Ultra-High Pressure Firefighting: The Fastest Attack

Size: px
Start display at page:

Download "Ultra-High Pressure Firefighting: The Fastest Attack"

Transcription

1 Ultra-High Pressure Firefighting: The Fastest Attack New technology is no stranger to the fire service. Consider our protective gear, SCBA, PPV, thermal imaging cameras, water additives, automatic proportioning systems and CAFS to name just a few. Ultrahigh pressure (UHP) firefighting is yet another new revolutionary technology that will forever change the way we fight fires. One of the best tools on the market for taking advantage of UHP is the PyroLance. This unique system installs in any fire vehicle to allow firefighters to gain access to interior fires by blasting a 3 mm hole through any wall, roof or other type of barrier. Once a barrier is penetrated, the PyroLance continues to shoot a UHP water fog to aggressively attack the gaseous phase of the fire. This effectively knocks down the fire and rapidly cools the environment, thereby allowing for a safe entry to conduct search and rescue as well as overhaul operations. Let s take a closer look at how PyroLance is changing firefighting by using ultra-high pressure to pierce barriers, then rapidly cool and extinguish fires at their source. THE BACKGROUND Traditionally, we have always attacked the fuel phase of the fire. Several years ago, researchers in Sweden began experimenting with flashover simulators and the gaseous phase of fire behavior. What the researchers discovered was that by flowing an ultra-high pressure water fog into a fire s thermal layer, they were able to inert the fire gases without introducing oxygen. As a result, the interior heat dropped significantly in a matter of seconds. With the fire controlled, the risk of flashover eliminated and the temperature reduced to a safe level, crews could now make a safe entry into the fire area. Subsequently, other groups have conducted their own research to evaluate the cooling and suppression capabilities of UHP. All had similar findings.

2 UHP THEORY Up to this point, the industry has not formally defined what ultra-high pressure is with respect to mobile firefighting applications. For this discussion, we will use the following definitions: Normal Pressure: Under 500 PSI (<35 Bar) High Pressure: 500 to 1,000 PSI (35 to 70 Bar) Ultra-High Pressure: Over 1,000 PSI (>70 Bar) The second point we need to understand is water droplet size. Water droplets are typically measured in microns. A micron (µ or m) is one millionth of a meter (0.001 mm) or 1/25,400 inches. A micron is also referred to as a micro meter. Generally, water droplets flowing from a Normal Pressure hand line range in size from 700 to 1,000 µ. By contrast, the droplet size flowing from a UHP line will typically fall in the range of µ. For a given volume of water, therefore, the surface area of UHP droplets is significantly greater than for Normal Pressure droplets. This greater surface area enables faster and more efficient cooling. Oil Fog Smoke Optimum UHP droplet size Typical Normal Pressure droplet Sea Fog Mist size Rain Clouds Drizzle Aerosols Nozzles Sprinklers Fine Sprays The smaller droplet size found in UHP streams tend to have a greater hang time in the air, thus enabling the water to better saturate the air and increase the humidity. This effect can readily be seen in a side-by-side comparison using a Normal Pressure hand line and a UHP hand line. When you point both streams up in the air and then simultaneously close both nozzles, the UHP water fog will hang in the air much longer than the Normal Pressure droplets. We know if we can build the humidity to 30%, combustion ceases. The additional hang time of UHP coupled with the smaller UHP droplet size make this possible. In theory, with greater surface area and a longer hang time we would expect UHP streams to outperform Normal Pressure streams. In fact, that is exactly what the tests demonstrate. 2

3 THE EMPIRICAL EVIDENCE Since the early 1980s, the U.S. Air Force has relied on the Model P-19 as their first response ARFF vehicle. The drawback with this apparatus is that only one vehicle can fit into the cargo area of a C-130 aircraft. In the early 2000s, the U.S. Air Force began looking for technologies that could provide as much or more punch as the P-19, only on a smaller platform. Their ultimate goal was to carry two of the replacement vehicles on a C-130 aircraft. The U.S. Air Force Research Lab conducted extensive testing involving UHP technology in They ran over 100 tests comparing a UHP-equipped P-19 vehicle flowing 300 GPM (1135 LPM) to a Normal Pressure P-19 flowing 700 GPM (2650 LPM). Some of the video footage of those tests are available on the PyroLance website at and the complete AFRL report is available at The goal of the tests was to obtain equal or greater punch on a smaller platform. The video footage on the PyroLance website shows side-by-side attacks on similar pit fires by the two test vehicles. The results are typical for the findings and conclusions of the AFRL report: UHP P-19 Normal Pressure P-19 Time To Knockdown: 31 seconds 43 seconds Total Water Consumed: 151 Gallons 525 Gallons (572 Liters) (1987 Liters) These results show UHP knocking down a fire with less than 29% of the water in 72% of the time than with Normal Pressure on a similar fire! UHP vs. Normal Pressure testing has shown similar results on wildland and structural fires. The following chart illustrates the findings for UHP vs. Normal Pressure in wildland, hydrocarbon and structural applications: Water Usage Comparison Wildland Fuel Structural Fire Fire Fire NORMAL PRESSURE ULTRA HIGH PRESSURE (UHP) The AFRL study also concluded the following: Optimum Droplet Size: m Optimum Droplet Velocity: m/s UHP provided faster knockdown than Normal Pressure UHP required less water than Normal Pressure UHP required less water additives than Normal Pressure 3

4 UHP THE PRACTICAL APPLICATION When a droplet from a Normal Pressure water stream enters a fire area, it has the potential to convert all of its mass to steam. In reality, only about 10% of that mass will convert to steam and cool the fire. When a droplet from a UHP water stream enters a fire area, that droplet will convert about 90% of its mass to steam. This explains the significant difference in efficiency between the two streams. Together, the smaller UHP droplets comprise more surface area than Normal Pressure water droplets. This is why they have the ability to cool more efficiently. So, let s compare a 100 GPM (380 LPM) Normal Pressure hand line at 10% efficiency with a 20 GPM (76 LPM) UHP hand line with 90% efficiency. The total volume of water flowed by the two streams over time is illustrated in the following chart. Total Water Flowed in Minutes (Gallons / Liters) Normal Pressure UHP 1,000 / 3,800 2,000 / 7, / / 1,520 3,000 / 11, / 2,280 4,000 / 15, / 3,040 5,000 / 19,000 1,000 / 3,800 6,000 / 22,800 1,200 / 4, The volume of water for the Normal Pressure stream exceeds the UHP stream by a factor of five. Now let s compare the volume of water in the two streams that is actually cooling. Remember, the efficiency for the Normal Pressure stream is 10% while the efficiency of the UHP stream is 90%. The comparison looks like this: Effective Water Flowed in Minutes (Gallons / Liters) Normal Pressure UHP 180 / / 1, / / 2, / 1, / 2, / 1, / 3, / 1,900 1,080 / 4, / 2, /

5 What we can see from this example is that while the Normal Pressure stream flowed five times the volume of water as the UHP stream, the UHP stream actually outperformed the Normal Pressure stream by 80%. This can be a significant advantage when one considers the resources (both equipment and manpower) required to flow the added volume of water, the weight of the added water on a structure and the subsequent water damage to that structure due to the added water volume. We discussed the improved efficiency of UHP, but now let s also look at some of the additional benefits that should be considered by anyone investigating UHP technology: Safety Ergonomic (18-26 m) throw range Ease of use Immediate knockdown Reduced weight Hydraulic ventilation Quick in-service and take-up time Environmental Design 90% water efficiency Compact less weight to carry Less water runoff Small installation footprint Less damage Easy to customize A number of manufacturers are now marketing UHP technology for attacking and cooling. However, there is another side of UHP technology, proprietary to PyroLance, which enables fire crews to punch through virtually any material in a matter of seconds. PENETRATING WITH UHP PyroLance perfected and patented the technology to penetrate walls and other barriers by flowing water at 10 GPM (38 LPM) with a pressure of 1,500 PSI (100 BAR) at speeds of 400 MPH (650 KPH) through a specially designed lance that integrates granite abrasive. This combination allows firefighters to pierce or cut virtually any material at a phenomenal rate. Once a barrier is penetrated, the operator continues to use the lance to inject UHP water fog into the thermal layer of the fire area. The UHP water fog shot through the lance can reach as much as (10m- 12m), with a heat absorption capacity in excess of 6,000 BTU/sec. And the lance does this while allowing fire crews to operate from a safe exterior position! This explains why UHP firefighting is such a paradigm shift from the way fire crews have traditionally operated. Working with the PyroLance system is more efficient, more effective and safer than Normal Pressure. 5

6 In a series of tests conducted in Oklahoma City, fire was started and allowed to burn in a second story apartment until the interior temperature reached 1,380 F (750 C). (Video footage of this burn can be seen on the PyroLance website at Crews entered the first floor of the structure, penetrated the first floor ceiling using the PyroLance s mix of UHP and granite abrasive, and then continued to flow UHP water fog into the second story apartment. From the time crews water flowing, it took only 2:00 minutes to bring the interior temperature of the second story apartment to 212 F (100 C). It is important to note, crews were never exposed to extreme heat or the risk of a flashover in utilizing this new technology! These same tactics can also be employed when penetrating and attacking a roof or attic space from the safety of an aerial bucket or ground ladder; a basement fire from the safety of an exterior position; or any type of vehicle, aircraft, train car, or ship compartment fire. The Oklahoma City tests concluded that the PyroLance offered the following advantages: Improved firefighter safety o Indirect attack o Reduced stress o Lighter hose o Non-sparking penetration Faster cooling Reduced damage Improved visibility Less water additives Preserved evidence for arson investigation The main components of the PyroLance technology consist of a UHP pump, abrasive tank, hose reel and penetrating lance. A gas or diesel engine, PTO or hydraulic motor can power the pump. The system is available with a wireless lance that s controlled by the operator or in manual version Water Tank Abrasive Tank UHP Pump Hose Reel Control Panel Piercing Lance with Wireless Transmitter controlled at the pump panel. At right is a standard configuration. The base unit (shown at left) is compact and easily installed in a compartment or on a skid unit. The typical dimension is 36 W x 24 D x 32 H (914 mm x 610 mm x 813 mm). The system is available with Lance only, Blitz only or in a combined Lance/Blitz configuration. The lance has numerous features, including a collapsible stock and adjustable fore end grip to accommodate different sized firefighters. The fore end grip doubles as a stand when the lance is not in use. The wireless version of the lance comes with a folding antenna, safety lock on the trigger, abrasive on/off switch with indicator light, and a low battery indicator. 6

7 About PyroLance PyroLance is a revolutionary firefighting tool used by fire units around the world. By integrating granite abrasive with an ultra-high pressure (UHP) stream of water, PyroLance allows fire crews to pierce through concrete, composites, plate steel and other barriers from a safe position, and then cooling the hot gases and attacking the fuel sources of a fire with a powerful UHP mist. For more information about UHP firefighting and the PyroLance operating system, visit sales@pyrolance.com or call +1 (303) PyroLance LLC. All Rights Reserved. 525 Main Street Box New Brighton, MN USA pyrolance.com 7

Chapter 16 Test. Directions: Write the correct letter on the blank before each question.

Chapter 16 Test. Directions: Write the correct letter on the blank before each question. Chapter 16 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Explain the way vaporization and steam relate to the extinguishing properties of water.

More information

Direct attack. 1 Introduction

Direct attack. 1 Introduction Direct attack 1 Introduction In several previous articles we discussed the direct attack. Simply put, this comes down to the following: direct attack is putting water onto the fuel. The goal is to lower

More information

Model SOP Standard Operating Procedure

Model SOP Standard Operating Procedure Model SOP Standard Operating Procedure Firetactics.com SOP 3/Version 1/2008 3. ENTRY PROCEDURES INTO FIRE-INVOLVED COMPARTMENTS Sections 1. Purpose 2. Objectives of compartment entry 3. Residential compartments

More information

Dräger Swede Survival System Phase 1 Flashover Development Observation

Dräger Swede Survival System Phase 1 Flashover Development Observation Dräger Swede Survival System Phase 1 Flashover Development Observation With today s improved fire prevention methods, firefighters have fewer opportunities to gain first-hand experience of fighting live

More information

Cobra Cold Cut System

Cobra Cold Cut System Cobra Cold Cut System D38 A Summary: This standard operating procedure concerns the use of the Cobra cold cut system within Avon Fire & Rescue. This piece of equipment will assist firefighters to attack

More information

BASIC FIRE SCHOOL VENTILATION, SALVAGE & OVERHAUL

BASIC FIRE SCHOOL VENTILATION, SALVAGE & OVERHAUL VENTILATION, SALVAGE & OVERHAUL VENTILATION The process of removing smoke, heat, and toxic gases from a burning building and replacing them with cooler, cleaner, more oxygen-rich air VENTILATION BENEFITS

More information

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087 SOG Name: One and Two Family Dwellings SOG Number: 403.18 Effective Date: February 2, 2015 Approved: Joey Cooper, Director Reviewed: Scope This procedure will provide an organized method in which to carry

More information

Introduction Volume & Area Based formulas Figure 1

Introduction Volume & Area Based formulas Figure 1 Introduction From Firefighter to Incident Commander, we all must understand Needed Fire Flows (NFF). What lines need pulled on arrival? What kind of water supply rate do we need to sustain? When things

More information

Idaho Fire Service Technology Fire Fighter II

Idaho Fire Service Technology Fire Fighter II ICS Skill Requirements Skill Sheet: 1 STANDARD: 6.1.2 TASK: Organize, coordinate, and function within an incident management system. PERFORMANCE OUTCOME: The candidate shall be able to determine the need

More information

Pipe-Away Pressure Vacuum Vent /Conservation Vent

Pipe-Away Pressure Vacuum Vent /Conservation Vent R R Pressure Vacuum Vent / End of Line Conservation Vent Flame Arrester with Pressure Vacuum Vent Pipe Away Pressure Vacuum Vent / Conservation Vent Vacuum Relief Vent Pressure Emergency Vent Free Vents

More information

FIRE FIGHTER II - SKILLS PERFORMANCE SHEET

FIRE FIGHTER II - SKILLS PERFORMANCE SHEET Fire Fighter II Skill Stations: NFPA 1001 2013 Edition Station A Fire Ground Communications & Operations / Interior Attack Coordination MANDATORY STATION Station B Sprinkler Drain/Pressures RANDOM STATION

More information

CLEARWATER FIRE ACADEMY

CLEARWATER FIRE ACADEMY CLEARWATER FIRE ACADEMY March 18-19-20 Orofino High School Orofino, Idaho Sponsored by: Clearwater Fire Chiefs Association Orofino Fire Department Eastern Idaho Technical College 2 0 Clearwater Fire Academy

More information

APPLCATIONS OF POSITIVE PRESSURE VENTILATION DURING AIRPORT AND ARFF INCIDENTS. Leroy B. Coffman III, Tempest Technology Corporation, USA

APPLCATIONS OF POSITIVE PRESSURE VENTILATION DURING AIRPORT AND ARFF INCIDENTS. Leroy B. Coffman III, Tempest Technology Corporation, USA APPLCATIONS OF POSITIVE PRESSURE VENTILATION DURING AIRPORT AND ARFF INCIDENTS Leroy B. Coffman III, Tempest Technology Corporation, USA ABSTRACT Positive Pressure Ventilation (PPV) is the use of high-powered

More information

Ventilation Practices and Evidence-Based Research. By: John Paul Jones, Fire Chief KCKFD

Ventilation Practices and Evidence-Based Research. By: John Paul Jones, Fire Chief KCKFD Ventilation Practices and Evidence-Based Research By: John Paul Jones, Fire Chief KCKFD In the world of fire suppression, I believe one can say that on the fire ground, ventilation is everything. Especially

More information

BacPac; A portable WaterMist fire suppression kit; designed for rapid response situations. Model: FB33

BacPac; A portable WaterMist fire suppression kit; designed for rapid response situations. Model: FB33 BacPac; A portable WaterMist fire suppression kit; designed for rapid response situations. Model: FB33 TM 2 Features Designed to enable rapid response to fire situations. BacPac features: Extinguishes

More information

FIRE FIGHTER II SKILL PERFORMANCE CHECK SHEETS NFPA FIRE FIGHTER II SKILL STATION MENU

FIRE FIGHTER II SKILL PERFORMANCE CHECK SHEETS NFPA FIRE FIGHTER II SKILL STATION MENU FIRE FIGHTER II SKILL STATION MENU STATION TASK(S) A FIREGROUND OPERATIONS/FIRE COMMUNICATIONS MANDATORY B SPRINKLER DRAIN/PRESSURES RANDOM C PITOT GAUGE USE RANDOM D INSPECTION/MAINTENANCE: GENERATOR,

More information

Nozzles and portable monitors

Nozzles and portable monitors Nozzles and portable monitors Rosenbauer Nozzles and portable monitors Nozzles and portable monitors. EN maximum extinguishing effect. The Rosenbauer nozzle enables the manual 4-stage adjustment of the

More information

CLEARWATER FIRE ACADEMY

CLEARWATER FIRE ACADEMY CLEARWATER FIRE ACADEMY March 15-16-17 Orofino High School Orofino, Idaho Sponsored by: Clearwater Fire Chiefs Association Eastern Idaho Technical College Clearwater Fire Academy Email: clearwaterchiefs@gmail.com

More information

CLEARWATER FIRE ACADEMY

CLEARWATER FIRE ACADEMY CLEARWATER FIRE ACADEMY March 20-21-22 Orofino High School Orofino, Idaho Sponsored by: Clearwater Fire Chiefs Association Eastern Idaho Technical College Clearwater Fire Academy Email: academy@orofinofire.com

More information

Enabling Objectives (EO): EO Identify certain practices that could be considered unsafe and result in injury or death.

Enabling Objectives (EO): EO Identify certain practices that could be considered unsafe and result in injury or death. Instructor Guide Topic: Personal Safety Awareness (Revised 6/2010) Teaching and Learning Domain: Cognitive Time Required: 2 hours Materials: Appropriate visuals and chalkboard or easel pad References:

More information

2017 Volunteer Week - Course Descriptions

2017 Volunteer Week - Course Descriptions 2017 Volunteer Week - Course Descriptions 40 Hour Course - S130/S190/L180 Introduction to Wildland Firefighting S190 This course provides instruction in the primary factors affecting the start and spread

More information

CLEARWATER FIRE ACADEMY

CLEARWATER FIRE ACADEMY CLEARWATER FIRE ACADEMY March 16-17-18 Orofino High School Orofino, Idaho Sponsored by: Clearwater Fire Chiefs Association Orofino Fire Department Eastern Idaho Technical College 2 0 Clearwater Fire Academy

More information

Turning robots into thinking firemen

Turning robots into thinking firemen Turning robots into thinking firemen 1 Firefighter training in the early 2000 s Basic firefighter training was limited to 90 hours in the early 2000 s. A significant part of the course was dedicated to

More information

CFBT LEVEL I COURSE INFORMATION SHEET

CFBT LEVEL I COURSE INFORMATION SHEET CFBT LEVEL I COURSE INFORMATION SHEET Course Description Compartment Fire Behavior Training (CFBT) Level I examines fire behavior in a structural environment. Critical learning outcomes include the ability

More information

TACTICAL VENTILATION Graeme Bowser, Tyne & Wear Fire Brigade, U.K.

TACTICAL VENTILATION Graeme Bowser, Tyne & Wear Fire Brigade, U.K. TACTICAL VENTILATION Graeme Bowser, Tyne & Wear Fire Brigade, U.K. Graeme@UKfirefighter.org.uk Ventilation when performed correctly saves lives, eases firefighting conditions and reduces damage. 1. Introduction

More information

Skill Sheet 17-I-2. Attack a structure fire above, below, and at ground level Interior attack. (NFPA 1001, , )

Skill Sheet 17-I-2. Attack a structure fire above, below, and at ground level Interior attack. (NFPA 1001, , ) Skill Sheet 17-I-2 Objective 22: Attack a structure fire above, below, and at ground level Interior attack. (NFPA 1001, 5.3.10, 5.3.13) Student Name: Date: Directions For this skills evaluation checklist,

More information

DISCLAIMER TSS is simply providing current information so you can make sound tactical decisions.

DISCLAIMER TSS is simply providing current information so you can make sound tactical decisions. Objectives Identify and secure an adequate water supply. Perform a 360 degree Size Up. Develop an appropriate IAP. Make the appropriate hose line selection, hose stretch and water application based on

More information

Autumn 2018 Firefighter 1

Autumn 2018 Firefighter 1 Autumn 2018 Firefighter 1 August 22, 2018 December 12, 2018 State of Ohio FF 1 course Mondays & Wednesdays 1800 2200 or as scheduled Saturdays as scheduled DATE TOPIC HOURS INSTRUCTOR Orientation 08/22/18

More information

UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to:

UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: BASIC FIRE FIGHTER ORIENTATION AND COMMUNICATIONS Orientation and Communications 1 UNIT OBJECTIVES Upon completion of this unit of study, the student should be able to: 1. Identify the organization of

More information

Mobile Breathing Air Systems

Mobile Breathing Air Systems FAMA BUYER S GUIDE TC053 Prepared by the FAMA Body Subcommittee This guide does not endorse any manufacturer or product Page 1 of 14 Contents Introduction... 3 Overview... 4 Mobile Breathing Air System

More information

Simplicity in VRU by using a Beam Gas Compressor

Simplicity in VRU by using a Beam Gas Compressor Simplicity in VRU by using a Beam Gas Compressor By Charlie D. McCoy and Mark Lancaster Abstract: Vapor Recovery Units are often expensive, complicated to operate and unable to deal with High H2S and liquids.

More information

Tube Puller CP/CPS series. Pullers designed with cutting edge technology

Tube Puller CP/CPS series. Pullers designed with cutting edge technology Q U A L I T Y T U B E T O O L S www.krais.com CP/CPS series Pullers designed with cutting edge technology Q U A L I T Y T U B E T O O L S w w w. k r a i s. c o m MAIN FEATURES All new CP collet type and

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised DRIVER OPERATOR Page 1 of 14 HYDRAULICS Hydraulics applied in the dynamic fire ground environment is an art that comes with study and experience. The following describes the factors that must be mastered

More information

PERFORMANCE CRITERIA AND INSTRUCTIONS

PERFORMANCE CRITERIA AND INSTRUCTIONS JPR Task(s): Roll Fire Hose OMMISSION ON FIRE PROTETION PERSONNEL STANDARDS AND EDUATION OMMONWEALTH OF KENTUKY FIREFIGHTER 1 OMPETENY EVALUATION andidate #: Skill No. 1-31 PERFORMANE RITERIA AND INSTRUTIONS

More information

Iowa s s Minimum Training Standard. How to Be Prepared?

Iowa s s Minimum Training Standard. How to Be Prepared? Iowa s s Minimum Training Standard How to Be Prepared? Volunteer Firefighters Volunteer Fact Sheet Volunteers comprise 73% of firefighters in the Unites States. Communities served by Volunteer Firefighters

More information

FIRE FIGHTER II JPR: FFII-1A

FIRE FIGHTER II JPR: FFII-1A JPR: FFII-1A STANDARD: 6.1.2 Task: Implement Incident Management System. General Requirements The candidate shall demonstrate the ability to determine need for command, organize and coordinate an incident

More information

Township of Cumru Fire Department 03/12/2008 Standard Operating Guidelines Page: 1 of 8 Section 15.05

Township of Cumru Fire Department 03/12/2008 Standard Operating Guidelines Page: 1 of 8 Section 15.05 Standard Operating Guidelines Page: 1 of 8 15.05 Scope: This procedure will provide an organized method in which to carry out the fire ground functions in a timely and safe manner. Discussed will be the

More information

PNEUMATIC IMPACT TOOLS

PNEUMATIC IMPACT TOOLS PNEUMATIC IMPACT TOOLS RESCUE STARTS HERE Paratech s Pneumatic Impact Tools are designed for forcible entry during fire fighting and rescue operations. They are used for cutting metal and composites, breaking

More information

There are three fuelling systems which use LNG/CNG and which may be found in vehicles today:

There are three fuelling systems which use LNG/CNG and which may be found in vehicles today: UKRO Humberside Education Workshop 2017 NATURAL GAS POWERED VEHICLES Some LGV manufacturers (currently IVECO and SCANIA) are able to offer and Alternative Fueled vehicles that use Compresses Natural Gas

More information

TESTING SKILLS PORTABLE FIRE EXTINGUISHERS

TESTING SKILLS PORTABLE FIRE EXTINGUISHERS PORTABLE FIRE EXTINGUISHERS #1 Selecting the Appropriate Fire Extinguisher Subject: Fireground Operations Section 101 NFPA 1001 5.3.16 Firefighter I OBJECTIVE Extinguish incipient Class A, Class B, and

More information

E X T E R I O R L I V E P R O P A N E F I R E P R O P P R O C E D U R E S F O R U S I N G T H E P R O P A N E P R O P

E X T E R I O R L I V E P R O P A N E F I R E P R O P P R O C E D U R E S F O R U S I N G T H E P R O P A N E P R O P E X T E R I O R L I V E P R O P A N E F I R E P R O P Gina Gonzales Created: July 11, 2016 Version 1 NFPA 1403 P R O C E D U R E S F O R U S I N G T H E P R O P A N E P R O P Prior to using any of the

More information

CLEARWATER FIRE AND RESCUE DEPARTMENT STANDARD OPERATING PROCEDURE APPROVED BY: EFFECTIVE DATE: 10/12/07 REVISION DATE:

CLEARWATER FIRE AND RESCUE DEPARTMENT STANDARD OPERATING PROCEDURE APPROVED BY: EFFECTIVE DATE: 10/12/07 REVISION DATE: CLEARWATER FIRE AND RESCUE DEPARTMENT STANDARD OPERATING PROCEDURE SUBJECT: Truck Company SUB PAGE 1 OF 6 APPROVED BY: JAMIE D. GEER, FIRE CHIEF, FIRE AND RESCUE DEPARTMENT FORMS REQUIRED: NOTE: Current

More information

CFBT LEVEL II COURSE INFORMATION SHEET

CFBT LEVEL II COURSE INFORMATION SHEET CFBT LEVEL II COURSE INFORMATION SHEET Course Description Compartment Fire Behavior Training (CFBT) Level II builds on the foundational knowledge and skills developed in CFBT Level I. Critical learning

More information

North Carolina Fire and Rescue Commission Live Fire Audit Form

North Carolina Fire and Rescue Commission Live Fire Audit Form Live Fire Audit Form Date of Burn: Address: Delivery Agency AHJ: Instructor in Charge: Written documentation received from owner: Evidence of clear title. Written permission secured from owner to burn

More information

The Evaluator shall ask the Apparatus Driver/Operator questions regarding the mechanical systems and size of the apparatus.

The Evaluator shall ask the Apparatus Driver/Operator questions regarding the mechanical systems and size of the apparatus. Section I: Apparatus Knowledge The Evaluator shall ask the Apparatus Driver/Operator questions regarding the mechanical systems and size of the apparatus. 1. The Apparatus Driver/Operator demonstrates

More information

===============================================================

=============================================================== TOPIC: TRAINING TECHNIQUES LEVEL OF INSTRUCTION: TIME REQUIRED: TWO HOURS INSTRUCTOR GUIDE MATERIALS: APPROPRIATE AUDIO-VISUAL MATERIALS REFERENCES: Fire and Emergency Services Instructor, 6 th ed., International

More information

Emergency Water Injection /28/2017 updated 07/21/2017

Emergency Water Injection /28/2017 updated 07/21/2017 Emergency Water Injection 101 06/28/2017 updated 07/21/2017 Written By: Ronald D. Huffman, www.respondertraining.com When something happens and you're faced with an uncontrollable liquid propane leak you

More information

Tools, Techniques and Tactics (3T) in Combination for Firefighting

Tools, Techniques and Tactics (3T) in Combination for Firefighting Discussion topic Tools, Techniques and Tactics (3T) in Combination for Firefighting 2015 Open Conference International Fire Instructors Workshop art.arnalich@cern.ch M.Eng Civil Engineering So who is this

More information

TESTING APPLICATION STANDARD (TAS)

TESTING APPLICATION STANDARD (TAS) TESTING APPLICATION STANDARD (TAS) No. 00(A)-9 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE AND/OR INCREASED WINDSPEED RESISTANCE OF SOFFIT VENTILATION STRIP AND CONTINUOUS OR INTERMITTENT VENTILATION

More information

FROM THE CLASSICAL FIRE FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE GAS COOLING TAKING GLEINALMTUNNEL AS AN EXAMPLE; PART II

FROM THE CLASSICAL FIRE FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE GAS COOLING TAKING GLEINALMTUNNEL AS AN EXAMPLE; PART II - 131 - FROM THE CLASSICAL FIRE FIGHTING WATER SUPPLY TO STRUCTURE AND SMOKE GAS COOLING TAKING GLEINALMTUNNEL AS AN EXAMPLE; PART II Kern H. AQUASYS Technik GmbH, Linz Austria ABSTRACT Traditionally fire

More information

NATURAL GAS RESPONSE SOG

NATURAL GAS RESPONSE SOG SCOPE NATURAL GAS RESPONSE SOG This guideline shall apply to all members of the Stoney Point Fire Department and shall be adhered to by all members. PURPOSE The purpose of this guideline is to explain

More information

Virtual Pipeline Emergency Response Guide

Virtual Pipeline Emergency Response Guide Virtual Pipeline Emergency Response Guide Revised 7/24/17 Rev A Preface The intent of this guide is to provide information to help you respond to emergency situations involving Quantum VP Trailers in

More information

Live Fire Training Safety 3 1 n/a 30 No None Video (a) CD-Rom (p) 3 1 n/a 30 No 1A and 1S or equivalent

Live Fire Training Safety 3 1 n/a 30 No None Video (a) CD-Rom (p) 3 1 n/a 30 No 1A and 1S or equivalent * 1A 01-05-0030 Live Fire Training Safety 3 1 n/a 30 No None Video (a) 3 * 1B 01-05-0009 Conducting Live Fire Training Evolutions 3 1 n/a 30 No 1A 1S or equivalent Video (a) 3 * 1C 01-15-0007 Incident

More information

Drilling Efficiency Utilizing Coriolis Flow Technology

Drilling Efficiency Utilizing Coriolis Flow Technology Session 12: Drilling Efficiency Utilizing Coriolis Flow Technology Clement Cabanayan Emerson Process Management Abstract Continuous, accurate and reliable measurement of drilling fluid volumes and densities

More information

Yakima County Fire District 12 Standard Operating Guidelines SOG 5-1 Hazardous Materials Operations

Yakima County Fire District 12 Standard Operating Guidelines SOG 5-1 Hazardous Materials Operations 1. General Yakima County Fire District 12 Standard Operating Guidelines 1.1 Purpose. This Standard Operating Guideline is intended to provide general guidelines for District personnel in responding to

More information

Apparatus Driver/Operator Evaluation Form Rosenbauer Tanker:

Apparatus Driver/Operator Evaluation Form Rosenbauer Tanker: Section I: Apparatus Knowledge The Evaluator shall ask the Apparatus Driver/Operator questions regarding the mechanical systems and size of the apparatus. 1. The Apparatus Driver/Operator demonstrates

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised Truck Module Page 1 of 5 GAS EMERGENCIES Introduction Natural gas and Liquid Propane Gas (LPG) are flammable gases. Many households and commercial buildings utilize these gases for everything from heating

More information

ESCONDIDO FIRE DEPARTMENT TRAINING MANUAL ENGINE MODULE HOSE PAGE 1 OF 24 Attack Hose Lays Revised

ESCONDIDO FIRE DEPARTMENT TRAINING MANUAL ENGINE MODULE HOSE PAGE 1 OF 24 Attack Hose Lays Revised HOSE 12-01-16 PAGE 1 OF 24 To effectively attack and extinguish a fire, hose lines must be removed from the apparatus and advanced to the location of the fire. The techniques used to advance hose lines

More information

Virtual Pipeline Emergency Response Guide

Virtual Pipeline Emergency Response Guide Virtual Pipeline Emergency Response Guide Use in conjunction with ERG 2016 Guide 115 Revised: November 2018 Rev C Preface The intent of this guide is to provide information to help you respond to emergency

More information

KMT Waterjet Systems Inc.

KMT Waterjet Systems Inc. Advancing Waterjet Technology Worldwide Sales and Support Network Making Waterjet Systems Easier to Use, with Greater Reliability ISO 9001:2000 Certification; CSA and CE Certified Trained, Certified Technicians

More information

A PARTIAL GUIDE TO MCFRS SAFE STRUCTURAL FIREFIGHTING POLICY. Section II Rapid Intervention

A PARTIAL GUIDE TO MCFRS SAFE STRUCTURAL FIREFIGHTING POLICY. Section II Rapid Intervention A PARTIAL GUIDE TO MCFRS SAFE STRUCTURAL FIREFIGHTING POLICY Section II Rapid Intervention PURPOSE The purpose of this presentation is to provide clarification for when necessary and expand on the new

More information

FIREGROUND HYDRAULICS

FIREGROUND HYDRAULICS INTRODUCTION This section is designed to give pump operators a quick and fairly easy process for determining fire ground hydraulics. Supplying water is a critical part of the control, and the efficient

More information

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Standard Operating and Maintenance Instructions for Pumping System Model PS-90 Standard Operating and Maintenance Instructions for Pumping System Model PS-90 High Pressure Equipment Company 2955 West 17th Street, Suite 6 PO Box 8248 Erie, PA 16505 USA 814-838-2028 (phone) 814-838-6075

More information

High-Rise Fireground Field Experiments Results

High-Rise Fireground Field Experiments Results High-Rise Fireground Field Experiments Results These graphs show average times for each critical task by crew size. Percentage calculations for all the charts were based on the overall time from detection

More information

Lesson 6: Flow Control Valves

Lesson 6: Flow Control Valves : Flow Control Valves Basic Hydraulic Systems Hydraulic Fluids Hydraulic Tank Hydraulic Pumps and Motors Pressure Control Valves Directional Control Valves Flow Control Valves Cylinders : Flow Control

More information

Title- FIREFIGHTER ASSIST AND SEARCH TEAM POLICY

Title- FIREFIGHTER ASSIST AND SEARCH TEAM POLICY Department of Emergency Response And Communications Cortland County 911 Public Safety Building; Suite 201 54 Greenbush Street Cortland, New York 13045 300-004 Title- FIREFIGHTER ASSIST AND SEARCH TEAM

More information

2012 SYLLABUS FOR IFE LEVEL 2 CERTIFICATE FIRE SCIENCE, OPERATIONS AND SAFETY 500/5925/7.

2012 SYLLABUS FOR IFE LEVEL 2 CERTIFICATE FIRE SCIENCE, OPERATIONS AND SAFETY 500/5925/7. 2012 SYLLABUS FOR IFE LEVEL 2 CERTIFICATE FIRE SCIENCE, OPERATIONS AND SAFETY 500/5925/7. The IFE Level 2 Certificate syllabus has been prepared as a series of well defined objectives with the intention

More information

To establish a guideline for the safe and effective deployment of apparatus, personnel, and resources at the scene of structural fires.

To establish a guideline for the safe and effective deployment of apparatus, personnel, and resources at the scene of structural fires. Buxton Fire-Rescue Standard Operating Guideline Subject: Structural Fire (3) Section: Operations at Structure Fires (2) Page 1 of 7 Purpose: To establish a guideline for the safe and effective deployment

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

Fire Apparatus Operator (FAO)

Fire Apparatus Operator (FAO) Fire Apparatus Operator (FAO) 1106 NATURE OF WORK This is skilled fire fighting work in combating, extinguishing, and preventing fires, in responding to render emergency medical services, in responding

More information

Wayne County Community College District

Wayne County Community College District FPT 110 Fire Fighter I Lecture CREDIT HOURS: 8.00 CONTACT HOURS: 120.00 COURSE DESCRIPTION: This course is designed to provide a student with the knowledge necessary for entry level positions on fire departments.

More information

Apparatus Operator Refresher Training Program

Apparatus Operator Refresher Training Program Division of Training In-Service Training Program Apparatus Operator Refresher Training Program 1 Single Engine / Single Line Operation Refresher Evolution #1 Objective: Charging single handlines at correct

More information

Backpack Cutting System. processes, from cutting to piercing. Patented style oxy-flame tubes handle the scope of almost any assignment.

Backpack Cutting System. processes, from cutting to piercing. Patented style oxy-flame tubes handle the scope of almost any assignment. MAG9000 Backpack Cutting System MAG9000 PORTABLE BACKPACK CUTTING SYSTEM Drop a serious amount of steel in half an hour on a single charge. Weighing in at a fractional 16 pounds, this featherweight backpack

More information

At the end of this lesson, you will be able to do the following:

At the end of this lesson, you will be able to do the following: Liquid-Phase Contacting Scrubbers Goal To familiarize you with the operation, collection efficiency, and major maintenance problems of liquid-phase contacting scrubbers. Objectives At the end of this lesson,

More information

second test was conducted using at 3/4inch nozzle to determine a practical maximum pressure for the pump.

second test was conducted using at 3/4inch nozzle to determine a practical maximum pressure for the pump. I am writing this memo to you from the perspective of a fire apparatus operator and tester. Though I offer this collection of my observations and opinions, I do so voluntarily but with the full integrity

More information

INSTRUCTOR GUIDE TOPIC: STOPPING UNSAFE PRACTICES LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS MATERIALS: APPROPRIATE AUDIO-VISUAL MATERIALS

INSTRUCTOR GUIDE TOPIC: STOPPING UNSAFE PRACTICES LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS MATERIALS: APPROPRIATE AUDIO-VISUAL MATERIALS TOPIC: STOPPING UNSAFE PRACTICES LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS INSTRUCTOR GUIDE MATERIALS: APPROPRIATE AUDIO-VISUAL MATERIALS REFERENCES: ESSENTIALS OF FIRE FIGHTING, FIFTH EDITION,

More information

West Metro Fire Protection District

West Metro Fire Protection District West Metro Fire Protection District Tower Task Book Developing Firefighter Instructions This is the Tower Task Book you will be required to complete during your one month rotation on a Tower. While it

More information

FSRS Relative Point Value Guide

FSRS Relative Point Value Guide FSRS Relative Point Value Guide Note: This document has been produced by PIAL as a "guide" to show each 's impact to your total score. Certain ideal scenarios were assumed to determine the score in the

More information

High Efficiency SO2 Scrubber Design to Reduce Caustic Consumption

High Efficiency SO2 Scrubber Design to Reduce Caustic Consumption High Efficiency SO2 Scrubber Design to Reduce Caustic Consumption Paper # 35 Andrew C. Bartocci Envitech, Inc. 2924 Emerson Street- Suite 320 San Diego, CA 92106 Ph: 619-223-9925, ext. 203 ABSTRACT An

More information

Hot Water Stationary Unit

Hot Water Stationary Unit S 312 E-VA Hot Water Stationary Unit Technical Data S 312 E-VA (18 kw) Flow rate max. 620 l/h Unloading pressure 190 bar Working pressure max. 30-170 bar Water temperature max. 45 C Water inlet 3/4 Power

More information

Materials Performance November Nitrogen generator inhibits corrosion within fire protection systems

Materials Performance November Nitrogen generator inhibits corrosion within fire protection systems Materials Performance November 2014 Nitrogen generator inhibits corrosion within fire protection systems When dry and pre-action fire protection systems experience internal corrosion in their piping network,

More information

RESOLUTION MSC.365(93) (adopted on 22 May 2014) AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS AMENDED

RESOLUTION MSC.365(93) (adopted on 22 May 2014) AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS AMENDED RESOLUTION MSC.365(93) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, RECALLING ALSO article

More information

Potter Nitrogen Generators

Potter Nitrogen Generators Potter Nitrogen Generators What is nitrogen? Nitrogen the inert gas Earth s atmosphere the air we breathe is composed of nitrogen, oxygen, and water vapor. While this atmosphere is great for life, it is

More information

MOBILAIR M 210 / M 235. Portable Compressor With the world-renowned SIGMA PROFILE Flow rate 18.0 to 23.3 m³/min ( cfm) COMPRESSORS

MOBILAIR M 210 / M 235. Portable Compressor With the world-renowned SIGMA PROFILE Flow rate 18.0 to 23.3 m³/min ( cfm) COMPRESSORS COMPRESSORS MOBILAIR M 210 / M 235 Portable Compressor With the world-renowned SIGMA PROFILE Flow rate 18.0 to 23.3 m³/min (640 825 cfm) www.kaeser.com MOBILAIR M 210 / M 235 The powerful combination of

More information

ALAMEDA COUNTY FIRE CHIEFS ASSOCIATION

ALAMEDA COUNTY FIRE CHIEFS ASSOCIATION ALAMEDA COUNTY FIRE CHIEFS ASSOCIATION RAPID INTERVENTION CREWS APPENDIX T Alameda County - Alameda - Albany - Berkeley - CalFire - East Bay Regional Parks - Emeryville - Fremont Hayward - Livermore-Pleasanton

More information

Standard Operating Procedures S.O.P. Sample Template Drafted by: Oklahoma State Firefighters Association Educational Advisory Committee

Standard Operating Procedures S.O.P. Sample Template Drafted by: Oklahoma State Firefighters Association Educational Advisory Committee Standard Operating Procedures S.O.P. Sample Template Drafted by: Oklahoma State Firefighters Association Educational Advisory Committee ** Remember Safety First ** INTRODUCTION Remember, the following

More information

COMMISSION ON FIRE PROTECTION PERSONNEL STANDARDS AND EDUCATION COMMONWEALTH OF KENTUCKY FIREFIGHTER 2 COMPETENCY EVALUATION

COMMISSION ON FIRE PROTECTION PERSONNEL STANDARDS AND EDUCATION COMMONWEALTH OF KENTUCKY FIREFIGHTER 2 COMPETENCY EVALUATION OMMISSION ON FIRE PROTETION PERSONNEL STANDARDS AND EDUATION OMMONWEALTH OF KENTUKY FIREFIGHTER 2 OMPETENY EVALUATION JPR Task(s): Establish Incident ommand and oordinate Interior Attack of a Structure

More information

Water Scooping Aircraft

Water Scooping Aircraft Water Scooping Aircraft Fire Manager s Guide Created by Matt Woodwick MN DNR Table of Contents Purpose... 2 Understanding the Water Scooper... 2 Considerations in preparation for Water Scoopers..2 Logistics.2

More information

POWER IS PRODUCED IN THE HEAD

POWER IS PRODUCED IN THE HEAD english & & The outstanding feature of the V series lances is their round head with its optimized ratio of interior to exterior surface. In conjunction with countersunk aluminum nozzles, the head remains

More information

Diagnosing EVAP systems By: Bernie Thompson

Diagnosing EVAP systems By: Bernie Thompson Diagnosing EVAP systems By: Bernie Thompson Perhaps one of the toughest jobs in the automotive field is diagnosing small leaks, especially A/C and Fuel Vapor (EVAP) leaks. Finding these leaks can be time

More information

Rio Hondo College Basic Fire Academy Class 83 Schedule

Rio Hondo College Basic Fire Academy Class 83 Schedule Rio Hondo College Basic Fire Academy Class 83 Schedule This schedule meets or exceeds the minimum requirements for Firefighter-1 Academy set forth by the Office of the California State Fire Marshal, State

More information

FIRE AND EXPLOSION HAZARD MANAGEMENT

FIRE AND EXPLOSION HAZARD MANAGEMENT FIRE AND EXPLOSION HAZARD MANAGEMENT Toolbox Talk Practical Applications (Part 2) Setting the standard in oil and gas safety 1 WHAT SHOULD I KNOW ABOUT FIRES AND EXPLOSIONS» One-size-fits-all solution

More information

Number of Pages: 13 SOG Number: 1-13

Number of Pages: 13 SOG Number: 1-13 Purpose: The purpose of this SOG is to establish command procedures, identify optional levels of rapid intervention capability, minimum training and equipment requirements for functioning RIT teams and

More information

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program

FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program FIRE LOGISTICS AND MATH EDUCATION A Rumpke Public Outreach Program Welcome & Introductions Identify emergency exits to all participants. Identify location of restroom facilities. Cover any other related

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

Firefighter Job Description Norwich Fire Department

Firefighter Job Description Norwich Fire Department Firefighter Job Description Norwich Fire Department 1. GENERAL PURPOSE 1.1. This job description applies to the position of firefighter. 1.2. Protects life, property and the environment by performing fire

More information

Irrigation System Winterization and Pressurization Procedures

Irrigation System Winterization and Pressurization Procedures Irrigation System Winterization and Pressurization Procedures Introduction Any time that an irrigation system is filled and pressurized, or when the system is drained and water flushed from the system,

More information

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition)

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition) Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs ( Edition) JPR # Task Initial Certification JPR Requirement: 15 Mandatory Renewal JPR Requirement: 100% of All JPRs (including

More information

Foam Systems. Fire Protection Solutions

Foam Systems. Fire Protection Solutions Foam Systems Fire Protection Solutions Foam Extinguishing Systems Foreword Foam fire suppression systems are, in most cases, the only suitable solution for the protection of special hazards. They are widely

More information