructions extend to where they could interfere with the line-of-sight discharge path from the nozzle, they should be treated as separate areas. All nozzles should be located in a manner that will provide a clear discharge path that reaches all of the outer extremes for the protected space. Note: See for nozzle coverage AEX-MAN V1.0 Mar

33 4.7 TEE ORIENTATION AEX Engineered Fire Suppression Systems has been tested to define the limitations necessary to accurately predict how the system will perform when discharged. The Tee orientation is an important characteristic in maintaining consistency of flow split percentages. Therefore, a simple rule MUST be observed concerning tee orientation: EVERY OUTLET of every tee MUST be orientated in the horizontal plane. Figure 23: Tee orientation AEX-MAN V1.0 Mar

34 5 INSTALLATION 5.1 SYSTEM INSTALLATION The system installation must comply with the requirements of this manual; NFPA 2001, latest edition; all applicable local codes, regulations, and standards and the authority having jurisdiction (AHJ). 5.2 AGENT STORAGE CONTAINERS The following sections provide pictorial clarification and procedures for the correct installation and mounting positions of AEX Engineered Fire Suppression Systems containers and associated hardware. Make certain that each container has been installed in the correct location. Each container should have a nameplate with an identifying part number. Check the container part number against those listed on the system plans to verify their locations. Containers should be located in clean, dry, and relatively vibration-free areas. Avoid aisle ways and other high traffic areas where physical damage or tampering is more likely. Containers should never be mounted where the container could potentially be splashed with, or submerged in, any liquid. Container brackets must be mounted securely to solid load-bearing surfaces that will support the container load. Some installations may require additional mounting support not supplied by Fike. 5.3 CONTAINER MOUNTING All containers are supplied with mounting brackets that must be secured to a solid, load-bearing surface using the appropriate number of fasteners. These containers can be floor or wall mounted in the vertical (valve up) or horizontal position. NOTE: Horizontally mounted container must be oriented with Actuation Port facing up. CAUTION: These containers have siphon tubes. DO NOT mount the containers in the inverted (valve down) position. Failure to comply with this requirement will result in an incomplete discharge. 5.4 FINAL SYSTEM CHECKOUT The checkout procedures outlined in this section are intended to represent the minimum requirements AEX Engineered Fire Suppression Systems. These procedures do not preclude those required by ISO 14520, and/or the authority having jurisdiction. The detection & control portion of the system should be thoroughly checked out according to the manufacturer's recommendations and the authority having jurisdiction (AHJ). AEX-MAN V1.0 Mar

35 5.5 HAZARD AREA CHECK A good review of the hazard area is just as important as the proper operation of system components. Certain aspects about the hazard may have changed or been overlooked; this could affect overall system performance. The following points should be thoroughly checked Area Configuration The area dimensions should be checked against those shown on the system plan(s). If the area volume has changed, the required agent weight should be recalculated and compared with the agent weight supplied. The area should also be checked for walls or movable partitions that have been added or changed. If walls or partitions have been added, check to see that all areas within the hazard still receive adequate nozzle coverage and agent distribution Area Leakage The hazard area should be checked for openings which could allow agent leakage after system discharge. Openings such as cable and duct penetrations into the area should be permanently sealed. Other sources of leakage should be checked for and sealed, especially in subfloor areas, where potential leak points are easily overlooked. Door(s) entering the hazard area(s) should be checked for tightness. Door seals and door sweeps should be installed to minimize leakage. Joints where walls contact floors, or other walls, should be sealed as these are potential leak points most often overlooked. Wall switch and receptacle boxes should be sealed. Sub-floor drains must have P - traps and be sealed with a non-evaporating liquid, such as anti-freeze or mineral oil. All penetrations between floors must be sealed Enclosure Integrity Door Fant Testing Door fan testing provides a method to evaluate room enclosure leakage and determine the system s ability to establish and maintain the design concentration after discharge. The calculation method provided makes it possible to predict the time it will take for a descending interface to fall to a given height or, for the continually mixed cases, the time for the concentration to fall to a given percentage concentration. Enclosure integrity testing is not intended to verify other aspects of Clean Agent system reliability; e.g., hardware operability, agent mixing, hydraulic calculations, and piping integrity. This procedure is limited to door fan technology. Discharge testing is generally not recommended; but may be required by the authority having jurisdiction. The door fan testing procedure should not be considered to be an exact model of a discharge test. The complexity of this procedure should not obscure the fact that most failures to hold concentration are due to the leaks in the lower surfaces of the enclosure, but the door fan does not differentiate between upper and lower leaks. The door fan provides a worst-case leakage estimate that is very useful for enclosures with complex hidden leaks, but will generally require more sealing than is necessary to pass a discharge test. (Refer to NFPA 2001, Appendix C; or ISO 14520, Annex E) AEX-MAN V1.0 Mar

36 6 SYSTEM MAINTENANCE 6.1 SYSTEM MAINTENANCE The following maintenance procedures and intervals indicated are meant to represent the minimum requirements for AEX Engineered Fire Suppression Systems. These procedures do not preclude those required by ISO 14520, and/or the authority having jurisdiction. More frequent service intervals may be necessary if systems are installed in more severe service applications. This section does not cover maintenance and service procedures for the electrical and control portions of the system. Consult the appropriate product manuals for those products. 6.2 DISCHARGE PIPING Every Six Months: Check the system discharge piping for corrosion and damage. Check all piping supports to make sure they are tight and all piping is securely supported. Every Year: Same as six month inspection. The piping should also be blown out with compressed air or nitrogen to check for obstructions. 6.3 DISCHARGE NOZZLES Every Six Months: Check to see that nozzle orifices are clear and unobstructed, and verify that the orifices are not showing signs of corrosion. Make sure the nozzles are aimed or positioned correctly. Verify that the correct nozzle part number is installed at the proper location in accordance with the system plans. 6.4 AGENT STORAGE CONTAINERS Every Three Months: Check the pressure gauge on each container. The nominal pressure should be approximately 25 bar at 21 C; however, the pressure will vary with temperature. In the range of 10 o C to 32 o C the difference is approximately 0.2 bar per degree. If the pressure loss indicated exceeds ten percent of the nominal pressure, check the container for leaks and repair as necessary. Temperature (ºC) Pressure (barg) Table 10: Pressure vs Temperature for HFC 227 ea (pressurized with N2 at 42 bar) AEX-MAN V1.0 Mar

37 Pressure (barg) vs Temperature (ºC) Temperature (ºC) Serie Pressure (barg) Figure 24: Pressure vs Temperature for HFC 227 ea pressurized with N2 at 42 bar) Every Six Months: Verify the weight of the agent in each container matches the agent weight stamped on the label. If the weight indicates a shortage exceeding five percent of required weight, the container must be removed from service for repair and/or recharge. WARNING: The control panel must be disabled BEFORE removing any container to be weighed. Every Five Years: All braided discharge hoses must be pressure tested at 1.5 times the maximum container pressure at 54 C. Refer to NFPA 2001 for specific testing procedures. After System Discharge: The containers should be removed and sent to the factory or an authorized AEX Engineered Fire Suppression Systems distributor for valve reconditioning and container recharge Valve Reconditioning The valve will need to be reconditioned using the appropriate reload kit after the container has been discharged. If the container has not discharged and a leaking valve needs to be reconditioned, the contents of the container must be transferred to another container before reconditioning the valve. WARNING: Container contents are under high pressure. NEVER attempt to recondition the valve until the contents have been transferred and the pressure gauge reads 0 bar. Care should be taken when handling valve components to avoid damage of any kind. AEX-MAN V1.0 Mar

38 6.5 REMOTE PNEUMATIC ACTUATION Systems that utilize a remote nitrogen actuator for system release must adhere to the following maintenance 6.6 CONTAINER TEST AND INSPECTION Containers shall be subjected to periodical tests as required by the relevant national standard. This may or may not include hydrostatic pressure testing after a system discharge or for systems AEX-MAN V1.0 Mar

39

40 SU PUNTO DE ASISTENCIA Y SUMINISTRO MAS PRÓXIMO SEDE CENTRAL C/ Julián Camarillo, 26 2ª Planta Madrid Tel: Fax: FACTORÍA DE TRATAMIENTO DE GASES Av. Alfonso Peña Boeuf, 6. Pol. Ind. Fin de Semana Madrid Tel: Fax: DELEGACIÓN NORDESTE C/ Rafael de Casanovas, 7 y 9.- Sant Adrià de Besòs Barcelona Tel: Fax: DELEGACIÓN LEVANTE Avda. Mediterránea 46 San Juan de Enova Valencia Tel: Fax: DELEGACIÓN NOROESTE C/ José Luis Bugallal Marchesi, A Coruña Tel: Fax: DELEGACIÓN SUR C/ Industria, 5 Edificio Metropol 3, 3ª Planta, Mod.17. P.I.S.A Mairena del Aljarafe, Sevilla Tel: Fax: DELEGACIÓN CANARIAS C/ Sao Paulo, 17. Pol. Ind. El Sebadal Las Palmas de Gran Canarias Tel: Fax: comercial@aguilera.es

IG01 EXTINGUISHANT AGENT

IG01 EXTINGUISHANT AGENT IG01 EXTINGUISHANT AGENT IG01 Inert Gas is a colorless, odorless, electrically non-conductive gas with a density approximately the same as air. (See Physical Properties for additional information). IG01

More information

FIREX200 CLEAN AGENT FIRE SUPPRESSION SYSTEM

FIREX200 CLEAN AGENT FIRE SUPPRESSION SYSTEM CYLINDERS Agent Tank The agent storage tank consists of a high pressure steel tank fitted with a valve and internal siphon tube, factory filled with FIREX200 gas (HFC-227 ea), and super-pressurized with

More information

Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent:

Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: P/N 06-236116-001 October 2014 Kidde Fire Systems ECS Fire Suppression System with HFC-227ea Agent: Modular Balanced Design, Installation, Operation and Maintenance Manual R LISTED UL Listing File No.

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

FM-200 Marine ECS Series Engineered Fire Suppression System. Design, Installation, Operation and Maintenance Manual LISTED LISTED

FM-200 Marine ECS Series Engineered Fire Suppression System. Design, Installation, Operation and Maintenance Manual LISTED LISTED P/N 90-FM200M-021 March 2008 FM-200 Marine ECS Series Engineered Fire Suppression System Design, Installation, Operation and Maintenance Manual FM R LISTED UL Listing File No. EX 4674 R LISTED FMRC J.I.OX6A2.AF

More information

with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%.

with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%. LPG Systems with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%. The agent is stored in seamless drawn steel high

More information

THE INERT GAS SYSTEM SO SAFE IT EVEN PROTECTS YOUR BUDGET.

THE INERT GAS SYSTEM SO SAFE IT EVEN PROTECTS YOUR BUDGET. I N E R T G A S F I R E P R O T E C T I O N S Y S T E M THE INERT GAS SYSTEM SO SAFE IT EVEN PROTECTS YOUR BUDGET. I N E R T G A S F I R E P R O T E C T I O N S Y S T E M The Most Cost-Effective Inert

More information

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013 Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release

More information

P/N 90-FM200M FM-200 ECS

P/N 90-FM200M FM-200 ECS P/N 90-FM200M-000 FM-200 ECS Series Engineered Fire Suppression Systems Design, Installation, Operation and Maintenance Manual R LISTED UL Listing File No. EX 4674 FM APPROVED FMRC J.I.1Y5A2.AF P/N 90-FM200M-000

More information

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on

More information

TOTAL SAFETY. It adapts perfectly to the problems of each project while being completely environmentally friendly and pollution-free.

TOTAL SAFETY. It adapts perfectly to the problems of each project while being completely environmentally friendly and pollution-free. TOTAL SAFETY Fire protection finds a great ally in IG-55. This agent combines adaptability to each project with excellent firefighting capacity, proven effectiveness and environmental friendliness. Companies,

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. than the water inlet pressure to the concentrate Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler

More information

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA. Trimpac 244a. September 16, 2013 September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

MSC Guidelines for Carbon Dioxide Fire Suppression Systems

MSC Guidelines for Carbon Dioxide Fire Suppression Systems C. J. Robuck, LCDR, Chief, Engineering Division References a. Title 46 CFR 34.15 (Subchapter D) b. Title 46 CFR 76.15 (Subchapter H) c. Title 46 CFR 95.15 (Subchapter I) d. Title 46 CFR 108.431 (Subchapter

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

Effective protection thanks to the latest technology

Effective protection thanks to the latest technology Effective protection thanks to the latest technology Fire protection is a top priority for any company, institution or public space. An accident of this type can irreparably affect the building, property

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Data Sheet Issue A

Data Sheet Issue A Features 1. Differential latching clappertype, lighweight, dependable construction. 2. Low Air Pressurized System, 8 psi -to- 26 psi (0,6 bar to- 1,8 bar) 3. Reset externally. Cover removal is not required.

More information

Guidelines for Clean Agent Fire Suppression Systems

Guidelines for Clean Agent Fire Suppression Systems References: S. T. Brady, Chief, Engineering Division a. National Fire Protection Association (NFPA) 2001, 2012 Edition (Clean Agent Fire Extinguishing ) b. International Code for Fire Safety (FSS), Chapter

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

KFI Approved. High Pressure CO2 System Technical Datasheets

KFI Approved. High Pressure CO2 System Technical Datasheets KFI Approved High Pressure CO2 System Technical Datasheets CONTENTS CO 2 CYLINDER 1 CYLINDER VALVE 3 NEEDLE VALVE 4 FLEXIBLE HOSE 5 SAFETY VALVE 6 SELECTOR VALVE 7 ACTUATING DEVICE 9 DISCHARGE NOZZLE 10

More information

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard CITY AND COUNTY OF DENVER CR&CF RISK UNIT 65.5.11 Compressed Gas Safety Standard 1.0 Introduction 2.0 Scope This standard has been developed to protect all City and County of Denver employees and contractors

More information

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes

Features. Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes Bulletin 357 Rev. E Model DDX-LP Dry Pipe Valve System 4 (100mm), 6 (150mm) & 165mm Sizes Bulletin 357 Rev. E Features 1. 2. 3. 4. 5. 6. 7. 8. 9. Differential-type valve, lightweight, dependable construction.

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013 September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking

More information

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction.

Model DDX-LP Dry Pipe Valve System 8 (200mm) Features. Differential latching clapper-type, lighweight, dependable construction. Bulletin 335 Model DDX-LP Dry Pipe Valve System 8 (200mm) Bulletin 335 Features 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Differential latching clapper-type, lighweight, dependable construction. Low Air Pressurized

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

G96 Series BASOTROL Dual Operator Valve

G96 Series BASOTROL Dual Operator Valve Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE Government of Bermuda Department of Maritime Administration 2015 027 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fixed Carbon Dioxide Fire Extinguishing Systems Ref: SOLAS 74/88 as amended, Regulation

More information

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013 October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve

More information

POWER FLUSH KIT INSTRUCTIONS

POWER FLUSH KIT INSTRUCTIONS 1 GENERAL INFORMATION POWER FLUSH KIT INSTRUCTIONS ACE Power Flush is an ozone-safe solvent engineered specifically for flushing refrigeration and air conditioning systems. Used exactly like the old R-11

More information

Tri-Tech Medical Inc.

Tri-Tech Medical Inc. Introduction Tri-Tech Medical manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

Safety Data Sheet. Zero Air 1 PRODUCT AND COMPANY IDENTIFICATION. Manufacturer NorLab a division of Norco 898 W. Gowen Rd.

Safety Data Sheet. Zero Air 1 PRODUCT AND COMPANY IDENTIFICATION. Manufacturer NorLab a division of Norco 898 W. Gowen Rd. Number: NLB 255 Page 1 of 5 1 PRODUCT AND COMPANY IDENTIFICATION Manufacturer NorLab a division of Norco 898 W. Gowen Rd. Boise, ID 8375 Contact: Phone: Fax: Web: Quality Dept. 28-336-1643 28-433-616 www.norlab-gas.com

More information

SAFE AND ENVIRONMENTALLY FRIENDLY

SAFE AND ENVIRONMENTALLY FRIENDLY SAFE AND ENVIRONMENTALLY FRIENDLY Thanks to our company s strong focus on innovation and development, we have developed the INERT-SIEX TM CFT-01 (Constant Flow Technology) system, one of the greatest advances

More information

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Installation Instructions BGA Series Issue Date October 3, 2017 BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Applications The BGA Series shutoff gas valve is an electrically operated gas valve that

More information

Compressed Gas Cylinders - Guideline

Compressed Gas Cylinders - Guideline Environmental Health and Safety Compressed Gas Cylinders - Guideline Date of Issuance: 1/10/18 Revision Number: Initial Revision Date: Prepared by: EH&S 1. Purpose Carnegie Mellon University has developed

More information

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve. Foam 302 a 1. DESCRIPTION (Refer to Figure 1 on page 302 e.) The Viking Low-Flow Foam/Water Proportioning System is a UL Listed and FM Approved system, for use with 3M and Viking brand foam concentrate.

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

TECHNICAL DATA Q= C. Table 1 - Specifications

TECHNICAL DATA Q= C. Table 1 - Specifications September 25, 2013 Pressure Regulation 537a 1. Description The Model B-3 Pilot Operated Pressure Control Valve is a factory assembled unit. The unit consists of a Model J-2 Halar coated Flow Control Valve,

More information

CABINEX-EWT. High Pressure Carbon Dioxide

CABINEX-EWT. High Pressure Carbon Dioxide CABINEX-EWT High Pressure Carbon Dioxide Fire Extinguishing System Installation, Operation & Maintenance Manual Please read and fully understand this installation manual, before installing and setting

More information

IPG IGNITION GAS PILOTS BACK-LOADED GAS

IPG IGNITION GAS PILOTS BACK-LOADED GAS INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated

More information

PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION

PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION DUAL SUPPLY REGULATOR ESCAPE CYLINDER VORTEX MAIN INLET PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION WARNING THIS MANUAL MUST BE READ CAREFULLY BY ALL PERSONS WHO HAVE OR WILL HAVE THE RESPONSIBILITY

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

Wet pipe low flow foam/water system

Wet pipe low flow foam/water system December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard

More information

Guidance on room integrity testing and its interpretation

Guidance on room integrity testing and its interpretation Guidance Note Guidance on room integrity testing and its interpretation Guidance on room integrity testing and its interpretation 1. SCOPE... 6 2. INTRODUCTION AND BACKGROUND... 6 2.1. DEVELOPMENT OF INTEGRITY

More information

BGA158 Series CE Approved Class B Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve

More information

TYPICAL TOXIC GAS SYSTEM INSPECTION VIOLATIONS

TYPICAL TOXIC GAS SYSTEM INSPECTION VIOLATIONS TYPICAL TOXIC GAS SYSTEM INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility,

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

GENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658

GENERAL DESCRIPTION MODEL RCW DRY SYSTEM CONFIGURATION. Technical Support Airpark Dr. Standish, MI 48658 077 Airpark Dr. Standish, MI 8658 989-8-583 www.globesprinkler.com Technical Support 989-1-00 MODEL RCW DRY SYSTEM GENERAL DESCRIPTION The Globe Model RCW* dry valve is a hydraulically operated external

More information

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax: 2 Table Of Contents 1. Introduction 3 2. About this Manual 3 3. Contacting YZ Systems 3 4. Vessel Components 4 5. Specifications 5 6. Application 6 7. Theory of Operation 7 8. DuraSite Installation & Use

More information

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

Mooney * Noise Controller Installation, Operation, and Maintenance Manual GE Oil & Gas Mooney * Noise Controller Installation, Operation, and Maintenance Manual imagination at work Scope This manual provides instructions for installation, operation and maintenance of the Mooney

More information

FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS

FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS Manual FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS User Guide Issue 1 October 2004 Assessed to ISO 9001: 2000 Certificate number 018 Chapter 2 Safety and Environmental Considerations Safety is of paramount

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

GM-7000 Series CE Approved Gas Control Valve

GM-7000 Series CE Approved Gas Control Valve Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate December 6, 2010 Foam 31a 1. Description With Multiple Pilot Pressure Regulating Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple pilot pressure regulating foam risers can be supplied from

More information

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS

GUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions VB-7323 Series 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions Application VB-7323 series three-way diverting valves control hot or chilled water in heating or air conditioning systems.

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet:

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet: OXY Integral INTERCON ENTERPRISES INC Tel: 800 665 6655 Fax: 604 946 5340 E-Mail: sales@intercononline.com Internet: www.intercononline.com Manual Integral 2006 1 INDEX 2-3 PREFACE 4 INTRODUCTION 5 Principle

More information

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems Translation. Only the Danish document has legal validity. Guidance no. 9514 of 9 July 2014 issued by the Danish Maritime Authority Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing

More information

Safe Handling. of Chlor Alkali Products

Safe Handling. of Chlor Alkali Products Safe Handling of Chlor Alkali Products Safe Handling of Chlorine Table of Contents 1. Regulatory Information 2. Production of Chlorine 3. Product Information 4. Fire Hazards 5. Health Concerns 6. Personal

More information

Vision Painting Inc Safety Management System

Vision Painting Inc Safety Management System Abrasive Blasting 1. PURPOSE The purpose of this program is to provide training and qualification guidelines for the safe operation of Abrasive Blasting. The Safety Officer is responsible for facilitating

More information

SUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE

SUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE Page 1 of 6 A. PURPOSE AND SCOPE This procedure establishes safe working practices for handling sulfur hexafluoride (SF 6 ) gas and release minimization practices. This document also specifies methods

More information

SAFETY TRAINING LEAFLET 06 CARBON DIOXIDE

SAFETY TRAINING LEAFLET 06 CARBON DIOXIDE SAFETY TRAINING LEAFLET 06 CARBON DIOXIDE Doc 23.06/18 EUROPEAN INDUSTRIAL GASES ASSOCIATION AISBL AVENUE DES ARTS 3-5 B 1210 BRUSSELS Tel: +32 2 217 70 98 Fax: +32 2 219 85 14 E-mail: info@eiga.eu Internet:

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE

More information

G92 Series BASOTROL Automatic Pilot Gas Valve

G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These

More information

Gas Cabinets and Valve Manifold Boxes: Applying CGA G13- Rev 2015 to Gas Delivery Equipment

Gas Cabinets and Valve Manifold Boxes: Applying CGA G13- Rev 2015 to Gas Delivery Equipment Gas Cabinets and Valve Manifold Boxes: Applying CGA G13- Rev 2015 to Gas Delivery Equipment The Standard Governing the Storage & Use of Silane: Compressed Gas Association s Publication CGA G-13 2015: Storage

More information

DESIGN, INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Direct Low Pressure (DLP) Models: DLP-300, DLP-600, & DLP-1200

DESIGN, INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Direct Low Pressure (DLP) Models: DLP-300, DLP-600, & DLP-1200 DESIGN, INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR FM-200 CLEAN AGENT PRE-ENGINEERED AUTOMATIC DIRECT FIRE DETECTION AND SUPPRESSION SYSTEM Direct Low Pressure (DLP) Models: DLP-300, DLP-600, &

More information

Quebec Quebec Tel : Fax : MSDS: Methane, Oxygen in Nitrogen Mixture PRODUCT INFORMATION

Quebec Quebec Tel : Fax : MSDS: Methane, Oxygen in Nitrogen Mixture PRODUCT INFORMATION Tel: 514-956-7503 Fax: 514-956-7504 Internet: www.megs.ca Email : support@megs.ca Montreal Ottawa St-Laurent Nepean Tel : 514-956-7503 Tel : 613-226-4228 Fax : 514-956-7504 Fax : 613-226-4229 Quebec Quebec

More information

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1 November 30, 1994 534 a 1. PRODUCT NAME VIKING 2" (50mm), 3" (75mm), 4" (100mm), 6" (150mm) 2. MANUFACTURER THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone:

More information

WARNING: FOR OUTDOOR USE ONLY

WARNING: FOR OUTDOOR USE ONLY Certified to CSA International 4.96 US For Outdoor Gas Fireplaces A HIGHER STANDARD IN QUALITY AND APPEARANCE SAFE AND BEAUTIFUL OUTDOOR LARGO FIRE PIT FOR PROPANE AND *NATURAL GAS OWNER S MANUAL WARNING:

More information

Operating Manual. Model 25200B/25202B Refrigerant Recovery Unit. (Not for use in automotive R-134a applications)

Operating Manual. Model 25200B/25202B Refrigerant Recovery Unit. (Not for use in automotive R-134a applications) Operating Manual Model 25200B/25202B Refrigerant Recovery Unit (Not for use in automotive R-134a applications) ROBINAIR Refrigerant Recovery Unit Model: 25200B /25202B Series Type of Equipment: Recovery

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 9 ACCUMULATORS The material needed for outcome 2 is very extensive so there are

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

VB-7213 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Stem Up Open, Two-Way Valves General Instructions VB-7213 Series 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions Application VB-7213 series single seat, stem up open, two-way valves control water from 20 to 281 F (-7 to 138 C)

More information

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate December 6, 2010 Foam 21a 1. Description With Multiple Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple deluge foam risers can be supplied from a single foam concentrate source. Where a bladder

More information

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA. Dry 132a. October 1, 2008 October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.

More information

INSTALLATION OPERATION MAINTENANCE

INSTALLATION OPERATION MAINTENANCE Bermad Electrically Controlled On-Off Deluge Valve Model: 400E-3D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working

More information

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50) Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge

More information

VBS-9263 Series. Application. Features. Applicable Literature

VBS-9263 Series. Application. Features. Applicable Literature TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com VBS-9263 Series 1/2" and 3/4" Screwed NPT 316 Stainless Steel Stem Up Closed, Two-Way Valves General Instructions Application

More information

TABLE OF CONTENTS PART 2 - CONFINED SPACES

TABLE OF CONTENTS PART 2 - CONFINED SPACES May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3

More information

Compressed Gases and Cryogens

Compressed Gases and Cryogens Compressed Gases and Cryogens University of Tennessee Safety Guide HM-011 Document Contact: EHS Date effective: January 1, 2009 Revision Date: October 1, 2015 Purpose This guideline adheres to the Occupational

More information

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under

More information