MEASURING AIR FLOW. Ventilation (Outside Air) Calculations. Derive % of OA as part of total air flow using air temperatures:

Size: px
Start display at page:

Download "MEASURING AIR FLOW. Ventilation (Outside Air) Calculations. Derive % of OA as part of total air flow using air temperatures:"

Transcription

1 MEASURING AIR FLOW 1 Ventilation (Outside Air) Calculations Derive % of OA as part of total air flow using air temperatures: % Outside Air (OSA) = [(Return Air T Mixed Air T) / (Return Air T Outside Air T)] x 100 Or [(Mixed Air T Return Air T) / (Outside Air T Return Air T )] x 100 We need to know the temperatures in the AHU/RTU! From BMS From Measurement Once you know the percentage, you also need to know the total air flow in system! 1

2 Total Air Flow in System Get specifications of total air flow from schedules (Note that the schedules will provide the design air flow which may be different from the actual air flow.) Or Measure total air flow in supply duct Pitot tubes to derive velocity pressure and then calculate velocity Direct velocity measurement with anemometer Remember Traverse requirements Calculate duct air flow from velocity FPM x duct cross sectional area (in ft 2 ) = CFM, total air flow Then Total Air Flow in CFM x % OA = OA Ventilation CFM Total Air Flow From Schedules Find any mechanical schedules Remember, though, this is design Distinguish outside ventilation air from the total air flow 2

3 Measuring Air Flow in Ducts Velocity Pressure ( W.C.) = Total Pressure Static Pressure Flow Velocity (Feet per Minute) = 4005 (constant) X Sqrt of Velocity Press CFM = Velocity (FPM) x duct cross sectional area (in Feet) FPM Feet per Minute or (Feet per second (measured) x 60 seconds per minute) 5 OA Air Quantity Problem DATA Pitot Tube Measurements:.8 Total.4 Static Supply Air Duct Size: 24 x 36 Outside Air Temperature: 60 Return Air Temperature: 75 Mixed Air Temperature: 70 Fan Total Flow = 4,806 CFM 3

4 Solution Velocity Pressure ( W.C.) = Total Pressure Static Pressure Velocity Pressure =.8.4 =.4 Velocity (Feet per Minute) = 4005 (constant) X Sqrt of Press Velocity = 4005 x.4 = 4005 x.2 = 801 fpm CFM = Velocity (FPM) x duct cross sectional area (in Feet) Flow = 801 x (24 /12 x 36 /12 ) = 801 x 2 x 3 = 4,806 CFM Deriving Outside Air (OA) Quantity from Air Temperature Readings % OSA = (Return Air T - Mixed Air T) / (Return Air T - Outside Air T) X = / X 100 Qty OSA = Tot CFM X % OSA 1,202 = 4,806 X 25% 4

5 HVAC Problems A building has a volume of 240,000 cubic feet. Assume that the ventilation rate provides 1 air change per hour (ACH). How many CFM of ventilation air is this? Is this sufficient for 250 occupants based on the ASHRAE 62.2 general Standard for Ventilation on an office building? CFM = CF (ft 3 ) X (ACH / [60 Minutes/Hr]) 4,000 CFM = 240,000 ft 3 X (1 ACH / [60 Minutes/Hr]) 250 people X 20 CFM per person = 5,000 CFM (required) 9 HVAC Problems A building has a volume of 240,000 cubic feet. Assume that the overall ventilation rate is 6,000 CFM. How many air changes per hour (ACH) is this? How many occupants will this cover? ACH = (CFM X 60 Minutes/Hr) / CF (ft 3 ) of Blg volume 1.5 ACH = (6,000 CFM X 60 Min/Hr) / 240,000 ft 3 6,000 CFM / (20 CFM/Person) = 300 people 10 5

6 Ventilation Problem An AHU serves a space designed for 200 people. It is equipped with a variable speed fan controlled by a demand controlled ventilation system. The AHU control panel display shows the fan speed in terms of Herz (HZ), where 60 Hz equal full fan output. At the control panel display you are also able to read Return Air temperature, Mixed Air temperature, and Outside Air temperature and total air flow (supply air). Applying the general guideline from ASHRAE 62.1, approximately how much outside air should be supplied in CFM when the space is at full capacity? 200 People X 20 CFM/Person = 4,000 CFM of outside air For the Same AHU When there are 50 people in the space, what fan speed read out should you expect to see in the AHU control panel display (Based on anticipated CO2 or cooling load and related fan speed adjustment)? 50 / 200 (People load ratio) X 4,000 CFM (Full Output) = 1,000 CFM 50 / 200 (People load ratio) X 60 Hz (Full Fan Output) = 15 Hz 6

7 For the Same AHU At a particular time you read from the control panel that you are delivering 2,000 CFM with the following air temperatures: Return Air: 78 F Mixed Air: 66 F Outside Air: 60 F. How would you calculate the percentage and the quantity of Outside Air that is being provided? %O/A = (RAT MAT) / (RAT OAT) X 100 %O/A = ( ) / ( ) X % = ( 12 ) / ( 18 ) X 100 2,000 CFM (Total Air) X 66.7% = 1334 CFM (O/A) Another AHU Problem An AHU is delivering 10,000 CFM with 20% outside air to a space that is 100 X 50 X 8 ceiling height. How would you calculate the number of ventilation air changes per hour (ACH) (fresh air only)? 10,000 CFM X 20% OA = 2,000 CFM of OA X 60 MIN/H = 120,000 CF/H 100 X 50 X 8 = 40,000 CF volume of space 120,000 CF/H X 1 AC/40,000 CF = 3 ACH 7

8 More Ventilation Problems In a rectangular 12 x 24 duct we measure an average air velocity of 4 feet per second (FPS). How would you calculate the air flow through across the coil in CFM? CFM = FPM X Duct cross sectional area But what about compatible units of measure? Velocity needs to be in Feet per Minute and duct cross sectional area must be in square feet duct cross sectional area in feet = 1 X 2 = 2 ft CF/M = (4 Ft/Sec X 60 Sec/Min) X 2 ft 2 8

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction Introduction A key task in commercial building HVAC design is determining outdoor ventilation airflow rates. In most jurisdictions in the United States, ventilation airflow rates must comply with local

More information

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY INTERPRETATION IC 62-2001-06 OF ANSI/ASHRAE STANDARD 62-2001 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY REVISION APPROVED: 1/12/2002 Originally issued as interpretation of Standard 62-1989 (IC 62-1989-23)

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

FMU4X, FMC4X FMU4P, FMC4P

FMU4X, FMC4X FMU4P, FMC4P ENVIRONMENTALLY SOUND REFRIGERANT FMU4X, FMC4X FMU4P, FMC4P Product Specifications HORIZONTAL FAN COILS FMU4P and FMC4P 1 1/2, 2, 2 1/2, and 3 Tons FMU4X and FMC4X 1 1/2, 2 and 2 1/2 Tons ALL MODELS Horizontal

More information

Double L Group, Ltd. TJP Inlets Number & Placement of Inlets Using Summer Fans with Minimum Ventilation on Endwalls

Double L Group, Ltd. TJP Inlets Number & Placement of Inlets Using Summer Fans with Minimum Ventilation on Endwalls Double L Group, Ltd. TJP Inlets Number & Placement of Inlets Using Summer Fans with Minimum Ventilation on Endwalls Poultry customers worldwide use TJP wall inlets to ventilate poultry houses with minimal

More information

How to Test Air Change Effectiveness

How to Test Air Change Effectiveness How to Test Air Change Effectiveness Presenter : Mark Jacobson Queensland Commissioning Manager 13 th June 2012 Presentation Agenda What is Air-Change Effectiveness (ACE)? Why is it important? Green Star

More information

Results of Field Measurements and CONTAM Simulation. Building Science

Results of Field Measurements and CONTAM Simulation. Building Science 28 Building Science Corporation Tracer Gas Testing January 26 Results of Field Measurements and CONTAM Simulation Aaron Townsend Building Science Tracer gas test of a production Building America house

More information

HVAC Air Duct Leakage. Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA

HVAC Air Duct Leakage. Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA HVAC Air Duct Leakage Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA Learning Objectives Understand the difference between System leakage and Duct leakage Understand

More information

Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program

Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program 1 Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Jim Meacham, CTG Energetics Agenda 2 In Situ Testing Results Reduced Ventilation after

More information

STUDENT SERVICES BUILDING HOWARD COMMUNITY COLLEGE COLUMBIA, MD TECHNICAL ASSIGNMENT #1 ASHRAE STANDARD VENTILATION COMPLIANCE EVALUATION

STUDENT SERVICES BUILDING HOWARD COMMUNITY COLLEGE COLUMBIA, MD TECHNICAL ASSIGNMENT #1 ASHRAE STANDARD VENTILATION COMPLIANCE EVALUATION STUDENT SERVICES BUILDING HOWARD COMMUNITY COLLEGE COLUMBIA, MD TECHNICAL ASSIGNMENT #1 ASHRAE STANDARD 62.1-2004 VENTILATION COMPLIANCE EVALUATION Jason P. Fair Mechanical Option October 5, 2005 Student

More information

6. EXPERIMENTAL METHOD. A primary result of the current research effort is the design of an experimental

6. EXPERIMENTAL METHOD. A primary result of the current research effort is the design of an experimental 6. EXPERIMENTAL METHOD 6.1 Introduction A primary result of the current research effort is the design of an experimental setup that can simulate the interaction of a windmill with a vortex wake and record

More information

Evaporator (DX) Freon Applications 1 12 Tons MHF

Evaporator (DX) Freon Applications 1 12 Tons MHF Evaporator (DX) Freon Applications 1 12 Tons > > Used For small to medium freon applications The Global Leader In Heat Exchange Technology With seven decades of experience and commitment to total client

More information

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION Mads Mysen* 1, Axel Cablé 1, Peter G. Schild 1, and Kari Thunshelle 1 1 SINTEF Building and Infrastructure Forskningsveien

More information

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1 Table of contents A1 Design criteria 1 A1.1 Local thermal discomfort indices........................... 1 A2 Experiment set-up 3 A2.1 Equipment....................................... 3 A2.2 Test cases.......................................

More information

Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation

Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation October 5, 2006 Table of Contents 1.0 Executive Summary... 2 2.0 Building Overview... 3 3.0 Analysis and Assumptions...

More information

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants.

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants. Field Evaluation of ASTM E741-00 in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants. Presented By Clinton B. Summers Eric M. Banks NUCON International, Inc.

More information

SECTION TESTING ADJUSTING AND BALANCING FOR HVAC

SECTION TESTING ADJUSTING AND BALANCING FOR HVAC SECTION 23 05 93 - TESTING ADJUSTING AND [Note to PSC: Existing System Coordination When connecting to an existing system, it is the PSC s Responsibility to examine existing documents, field verify existing

More information

The process of measuring air

The process of measuring air Measuring Leakage in High-Rise Buildings By Colin Genge The process of measuring air leakage to the outside in singlefamily homes is fairly well known among home performance professionals and anyone familiar

More information

Laboratory Ventilation. Environmental, Health, and Safety

Laboratory Ventilation. Environmental, Health, and Safety No.: BCF020.054 Page: 1 of 7 RECORD OF REVISIONS Date Rev # Details of Change 09/13 1 Updated job titles to reflect ICON job descriptions. Added a definition for Approved Ventilation Contractor and included

More information

Testing the Vented, 7-Liter Induction Chamber. Report 6 April 2008

Testing the Vented, 7-Liter Induction Chamber. Report 6 April 2008 Report 6 April 2008 Page 1 of 11 Report 6 April 2008 The final review and approval of this document before its release to the client is the responsibility of the following person at Technical Safety Services.

More information

University of North Florida Performance Requirements For Laboratory Fume Hoods. As Manufactured Performance Tests. As Installed Performance Tests

University of North Florida Performance Requirements For Laboratory Fume Hoods. As Manufactured Performance Tests. As Installed Performance Tests University of North Florida Performance Requirements For Laboratory Fume Hoods As Manufactured Performance Tests As Installed Performance Tests As Used Performance Tests October 27, 2010 University of

More information

AF100. Subsonic Wind Tunnel AERODYNAMICS. Open-circuit subsonic wind tunnel for a wide range of investigations into aerodynamics

AF100. Subsonic Wind Tunnel AERODYNAMICS. Open-circuit subsonic wind tunnel for a wide range of investigations into aerodynamics Open-circuit subsonic wind tunnel for a wide range of investigations into aerodynamics Page 1 of 4 Works with Computer, chair and work table shown for photographic purposes only (not included) Screenshot

More information

Field Installed Options: * Louvered or non-louvered ceiling access panels. * Time delay relay.

Field Installed Options: * Louvered or non-louvered ceiling access panels. * Time delay relay. Description: The High Efficiency Series air handlers are engineered to achieve or exceed today s demanding energy rating requirements. Specifically designed for horizontal mounting into a furred down ceiling.

More information

Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series

Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies ASHRAE, St. Louis Chapter November10, 2014 Agenda Introduction (concept, purpose,

More information

Defining Terms. Types Of Ventilation Systems: Types Of Ventilation Systems: Natural Ventilation - Winter

Defining Terms. Types Of Ventilation Systems: Types Of Ventilation Systems: Natural Ventilation - Winter Improving Ventilation in Calf and Heifer Housing Brian Holmes Extension Agricultural Engineer UW Madison Biological Systems Engineering Young Stock Facilities College & Tour Calumet County December, 2010

More information

VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES

VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES Proceedings: Indoor Air 005 A SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES PH Zhang * Jacobs Civil, Inc. 60 Madison Avenue, 1 th Floor, NYC, NY10016, USA ABSTRACT This paper discusses indoor

More information

acculink platinum zv zoning system

acculink platinum zv zoning system acculink platinum zv zoning system Components: AZONE950AC52ZA ZZONEPNLAC52ZA AZONE940 ZZONEEZPAC52ZB Platinum 950 Control Zone Panel Kit up to 4 zones Included: Discharge Air Temp sensor Static Pressure

More information

Mott Manufacturing Limited

Mott Manufacturing Limited Mott Manufacturing Limited 452 Hardy Road, Brantford, Ontario, Canada, N3T 5L8. Telephone: 519-752-7825 Fax: 519-752-2895 Web Site: www.mott.ca Fume Hood Performance Test Test Date: 9-Sep-08 Model Number:

More information

Water Cooling and Evaporator Coils. Types HI-F5 and E-F5. Catalog 411-9

Water Cooling and Evaporator Coils. Types HI-F5 and E-F5. Catalog 411-9 Water Cooling and Evaporator Coils Types HI-F5 and E-F5 Catalog 411-9 Table of Contents Introduction.... 3 HI-F5 and E-F5 Water Cooling and Evaporator Coils 3 Daikin SelectTools for Contractor Coils...3

More information

Emerging Technologies in Room (Suite) Pressure Control, Performance Modeling and Design Practices

Emerging Technologies in Room (Suite) Pressure Control, Performance Modeling and Design Practices Emerging Technologies in (Suite) Pressure Control, Performance Modeling and Design Practices Wei Sun, P.E. ASHRAE Principal, Director of Engineering Engsysco, Inc. Ann Arbor, Michigan, USA Emerging Technologies

More information

Krantz Components. Multifunction Sail AVACS. Cooling and Heating Systems

Krantz Components. Multifunction Sail AVACS. Cooling and Heating Systems Multifunction Sail AVACS Cooling and Heating Systems 2 AVACS Air Ventilation And Cooling System 3 System design Air diffuser box Air connection Sound absorbers (optional) Cooling element with heat conducting

More information

Testing the Vented, 2-Liter Induction Chamber. Report 14 October 2004

Testing the Vented, 2-Liter Induction Chamber. Report 14 October 2004 Report 156August 2004 Page 1 of 17 Report 14 October 2004 The final review and approval of this document before its release to the client is the responsibility of the following person at Technical Safety

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION TECHNICAL DESCRIPTION Exhaust Hose Reel ser. 865, electric motor driven No. 981118101 Description Limit switches, for hose coiling and uncoiling integrated in drive unit. Motor turns drum via a planetary

More information

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood Statesville, NC Results of AM ASHRAE 11 Laboratory Fume Hood Performance Evaluations Venturi Hood January, 217 Prepared By: Exposure Control Technologies Inc. 231-C East Johnson Street Cary, NC 27513 Phone:

More information

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN (This page intentionally blank) ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN TABLE OF CONTENTS O- Definitions... O- Objective... O- Design

More information

RLP100F910, F916, F918: Dual-channel volume flow controller

RLP100F910, F916, F918: Dual-channel volume flow controller Product data sheet 7. 7.440 RLP00F90, F9, F98: Dual-channel volume flow controller How energy efficiency is improved For demand-based volume flow control of dual-channel systems in offices Features Optimum

More information

Navy Guidance and Tips for Using DOEHRS-IH Ventilation NAVY & MARINE CORPS PUBLIC HEALTH CENTER

Navy Guidance and Tips for Using DOEHRS-IH Ventilation NAVY & MARINE CORPS PUBLIC HEALTH CENTER Navy Guidance and Tips for Using DOEHRS-IH Ventilation NAVY & MARINE CORPS PUBLIC HEALTH CENTER October 2010 Purpose This document is a supplemental Navy guide to the DOEHRS Student Guide/User Manual Version

More information

ASHRAE WILL ILL GIVE Y OU THE W ORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique

More information

LindabSolus. Supply air beam. lindab we simplify construction

LindabSolus. Supply air beam. lindab we simplify construction lindab we simplify construction Lindab 03.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,

More information

The Advancement of Pressure Independent Technology

The Advancement of Pressure Independent Technology The Advancement of Pressure Independent Technology This session will look at the new pressure independent technology and its energy savings potential. Topics include: A brief review of the differences

More information

Subsonic Wind Tunnel 300 mm

Subsonic Wind Tunnel 300 mm aerodynamics AF1300 An open circuit suction subsonic wind tunnel with a working section of 300 mm by 300 mm and 600 mm long Screenshot of the optional VDAS software Saves time and money compared to full-scale

More information

Mott Manufacturing Limited

Mott Manufacturing Limited Mott Manufacturing Limited 452 Hardy Road, PO Box 1120, Brantford, Ontario, Canada, N3T 5T3. Telephone: 519-752-7825 Fax: 519-752-2895 Web Site: www.mott.ca Fume Hood Performance Test Test Date: January

More information

DESIGN OF AN EFFECTIVE LOW PRESSURE VAV AIR DISTRIBUTION SYSTEM

DESIGN OF AN EFFECTIVE LOW PRESSURE VAV AIR DISTRIBUTION SYSTEM ABSTRACT The aim of this paper is to provide the air conditioning engineer with a clear set of guidelines for use in the design of the air distribution system for a low pressure Variable Air Volume system.

More information

The System Curve, the Fan Curve, and the Operating Point

The System Curve, the Fan Curve, and the Operating Point The System Curve, the Fan Curve, and the Operating Point AIHA-RMS Sept. 12, 2018 Keith D. Robinson, P.E. Overall Objective To equip an Industrial Hygienist with the skills necessary to document the performance

More information

Universities of Leeds, Sheffield and York

Universities of Leeds, Sheffield and York promoting access to White Rose research papers Universities of Leeds, Sheffield and York http://eprints.whiterose.ac.uk/ White Rose Research Online URL for this paper: http://eprints.whiterose.ac.uk/7819/

More information

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL Supersedes: 100.50-CL1 (1014) Form 100.50-CL1 (517) MECHANICAL CONTRACTOR INSTALLATION CHECKLIST AND UNIT SETUP DATA SHEET CUSTOMER: ADDRESS: PHONE: SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL 035-21780-030

More information

Building Official's Guide to Duct Testing based on 2009 IECC

Building Official's Guide to Duct Testing based on 2009 IECC Why test ducts? Leaky ducts pose health, safety and comfort problems and account for about 25% of the total energy lost in a typical house. Because it s by far the most cost effective way to save energy

More information

Draft. Equipment/Instrument

Draft. Equipment/Instrument Heating Ventilation Air Conditioning (HVAC) Technical Platform Recommended specialist equipment including instruments for those working with Healthcare Ventilation Systems Those working with Healthcare

More information

Excellent Duct Systems Require Design, Not Guesswork!

Excellent Duct Systems Require Design, Not Guesswork! Design Advisory #2: CAS-DA2-2003 Excellent Duct Systems Require Design, Not Guesswork! Duct System Design Guide: Chapter 2 HVAC system performance is only as good as it s weakest link. Unfortunately, duct

More information

SECTION TESTING, ADJUSTING, AND BALANCING CONTRACT NO SECTION TESTING, ADJUSTING, AND BALANCING

SECTION TESTING, ADJUSTING, AND BALANCING CONTRACT NO SECTION TESTING, ADJUSTING, AND BALANCING SECTION 15990 TESTING, ADJUSTING, AND BALANCING PART 1 -GENERAL 1.01 GENERAL A. This section of the Specifications covers testing and balancing of environmental systems, including, but not limited to distribution

More information

The principal mechanism for taking medium air velocity measurement is the Anemometer.

The principal mechanism for taking medium air velocity measurement is the Anemometer. 1 Introduction Face Ventilation Stoppings Check Curtains Air Measurements Principals of Airflow Respirable Dust Control Use of Scrubbers Actions for Excessive Methane Rock Dusting Permissibility 2 The

More information

WAT305 Math Part 1 ABC Math

WAT305 Math Part 1 ABC Math WAT305 Math Part 1 ABC Math Good to know for certification: You have used 35 150lb cylinders of Chlorine in 2011 how many pounds total did you use? How many pounds per month did you use? If demand is expected

More information

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine Page 1 of 5 Title Design and maintain effective ventilation systems for an underground coal mine Level 5 Credits 20 Purpose People credited with this unit standard are able to, for an underground coal

More information

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee ASHRAE WILL ILL G IVE Y OU THE W ORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique

More information

Quick Reference Technical Data

Quick Reference Technical Data Bulletin 127C 2 Quick Reference Technical Data For over 100 years, The Spencer Turbine Company has specialized in innovative solutions to air and gas handling problems. Spencer's product line includes

More information

Are you really doing your job if you fail to measure static pressure every time you service a unit? The answer is no.

Are you really doing your job if you fail to measure static pressure every time you service a unit? The answer is no. GET IN TOUCH WITH YOUR AIR SIDE by Rob Falke Like a doctor taking a blood pressure reading, measuring static pressure should be at the heart of every HVAC system exam EDITOR'S NOTE TOOLS OF THE TRADE AIR

More information

EXTRUDED ALUMINUM SQUARE AND RECTANGULAR DIFFUSERS

EXTRUDED ALUMINUM SQUARE AND RECTANGULAR DIFFUSERS INDUSTRIAL REGISTRATION NO.353 EXTRUDED ALUMINUM SQUARE AND RECTANGULAR DIFFUSERS SQUARE AND RECTANGULAR FLUSH CEILING DIFFUSERS OUTSTANDING FEATURES: Extruded aluminum construction 1-2-3-4 way throw patterns.

More information

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage William M. Pitts, Jiann C. Yang, Kuldeep Prasad, and Marco Fernandez National Institute of Standards

More information

NZQA unit standard New US 1Non-coal of 7145 version 1 Page 1 of 5

NZQA unit standard New US 1Non-coal of 7145 version 1 Page 1 of 5 Page 1 of 5 Title Design and maintain effective ventilation systems for a non-coal underground operation Level 5 Credits 20 Purpose People credited with this unit standard are able to: explain the principles

More information

Demand Control Ventilation Using CO 2

Demand Control Ventilation Using CO 2 ASHRAE Journal Ventilation Demand Control Ventilation Using By Mike Schell and Dan Int-Hout Member ASHRAE Member ASHRAE Carbon dioxide ( )-based demand controlled ventilation (DCV) is increasingly used

More information

Coils Designed to Fit Your Requirements. Temtrol Manufacturing OEM & Replacement Coils Since 1955

Coils Designed to Fit Your Requirements. Temtrol Manufacturing OEM & Replacement Coils Since 1955 Temtrol Manufacturing OEM & Replacement Coils Since 1955 Coils Designed to Fit Your Requirements Chilled & Hot Water Direct Expansion Steam Distributing Condenser Standard Steam Quick Ship Program with

More information

for Pleasant & Healthy Air-Distribution ISO 9001:2000 Linear Slot Diffusers Product Bulletin 133-D

for Pleasant & Healthy Air-Distribution   ISO 9001:2000 Linear Slot Diffusers Product Bulletin 133-D for Pleasant & Healthy Air-Distribution ISO 9001:2000 Product Bulletin 133-D Linear Slot Diffusers Pleasant.. Serene.. YOU & DASCO... Since 1964 Partners for good health INTRODUCTION Linear slot diffusers

More information

Question : What are some tips and recommendations and choices for roof venting?? Part One

Question : What are some tips and recommendations and choices for roof venting?? Part One Greenhouse - Q and A TIPS AND ADVICE Agroponic Industries Ltd. Calgary, Alberta, Canada ph 403 241 8234 email: agropon@agroponic.com Ask the Experts Question : What are some tips and recommendations and

More information

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS 3 rd International Conference on Energy Systems and Technologies 16 19 Feb. 2015, Cairo, Egypt ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

More information

LEV Inspection & Test Report

LEV Inspection & Test Report LEV Inspection & Test Report CLIENT: SITE: XXXXXXX LTD XXXXXXX Report Reference: Hinge Room-LEV System Identification: BeCu ESTA Survey Conducted By: Name: Position: Signed: XXXX Environmental Consultant

More information

Operation Manual. rev Pressure Gauges DM-2

Operation Manual. rev Pressure Gauges DM-2 Operation Manual rev-2013-12-02 Pressure Gauges DM-2 Copyright 2017 Retrotec All rights reserved. This document contains materials protected under International and Federal Copyright Laws. This book contains

More information

AIR FLOW MEASUREMENT By: James P. Curley Carrier Corporation

AIR FLOW MEASUREMENT By: James P. Curley Carrier Corporation Service Applicion Manual SAM Chapter 63 Section A AIR FLOW MEASUREMENT By: James P. Curley Carrier rporion INTRODUCTION Poor system performance and reliability is often a direct result of improper air

More information

TEL/jlRE" Introduction. Display Features and Modes. Startup Procedure. Power-Up Procedure. Adjustment Modes

TEL/jlRE Introduction. Display Features and Modes. Startup Procedure. Power-Up Procedure. Adjustment Modes TEL/jlRE" Introduction The Telaire 7001 CO 2 /T emperature monitor (shown in Fi gt u e 1 below) is an easy to use hand-held instnunent, which provides stable and highly accurate readings due to Telaire

More information

IH Report: SUFMO 08/09-CC21 1/27/2009 Stanford University Gas Cabinet Installation and Performance Criteria

IH Report: SUFMO 08/09-CC21 1/27/2009 Stanford University Gas Cabinet Installation and Performance Criteria Stanford University Gas Cabinet Installation and Performance Criteria I. Application Gas cabinets are ventilated enclosures that are used to isolate hazardous gas cylinders from the surrounding work place.

More information

Miami Retail Dehumidification Load peak )

Miami Retail Dehumidification Load peak ) Miami Retail Dehumidification Load (lb/h @ peak ) Respiration (PPL) Occupant Ventilation Bldg. Ventilation 14.25 29 61 Infiltration (ACH Nat) 19 Door Activity 5 Humid Product Damp Carpet Permeation (Walls)

More information

GENERAL OVERVIEW GENERAL OVERVIEW

GENERAL OVERVIEW GENERAL OVERVIEW GENERAL OVERVIEW A GENERAL OVERVIEW Traditional HVAC systems in most commercial buildings today employ Overhead Mixing (Mixed Ventilation, MV) to meet both outdoor air ventilation and space conditioning

More information

VENTILATION DURING TUNNEL CONSTRUCTION INDUSTRY CONSIDERATIONS

VENTILATION DURING TUNNEL CONSTRUCTION INDUSTRY CONSIDERATIONS VENTILATION DURING TUNNEL CONSTRUCTION INDUSTRY CONSIDERATIONS Air Quality Working Group Information Package - Part 7 of 12 December 2018 Doc No. AQWG_5_0.08 Page 1 of 12 Ventilation during Tunnel Construction

More information

MANAGEMENT PROCEDURE FOR LABORATORY VENTILATION

MANAGEMENT PROCEDURE FOR LABORATORY VENTILATION UNIVERSITY OF ALASKA FAIRBANKS SAFETY SYSTEM POLICY AND PROCEDURE DOCUMENT NUMBER: 508 ISSUE DATE: SEPTEMBER 1996 SUBJECT: Management Procedure for Laboratory Ventilation MANAGEMENT PROCEDURE FOR LABORATORY

More information

Model 26.5 WEAU242AA WEAU244BA 29.0 WEAU242BA 29.0 WEAU304AA 33.0 WEAU302AA WEAU304BA 33.0 WEAU302BA 33.

Model 26.5 WEAU242AA WEAU244BA 29.0 WEAU242BA 29.0 WEAU304AA 33.0 WEAU302AA WEAU304BA 33.0 WEAU302BA 33. EVAPORATOR COILS A COIL UNCASED R 22 or R 410A SYSTEMS 1 5 Tons WEAU Certification applies only when the complete system is listed with ARI ISO 9001:2000 REGISTERED R 410A R 22 Size Shipping Weight Size

More information

Back to Basics: Pumping Systems RM ASHRAE TECH CONFERENCE

Back to Basics: Pumping Systems RM ASHRAE TECH CONFERENCE Back to Basics: Pumping Systems RM ASHRAE TECH CONFERENCE 4/29/2016 1 AGENDA Closed loop heating and cooling piping systems Expansion Tanks Pumps 2 BASIC PUMPING LOOP Nice and simple too simple? Constant

More information

HCD HIGH CAPACITY DRUM LOUVER

HCD HIGH CAPACITY DRUM LOUVER HIGH CAPACITY DRUM LOUVER The s (HCD) consist of extruded aluminum blades mounted inside a rotatable drum to produce long air throws with a high degree of directional control. Rotateable drum provides

More information

Operating instructions Pitot Static Tube

Operating instructions Pitot Static Tube Operating instructions Pitot Static Tube halstrup-walcher GmbH Stegener Straße 10 D-79199 Kirchzarten, Germany Phone: +49 (0) 76 61/39 63-0 Fax: +49 (0) 76 61/39 63-99 E-mail: info@halstrup-walcher.de

More information

AerE 343L: Aerodynamics Laboratory II. Lab Instructions

AerE 343L: Aerodynamics Laboratory II. Lab Instructions AerE 343L: Aerodynamics Laboratory II Lab Instructions Lab #2: Airfoil Pressure Distribution Measurements and Calibration of a Small Wind Tunnel Instructor: Dr. Hui Hu Department of Aerospace Engineering

More information

WhisperValue DC. The ideal Multi-Family Solution High Performance Built for the Long Run

WhisperValue DC. The ideal Multi-Family Solution High Performance Built for the Long Run WhisperValue DC The ideal Multi-Family Solution High Performance Built for the Long Run The ideal Multi-Family Solution - Cost Efficient Code Compliance Made Easy Though small in size, Panasonic s WhisperValue

More information

Getting the Most From Your Duct Blaster

Getting the Most From Your Duct Blaster Bob Davis, Ecotope Bruce Manclark, Delta T The Duct Blaster, made by the Energy Conservatory, or similar devices like it, is a durable, versatile calibrated fan/flexible duct assembly that accurately measures

More information

CASED HORIZONTAL FURNACE COIL. Model CK3B. Form No. SS-CK3B-01 FEATURES

CASED HORIZONTAL FURNACE COIL. Model CK3B. Form No. SS-CK3B-01 FEATURES SIZES AVAILABLE: The horizontal N-Coil is available in six coil sizes (024 through 060). It is designed to provide the highest standard of reliability and durability. CASING: The CK3B coil casing is unpainted

More information

Fan and air movement essentials

Fan and air movement essentials 1 Properties of air For the purposes of this section we will assume that it is air that will be moved by the various types of fans. The air we breathe is made up of a mixture of gasses - nitrogen 78%,

More information

SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION

SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION Chrysanthi Sofia Koulani 1, Remus Mihail Prunescu 2, Christian Anker Hviid 1, and Søren Terkildsen *1 1 Technical University of Denmark

More information

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS APPLICATION NOTE LC-136 Introduction Specialized spaces often times must

More information

HVAC Considerations for Gaseous Decontamination of Laboratory Spaces using Hydrogen Peroxide Vapor

HVAC Considerations for Gaseous Decontamination of Laboratory Spaces using Hydrogen Peroxide Vapor HVAC Considerations for Gaseous Decontamination of Laboratory Spaces using Hydrogen Peroxide Vapor Copyright 2006 Phoenix Controls Corporation The material in this paper is for information purposes only

More information

CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE

CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE for the DG-700 Pressure and Flow Gauge The ENERGY CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE The Energy Conservatory 2801 21 st Ave. S., Suite 160 Minneapolis, MN 55407 Ph.: (612) 827-1117

More information

BAPI Pressure Line of Products - FAQs

BAPI Pressure Line of Products - FAQs Table of Contents 1. Several manufacturers produce pressure transmitters, why should I purchase from BAPI?... p. 2 2. BAPI makes several styles of pressure transmitters. What are the features of each?...

More information

The Stack Effect. Mat Ansari PE

The Stack Effect. Mat Ansari PE The Stack Effect Mat Ansari PE All young Engineers and Architects who are going to be involved with the design of tall buildings need to thoroughly understand the concept of Stack Effect. By thorough I

More information

NZQA unit standard version 5 Page 1 of 5. Describe, develop, and maintain basic ventilation systems for an underground coal mine

NZQA unit standard version 5 Page 1 of 5. Describe, develop, and maintain basic ventilation systems for an underground coal mine Page 1 of 5 Title Describe, develop, and maintain basic ventilation systems for an underground coal mine Level 4 Credits 15 Purpose People credited with this unit standard are able to: describe the basic

More information

Product Data. CK5A, CK5B, CK5P Furnace N-Coils. Sizes A018 thru A060

Product Data. CK5A, CK5B, CK5P Furnace N-Coils. Sizes A018 thru A060 Product Data CK5A, CK5B, CK5P Furnace N-Coils Sizes A018 thru A060 This vertical design N-coil is a furnace coil designed to provide the highest standards of reliability and durability. The coils are offered

More information

Application Block Library Fan Control Optimization

Application Block Library Fan Control Optimization Application Block Library Fan Control Optimization About This Document This document gives general description and guidelines for wide range fan operation optimisation. Optimisation of the fan operation

More information

IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring

IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring IC Sentinel is a real-time environmental quality monitoring solution, comprised of facilitywide, low-cost, compact, multi-sensor

More information

OWNER S MANUAL. AXD 530 MicroManometer

OWNER S MANUAL. AXD 530 MicroManometer OWNER S MANUAL AXD 530 MicroManometer Limitation of Warranty and Liability Seller warrants that this product, under normal use and service as described in the operator's manual, shall be free from defects

More information

Good News From the Doctor

Good News From the Doctor Good News From the Doctor Understanding Temperature and Altitude Corrections The most common influences on air density are the effects of temperature other than 70 F and barometric pressures other than

More information

BIOME DESIGN TECHNICAL DATA

BIOME DESIGN TECHNICAL DATA March 03, 2006 BIOME DESIGN TECHNICAL DATA 1) Dimensions: Each biome has the following clear interior dimensions: length 6,096 m, width: 3,404 m Interior clearance throughout: 4,268 m (floor to underside

More information

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS Chapter 65 EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS Ch.D. Taylor NIOSH/Pittsburgh Research Laboratory Pittsburgh, PA J.A. Zimmer NIOSH/Pittsburgh Research Laboratory

More information

Effect of airflow direction on human perception of draught

Effect of airflow direction on human perception of draught Effect of airflow direction on human perception of draught J. Toftum, G. Zhou, A. Melikov Laboratory of Indoor Environment and Energy Department of Energy Engineering Technical University of Denmark Abstract

More information

A position graph will give the location of an object at a certain time.

A position graph will give the location of an object at a certain time. Calculus 3.4 Notes A position graph will give the location of an object at a certain time. At t = 4, the car is 20 miles away from where it started. A position function is usually written as or. If the

More information

LindabPremax. Supply air beam. lindab we simplify construction

LindabPremax. Supply air beam. lindab we simplify construction lindab we simplify construction Lindab 03.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,

More information

WIND AFFECTED ISOTHERMAL AIRFLOW PATTERNS IN A SCALE MODEL OF A SWINE BARN MEASURED WITH PIV SYSTEM

WIND AFFECTED ISOTHERMAL AIRFLOW PATTERNS IN A SCALE MODEL OF A SWINE BARN MEASURED WITH PIV SYSTEM ISTP-6, 25, PRAGUE 6 TH INTERNATIONAL SYMPOSIUM ON TRANSPORT PHENOMENA WIND AFFECTED ISOTHERMAL AIRFLOW PATTERNS IN A SCALE MODEL OF A SWINE BARN MEASURED WITH PIV SYSTEM Pavel Bárta Czech Technical University,

More information