National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Size: px
Start display at page:

Download "National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: FROM: NFPA Technical Committee on Water Tanks Elena Carroll, Administrator, Technical Projects DATE: August 18, 2011 SUBJECT: NFPA 22 ROP TC Letter Ballot (F2012) The ROP letter ballot for NFPA 22 is attached. The ballot is for formally voting on whether or not you concur with the committee s actions on the proposals. Reasons must accompany all negative and abstention ballots. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. Please complete and return your ballot as soon as possible but no later than Thursday, September 8, As noted on the ballot form, please return the ballot to Elena Carroll either via to ecarroll@nfpa.org or via fax to You may also mail your ballot to the attention of Elena Carroll at NFPA, 1 Batterymarch Park, Quincy, MA The return of ballots is required by the Regulations Governing Committee Projects. Attachments: Proposals Letter Ballot

2 22-1 Log #CP1 Technical Committee on Water Tanks, Review entire document to: 1) Update any extracted material by preparing separate proposals to do so, and 2) review and update references to other organizations documents, by preparing proposal(s) as required. To conform to the NFPA Regulations Governing Committee Projects. Update all referenced publications to the most recent editions. ****Insert Include 22-LCP1_CA **** 22-2 Log #CP7 Technical Committee on Water Tanks, 1.2 Purpose. The purpose of this standard is to provide a basis for the design, construction, operation, and maintenance of water tanks for private fire protection. Nothing in this standard shall prevent the use of systems, methods, or devices that are equivalent in quality, strength, fire resistance, effectiveness, and durability to those prescribed by this standard, provided technical documentation is made available to the authority having jurisdiction that demonstrates equivalency and the system, method, or device is appropriate for the intended purpose. The text has been removed and is covered in section Log #9 Kenneth E. Isman, National Fire Sprinkler Association, Inc. Add new text to read as follows: Insert new sections and as follows: Bladder Tanks Not Within NFPA 22 Scope. The following types of bladder tanks are not required to meet NFPA 22: (1) Listed bladder tanks used as surge suppressers on the discharge side of fire pumps installed in accordance with NFPA 20. (2) Listed bladder tanks used as expansion tanks for antifreeze sprinkler systems installed in accordance with NFPA 13. (3) Bladder tanks used as foam concentrate tanks installed in accordance with NFPA 16 or NFPA Bladder Tanks Within the Scope of NFPA 22. Bladder tanks shall be permitted to be a part of the water supply for a fire protection system when they meet the requirements of pressure tanks of this standard. The standard is currently silent on the issue of bladder tanks. There are many different types of bladder tanks used in the fire protection industry. Our intent is not to disturb the current practice of using bladder tanks in a variety of ways that do not technically meet NFPA 22. But for those circumstances where the bladder tank is used as a part of the water supply for a sprinkler (or other fire protection system), the tank needs to be pressurized and should be treated like a pressure tank. 1

3 Reference Publication Year in Code Title Change Most Recent Publication Year NFPA NFPA NFPA NFPA NFPA NFPA NFPA NFPA NFPA NFPA ACI ACI 350R ANSI SI IEEE/ ASTM S API 5LC ASHRAE ASME Boiler and Pressure Vessel Code ASTM A 6/ A 6M ASTM A 27/ A 27M ASTM A 36/ A 36M ASTM A ASTM A 105/ A105M ASTM A ASTM A ASTM A 131/ A 131M ASTM A ASTM A 181/ A 181M ASTM A 283/ A 283M ASTM A 285/ A 285M ASTM A ASTM A ASTM A 516/ A 516M ASTM A 572/ A 572M ASTM A 615/ A 615M ASTM A 668/ A 668M ASTM A 675/ A 675M ASTM A 992/ A 992M ASTM A ASTM C NFPA 22 Log #CP1 CA F2012 ROP

4 ASTM C ASTM D ASTM D ASTM D ASTM D ASTM D Standard Specifications of the American Wood Preservers Association by the Empty-Cell Process AWS A AWS D AWWA C AWWA D AWWA D AWWA D AWWA D AWWA D AWWA D NWTI Bulletin S SSPC SSPC SP SSPC SP SSPC SP Merriam-Webster's Collegiate Dictionary NFPA 22 Log #CP1 CA F2012 ROP

5 22-4 Log #25 Update referenced AWWA standards to latest editions: AWWA C AWWA D (2011 edition currently in pre-publication phase) AWWA D (2011 edition currently in pre-publication phase) AWWA D AWWA D AWWA D Referenced AWWA standards have been update to comply with applicable new codes and regulations. Update referenced AWWA standards to latest editions: AWWA C AWWA D AWWA D AWWA D AWWA D AWWA D Revised to reference the newest editions, which have been formally accepted by the AWWA Log #22 Technical Committee on Fire Pumps, Add new text to read as follows: A tank providing suction to a fire pump whose capacity is less than the fire protection demand (flow rate times flow duration). Resequence existing Section Guidance for designing break tanks is needed in NFPA 22. This definition is part of the submittal for design guidelines. This submittal to NFPA 22 was accepted by the NFPA 20 committee at the January 2011 ROP meeting in Orlando. This comment was balloted through the Technical Committee on Fire Pumps with the following results: 30 Members Eligible to Vote 5 Not Returned (J. Beals, D. Haagensen, J. McGrath, J. Roberts, and H. Stewart) 25 Affirmative on All 0 Negatives 0 Abstentions 2

6 22-7 Log #18 Kenneth E. Isman, National Fire Sprinkler Association, Inc. New text to read as follows: Add a new definition for suction tank as follows: Suction Tank. Any tank that provides water to a fire pump. The term suction tank is used throughout the standard (section and Table (c) to show a few examples) but is not defined. Although the term is understood by people that know the industry, codes and standards should not rely on such understanding Log #CP8 Technical Committee on Water Tanks, Add new definition as follows: A large diameter shaft that surrounds and encloses the piping below an elevated gravity tank to provide a measure of insulation and protection. Change the term " " to " " throughout the entire document. The committee believes that there is potential confusion over the term "riser" as used in NFPA 13 and NFPA 22. The committee has redefined the term "riser" to "tank riser" to maintain terminology separation and clarity. For consistency the term will be revised throughout the document. 3

7 22-8 Log #23 Technical Committee on Fire Pumps, Insert new Section 4.2. The size and elevation of the tank shall be determined by conditions at each individual property after due consideration of all factors involved. Wherever possible, standard sizes of tanks and heights of towers shall be as specified in 5.1.3, 6.1.2, 8.1.3, and Section 9.2. For suction tanks, the net capacity shall be the number of U.S. gallons (cubic meters) between the inlet of the overflow and the level of the vortex plate. A tank shall be sized so that the stored supply plus reliable automatic refill shall be sufficient to meet the demand placed upon it for the design duration. A break tank shall be sized for a minimum duration of 15 minutes with the fire pump operating at 150 percent of rated capacity. The adequacy and dependability of the liquid source for filling the are of primary importance and shall be fully determined, with due allowance for its reliability in the future. Any source of water that is adequate in quality, quantity, pressure, and reliability to fill the tank in accordance with this standard shall be permitted. Where the water supply from a public service main is not adequate in quality, quantity, or pressure, an alternative water source shall be provided. The adequacy of the liquid supply shall be determined and evaluated prior to the specification and installation of the tank. Resequence Existing Section Guidance for designing break tanks is needed in NFPA 22. This definition is part of the submittal for design guidelines. This submittal to NFPA 22 was accepted by the NFPA 20 committee at the January 2011 ROP meeting in Orlando. This comment was balloted through the Technical Committee on Fire Pumps with the following results 30 Members Eligible to Vote 5 Not Returned (J. Beals, D. Haagensen, J. McGrath, J. Roberts, and H. Stewart) 25 Affirmative on All 0 Negatives 0 Abstentions Insert new Section 4.2. The size and elevation of the tank shall be determined by conditions at each individual property after due consideration of all factors involved. Wherever possible, standard sizes of tanks and heights of towers shall be as specified in 5.1.3, 6.1.2, 8.1.3, and Section 9.2. For suction tanks, the net capacity shall be the number of U.S. gallons (cubic meters) between the inlet of the overflow and the level of the vortex plate. A tank shall be sized so that the stored supply plus reliable automatic refill shall be sufficient to meet the demand placed upon it for the design duration. A break tank shall be sized for a minimum duration of 15 minutes with the fire pump operating at 150 percent of rated capacity. The adequacy and dependability of the water source for filling the tank are of primary importance and shall be fully determined, with due allowance for its reliability in the future. Any source of water that is adequate in quality, quantity, pressure, and reliability to fill the tank in accordance with this standard shall be permitted. Where the water supply from a public service main is not adequate in quality, quantity, or pressure, an 4

8 alternative water source shall be provided. The adequacy of the water supply shall be determined and evaluated prior to the specification and installation of the tank. Resequence Existing Section NFPA 22 pertains only to water tanks and not to storage of other liquids Log #26 Delete the language 'and heights of towers'. The referenced sections don't address heights of towers. See Committee Proposal (Log #CP9) Log #CP9 Technical Committee on Water Tanks, Wherever possible, standard sizes of tanks and heights of towers shall be as specified in 5.1.3, 6.1.2, 8.1.3, and Section 9.2 and The standard sizes for concrete tanks should also be referenced here in Chapter Log #27 Revise this section to provide specific distances required to be considered not subject to fire exposure or provide reference to another standard that does provide specific direction. The location of tanks shall be such that the tank and structure are not subject to fire exposure. It is unclear how to identify what distance constitutes 'not subject to fire exposure'. The location of tanks shall be such that the tank and structure are protected from not subject to fire exposure in accordance with through The subsections provide the manner by which the tank shall be protected from fire exposure Log #28 Coordinate the language of Sec and to eliminate the contradictory language by stating something like Except as provided in , the location of tanks " This section allows tanks to be subject to fire exposure contradicting Sec that prohibits locations where the tank would be subject to fire exposure. Which requirement applies? The language is not contradictory. See Committee Action on Proposal (Log #270). 5

9 22-13 Log #13 Kenneth E. Isman, National Fire Sprinkler Association, Inc. Revise section by inserting the words, supporting tanks so that the sentence reads, Fireproofing, where necessary, shall be provided for steelwork supporting tanks within 20 ft... The proposed additional words are necessary to show that the steel of the tank itself is not required to be fireproofed. Only the support structure is required to be protected from fire exposure Log #29 Revise this section to identify specific conditions for which the manufacturer must provide systems or features not described in NFPA 22. This section requires: In addition to complying with the requirements of this standard, it is expected that the manufacturers of approved structures will also follow the spirit of the standard, by using their experience and ability to create structures that prove reliable under specified conditions. As written, the language does not provide specific requirements which can lead to conflict between contractor, owner and AHJ. Are there sections of NFPA 22 that do not include sufficient requirements such that the manufacturer would be expected to provide designs, details or methods in excess of the requirements of NFPA 22? Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee Log #31 Revise the requirement by deleting the words where a balcony is omitted. This section requires inspection to include a check of the appearance of welding in tank plates where a balcony is omitted. Is the appearance of welding really important if the balcony is omitted? Is there an acceptance criteria for 'appearance' or do we just comment that the welding may be of unsightly or unacceptable appearance? 6

10 22-16 Log #30 Delete the requirement for measuring the extent of inaccessible dents. This section requires the inspection to include the extent of inaccessible dents. If the dents are inaccessible how is the extent of the dents to be determined? The inspection shall include, but shall not be limited to, a check of the following: (1) The thickness of butt-welded plates in tanks and tubular columns (2) The appearance of welding in tank plates where a balcony is omitted and in tubular columns and at struts, except near the ladder and base of the structure (3) The extent of inaccessible dents and out-of-roundness of tubular columns and struts The committee agrees with the submitter's point. Specific text was not provided Log #6 Jon Nisja, Northcentral Regional Fire Code Development Committee Alter section 4.8 as follows: To prevent lightning damage to tanks, protection shall be installed in accordance with Section 4.4 of NFPA 780. Section 4.4 of NFPA 780 is a very small part of the Standard that deals with mechanical damage or displacement only. There are numerous references throughout 780 dealing with lightening protection in tanks and 4.4 is not the only reference. If the intent is to require lightning protection, NFPA 780 should be referenced in its entirety Log #32 Revise the reference section of NFPA 780 to Sec This section requires lightning protection in accordance with Sec. 4.4 of NFPA 780. See Committee Action on Proposal (Log# 6). The committee believes that NFPA 780, Standard for the Installation of Lightning Protection Systems, should be referenced in its entirety Log #33 Revise this section by adding specific acceptance criteria or tolerances. This section requires that workmanship be of such quality that defects or injuries are not produced during manufacture or erection. What constitutes a defect if dents and out of roundness are acceptable (as identified in inspection per )? Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee 7

11 22-20 Log #34 Revise the language of Sec in conjunction with Sec to eliminate the contradictory requirements. This section requires the when the roof is essentially airtight, there shall be a substantial vent above the maximum water level. Sec requires that the roof fit tightly to the top of the tank to prevent the circulation of air over the surface of the water. See Committee Action on Proposal (Log# 52) Log #35 Revise this section by deleting the end of the sentence beginning with to minimize the risk If necessary, move language to the Annex. This section states Where dual service is specified and where local health departments require screening vents against insects, a non-metallic screen or special fail-safe vent shall be provided to minimize the risk in the event that the screens frost over. How does a non-metallic screen minimize risk in the event that the screens frost over? Where dual service is specified and where local health departments require screening vents against insects, a nonmetallic screen or special fail-safe vent shall be provided to minimize the risk in the event that the insect screens occlude frost over. The committee agrees that the use of non-metallic screens does not minimize the risk of the screen occluding Log #36 Replace 'roof vent' with 'vent fan'. This section requires that a roof vent be attached to a flanged neck prior to entering the tank. If a vent would suffice, then the cover of the flanged neck could just be removed to provide the same natural ventilation provided by a vent. It seems that the intention was to add a fan to the flanged neck to provide forced ventilation. 8

12 22-23 Log #37 Revise this section to reference AWWA D100 for limitations on plate thickness. Under AWWA D100, ASTM A283 Gr A is only allowed for non-structural components, Gr B and Gr C are limited to 1 in. for shell plates and Gr D is limited to 3/4 in. for shell plates. API 650 has similar limitations. Under NFPA 22, no restrictions apply. Plate materials shall be of open-hearth, electric furnace, or basic oxygen process steel that conforms to AWWA D100 and one of the following ASTM specifications: (1) ASTM A 36/A 36M (2) ASTM A 283/A 283M, Grades A, B, C, and D The committee agrees with the submitter's substantiation. Specific text was not provided Log #38 Revise this section to read ' that complies with one of the following ASTM specifications " As written, this sections requires plates to comply with all referenced specifications, which they will not. See Committee Action on Proposal (Log# 37) Log #39 Revise this section with limitations on plate thickness or delete this material option. ASTM A285 specification includes grades A, B and C with minimum published yield strengths ranging from 24,000 psi to 30,000 psi. ASTM A285 material is not allowed by under AWWA D100 requirements and API 650 (for oil tanks) only allows grade C for thickness not over 1 inch. ASTM A283 specification is limited in thickness and application in both AWWA D100 and API 650. See Committee Action on Proposal (Log# 37). By referencing AWWA D100, this section does not need to be revised Log #40 ASTM A20 should be referenced for these. ASTM A6 is not applicable to ASTM A516 and ASTM A285 plate. Plates shall be furnished, based on weight, with permissible underrun and overrun in accordance with the tolerance table for plates ordered to weight in ASTM A 620. The committee agrees with the submitter's substantiation. Specific text was not provided. 9

13 22-27 Log #41 Revise this section to reference ASTM F1554 or reference AWWA D100 requirements. ASTM A307 no longer includes anchor bolts (Grade C). The 2007 edition was revised to delete ASTM A307 Grade C (anchor bolts) and all related references to anchor bolts and reference made to ASTM F1554 Gr 36 instead. ASTM A307 Gr A and B do not cover anchor bolt specifications. Bolts and anchor bolts shall conform to AWWA D100 ASTM A 307, Grade A or Grade B. The committee agrees with the submitter's substantiation. Specific text was not provided Log #42 Revise this section to specifically allowable the stress increase per AWWA D100. Section prescribes earthquake resistance per D100. Under AWWA D100, seismic design would include a 1/3 increase in allowable stress. The increase in allowable stress is specified by reference to AWWA D Log #43 Revised Sec. 5.4 to indicate Table 5.4 values plus the increase per , if applicable. This section states that stress produced by specified loads, including seismic loads, shall not exceed the values listed in Table 5.4. This does not allow the 1/3 increase indicated by Sec Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee Log #91 Revise the table to include an allowable for A36, the common steel grade in use today with a published minimum yield strength, Fy, of 36,000 psi. The allowable stress value for tension on net section of rolled steel does not reflect the current requirements in AWWA D100 that address different classes of steels based on their minimum published yield strength. The allowable tension stress in Table 5.4 appears to be based on outdated requirements that did not consider Class 2 materials. The older requirements were based on 0.50Fy and considered that the commonly used material had a published minimum yield strength, Fy, of 30,000 psi. The committee agrees with the submitter. However, the proposal did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee Projects. The committee will form a task group to modify Table 5.4 at the comment stage. 10

14 22-31 Log #92 Revise the table name or change the table contents to only include bending allowables. The title of Table 5.4 indicates that only bending stresses are included in the table. The table includes values for other types of stresses (the first two entries are for direct tension stress, not tension due to bending). See Committee Action on Proposal (Log #91) Log #93 Add a section referencing AWWA D100 for allowable anchor bolt stresses for load cases including seismic loads. The allowable tension stress for anchor bolts is very low compared with other industry tank standards such as AWWA D100 or API 650 resulting in anchor bolts substantially larger than normal. See Committee Action on Proposal (Log #91) Log #94 Revise the table values for anchor bolts to reflect current design practices of AWWA D100-05, Table 5. AWWA D100 provides allowable stresses for several different material specifications and grades of anchor bolts. Also, the allowable stresses for anchor bolts subject to seismic loading are higher than shown in Table 15.4, even if the one-third allowable stress increase is applied. The allowable stress levels in Table 5.4 appear to be based on outdated AWWA D100 requirements. See Committee Action on Proposal (Log #91) Log #95 Revise this table with a footnote that the allowable stress on anchor bolts is based on the area at the root of the threads. The allowable tension stress for anchor bolts does not indicate to which area they must be applied: root area, tensile stress area, gross area. AWWA D100 requires the anchor bolts to be designed based on the root area of the threaded portion. See Committee Action on Proposal (Log #91). 11

15 22-35 Log #96 Revise the formulas for compressive allowable. ***Insert Artwork (Table 5.4) Here*** The table inaccurately displays the values for compression on extreme fibers of rolled sections, plate girders and built-up members. See Committee Action on Proposal (Log #91) Log #44 Revise this section by adding the following sentence: The minimum thickness shall apply to the order thickness, regardless of thickness under-run allowed in the material specification. This section requires that the minimum thickness of tubular columns and struts shall be 1 / 4 in. of 1/4 in. The current text is clear as written. The committee's intent is to require a minimum thickness Log #45 Revise Section as follows: "Except for cylindrical shell plates in contact with water, the minimum thickness of..." This section contradicts with respect to minimum thickness. The committee disagrees that there is a conflict between and , since does not specify any minimum thickness that is less than 1/4 in Log #97 Revise the table to indicate the intended transition point or revise Bottom rings to Bottom ring. What is meant by the following terms: - Bottom rings (does this mean all rings below the top ring or all rings below mid height of the shell?) - Upper rings (does this mean all rings above the bottom ring or all rings above mid height of the shell?) Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee 12

16

17 22-39 Log #46 Revise Section as follows: "Except for tubular sections, the sections shall be..." This section requires tubular sections to be hermetically sealed. If they are hermetically sealed tubular sections, then they cannot be open sections as required by Except for hermetically-sealed tubular sections, the sections shall be open to facilitate cleaning and painting. Tubular sections used for columns on elevated legged tanks shall be hermetically sealed to prevent internal corrosion. Not all tubular sections are hermetically sealed Log #47 Revise this section by specifying the salt concentration and the types of salt intended to be covered. This section includes requirements for tanks that are to contain salt. How much salt must be present to be considered a tank that is to contain salt? Does this requirement apply to table salt or sea salt only, or does it apply to other salts as well? Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee Log #48 Revise this section by specifying the salt concentration above which the corrosion allowance applies. This section includes requirements for tanks that are to contain salt. Was this intended to mean tanks that are to contain salt water? If so, is there a minimum concentration at which the corrosion allowance applies? Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee 13

18 22-42 Log #49 Revise this section by specifying the ph range(s) for which the corrosion allowance applies. This section includes corrosion allowance requirements for tanks that are to contain alkaline water. If the ph of the water exceeds 7 it is considered alkaline, even if it is only 7.1. For purposes of this requirement for corrosion allowance, there must be a ph level at which the water is to be considered alkaline and a corrosion problem. Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee Log #50 Revise this section to include the 1/3 increase in allowable stress for load cases including seismic loads (per Sec or AWWA D100). (see also related comment on Sec. 5.4). This section allows tank design in accordance with AWWA D100, Sec. 14. Under AWWA D100 Sec. 14 design, a 1/3 increase in allowable stresses would apply for the seismic load case. Does the 1/3 increase in allowable stress provided in AWWA D100 apply for this case? If this option is not selected, does the 1/3 increase in allowable stress of Sec apply for the seismic load case? Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee Log #51 Revise the language to reference AWWA D100 requirements for allowable local buckling stress; or Revise to say the selected plate thickness shall comply with the allowable local buckling provide allowable local buckling stresses of this standard. And then add provisions for allowable local buckling stresses. This section includes a requirement that in cases where compressive stresses exist, the selected plate thickness shall prevent local buckling. The design requirements cannot prevent local buckling, but we can design within the allowable local buckling stresses to achieve the recommended strength for buckling resistance. Where compressive stresses exist, the selected plate thickness shall prevent local buckling in accordance with AWWA D100. The committee agrees with the submitter's substantiation, but specific text was not provided. Between the options proposed by the submitter, the committee prefers to reference AWWA D

19 22-45 Log #53 Delete this exception or rewrite this section in conjunction with Sec This requirement ( ) shall not apply to plate thicknesses calculated in accordance with Sec Based on review of the standard, it appears that all tank plates must be calculated in accordance with Sec , so this exception means that it does apply to any tank plates. Delete Section The committee agrees with the submitter's recommendation to remove Log #54 Revise this section to read: The longitudinal joints in adjacent circumferential courses shall be staggered or shall be aligned. The entire Chapter 5 is for welded steel tanks. Submitter did not provide a technical justification Log #55 Because applies to all tank plates, delete Sec and all subsections or rewrite the exception to match the intent. Permission to use 4-way junctions shall not apply to plate thicknesses in accordance with Sec Based on review of the standard, it appears that all tank plates addresses in Sec must be calculated in accordance with Sec , so it appears that Sec negates the validity of Sec. 5.8 Delete section The committee agrees with the submitter and chooses to delete the section Log #1 Steven Adolphsen, CBI Services Revise text as follows: The roof purlin depth shall NOT be less than 1/30 of the span length. Limiting depth causes purlins to be springy and adds to ponding on roof due to mid span deflection. If lateral stability is of concern, then specify bracing (we use 12.5' max). See Committee Action on Proposal (Log #CP2). 15

20 22-49 Log #56 Revise the term 'shall' should be 'may' allowing rafters to be less than L/30 rather than requiring it, or Revise the term shall to shall not if it is intended to require stiffer roofs for NFPA 22 tanks than would otherwise be provided for AWWA D100 water tanks. This requirement is an inadvertent error when updating from earlier editions of AWWA and AISC requirements. Under the 1955 edition of AWWA D100, based on the then applicable AISC specifications for design of structural steel (June 1949 edition), D100 included an exception to the requirements of the AISC rules. The AISC specification at that time required that the depth of roof purlins be no less than 1/30 of the span. AWWA D100 then required design in accordance with the AISC specification except that the minimum depth of roof rafters may be less than 1/30 of the span. Later editions of the AISC specification eliminated the minimum depth of members support roofs. AWWA D100 requirements continued to carry the exception until the 1973 edition, where the exception was only allowed as long as the design roof pitch was at least 3/4 :12 in order to minimize ponding. Then, in the 2005 edition, AWWA D100 was revised to require a minimum roof slope of ¾:12, therefore the reference to minimum depth has been deleted. It appears that at some point, the NFPA standard decided to revise the language from may be less than 1/30 of the span length to shall be less than 1/30 of the span length, but failed to realize that the language in AWWA D100 was stated as may be less because it was an exception to the AISC requirement. So, when the language in NFPA 22 was revised, may should have changed to shall not. As stated in the current standard, this requires rafters of relatively short depth which produces springy roof structures with more deflection. The current AWWA D100 requires a minimum roof slope of ¾:12, therefore the reference to minimum depth has been deleted. See Committee Action on Proposal (Log #CP2) Log #CP2 Technical Committee on Water Tanks, Delete Section This section is being removed for compatibility with AWWA D

21 22-51 Log #57 Revise Sec to only apply to elevated tanks as follows: For elevated tanks, plates shall be Add a new section to 5.6 referencing erection tolerances from AWWA D100 as follows: Tanks shall meet the erection tolerance requirements of AWWA D100. Current industry standards only require rolling of shell plates for elevated steel tanks. Also, under AWWA D100, all tanks must meet specific erection tolerances to confirm validity of design for compressive loads Log #52 Delete this section or rewrite to coordinate with Sec It seems that prevent circulation of air over the surface of the water prevents open vents above the top capacity line which conflicts with Sec that requires a vent. The roof shall fit tightly to the top of the tank to prevent the circulation of air over the surface of the water shell to eliminate any gap between the roof and the shell. The revised text clarifies the intent of the section Log #58 Delete the words: to prevent the circulation of air over the surface of the water.' Roof fitted tight to the top of the tank does not prevent the circulation of air over the surface of the water. Which is the requirement: roof fitted tight to the top of the tank or prevention of air circulation of the surface of the water? Why is this required? See Committee Action on Proposal (Log# 52). 17

22 22-54 Log #59 Revise this section to reference that the sand base shall conform to the requirements of AWWA D100 as follows: The sand pad, including ph range of the lime sand mix, sulfate content and chloride content shall meet the requirements of AWWA D100. This section requires a lime treatment of the undertank sand pad to achieve a ph between 6.5 and 7.5 and limits the chloride content to 300 ppm and the sulfate content to 1000 ppm. For corrosion protection of the underside of the tank bottom, AWWA D100 requires limits on chlorides of 200 ppm and sulfates of 100 ppm and, if the sand is treated with lime, a minimum ph of 10.5 for the lime sand mix. Are the higher limits of chlorides and sulfates and low ph range required by NFPA 22 based on testing or research or is this requirement a holdover from previous editions? Log #60 Revise the language by deleting the reference to the inside ladder being located at the second hatch and adding language that an inside ladder be provided for access to the tank floor. Sections , and contain the following requirements: - An easily accessible roof hatch shall be provided. - A second roof hatch shall be place 180 from the existing roof hatch with a ladder to access the tank floor. - Outside and inside steel ladders that are arranged for convenient passage from one to the other and through the roof hatch shall be provided. From these requirements, the inside ladder will be 180 apart from the outside ladder since the outside ladder will provide easy access to the first hatch, and the inside ladder is located at the second hatch. ***Insert Figure Here*** A second roof hatch shall be placed 180 degrees from the primary existing roof hatch with a ladder to access the tank floor Outside and inside steel ladders that are arranged for convenient passage from one to the other and through the primary roof hatch shall be provided. Revise Fig B.1(I) to show secondary roof hatch 180 deg from primary roof hatch. Delete the centerline of the hatch. ***INSERT 22- (Log# 60)-CA. FIGURE B1(I).*** HERE The revised language clarifies the committee's intent that a second interior ladder is not required. The purpose of the second roof hatch is for ventilation. 18

23

24

25 22-56 Log #61 Revise section to read: All outside ladders shall be Section addresses Outside Fixed Shell and Roof Ladder. The text is located under the Outside Ladder section Log #62 Except for the underside of the floor on ground-supported flat-bottom tanks, interior dry surfaces of single pedestal tanks, and faying surfaces of bolted joints that prohibit coatings, parts that are inaccessible after fabrication shall be protected by paint before assembly. Clarify but that are subject to corrosion - Does this mean only interior parts exposed to the stored water or vapor zone? - Does it include exterior weather exposed parts? - Is it only intended to exclude parts such is inside dry surfaces (pedestal tanks) or inaccessible parts that are hermetically sealed from the water, water vapor, or weather? Except for the underside of the floor on ground-supported flat-bottom tanks, parts that are inaccessible after fabrication, but that are subject to corrosion, shall be protected by paint before assembly. The rejected parts of the proposal are covered under the definition of parts that are inaccessible after fabrication Log #63 Revise this section to state either protected by primer or protected by full coating system This section requires that parts that are inaccessible after fabrication, but that are subject to corrosion, shall be protected by paint before assembly. It is unclear whether protected by paint means primed and finish coated or whether the primer coat of paint is sufficient. The intent of the standard is not to dictate how many coats of paint are required to protect steel. It is up to the purchaser to determine. 19

26 22-59 Log #64 Revise the language to clarify that this requirement does not apply to the underside of tank bottoms that are covered by Section This section as written does not exclude applicability to underside of tank bottoms. See Committee Action on Proposal (Log# 62) Log #65 Delete this section. We haven t used riveted tank construction for sixty of seventy years and this requirement is in the section for welded steel tanks, so I have no clue what is intended by this requirement. It is improbable that suitable welding procedure specifications can be developed to weld a joint that includes oil or lacquer on the surfaces contained inside the joint such as contact surfaces between two members being completely welded together Log #66 Revise this section by deleting the words:, or pickling in accordance with SSPC SP 8, SSPC SP8 may not give suitable profile for adhesion of coatings. Most coating systems today require a surface profile not achievable by pickling Log #67 Revise the section to address the following items: 1. Allow weld margins on components to be welded together in the field after being primed in the shop. 2. Not require coatings on faying surfaces of structural bolted joints that prohibit coatings. None given. The submitter did not provide specific language or technical substantiation. 20

27 22-63 Log #68 Revise this section by deleting the words:, or pickling in accordance with SSPC SP 8, SSPC SP8 may not give suitable profile for adhesion of coatings. Most coating systems today require a surface profile not achievable by pickling Log #69 Revise the section to address the following items: Delete the words lead-free. This requirement is covered by Sec Revise the language to clearly not require priming on the underside of the floor unless Sec applies. Revise to allow weld margins on components to be welded together in the field after being primed in the shop All exterior surfaces and inside dry surfaces (pedestal tanks) shall be cleaned by commercial blasting in accordance with SSPC SP 6, or pickling in accordance with SSPC SP 8, and shall be primed with one coated of lead-free alkyd in accordance with the requirements of for Outside Paint System No. 1 of AWWA D102. The committee removed the words "lead free" and added language to coincide with AWWA D Log #70 Revise the language to clearly not require priming on the underside of the floor unless Sec applies. None given. See Committee Action on Proposal (Log# 62) Log #71 Revise the section to include unprimed surfaces as follows: After construction, all weld seams, unprimed surfaces, and any areas " As written, this section implies that the tank components must be primed prior to erection even though Sec and do not require that After construction, all weld seams, unprimed margins, or and any areas where the primer (if preprimed) has been damaged shall be blast-cleaned and patch-primed with the same primer. The revised text removes the implication that all components must be shop primed. 21

28 22-67 Log #72 Revise to read interior surfaces (exposed to stored water or the vapor zone) (See also comment related to Sec ) This section provides requirements for finish coats of interior surfaces exposed to stored water, but fails to include those interior surfaces exposed to the vapor zone. Revise text to read as follows; All finish coat painting for interior surfaces (exposed to stored water) shall be in accordance with the requirements for Inside Paint System No. 1 of AWWA D102., using the same basic system throughout. The intent of the standard is not to limit the use of only one AWWA D102 system Log #73 Revise this section to allow different AWWA D102 Inside Coating Systems to be used for the surfaces above and below the top capacity level. Depending on the details of roof constructions utilized, it is sometimes desirable to utilize a different interior coating system. If Sec is intended to apply to all interior surfaces (not only immersion surfaces), then it does not allow a different coating system for the roof surfaces? See Committee Action on Proposal (Log #72) Log #74 This is not good practice. Add the language or the vapor zone into Sec The finish coats for interior surfaces exposed to stored water are required to comply with AWWA D102 Inside Coating System No. 1 per Sec Because section does not include the language interior surfaces (exposed to stored water or the vapor zone), the interior surfaces above the top capacity level would fall under Sec and be finish coated with an exterior coating system. Finish coat painting for all exterior and interior surfaces not exposed to stored water shall be in accordance with the requirements for Outside Paint System No. 1 of AWWA D102., using two coats of aluminum or alkyd enamel in a color, as specified by the purchaser, to provide a minimum total system dry (not exposed to stored water) film thickness of 3.5 mils (0.09 mm) for aluminum finishes and 4.5 mils (0.1 mm) for alkyd enamels. The intent of the standard is not to limit the use of only one AWWA D102 system. 22

29 22-70 Log #75 Delete the words not exposed to stored water. In this sentence, dry applies to dry film thickness, not to surfaces not exposed to the water or the weather. See Committee Action on Proposal (Log# 74) Log #76 Since the reader must go to the AWWA standard for requirements of the coating systems, revise this section by deleting the end of the sentence beginning with the words, to provide a minimum total system dry The coating system specifications in AWWA D are different than those in AWWA D Outside Coating System No.1 still defines and alkyd coating system with an option for a four-coat system and an option for aluminum finish coats, but now adds an option silicone alkyd finish coat. The total dry film thickness for each coating system option varies, but they do not match those specified in Sec See Committee Action on Proposal (Log# 74) Log #77 Delete Sec This section states 'As provided for in Outside Paint System No. 4 ', but Sec states that coatings shall be per OCS-1. Outside system No. 4 in the 1997 edition of AWWA D102 described a vinyl coating system that would not generally be compatible over an alkyd primer. AWWA D no longer includes a vinyl system. Sec and Sec allow for other systems to be used, so this section is not necessary. 23

30 22-73 Log #78 Revise to read as follows: With approval of the authority having jurisdiction, other finish coats shall be permitted to be used where they are compatible with the selected primer, comply with AWWA D102, and are approved by the authority having jurisdiction. This section allows other finish coats (excluding Inside Coating System No. 5) to be used with approval of the AHJ. This allows finish coats to be used that may not be compatible with the prime coats. Also, current editions of AWWA D100 no longer include coal tar coating system (in AWWA D102-06, ICS-5 is now a zinc rich primer / epoxy / epoxy coating system). See Committee Action on Proposal (Log #CP3) Log #CP3 Technical Committee on Water Tanks, Delete section The standard does not want to refer to coating systems individually. The intent is to reference AWWA D102 in its entirety. 24

31 22-75 Log #20 Kenneth E. Isman, National Fire Sprinkler Association, Inc. Revise Section and add an annex note as follows: Pressure tanks shall be kept with a supply of water to meet the flow and duration demands of the fire protection system as calculated in Chapter 14 of NFPA 13, for the duration required by Chapter 11 of NFPA 13. The quantity of air in the tank and pressure shall be sufficient to push all of the water out of the tank while maintaining the necessary residual pressure required by Chapter 14 of NFPA 13 at the top of the system. Where otherwise approved by the authority having jurisdiction, this requirement shall not apply. Pressure tanks must contain a volume of air, that when pressurized, pushes the water out of the tank (see Figure A ). The larger the quantity of air, the less pressure is necessary to push the water out of the tank. To size a pressure tank properly for a hydraulically calculated fire sprinkler system, determine where you are going to locate the tank, calculate the demand of the fire protection system to the discharge flange of the tank, and then select a volume of tank larger than what is needed to meet the flow and duration demand of the fire protection system. Next, calculate the pressure necessary to push the water out of the tank and maintain the pressure demand in the fire protection system. If the pressure necessary to hold in the tank is higher than the pressure rating of the fire protection system components, select a larger tank. Finally, convey to the owner the ratio of water to air that must be kept in the tank and the minimum tank pressure for maintenance purposes. A formula that can be used for determining the pressure at which the tank needs to be held is: P i = (P f + 15)/A 15 Where P i = tank pressure P f = pressure demand of the fire protection system calculated to the discharge flange of the tank A = percentage of the volume of the tank set aside for air, expressed as a decimal (for example 50% would be expressed as 0.5 ) For example, consider a light hazard sprinkler system with a duration demand of 30 minutes and a demand of 125 gpm at 55 psi calculated to the discharge flange of the tank. If a 5000 gallon tank was used and filled 75% with water, this would meet the 3750 gallon duration demand of the sprinkler system ( = 3750). The remaining 25% of the volume of the tank would be available for air and the tank would need to be pressurized to 265 psi as calculated below: P i = (P f + 15)/A 15 = ( )/ = 265 Clearly this pressure is too high for a sprinkler system where most of the components are rated for a maximum of 175 psi. Unless high pressure rated components are going to be used, a larger thank should be considered. For this same sprinkler system, a 7,000 gallon tank could be used and filled with 3750 gallons of water (54% water and 46% air). This tank would only need to be pressurized to 137 psi, calculated as follows: P i = (P f + 15)/A 15 = ( )/ = 137 This would clearly be a better selection of a tank for this fire protection system. Note that the owner will need to know where the 3750 gallon fill point of the tank is. If the tank is overfilled, then the quantity of air will be decreased and the pressure of 137 will be insufficient to push the water out of the tank at the proper pressure. Tanks above fire protection systems have the advantage of needing less pressure because the water will gain pressure as it drops out of the tank. However, putting tanks above the fire protection system is not always possible. Tanks in basements will work fine if the pressure is calculated correctly. ***Insert 22_L20_Fig A _Rec here*** The pressure tank chapter permits pressure tanks to be used for all kinds of fire protection systems, but only references NFPA 13 in the sizing situation. This is because NFPA 13 is the only document with good information on sizing and calculating the pressure for the tank. Rather than reference NFPA 13, it would be better to put this information in NFPA 22 directly. Since the information keeps moving in NFPA 13, the chapter references become obsolete anyway. 25

32

33 22-76 Log #21 Kenneth E. Isman, National Fire Sprinkler Association, Inc. Delete text to read as follows: Delete the sentence that is currently and all of Section Renumber existing as a new so that all that is left of is the following: Subject to the approval of the authority having jurisdiction, tanks shall be permitted to be buried in accordance with the requirements of There is no reason to require tanks to be above the top level of sprinklers and there is no reason to require special permission of the AHJ to put tanks in the basement or anywhere below the top level of sprinklers. The formula used by NFPA 13 to size tanks and determine pressure (and proposed for NFPA 22 in our previous proposal) adjusts for the elevation pressure situation by forcing a higher pressure for the tanks below the activating sprinklers/nozzles Log #CP10 Technical Committee on Water Tanks, A listed horizontal bronze-seat swing-check valve and an renewable-disc globe indicating control valve shall be provided in the horizontal position in the pipe near the tank The globe indicating control valve shall be placed between the check valve and the tank. The language indicates the modern practice Log #79 Revise sections , , , and to provide consistent, unambiguous requirements that are not contradictory with each other. Section requires the tank to be set on a compacted crushed stone or granular base or on concrete foundations. Then, Sec requires a 3 in. layer of clean dry sand be laid on the compacted grade, but does not indicate to which of the types of foundations addressed in Sec this will apply. Projects. Submitter did not provide specific text, per 4.3.3(c) of the Regulations Governing Committee 26

AWWA D103 - AWWA issued an addendum to D103 incorporating important changes to the standard. The reference should incorporate the addendum.

AWWA D103 - AWWA issued an addendum to D103 incorporating important changes to the standard. The reference should incorporate the addendum. 1 of 104 6/15/17, 7:53 AM Public Comment No. 13-NFPA 22-2016 [ Section No. 2.3.8 ] 2.3.8 AWWA Publications. American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235. AWWA C652, Disinfection

More information

Vertical and Horizontal Bladder Tanks

Vertical and Horizontal Bladder Tanks DATA SHEET Vertical and Horizontal Tanks Application The ANSUL bladder tank is one component in a balanced pressure proportioning system. Its operation requires no external power other than a pressurized

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE June 1, 2008 Foam 240a 1. DESCRIPTION The Chemguard Bladder Tank is one component in a balanced pressure foam proportioning system. It requires no external power, other than the water pressure to ensure

More information

Vertical Bladder Tanks

Vertical Bladder Tanks DATA SHEET Vertical Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

Horizontal Bladder Tanks

Horizontal Bladder Tanks DATA SHEET Horizontal Bladder Tanks Features UL Listed and FM Approved for use with various ANSUL proportioners and foam concentrates 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

Model MTB-ASME Vertical Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)

More information

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company CIF A Tyco International Company 1 Foam Concentrate CIF 3% AFFF -UL Listed -UL Canada Listed 6% AFFF 6 parts AFFF concentrate to 94 parts water -UL Listed- Foam Liquid -UL Canada Listed 3% FLUOROPROTEIN

More information

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Horizontal Bladder Tanks DATA SHEET Model MTB-ASME Horizontal Bladder Tanks Features n UL Listed and FM Approved for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure

More information

Liquefied gas cargo tanks and process pressure vessels

Liquefied gas cargo tanks and process pressure vessels .1 -.3 Liquefied gas cargo tanks and process pressure vessels.1 General.1.1 The present texts give the general principles which are applied by Classification Societies for approval and survey of the relevant

More information

AWWA C504 COMPLIANT VALVES FROM 3 THRU 108

AWWA C504 COMPLIANT VALVES FROM 3 THRU 108 AWWA C504 COMPLIANT VALVES FROM 3 THRU 108 PO Box 411 Berwick PA 18603 800-247-VALV www.crispinvalve.com 500 SERIES: Sizes 3-20 Available The K-Flo 500 Series is a heavy-duty resilient seated butterfly

More information

MSC Guidelines for Independent Fuel Tanks

MSC Guidelines for Independent Fuel Tanks References: Contact Information a. 46 CFR 58.50 (Independent Fuel Tanks) b. 46 CFR 119.440 (Independent Fuel Tanks) c. 46 CFR 182.440 (Independent Fuel Tanks) C. J. Robuck, LCDR, Chief, Engineering Division

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Electrical Equipment

More information

MEMORANDUM. NFPA Technical Committee on Lightning Protection Systems. NFPA 780 Supplement ROC TC FINAL Ballot Results (F2012Cycle)

MEMORANDUM. NFPA Technical Committee on Lightning Protection Systems. NFPA 780 Supplement ROC TC FINAL Ballot Results (F2012Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Lightning Protection

More information

SECTION BUTTERFLY VALVES

SECTION BUTTERFLY VALVES SECTION 15112 BUTTERFLY VALVES PART 1 GENERAL 1.01 SUMMARY A. All butterfly valves shall be of the tight closing, rubber seated type and fully comply with the latest revision of AWWA Standard C504, Class

More information

SECTION PRESSURE TESTING OF PIPING

SECTION PRESSURE TESTING OF PIPING SECTION 15044 PRESSURE TESTING OF PIPING PART 1 - GENERAL 1.01 DESCRIPTION A. Scope of Work: This section specifies the leakage and pressure testing of piping. B. Testing Records: PART 2 - PRODUCTS 2.01

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL)

STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL) STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL) TEE (HOT TAPPING MATERIAL) S-04-02-040 Page 1 of 7 1.0 SCOPE This specification covers the basic requirements for the design, manufacture and supply

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Public Comment No. 2-NFPA 30-2013 [ Section No. 21.4.1.1 ] 21.4.1.1 The materials of construction for tanks and their appurtenances shall be compatible with the liquid to be stored. In case of doubt about

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1048 - REVISED: 2009 Double Check Detector Fire Protection Backflow Prevention Assemblies Separate, complete laboratory

More information

Section GATE VALVES

Section GATE VALVES Section 02521 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of gate valves for isolation and dead-end service as shown on Plans and as specified herein. 1.02 MEASUREMENT

More information

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions

More information

Flange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing

Flange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing Flange Bolt Torquing for Resistoflex Plastic-Lined Piping Products Torquing When assembling flange connections, always use a full complement of clean, new high strength A193-B7 bolting. If using stainless

More information

MSC Guidelines for Pressure Vessels

MSC Guidelines for Pressure Vessels References: a. 46 CFR Part 54 Pressure Vessels S. T. Brady, CDR, Chief, Engineering Division b. ASME Boiler and Pressure Vessel Code (BPVC), Section VIII, Division 1, (1998 Edition) c. Navigation and Inspection

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Butterfly Valves C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Butterfly Valves C O N T E N T S SPECIFICATIONS - DETAILED PROVISIONS Section 15103 - Butterfly Valves C O N T E N T S PART 1 - GENERAL... 1 1.01 REQUIREMENT... 1 1.02 VALVE MANUFACTURER... 1 1.03 GUARANTEE... 1 PART 2 - PRODUCT... 1

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Pulverized Fuel Systems Jeanne Moreau-Correia DATE: August 5, 2009 SUBJECT: NFPA 85 ROP Letter Ballot The ROP letter ballot

More information

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks

API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks API MPMS Chapter 17.6 Guidelines for Determining the Fullness of Pipelines between Vessels and Shore Tanks 1. Scope This document describes procedures for determining or confirming the fill condition of

More information

SECTION DOMESTIC WATER PIPING

SECTION DOMESTIC WATER PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections

More information

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC 157-20067 1 PURPOSE 1.1 The purpose of this standard is to establish an acceptable standard

More information

General Inspection Guidance for Waste Management Units Requiring Air Emission Controls Under RCRA Air Standard Subpart CC

General Inspection Guidance for Waste Management Units Requiring Air Emission Controls Under RCRA Air Standard Subpart CC United States Environmental Protection Agency RCRA Programs Branch Region IV Atlanta, GA CAA/RCRA Air Rules 27 November 2000 General Inspection Guidance for Waste Management Units Requiring Air Emission

More information

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item:

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item: This ballot covers the following item: API 520 Part I 10 th Edition Ballot Item 2.1 2008 12 Modify guidance to PRV datasheets (Line 17) to assist user s with determining the temperature to use for selecting

More information

NSPS SUBPART Ka Check-off Form JULY 11, LAFAYETTE ROAD NO., ST. PAUL, MN

NSPS SUBPART Ka Check-off Form JULY 11, LAFAYETTE ROAD NO., ST. PAUL, MN 520 LAFAYETTE ROAD NO., ST. PAUL, MN 55155-4194 NSPS FORM NSPS-Ka NSPS SUBPART Ka Check-off Form JULY 11, 2005 I. Introduction An owner or operator may fill in this form in replacement of a highlighted

More information

MSC Guidelines for Engine Cooling Systems

MSC Guidelines for Engine Cooling Systems S. T. Brady, CDR, Chief, Engineering Division References: Contact Information: a. 46 CFR 56.60, 56.50-95 & 56.50-96 (Subchapter F) b. 46 CFR 77.03-1 (Subchapter H) c. 46 CFR 90.20 & 46 CFR 96.03 (Subchapter

More information

Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on Locomotives)

Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on Locomotives) Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on Locomotives) December 5, 1994 TM Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on

More information

Homestead Series 820 AWWA Butterfly Valves

Homestead Series 820 AWWA Butterfly Valves Homestead Series 820 AWWA Butterfly Valves Dependable Valves for Water & Wastewater Service BODY: The ductile iron body meets or exceeds the design strength requirements of the AWWA C504 standards. Flange

More information

22. Specialty Valves.

22. Specialty Valves. 22. Specialty Valves. a. Types of Specialty Valves. 1) Use of the following specialty valves is covered in this section: Altitude Valve, Pressure Reducing Valve, Pressure Relief Valve, Swing Check Valve,

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated

More information

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate December 6, 2010 Foam 21a 1. Description With Multiple Foam/Water Deluge Systems Supplied by a Bladder Tank, multiple deluge foam risers can be supplied from a single foam concentrate source. Where a bladder

More information

Regulations Respecting Compressed Gas Pressure Vessels

Regulations Respecting Compressed Gas Pressure Vessels COMPRESSED GAS PRESSURE VESSELS SR 99/70 1 Regulations Respecting Compressed Gas Pressure Vessels Repealed by Chapter B-5.1 Reg 1 (effective January 1, 2007) Formerly Saskatchewan Regulations 99/70 (effective

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Gas Products No. 335 (Supersedes Notice Gas Products No. 270, Ref No: N12-055) Effective Date: October 1, 2015 Date: July 21, 2014 Apply Before February 2, 2015 Announcing:

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data Technical Services: Tel: (800) 381-312 / Fax: (800) 71-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Model B-1 Pipe Line Strainer 3,, 6 & 8 Inch (DN80, DN100, DN150

More information

SECTION SWIMMING POOLS

SECTION SWIMMING POOLS SECTION 13 1100 SWIMMING POOLS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pool shell. 2. Pool mechanical system. 3. Pool heating system. 4. Interior pool finish. 5. Final testing and demonstration

More information

BLADDER TANK PROPORTIONING SYSTEM PRE-PIPED

BLADDER TANK PROPORTIONING SYSTEM PRE-PIPED BLADDER TANK PROPORTIONING SYSTEM PRE-PIPED HD FIRE PROTECT TECHNICAL DATA TANK MOUNTING Vertical or Horizontal TYPE COENTRATE For Vertical Tank 140 liters STORAGE CAPACITY to7500 liters (36 TO 2000 Gallon

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Heat Recovery Steam Generators Jeanne Moreau DATE: April 23, 2010 SUBJECT: NFPA 85 F10 ROC Letter Ballot The ROC letter ballot

More information

1213B2 Service Regulators Maximum Inlet Pressure 125 PSIG

1213B2 Service Regulators Maximum Inlet Pressure 125 PSIG SB-8506. B Service Regulators Maximum Inlet Pressure 5 PSIG Measurement Engineers Since 86 www.americanmeter.com B Service Regulators General Information The American Meter Series B pressure regulator

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016)

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Kelly

More information

Chapter 10 SWIMMING POOLS

Chapter 10 SWIMMING POOLS 4-10-1: COMPLIANCE REQUIRED: Chapter 10 SWIMMING POOLS It shall be unlawful to construct, maintain, install or enlarge any swimming pool in the City except in compliance with the provisions of this Chapter.

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

1800CPB2 Pilot-Loaded Service Regulators

1800CPB2 Pilot-Loaded Service Regulators 1800CPB2 Pilot-Loaded Service Regulators Technical Bulletin www.elster-americanmeter.com Table of Contents 1800CPB2 Regulator Information................ 2-3 1800CPB2 Capacity Performance................

More information

To be used as a coating for potable water tanks and pipes. Independently tested and certified for potable water storage. Other

To be used as a coating for potable water tanks and pipes. Independently tested and certified for potable water storage. Other Approved 31462;9441 1,2 31462 epoxy ^(ValidationDate) 1 Product description This is a two component solvent free amine cured epoxy coating. It is specially designed for drinking water tanks. Can be used

More information

CLEANING, INSPECTION, AND TESTING OF SEWERS

CLEANING, INSPECTION, AND TESTING OF SEWERS CLEANING, INSPECTION, AND TESTING OF SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Cleaning, Inspecting, and Testing Sanitary Sewers B. Cleaning, Inspecting, and Testing Storm Sewers C. Cleaning and

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644 Technical Services: Tel: (00) 31-9312 / Fax: (00) 791-5500 Model C Pipe Line Strainer 6, & 10 Inch (150, & 250) 250 psi (17,2) General Description The welded steel body Model C Pipe Line Strainers (Ref.

More information

ITEM 400 STRUCTURAL EXCAVATION AND BACKFILL

ITEM 400 STRUCTURAL EXCAVATION AND BACKFILL AFTER MARCH 1, 2012 ITEM 400 STRUCTURAL EXCAVATION AND BACKFILL 400.1 Description. This item shall govern for all excavation required for the construction of all structures, except pipe or box sewers for

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

2009 NEW MEXICO SWIMMING POOL, SPA AND HOT TUB CODE

2009 NEW MEXICO SWIMMING POOL, SPA AND HOT TUB CODE TITLE 14 CHAPTER 8 PART 3 HOUSING AND CONSTRUCTION PLUMBING CODES 2009 NEW MEXICO SWIMMING POOL, SPA AND HOT TUB CODE 14.8.3.1 ISSUING AGENCY: Construction Industries Division (CID) of the Regulation and

More information

pvc well casing & drop pipe

pvc well casing & drop pipe C e r t a i nte e d pvc well casing & drop pipe P V C We l l P r o d u c t s Sure Fit PVC well casing and drop pipe have gained broad acceptance since their introduction almost 40 years ago. Today, due

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

PIP PNE00012 Piping Examination and Leak Test Guide

PIP PNE00012 Piping Examination and Leak Test Guide October 2017 Piping PIP PNE00012 Piping Examination and Leak Test Guide PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has

More information

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys (Feb 2010) PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys Contents 1 Introduction 2 Preparations for Survey 2.1 General 2.2 Conditions for survey 2.3 Access to structures 2.4 Survey

More information

94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work?

94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work? 94270 What is Tank Blanketing? blanketing systems are used to prevent the escape of liquid vapors into the atmosphere or to prevent moisture from entering a tank and contaminating its contents. A tank

More information

REPORT HOLDER: FRAMECAD LICENSING LTD. POST OFFICE BOX 1292 AUCKLAND 1140 NEW ZEALAND EVALUATION SUBJECT: COLD FORMED STEEL C SHAPES AND TRACKS

REPORT HOLDER: FRAMECAD LICENSING LTD. POST OFFICE BOX 1292 AUCKLAND 1140 NEW ZEALAND EVALUATION SUBJECT: COLD FORMED STEEL C SHAPES AND TRACKS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2361 Reissued 05/2017 This report is subject to renewal 05/2019. DIVISION: 05 00

More information

Series 8500 Expansion Compensators. Catalog 674H

Series 8500 Expansion Compensators. Catalog 674H Series 8500 Expansion Compensators Catalog 674H 500 Laminated Bellows Expansion J Series 8500 on Joints Expansion Compensators Sizes 3/4" through 4" Threaded, welded, flanged and grooved steel pipe joints

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mechanical Systems

More information

Eaton Filtration, LLC

Eaton Filtration, LLC Eaton Filtration, LLC 900 Fairmount Avenue, Elizabeth, NJ 07207 Phone: 908-787-1000 Fax: 908-351-7893 E-Mail: filtration@eaton.com Web: www.filtration.eaton.com Installation, Operation & Service Manual

More information

THE PROCESS OF JOINT INTEGRITY

THE PROCESS OF JOINT INTEGRITY BOLTED JOINTS A.333 THE PROCESS OF JOINT INTEGRITY To assist in managing a process, ask yourself the following questions: why, what, who, and how? Why do we need a Flange Joint Integrity program? This

More information

Installation Operation Maintenance

Installation Operation Maintenance 682 Seal Cooler New generation seal cooler to meet and exceed the seal cooler requirements stated in the 4th Edition of API Standard 682 Installation Operation Maintenance Experience In Motion Description

More information

Existing Rule Language Compared to Proposed Rule Language

Existing Rule Language Compared to Proposed Rule Language Existing Rule Language Compared to Proposed Rule Language MINNESOTA RULES, CHAPTER 4717; REVISOR S ID NUMBER 4442 The following table is a summary of existing and proposed rules. For complete regulations

More information

OPENINGS AND REINFORCEMENTS 26

OPENINGS AND REINFORCEMENTS 26 ASME BPVC.VIII.1-2015 UG-35.2 UG-36 (4) It is recognized that it is impractical to write requirements to cover the multiplicity of devices used for quick access, or to prevent negligent operation or the

More information

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS SEC Project No. 1803007-000 November 20, 2006 TABLE OF CONTENTS I. ABSTRACT...1 II. INTRODUCTION...1 III. HISTORY...2 IV. VARIABLE SPEED

More information

Standard Pneumatic Test Procedure Requirements for Piping Systems

Standard Pneumatic Test Procedure Requirements for Piping Systems the pressure equipment safety authority Standard Pneumatic Test Procedure Requirements for Piping Systems AB-522 Edition 2, Rev. 1 Issued 2016-10-24 Table of Contents FOREWORD... 1 1.0 INTRODUCTION...

More information

Bladder Tank Installation & System Design Information

Bladder Tank Installation & System Design Information Bladder Tank Installation & System Design Information The Chemguard Bladder Tank is one component in a balanced pressure foam proportioning fire protection system. It requires no external power other than

More information

Guide for Evaluating Your Hose Assembly Supplier

Guide for Evaluating Your Hose Assembly Supplier Guide for Evaluating Your Hose Assembly Supplier Supplier Evaluation Checklist, and How to Clearly Define Application Requirements Safe, reliable hose assemblies require appropriate specification work

More information

NATURAL GAS MAINTENANCE. Part 192 Subpart "M"

NATURAL GAS MAINTENANCE. Part 192 Subpart M NATURAL GAS MAINTENANCE Part 192 Subpart "M" CONTACT INFORMATION Pamela West Pipeline Safety Specialist U.S. Department of Transportation PHMSA Inspector Training and Qualifications Main: (405) 686-2310

More information

CHEMICAL. Straight cut rod is provided in the materials listed below and includes nuts / washers.

CHEMICAL. Straight cut rod is provided in the materials listed below and includes nuts / washers. 161 STRAIGHT CUT ROD Straight cut rod is provided in the materials listed below and includes nuts / washers. Straight Rod 22-1/2 Bent Rod A 307 THREADED ANCHOR ROD, ZINC PLATED (ASTM B633, CLEAR CHROMATE)

More information

Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS

Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS Section 1.3: PRESSURE VESSEL COMPONENTS AND SYSTEMS AND COMPRESSED GAS CYLINDERS TABLE OF CONTENTS Page A. Regulations, Standards and References 1.3-2 B. Scope 1.3-2 C. Design Features for the Storage

More information

Eaton Filtration, LLC

Eaton Filtration, LLC Eaton Filtration, LLC 900 Fairmount Avenue, Elizabeth, NJ 07207 Phone: 908-787-1000 Fax: 908-351-7893 E-Mail: filtration@eaton.com Web: www.filtration.eaton.com Installation, Operation & Service Manual

More information

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG A C E D SB-8520.2 1800CPB2 Service Regulators Maximum Inlet 125 PSIG AMC Quality System QMI is Accredited by: C R E D I T ISO 9001 Certified Certificate #006697 R E ANSI RAB G I S T R A R Dutch Council

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Dean Pump Self-Priming Chemical Process Pumps

Dean Pump Self-Priming Chemical Process Pumps Bulletin C 1.2.34.7 Dean Pump Self-Priming Chemical Process Pumps php Series HEAD CAPACITY RANGE CHARTS php Self Primer - 2 Pole 3500 RPM 500 CAPACITY M 3 /HR 2900 RPM 50 HERTZ 25 50 75 125 150 400 TOTAL

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

Foam Chamber Model-FC

Foam Chamber Model-FC Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com 2nd FLOOR 145-157 ST.JOHNS STREET LONDON EC1V 4PY UNITED KINGDOM Foam Chamber Model-FC TECHNICAL DATA : MODEL SIZE inlet WORKING

More information

Air Operated Hydraulic Pumping Systems to 50,000 psi

Air Operated Hydraulic Pumping Systems to 50,000 psi High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air

More information

AFL Industries, 1101 West 13 th St, Riviera Beach, FL 33404 PHONE: (561) 848-1826 FAX: (561) 848-9454 E-Mail: Sales@aflindustries.com AFL-STD MODEL OSV-4 SS INSTALLATION, OPERATION & MAINTENANCE BROCHURE

More information

MSC Guidelines for Refrigeration Machinery

MSC Guidelines for Refrigeration Machinery Procedure Number E1-32 Revision Date: 07/27/10 S. J. Kelly, CDR, Chief of Engineering Division References: a. 46 CFR Part 56.50-105 Low Temperature Piping b. 46 CFR Part 58.20 Refrigeration Machinery c.

More information

Pipe-Away Pressure Vacuum Vent /Conservation Vent

Pipe-Away Pressure Vacuum Vent /Conservation Vent R R Pressure Vacuum Vent / End of Line Conservation Vent Flame Arrester with Pressure Vacuum Vent Pipe Away Pressure Vacuum Vent / Conservation Vent Vacuum Relief Vent Pressure Emergency Vent Free Vents

More information

IAPMO IS PUBLIC REVIEW DRAFT Thrust Blocking for Rubber Gasketed and Solvent Cement Joints

IAPMO IS PUBLIC REVIEW DRAFT Thrust Blocking for Rubber Gasketed and Solvent Cement Joints IAPMO IS 33-2019 PUBLIC REVIEW DRAFT Thrust Blocking for Rubber Gasketed and Solvent Cement Joints IAPMO Standard IAPMO IS 33 2019 Published: Month Year Published by International Association of Plumbing

More information

Code Compliance Research Report CCRR-0145

Code Compliance Research Report CCRR-0145 Code Compliance Research Report CCRR-0145 Issue Date: 11-16-2009 Revision Date: 11-29-2018 Renewal Date: 11-18-2019 DIVISION: 05 - Metals Section: 05 50 00 Metal Fabrications Marshall Stamping Company

More information

Limited quantities of compressed gases.

Limited quantities of compressed gases. 173.306 Limited quantities of compressed gases. (a) Limited quantities of compressed gases for which exceptions are permitted as noted by reference to this section in 172.101 of this subchapter are excepted

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

MSC Guidelines for Compressed Air Systems

MSC Guidelines for Compressed Air Systems Procedure Number: E1-04 Revision Date: 12/16/2013 References: a. 46 CFR 54 Pressure Vessels (Subchapter F) P. W. Gooding, CDR, Chief, Engineering Division b. 46 CFR 56 Piping Systems & Appurtenances (Subchapter

More information

AIR FOAM CHAMBER DATA SHEET

AIR FOAM CHAMBER DATA SHEET FIRE FIGHTING EQUIPMENT DATA SHEET AIR FOAM CHAMBER DATA SHEET JOB NO. : RFQ. NO. : ISSUE : SHEET OF 01 CUSTOMER : ITEM NO. : 02 PROJECT : QUANTITY : 03 LOCATION : SERVICE : FOAM SYSTEM 04 05 CODE & STANDARDS

More information

Item 404 Driving Piling

Item 404 Driving Piling Item Driving Piling 1. DESCRIPTION Drive piling. 2. EQUIPMENT 2.1. Driving Equipment. Use power hammers for driving piling with specified bearing resistance. Use power hammers that comply with Table 1.

More information