Model HS40V/HS40V-DO

Size: px
Start display at page:

Download "Model HS40V/HS40V-DO"

Transcription

1 Model HS40V/HS40V-DO Advanced Bubbler System Installation and Operation Manual HYDROLOGICAL SERVICES Pty Ltd Scrivener Street Liverpool NSW 2170 Australia Ph Fax Internet: sales@hydrologicalservices.com Copyright 1 of 46 2/10/2014

2 TABLE OF CONTENTS 1. Introduction Product Overview Installation Extending the Battery Cables Adjusting the Bubble Rate WL3100 Connection Operation Description of Controls Startup Sequence Tank Pressurisation & Mist Separator Flushing Battery Size Battery Indication Maintenance Fault Finding Specifications Appendix A WL3100 Operation Manual Appendix B Installing Polyethelene Tubing and Orifice Fittings Appendix C Using Pressure to Measure Water Level Appendix D HS40V-DO (Dual Orifice) Appendix E Gas Chamber Orifice Assembly Appendix F Typical Installations Appendix G Automatic Moisture Extraction Control System G.1 Filter Maintenance for the HS40V Copyright 2 of 46 2/10/2014

3 1. Introduction The HS40V Gas Purge Compressor + Bubbler System has been designed to replace conventional nitrogen gas bottle supply to bubble units / gas purge systems, used for measuring water level in dams, rivers, canals and tanks with up to 30 mh 2 O (100 ft) head. The basic system consists of an air compressor, a 2 litre receiving tank, a single mist separator with an auto purge valve, and a bubbler system all built into a single small enclosure. The system continually monitors the tank pressure and when it falls below 400kPa (58 psi), the compressor will start and pump the tank pressure back up to 750kPa (110psi). The HS40V, with the optional inbuilt WL3100 pressure transducer, allows the measurement of water level to an accuracy of ±0.02% F.S. (The WL3100A is a more advanced model that allows the fine tuning of the user factor relationship between pressure and water level, and is temperature compensated from 40 o C to 80 o C) The inbuilt WL3100 / WL3100A have an SDI-12 interface and a 4-20mA interface that can be used at the same time to provide data to 2 separate systems if required. Advantages over other systems: Compact single unit. Low maintenance (no gas bottle or desiccant to be replaced) the air dryer has an auto purge feature that purges moisture build up to atmosphere at the end of each pumping cycle. A yearly check of the internal filter element is recommended. Hydrological Services would recommend replacing this filter every 2 years or when necessary depending on site conditions. (Replacement elements can be purchased from Hydrological Services when needed.) Can interface to SDI-12 and 4-20mA outputs simultaneously. Easy to install. There are 6 separate models available: HS40V - Includes compressor tank air dryer bubbler. HS40VA - ( 40 o C operation) Includes compressor tank air dryer bubbler system. HS40V/ Includes compressor tank air dryer bubbler system inbuilt WL3100. HS40V/3100A ( 40 o C operation) Includes compressor tank air dryer bubbler system inbuilt WL3100A. HS40V-DI/3100 As HS40V/ additional external instrument line. HS40V-DO/3100 As HS40V/ dual orifice connection valves. Copyright 3 of 46 2/10/2014

4 2. Product Overview The Air Force Model HS40V is designed to replace conventional Dry Nitrogen bubbler systems. A dot point view of the product is as follows: Low maintenance gas purge system for water level measurement. In-built Air Compressor. In built two stage dryer system 2 litre Receiver Tank. HS40V model (no internal pressure transducer fitted). Operates with up to 30m (100ft) head of water. (40m available on request) Low average power consumption. True continuous bubbler system can be used with or without Hydrological Services Gas Chamber Orifice GCO1P. User adjustable bubble rate. Internal view of the Air Force Model HS40V. The built-in WL3100 Pressure Transducer fits in the top right of the cabinet on HS40V/3100 models Copyright 4 of 46 2/10/2014

5 3. Installation The HS40V MUST be mounted in a vertical position. The air dryer and auto purge moisture feature will not function properly if the unit is in a horizontal position. Before connecting 12V power to the HS40V, fit the 3/8 inch river-line as shown. Connect the 12V DC battery to the power cable shown, and add a mains or solar charger if required. The status LED, at the bottom right of the cabinet, will cycle through its initial sequence, and then if the tank pressure is less than 400kPa (58psi), the compressor will start and pump the tank pressure up to 750kPa (110psi). This initial pump up cycle may take several minutes. Push trigger down to pull tube out if required Tank Pressure River Line Select Valve Valve allows transducer calibration to be checked Status indicator LED Manual Start Air Dryer With Valve 3/8 River Line Built-in WL3100 Test Port WL3100 Connections 12V Battery Cable Bubble rate adjust with lock screw 3/8 River Line WL3100 Power + SDI-12 / 4-20mA Interface Note: The HS40V bowl is connected to an automated purge valve that purges moisture from the drying system at the end of each pumping cycle. - 12V 38Ah Battery + Copyright 5 of 46 2/10/2014

6 3.1 Extending the Battery Cables The HS40V is supplied with a 2m power cable, with each core being 2.5mm 2. If the user needs to extend this cable, extreme caution should be exercised, because whenever high currents are drawn through cables, there will be voltage drops!!! With the supplied cable (2m of 2.5mm 2 ) there is a 0.2V drop on each conductor when the compressor draws 15A. Since there is a positive and negative wire, the voltage seen by the HS40V is 2 x 0.2V = 0.4V less than the voltage seen at the battery terminals and at 15A the battery voltage will also droop. (This is before the cables are extended.) HS40V V HS40 = V batt V drop1 V drop2 Extended Power Cable (V drop1 ) Supplied Power Cable (V drop2 ) V HS40 V batt 12V Battery Use the following table to get an idea of the total cable voltage drop, keeping in mind that small batteries droop more under heavy load and the HS40V will disconnect the compressor when the voltage it sees drops below 10V. (This was 11V in units prior to S/N ). Extended Cable Length Cable Size (mm 2 / AWG) V drop1 on extended cable V drop2 on supplied cable Total V drop Battery Voltage V batt when HS40V disconnects compressor 2m (6ft) 2.5 / V 0.4V 0.8V 10.8V 4m (12ft) 2.5 / V 0.4V 1.2V 11.2V * 6m (18ft) 2.5 / V 0.4V 1.6V 11.6V * 6m (18ft) 10 / 7 0.3V 0.4V 0.7V 10.7V 10m (30ft) 10 / 7 0.5V 0.4V 0.9V 10.9V 15m (45ft) 10 / 7 0.8V 0.4V 1.2V 11.2V * 15m (45ft) 16 / 5 0.5V 0.4V 0.9V 10.9V 20m (60ft) 16 / 5 0.7V 0.4V 1.1V 11.1V * => Not Recommended NOTE : Increasing the battery capacity (to say 38Ah or higher) also helps, because the battery voltage will drop less under heavy load. Copyright 6 of 46 2/10/2014

7 3.2 Adjusting the Bubble Rate Set the River Line control valve to the Close position. (Keep the Calibrate valve in the Open position) Attach the HS23QC (supplied as standard) to the HS40V Test Port and immerse the HS23QC in a beaker of water. Allow up to 10 minutes for the bubble rate and differential regulator to stabilise. Undo the bubble rate lock screw and adjust the bubble rate (to say 21 bubbles/min) The bubble rate at the Test Port will be the same as would be at the River Line orifice. Nip up the lock screw and test the bubble rate again it may change slightly as the lock screw is done up. CAUTION: ADJUSTMENT OF THE BUBBLE RATE HIGHER THAN THE MAXIMUM 45 BPM MAY VOID THE MANUFACTURER WARRANTY ON THIS PRODUCT. Disconnect the HS23QC from the HS40V Test Port. Rotate the River Line control valve from the Close position to the Open position to direct the bubbles from the Test Port back to the River Line. *** Warning : Close the river line when using the test port Test Port Actual Bubble Rate setting at Test Orifice or River Line (bubbles/min) Suitability HS23QC Bubble rates will be the same. Refer to table RiverLine 10 BPM (Recommended for GCO1P) 16BPM 21BPM 26BPM Factory Set Rate (Recommended for BU07) Maximum do not exceed 45BPM BPM (BUBBLES PER MINUTE) EXCEEDING THE MAXIMUM BUBBLE RATE WILL CAUSE EXCESIVE WEAR TO COMPRESSOR PUMP Suitable for Slow rising streams For medium rising streams Suitable for Fast rising streams 3.3 WL3100 Connection The wiring connections to the WL3100 are via a plug-in terminal block underneath the HS40V enclosure. You must have +12V and 0V power for the WL3100 to operate. You may connect the SDI-12 and the 4-20mA interfaces at the same time. (These terminals are screwless and keep a constant V DC Power Da SDI-12 Data 0V 0V DC Power +S +ve 4-20mA Signal -S - ve 4-20mA Signal tension on the wire, thus producing a more reliable connection simply use a screwdriver to push on the orange lever to release the terminal spring tension, to insert or remove the wire.) (Consult the WL3100 Manual in Appendix A for a detailed description of the WL3100 connection and operation.) If connecting to the 4-20mA interface, make sure that the data logger (or RTU) powers up the 4-20mA loop long enough for the WL3100 to recognize it, take a measurement and put the result back on to the 4-20mA loop. (5 secs when Continuous Mode is set to YES and 15 secs when Continuous Mode is set to NO ) Copyright 7 of 46 2/10/2014

8 4 Operation 4.1 Description of Controls Manual Start button : The operator may manually start a tank pump up cycle by pressing the blue button underneath the enclosure. This button also provides a manual stop of a pump up cycle. Note : The compressor has a manufacturer s maximum duty cycle of 10%. If the compressor is on for 1 minute, make sure it rests for 10 minutes. DO NOT purge or perform manual pump up cycles un-necessarily. Status LED indicator : Flash => Everything is operating normally. Flash => Battery voltage is low. (If the battery voltage falls below 10V, the LED will flash red, and will only return to a green flash when the voltage rises above 12.5V). Slow Flash (1 flash/2 sec) => There is a problem with the compressor / tank pressure. Possible causes are: - Max tank pressure could not be reached within 3 minutes this could be due to a leak in the tank / tubing, or the compressor has lost its capacity to pump. - Tank pressure was not increasing while the compressor was on a possible leak in one of the connections. Even when the LED is slow flashing blue, the system will attempt to pump up the tank every 12 hours. Fast Flash (5 flashes/sec) => The compressor on/off duty cycle of 10% has been exceeded. The system will wait for 30 minutes and then automatically complete the pump up cycle. *** See the Fault Finding guide in Ch 6 to get more detailed assistance. Copyright 8 of 46 2/10/2014

9 River Line Control Valve : This Control Valve has 3 positions: Open - In the Open position, the bubbler (regulator) is open to the River Line port and the transducer. Close - In the Close position, the bubbler (regulator) is closed to the River Line. (If there is nothing plugged into the Test Port Quick Connect, the transducer pressure will continue to increase very slowly as the regulator reacts to a closed system DO NOT leave it in this position for extended periods as the internal pressure build up may exceed the burst pressure of the transducer element!!!!) Purge - In the Purge position, the receiver tank is directly connected to the River Line port to allow a Purge of the River Line. After a River Line Purge is performed, rotate the control valve back to the Close position and wait until the River Line pressure drops to a normal level (say 5 seconds) before rotating the control valve back to the Open position. (Otherwise the Purge pressure may be introduced to the transducer and cause damage!!!) **** IMPORTANT **** When purging, STOP when the tank pressure falls below 400kPa, otherwise the riverline pressure may fall below the water head pressure resulting in water entering the River Line!!! Calibrate Valve: The Calibrate Valve is used to allow the Bubble Rate Test Port to be used to check the transducer (WL3100) calibration. The procedure is as follows: Set the River Line Select valve to the Close position. Set the Calibrate Valve to the Calibrate position. Set the pump up calibrator to vent so that the existing water head pressure is vented during the next step. Connect the pump up calibrator to the Bubble Rate Test Port. The pressure from the pump up calibrator can now be applied directly to the transducer (WL3100) input. Set a required pressure (or water level) on the pump up calibrator, then read the water level from the transducer (WL3100). After the transducer calibration has been verified, the system can be returned to normal operation by : Remove the pump up calibrator from the Bubble Rate Test Port Set the Calibrate Valve back to the Open position. Set the River Line Select valve back to the Open Position. Copyright 9 of 46 2/10/2014

10 4.2 Startup Sequence After power-up the status LED flashes all 3 colours, Green then Red then Blue then all 3 colours together to confirm the LED is working OK. The HS40V then enters a tank pressurization check. 4.3 Tank Pressurisation & Mist Separator Flushing When the tank pressure falls below 400kPa (58psi), the compressor will start and pump the pressure back up to 750kPa (110psi). (While the compressor is on, the LED will be steady blue. At the end of the pump up cycle, the LED will flash green if completed successfully, or flash red if there is a problem.) Tank pressure kpa (psi) 750 (110) 400 (58) At the end of the pumping cycle the purge valve is activated Compressor on At the end of each pumping cycle, the purge valve will open and the air from the pump will force any available condensation out of the mist separator to atmosphere. Time 4.4 Battery Size The HS40V consumes a quiescent of about 7mA and draws about 15A for 1 min every 18 hours when the rate at the test orifice is set to 26 bubbles/min This averages to 15A x 1min / (18hr x 60min/hr) = 13.9mA. The total average current is therefore: HS40V quiescent 7.0mA HS40V Compressor average 13.9mA WL3100 average 3.3mA ===== Total consumption 24.2mA A 38Ah battery will run for 38Ah / 24.2mA = 1570 hrs = 65 days = 2 months (without any solar or additional charging) The battery endurance will be dependant on the following: The consumption of other equipment connected to the battery. The frequency that the system wakes up to take a measurement. The length of time the system is awake for each measurement. The selected bubble rate the higher the bubble rate, the more often the compressor will be required to replenish the tank. The battery Ah capacity the minimum recommended battery capacity is 18Ah. (Use the above method to estimate the battery endurance.) Copyright 10 of 46 2/10/2014

11 4.5 Battery Indication The battery voltage is monitored during all phases of operation. If the battery voltage falls below 10.0V then the status LED will show the battery low indication and all compressor operation will stop immediately. The battery voltage must then rise above 12.5V before clearing the battery low condition. (The 10V limit was 11V in units prior to S/N ) Batt V Mains or Solar Charging 12.5V 10.0V Battery OK Green LED Battery Low Red LED Battery OK Green LED A green LED flash indicates the battery is OK, a red LED flash indicates the battery low indication has been tripped. Once the battery voltage rises above 12.5V the battery low condition will be cleared and the status LED will return to a green flash. A pump up cycle will be aborted if a battery low condition occurs. This condition is most likely to occur when the compressor is on because it draws approximately 15A when operating causing the battery voltage to drop. A compressor soft start feature was added to units with S/N and higher, which allows the compressor to slowly ramp up to speed, limiting the initial peak current draw which always occurs when motors start up. This also helps prevent a battery low condition being registered as the compressor starts. Copyright 11 of 46 2/10/2014

12 5. Maintenance The HS40V will require little maintenance however a yearly check of the moisture trap filter element is recommended to ensure that moisture is being removed from the system effectively. You will also need to ensure that your battery / power supply is sufficient for the equipment that you have installed and that both your battery and charging system are working correctly. (See Specification page). All fittings must be secure. maintained. Even a minor leak will prevent the pressure from being 6. Fault Finding This fault finding guide should be used by the HS40V user before they consult Hydrological Services to assist with specific problems. HS40V Not Powering Up Check battery voltage should be above 12V DC. Check battery POWER and GROUND connections to the battery make sure they are done up tightly and there is no corrosion. The compressor won t start when I press the manual start (blue button) OR The compressor doesn t start when the pressure falls below 400kPa (58psi). If the LED is not flashing, check the battery voltage is above 12V, and check the battery connections for signs of corrosion clean, retighten and retry. If the LED is flashing red, check the steps listed below under LED is flashing red. If the LED is flashing blue very fast, check the steps listed below under LED is flashing blue fast. If the LED is flashing green, then it could be a fault with the controller. Remove the controller from the battery, and then connect it again, to see if a reboot fixes the problem. Maybe the 400kPa pressure limit has been lost, contact the factory. The compressor starts but then cuts out before 750kPa (110psi) is reached. If you press the blue button during a pump up cycle, it will be aborted. Check the LED flash sequence after the compressor stops if it is flashing red or blue then follow the steps listed below. If the LED is flashing green then it may be a fault with the controller. Remove the controller from the battery, and then connect it again, to see if a reboot fixes the problem. Maybe the 400kPa pressure limit has been lost, contact the factory. LED is flashing red. If the LED is flashing red, then it has detected a low battery voltage. This could be due to the battery voltage drooping below 10V as the compressor starts and draws the required 15A. (If you are measuring the battery voltage at the battery itself, it may be lower at the HS40V due to cable and connection voltage drops.) Check the following : The battery has been sufficiently charged. Check the battery connections are done up securely. Copyright 12 of 46 2/10/2014

13 The battery capacity is sufficient (an absolute minimum of 12V 18Ah is required). If using a power supply instead of a battery, it may be going into current limit with the compressor start current. The HS40V power wiring is connected directly to the battery. (If the HS40V has been connected to the Solar Regulator load terminals, there may be a large voltage drop through the regulator as the HS40V compressor starts and draws 15A.) If the HS40V power wiring has been extended, make sure the cable sizes specified in the manual have been followed, otherwise cable voltage drops will occur when the compressor starts and draws 15A. LED is flashing blue slowly (1 flash every 2 seconds) The compressor has tried to pump up the tank, but the pressure is not increasing, or the overall pump up time of 3 mins has been exceeded, so the compressor is stopped assuming there is a leak somewhere : Make sure the control valve is not in the Purge position. Check the sealing of the air drying moisture cylinders at the bottom of the cabinet listen for air leaks maybe they are not seated properly or maybe the older style plastic bowl is cracked. If everything else looks OK then check the internal tube connections for leaks by spraying a bubble solution on all internal fittings. Tighten or repair the leaking fitting. (This will require the control knobs and the bubble rate knob to be removed using an allen key - the front panel can be opened by removing the 4 front panel corner screws and hinging to the right.) If there are no leaks, there may be a problem with the compressor itself. If the LED is flashing blue fast (5 flashes every second) The compressor duty cycle has been exceeded! You have possibly done several purges consecutively wait 30 mins until the LED flashes green and retry. (If the pressure is below 400kPa, it will automatically pump up when the LED flashes green) The compressor doesn t stop at 750kPa (110psi) There is a fault with the controller or the internal pressure sensor. Remove the controller from the battery, and then connect it again, to see if a reboot fixes the problem. Maybe the 750kPa pressure limit has been lost, contact the factory. The LED is flashing green / blue Units with serial number and higher, have a solenoid valve connected to the air filter. If this valve latches during a pump up cycle, due to the temperature being below -20C for an extended period, the cycle will pause, and leave power on the solenoid valve to warm it up and unlatch it. During this time the LED will flash green / blue for 5 minutes. The pump up cycle will then be re-attempted. Copyright 13 of 46 2/10/2014

14 7. Specifications Power : Operating Voltage : Recommended Battery : 12V DC Nominal 12V DC Sealed Lead Acid (38Ah) (10 bubbles/min, will provide approx 100 days continuous operation, without any solar charging, using GCO1-P orifice) Minimum Battery Size : 12V DC Sealed Lead Acid (18Ah) Low Battery cut-out : 10.0 V DC (This was 11V in units prior to S/N ) Battery recharge recovery : 12.5V DC Operation Range : Up to 30m (100ft) of water pressure head [40m (130 ft) available on request] Electronics Quiescent : 7 ma Compressor Current : 15 Amps(for 1 min every 18 hrs, 26 10mH 2 0) (Compressor soft start in units with S/N and higher) Average battery consumption : 24.2 ma(with bubble rate set to 26 10mH 2 0) Solar : Maximum Tank/Purge Pressure : Minimum Pump/Purge Pressure : Differential Pressure : Bubble Rate : Transducer Pressure Connection : River Line Connection : Max River-line Length : Air Dryer : Operating Temperature Range : Enclosure : A small 10Watt solar panel is sufficient to keep the battery fully charged 750 kpa (110 psi) 400 kpa (58 psi) 20kPa (3psi) to 35kPa (5psi) Adjustable from 0 to 45 bubbles / min 1/4 inch tube 3/8 inch tube, Dual orifice (2) x 3/8 inch tube 200m (600ft) using 3/8 in OD and 1/8 ID tubing Single mist separator with auto purge valve -40 o C to +70 o C HS40V and HS40V/3100A -20 o C to +70 o C HS40V/3100 Zinc plated steel enclosure, powder coated grey Enclosure Size : 400mm x 300mm x 180mm (H x W x D) 16 inch x 12inch x 7 inch Weight (with built-in WL3100) : 12 kg (26.5 lbs) Copyright 14 of 46 2/10/2014

15 Appendix A WL3100 Operation Manual Operation The WL3100 Multi Output Dry Transducer powers up and takes a measurement at the following times : When the Level is displayed on the LCD, a reading is taken every 12 seconds and the Level on the LCD is updated. When the 4-20mA current loop has power applied, a reading is taken every 12 seconds. The 4-20mA current loop is updated at the same time. When the SDI-12/RS232 interface requests a measurement using the M or C commands. When the LCD menu Continuous Meas is set to YES, measurements are continuously taken. External Power The WL3100 requires an external power source of +12VDC (9.6V to 16VDC) connected via the SDI-12 port. The 4-20mA current loop circuitry is optically isolated from the measuring and SDI-12 electronics, therefore separate loop power must be provided by the telemetry or data logging equipment. LCD Screen There are 7 main LCD screens available. Some screens display internal data and some allow parameters to be changed. The screens are : LCD Screen WL3100 S/W 7.2 Level : 5.127m Sensor Addr : 2 Sensor ID : Comms Type : SDI-12 4mA / 20mA Level : 0.0m / 10.0m Set Level : 5.127m Calc Offset : 0.003m Sampling Mode : Single Description Display model, S/W Rev and Water Level Display sensor SDI-12 address and 5 digit ID Display type of communications SDI-12 or RS232 Indicates the 4mA Level and the 20mA Level Allows the present River Level to be preset internally calculates an offset Displays the internally calculated offset Contin+Avg 5 => the river level is continuously measured and the last 5 values are averaged. Single=> the river level is only measured when requested. Copyright 15 of 46 2/10/2014

16 There are many other menu screens that allow the fine tuning of calibration if this is required. The following menu tree should be examined carefully before embarking through it. (The scroll button steps down to the next screen or changes the value if it is flashing, and the select button allows you to enter the edit mode. (5 secs) means hold the select button for 5 secs to enter this menu.) Copyright 16 of 46 2/10/2014

17 Configuring the WL If using the SDI-12 interface, set the required address by stepping to the Sensor Addr menu, and pressing the Select button and then use the Scroll button to set the address from 0 to If using an SDI-12 logger, make sure the Comms Type is set to SDI-12. If using an RTU with an SDI-12 to RS232 adapter then set the Comms Type to RS Use the staff gauge in the river to measure the water level (1.450m) 4. Step to the Set Level menu and set it to 1.450m *** If operating in SDI-12 mode, setup is complete. *** If operating in 4-20mA mode then continue with step Estimate the range over which the water level will change. (eg. Min level = 1.000m : Max Level = 8.000m) 6. Step to the 4mA / 20mA Level menu Set the 4mA level to 1.000m Set the 20mA level to 8.000m When the water level is at 1.000m the 4-20mA current will be 4.000mA When the water level is at 4.500m the 4-20mA current will be mA When the water level is at 7.000m the 4-20mA current will be mA 7. The range in this example is = 7.000m Set the logger range to 7.000m (eg. ML420 range is set with TxR=7.000) 8. The offset in this example is 1.000m Set the logger offset to 1.000m (eg. ML420 offset is set with RvHR=1.000) 9. Set the logging interval and transducer warmup period in the data logger. There are 2 ways to set the transducer warmup period if Continuous Meas? is set to Yes, then the warmup can be set as low as 1 sec. (Slightly more power is drawn in this mode as the WL3100 continually takes measurements.) If however, Continuous Meas? is set to No, then the warmup must be set for about 15 secs. (eg. Say ML420 interval is 15mins and warmup is 1 sec then TXI=015/01 ) NOTE : Setting the 4-20mA range to the smallest possible will give the best resolution on a 4-20mA interface! Copyright 17 of 46 2/10/2014

18 Sampling Mode Single, Continuous, Averaging In S/W Rev 7.1 and lower, the last menu item shown on page 12 is Continuous Mode?. This could either be set to YES or NO. When Continuous Mode is set to NO the WL3100 only takes a sample when : 1. The water level is displayed on the LCD or 2. An SDI-12 Measure command is received or 3. The 4-20mA loop power is detected. When Continuous Mode is set to YES the WL3100 takes a sample : 1. Every 12 secs. (Continuously) (This is useful if you use the SDI-12 command 0R0! as it will immediately return the most recent measurement made within the last 12 secs which makes the WL3100 SDI-12 interface the same as the AD375A SDI-12 interface. It can also be useful when using the 4-20mA interface, as the 4-20mA loop current will be accurately updated 100mS after loop power is applied without having to wait 12 secs for a measurement to be made!!) In S/W Rev 7.2 and higher, the last menu item shown on page 12 is Sampling Mode. This could either be set to Single, Contin+Avg 1, Contin+Avg 2,..., Contin+Avg 20. When Sampling Mode is set to Single the WL3100 only takes a sample when : 1. The water level is displayed on the LCD or 2. An SDI-12 Measure command is received or 3. The 4-20mA loop power is detected. When Sampling Mode is set to Contin+Avg X the WL3100 takes a sample : 1. Every 12 secs. (Continuously) (When a sample is requested, via the display or via SDI-12 or 4-20mA, the last X samples are averaged. If it is known that the water level will change very slowly, it is advantageous to set X to a high number, so that the last say 20 samples will be averaged. Note that 20 samples will take 20 x 12secs = 240 secs = 4 mins. (So the water level is averaged over a 4 minute period) If it is known that the water level changes rapidly, then it would be better to set X to a low number, so that say 2 samples will be averaged.) The Contin+Avg 1 mode only averages 1 sample, which at first appearance doesn t seem to be very useful this was included to give the same operation as the above described Continuous Mode set to YES. (Read the description above to see why this mode is useful.) Copyright 18 of 46 2/10/2014

19 Averaging The following diagram shows what happens when the WL3100 is set to average 5 samples. (When in average mode, the WL3100 takes a sample every 12 secs (Each circle represents a sample that is a highly filtered, 24 bit high accuracy, temperature compensated value!) 12 Sampl e Sampl e Sampl e Sampl e Reply is the average of the previous 5 samples Reply is the average of the previous 5 samples Reply is the average of the previous 5 samples When a sample is requested (via the LCD, SDI-12 M command or 4-20mA), the next periodic sample will reply with an average of the previous 5 samples (obviously the number of samples used to calculate the average will depend upon the setting selected - between 1 and 20). (If the SDI-12 0R0! command is used, then the samples immediately prior to the command being received are used to perform the average!) Copyright 19 of 46 2/10/2014

20 RS 232/SDI-12 Selection The SDI-12 protocol has very strict timing requirements. The operator may use the SDI-12 to RS232 adaptor cable and then communicate using RS232 from a PC. The RS232" option must be selected via the LCD and pushbuttons. In this mode all of the timing/break requirements of the SDI-12 are removed. Commands may be typed from a terminal program such as Hyperterm. *** Note *** You must use 1200 baud, 7 bits, even parity and no handshaking. If using an SDI-12 logger you must select the SDI-12 option via the LCD and pushbuttons. SDI-12 V1.3 Compliant Command Set (CRC commands are implemented) (Please note the letter a in the commands below refer to the SDI-12 address 0, 1, 2,.9) Name Command Response Break Continuous None spacing for at least 12 milliseconds Acknowledge Active a! a<cr><lf> Send Identification ai! allccccccccmmmmmmvvvxxx...xx<cr><lf> (Refer Note 1.) Change Address aab! b<cr><lf> Address Query?! a<cr><lf> Start Measurement am! or amc! atttn<cr><lf> (Refer Note 2) Send Data ad0! a<value><cr><lf> or a<value><crc><cr><lf> Continuous Measurement ar0! or a<value><cr><lf> (Refer Note 3) arc0! a<value><crc><cr><lf> Start Verification av! atttn<cr><lf> Start Concurrent Measurement ac! or acc! atttnn<cr><lf> (Refer Note 2) Note 1. a13hydrservwl <cr><lf> digit Sensor ID (eg 12345)(as set in ax4 command) S/W Revision (eg 5.1) Model (WL3100) Company ID (HydrServ) SDI-12 Version V1.3 Compliant Unit Address Note 2. The measurement command M and the concurrent command C will both return a time ttt of 012 indicating that the measurement will be ready in 12 seconds. Do not request data within this 12 second window, or an empty reply will be received. (In accordance with the SDI-12 protocol.) When an M command is in progress, the dry transducer will issue a service request a<cr><lf> when the measurement is complete and ready for a data request. (Again, in accordance with the SDI-12 protocol) Note 3. The Continuous Measurement command returns the present River Level. If the LCD command Continuous Meas? is set to Yes then the river level is continuously measured when 12V is present and so the ar0! returns the river level without having to issue an am! Measure command. Copyright 20 of 46 2/10/2014

21 *** PLEASE NOTE *** For more information on SDI-12 commands, go to the website and download the SDI-12 Protocol Specification available on the home page. Special Commands The following commands conform to the SDI-12 protocol, and allow specific parameters within the WL3100 to be configured. Care should be taken with some commands, as they may destroy the factory calibration. axn! axn+xxxx! Return data associated with command n. The multi output dry transducer will reply with a0001<cr><lf> The ado! command must be issued to get the actual data. Set parameter for command n. The multi output dry transducer will reply with a0001<cr><lf> The ado! command must be issued to get the actual data. Set/Get Current Value ax0! Get the river level (River level from last measurement). ax ! Set the river level to m (or ft). Get Multi Output Dry Transducer Pressure ax1! Get the Pressure. eg psi (or kpa) Get/Set the 4mA Level ax2! ax ! Get the 4mA Level. Sets the 4mA Level to 2.5m (or ft) When the water level is 2.5m then the 4-20mA loop will pass 4mA Get/Set the 20mA Level ax3! ax ! Get the 20mA Level. Sets the 20mA Level to 20.0m (or ft) When the water level is 20.0m then the 4-20mA loop will pass 20mA Set/Get ID Number ax4! ax ! Get the dry transducer ID. Set the dry trasnducer ID. Acceptable values This value appears in the Identify command. Set/Get the User Factor ax7! Get the User Factor. ax ! Set the User Factor to m/psi Copyright 21 of 46 2/10/2014

22 WL3100 Field Setup Procedure 1. Press either of the two push buttons on the dry transducer to activate the LCD display. 2. Use the scroll button to scroll through the menu to Set Level and press the select button. 3. Use the select button to move the blinking cursor to the desired digit position (that needs to be changed), and use the scroll button to increment the value. When the rightmost digit is at the desired value press the select button to save the value. Press select button again to start with the left most digit again. 4. After the select button is used to save a value ie. Water level, then pressing the scroll button will continue to step you through the menu as before. 5. The 4-20mA current loop will be continuously updated as the various parameters are changed. 6. The 4mA water level and the 20mA water level can be set separately. (See the menu tree structure in the LCD Operation section) 7. The various parameters may also be set by the SDI-12 special command set, via the SDI-12 Input connection, or the RS-232 connection if a laptop is available using a simple terminal emulation program whereby ASCII characters are typed (adhering to the SDI-12 Ver 1.3 protocol). Note: If the commands are being typed by the operator, the Comms Type must be set to RS232. In this mode the strict SDI-12 timing is ignored. An adapter cable needs to be used in this mode. See the SDI-12 to RS232 Interface drawing at the end of this Appendix for details. Copyright 22 of 46 2/10/2014

23 WL3100 Wiring Details Screwless Terminals The WL3100 electrical connections are made on a plug in terminal block underneath the HS40V. The plug in terminal block shown is a screwless terminal that keeps a constant tension on the wire that is inserted. Multimeter probe can be inserted here!!! 1. Use a small flat blade screwdriver and push-in on the orange groove. 2. Insert the stripped wire here. External Power 3. Release the orange part to put secure the wire. 4. Pull on the wire to make sure it is secure. The WL3100 will only be able to make a water level measurement if +12VDC (9.6V to 16VDC) power is connected. An adequate 12VDC (9 to 30VDC) battery and charger option should be used if the optically isolated 4-20 ma current loop is to be powered continuously and independently of the telemetry module or data logging equipment. The easiest way to see if +12V is present is to press one of the WL3100 buttons and check that the backlighting comes on. SDI-12 Data 0V To data logger +12V 0V Copyright 23 of 46 2/10/2014

24 4-20mA Interface The 4-20mA interface in the WL3100 is optically isolated from the 0V and +12VDC on the right hand end of the connector. The 4-20mA circuitry must be powered by the loop. There are 2 ways to take 4-20mA measurements : 1. Continuous Meas set to Off (S/W Rev 7.1 and lower) Sampling Mode set to Single (S/W Rev 7.2 and higher) When the WL3100 detects loop power, it initiates a water level measurement this takes 12 seconds the 4-20mA current is updated at the end of the measurement and the data logger can measure the current. Therefore the data logger must be set for transducer warm-up of about 15 secs. 2. Continuous Meas set to On (S/W Rev 7.1 and lower) Sampling Mode set to Contin+Avg X (S/W Rev 7.2 and higher) The WL3100 is set to take a measurement continuously (every 12 secs). When the WL3100 detects loop power, it updates the 4-20mA current within 100mS - with the water level previously measured within the last 12 secs. Therefore the data logger can be set for a transducer warm-up of about 1 sec. The following diagram shows how the 4-20mA interface must be loop powered. (This example uses the Hydrological Services ML420 Data Logger.) Batt +12V mA V Battery Batt 0V ML420 Data Logger mA WL3100 Connections Sense ML420 Data Logger measuring the 4-20mA To conserve power, the data logger switches power to the 4-20mA circuit only when it wants to make a measurement. PLEASE NOTE : The SDI-12 interface and the 4-20mA interface can be used at the same time by 2 different devices. For example, a data logger can be connected to the SDI-12 interface while an RTU is connected to the 4-20mA interface!!! Copyright 24 of 46 2/10/2014

25 Fine Tuning The WL3100 Software Rev 6.5 has many enhancements to improve the performance. These include : Measures pressure in psi or kpa - factory calibrated. Displays water level in m or ft. User scaling factor to take into account local conditions such as gravity, water density, etc. Ability to calculate gravity, water density, air density and user factor. Factory calibration of the 4mA and 20mA current end points. Adjustable 4mA and 20mA water levels. Negative levels for the 4mA and 20mA levels - to match the site gauge readings. Display of the internally calculated water level offset + ability to zero this offset if required Update the 4-20mA current within 100mS of detecting loop power SDI-12 Version 1.3 compliant with CRC The WL3100 measures gauge pressure and applies temperature compensation to correct for errors in the transducer. The measured pressure is converted to a water level through a User Factor. Adjustment of this User Factor allows for variations introduced by the equipment location in the world, as well as local conditions. Water Level = Pressure x User Factor + Offset The User Factor is a function of gravity, water density, air density, equipment height above the orifice, and nominal water level. (Note that gravity is itself a function of latitude and altitude) (Note that water density is a function of water temperature) (Note that air density is a function of altitude) The User Factor may be entered directly into the WL3100, or it can be calculated internally by entering the information listed above (for the WL3100A only). (See the Menu Tree in the LCD Screen section) Various combinations of information may be entered, depending on what is known. For example, the operator could enter the gravity directly - or alternatively the latitude and altitude could be entered and the WL3100A will calculate the gravity for you. The WL3100 can be configured to measure pressure in psi or kpa - and it can be configured to measure the water height in m or ft. The User Factor is automatically corrected to account for any change in units. Typical errors that are introduced by the above factors are demonstrated in the graphs on the following pages. Copyright 25 of 46 2/10/2014

26 Copyright 26 of 46 2/10/2014

27 4-20mA Level The 4-20mA Level parameters in the enhanced WL3100 sets the water level required to make 4mA and 20mA appear on the 4-20mA interface. That is : Water Level 4mA Level 20mA Level 4-20mA Current 4.000mA mA These levels may be changed by the user by : 1. Use the scroll button to view the 4-20mA Level menu item. 2. Press and hold the select button for 5 seconds until Set 4mA Level appears. 3. Press the select button to make the first digit flash. 4. Press the scroll button to change it. Press select for the next digit etc. 5. When the 4mA Level is complete, press scroll to select the 20mA Level. 6. Repeat steps 3 and 4 to change the 20mA Levels. Calculated Offset When the Set Level function is performed (see the standard manual), the WL3100 calculates an offset between the measured water level and the desired water level. That is : Displayed (desired) Water Level = Measured Water Level + Calculated Offset This calculated offset can now be viewed in the Calc Offset menu. (This is for reference only, and serves no other purpose) If the user wishes to force this offset to 0, then simply press and hold the select button for 5 seconds while Calc Offset is displayed. Copyright 27 of 46 2/10/2014

28 SDI-12 to RS232 Interface The following schematic is for an SDI-12 to RS232 adapter that can be used for any Hydrological Services SDI-12 transducer. The adapter will allow an SDI-12 transducer to be connected to a PC, and will communicate on an RS232 port at 1200 Baud, 7 bits and even parity using an application such as HyperTerm or similar. Copyright 28 of 46 2/10/2014

29 Appendix B Installing Polyethelene Tubing and Orifice Fittings General The polythene tubing - SC is provided in three hundred metre rolls. It is an extremely durable material that has been used successfully in this application world wide for many years. The tubing is flexible, easy to handle and can be cut with a knife. The orifice fitting is comprised of a moulded polythene threaded cap, an orifice outlet and a tube fitting. The moulded cap will screw onto a standard 50mm nominal bore galvanised pipe. Orifice Fittings The site and reference level for the orifice fittings should be resolved before installation proceeds. The length of tubing from the HS55 to the orifice should not exceed 150 metres. A suggested method for installation of the orifice fitting is shown below. The site of the orifice should be positioned in quiet water out of the mainstream to provide protection. The area should be free of silting and aquatic growth. The mounting for the orifice fitting should consist of a section of 50mm nominal bore galvanised pipe threaded at one end and secured at the appropriate reference level. The securing of the orifice mounting should be such that it can withstand the forces applied by the flowing stream and associated floating debris. Preparation of Orifice Tubing Do not open the carton or remove the strapping. To prepare the roll of tubing for use, cut a 300mm diameter hole in the centre of the cardboard carton, retrieve the end of the tubing from the middle of the coil, then cut the strapping retaining the coil. This method will reduce the possibility of tangling the tubing. Prevent the ingress of dirt etc. from entering the tubing, by taping up the ends. At no time should the open end of the tubing be permitted to contact the soil. Orifice Tubing It is recommended that a trench be dug (minimum 600mm deep) between the equipment shelter and the proposed positions of the orifice The trenches should not have any low points in their length, they should have a continuous fall to the river. Pull the free end of the coiled tubing to the orifice position laying the tubing in the trench as you go. Refer to diagrams below Remove the protective tape from the end of the tubing, and push the tubing through the 50mm nominal bore pipe mounting. Insert the tubing into the tube fitting on the rear of the orifice fitting, ensuring that both ferrules are in place. Tighten the fitting nut. (Refer to the following diagram for tightening procedure). Place the orifice fitting onto the mounting pipe and tighten. Cut the tube at the coil end (tape both ends), ensuring that there is sufficient length to make the joint at the HS40V within the shelter. Check the lay of the tubing in the trench to ensure that it is free of coils and kinks. Under no Copyright 29 of 46 2/10/2014

30 circumstances should the tube form hollows where moisture can be trapped within the tube. Lay the tubing into position in the equipment shelter as required. Remove the protective tape from the end of river line tube. Insert the end of the tube into the appropriate river line fitting on the HS55 and tighten both fittings. (Refer to diagram for tightening procedure). Open the valve to the orifice. Copyright 30 of 46 2/10/2014

31 Appendix C Using Pressure to Measure Water Level Gas Purge Principle The behaviour of a gas flowing under a variable back pressure is utilised as an accurate means of measuring liquid head. Provided that: 1. The density of the gas is nearly the same as air. 2. The velocity of gas is low enough so as not to produce significant pressure drop down the line then the system pressure will be equal to the back pressure. This principle is illustrated in the following series of diagrams. In the first example, the tube exhausts to atmosphere and hence the water manometer indicate zero pressure in the system because it is acted on by two equal pressures- the system pressure and the atmospheric pressure Fig.1 - Depicts first stage in application of gas purge principle Fig.1 also illustrate another feature of all pressure systems, namely the gas endeavours to escape through any material that it is in contact with to find a lower pressure, but for practical purposes, the system pressure reflects the lowest of the outlet pressures. In this case, gas endeavours to pass through the walls of the tubing and fittings, through the water, but elects to take the easier path to atmosphere, which is in effect a massive leak. Copyright 31 of 46 2/10/2014

32 Therefore, it follows that in any pressure system that can exhaust to atmosphere, either through a valve or by a large leak, the system pressure is atmospheric and will not reflect any other pressure. Provided air or a gas that has a very similar density to air is used, then the errors from this source can be neglected. Nitrogen is preferred as it does not promote the formation of aquatic growth. The effect of the velocity of the gas can be observed by opening valve A, a higher pressure will be needed to force a high volume of gas through the line, resulting in a pressure drop between valve A and the outlet. Depending on the location of the manometer connection, the manometer will reflect a proportion of this increase in pressure. Fig. 2 High gas flow * Refer Bubbler System Instrumentation for Water Level Measurement - Report of Investigation No. 23 state of Illinois, U.S.A Head To Pressure Conversion As we are not seeking to measure atmospheric pressure, but liquid head, how is the principle applied? Simply by using two physical characteristics. 1. The tendency of the gas under pressure to seek a lower pressure. 2. The ability of a gas to pass through liquids. The first characteristic has already been demonstrated. The second characteristic can be appreciated by blowing through a hollow tube (straw) that is immersed in water. No bubble will appear until the pressure in the tube is sufficient to expel all the water from the tube. Copyright 32 of 46 2/10/2014

33 Fig 3. I. If a tube is immersed in a liquid, it can be seen that the pressure at the bottom of the tube is that exerted by the head of liquid above it. II. If we connect a gas supply to the tube, the gas will act on the surface of the liquid in the tube and tend to force it down. Assuming there is no change in level, the pressure at the end of the tube must be still the same. III. If we increase the pressure so that the gas can push out all the liquid against pressure level A, then it follows that the pressure at A will be the back pressure in the system. Also the pressure of each bubble of gas as it emerges from the end of the tube will a that point have an internal pressure equal to the head, and this internal pressure reduces until the bubble emerges at the surface at atmospheric pressure. Therefore the gas acts like a plunger to keep the water out of the tube and in effect, precisely balances the head of water that would naturally occur if the tube was opened to atmospheric pressure. In other words, the system pressure (back-pressure) is supporting a column of water, equal to the pressure head. Hence, any pressure measuring device, if connected to the pressure system will record the pressure head over the tube outlet (orifice). Fig. 4 depicts a water manometer connected to the system and it is recommended that such an arrangement be set up in a workshop for staff training. Gas Purge Operational Characteristics In the foregoing, the discussion has been limited to static head conditions, whereas in practice, the levels in stream are constantly fluctuating. Copyright 33 of 46 2/10/2014

34 Rising Situations It is the rising or increasing head situation that is critical for the correct operation system. Consider a situation where the gas supply is cut off and the level rises- refer Fig.5. Fig.5 - With gas supply cut off. Head increased from H1 to H2, gas is forced down the tube by an amount X. In this situation, it can be seen that whilst the system pressure has increased, it is not equal to the new head H2, but rather H2-x. This condition will remain as long as the gas is shut off. In other words, we now have a closed system, which respond to changes in accordance with universal gas law- PV i i a constant Ti To revert back to the open system, we must restore gas supply, which will eventually build up pressure in the system, until the gas escape from the orifice and the system pressure again becomes the precise head measurement. The time taken for the pressure system to respond to a given head pressure is commonly referred to as follow rate. The normal procedure is to establish the maximum rate of rise to be measured and adjust the gas flow so that there is no significant lag in the pressure system. However, in order to conserve the gas supply, the flow rate (bubble rate) is set to the minimum that will meet these conditions. Falling Situation The falling situation is of course the reverse of the rising situation except that there is now excess pressure in the system. If we were to suddenly lift up the orifice in Fig. 4, the pressure would drop to the new head, seen by the sudden rush of bubbles. Accordingly, even the lowest bubble rate will suffice for falling conditions. In practice, it may take some time to the pressure to bleed away, but this is usually less than the response time of the sensing unit. Copyright 34 of 46 2/10/2014

35 Field Requirement of Gas Purge Systems The principle requirements of gas purge are : I. A fine metering valve and sight feed for accurately setting the bubble rate. II. Constant regulator to maintain a constant bubble rate with changes of head. III. Pressure connections and valves for connecting the tubing to the river and the instrument. With the overall provision that the unit must be leak proof, otherwise the true head will not be recorded. The configuration most widely used is shown in Fig 6. Dual Line Connections Fig. 6 - Diagramatic view of field gas purge, single line without purge facilities. For long line, the effect referred to in Fig.2 becomes significant and it is usual to make the connection to the system near the orifice, so in effect there are two lines running the orifice. Hence the term dual line. The operation of Hydrological Services units is described in more details in diagrams 15 and 16 of instruction Manual for Sherlock Pressure Sensing Units. Copyright 35 of 46 2/10/2014

36 Pressure Bulb or Closed System The pressure bulb system relies on the normal under pressure. PV i i T i = constant relationship for gases Using similar diagrams to before, the closed system can be illustrated follows:- Fig. 7- Atmosphere- up to the level at which the water seals off the bottom of the bulb. Fig.8 - water seals off air and at this point system pressure is still atmosphere. Fig. 9 - system operating under head conditions Copyright 36 of 46 2/10/2014

37 As the water rises, the system pressure increases to the equivalent of the head H minus the amount the water rises within the bulb. This amount x, is non-linear and therefore cannot be completely compensated for by simple calibration. Provided the head H does not fall below say 300 mm, error from this cause is minimal. Basically the closed system will give good results subject to gradual changes of water temperature being experienced and the system being completely gas tight. A full discussion of this principle in given in Low Cost Stream Height Recorders - Unisearch (N.S.W) publication. Copyright 37 of 46 2/10/2014

38 Appendix D HS40V-DO (Dual Orifice) Features of Dual Orifice The Model HS40V-DO comes with a dual orifice application. It consists of 2 orifices located at different heights from the river bed. Under normal conditions the bottom orifice is active and the top orifice is inactive. The dual orifice application become beneficial in a situation where severe siltation appears and causes the blockage of the bottom orifice at which instance the valve of the bottom orifice (1) is closed and the valve of the inactive (top) orifice (2) is opened to keep the bubbler system operating. Orifice 1 Orifice 2 Note: Only one orifice can operate at a time. If the level of the second orifice exceeds the range of the transducer; the transducer level can be set again at the second orifice. Copyright 38 of 46 2/10/2014

39 Appendix E Gas Chamber Orifice Assembly Step 1: Secure Socket/Locknut to the 2 BSP pipe 2 BSP THREADED PIPE Step 2: Undo the nut and ferrules; feed the tube nut and the two ferrules onto the river line as shown in figure below Step 3: Tighten the tube nut to the GCO1 fitting as shown in figure below Copyright 39 of 46 2/10/2014

40 Step 4: Place the GCO1 assembly onto the mounting pipe, adjust coupling so the GCO1 is horizontal to the water, and tighten the flexible coupling with GCO1 in position. 30 Note: Ensure that the GCO1 is horizontally level as shown. Flexible coupling allows adjustment up to 30 degrees. 2 Galvanised Pipe Flexible Coupling (L) GCO1 Body Volume = 2000 ml (H) Tube Nut River Line Tube Back Ferrule Front Ferrule Orifice fitting Revolving Screen (for cleaning Purposes) (D) GCO1 DIMENSIONS Dimension Metric (mm) Imperial (inch) L D H Copyright 40 of 46 2/10/2014

41 Appendix F Typical Installations Typical installation for HS40V & HS40V-DO (Dual Orifice) Antenna + Antenna Bracket Hut 10 Watt Solar Panel Voltage Regulator Data Logger 3/8 River Line Tube 12VDC Battery 38 AmpHr Gas Chamber Orifice Model GCO1P with adjustable coupling HS4V0 Typical Installation Copyright 41 of 46 2/10/2014

42 Antenna + Antenna Bracket Hut 10 Watt Solar Panel Valve (1) of Orifice (1) Valve is open Valve (2) of Orifice (2) Valve is closed Note: Only one orifice in use at a time Voltage Regulator Data Logger 12VDC Battery 38 AmpHr 2 x 3/8 River Line Tube Gas Chamber Orifice Model GCO1P with adjustable coupling Orifice 2 Inactive Orifice 1 Active HS40V-DO Typical Installation Copyright 42 of 46 2/10/2014

43 Appendix G Automatic Moisture Extraction Control System Units with Serial Number and above have a new control system that automatically purges any built up moisture in the air dryer, at the end of the pump up cycle, by controlling a solenoid release valve. G.1 Filter Maintenance for the HS40V Step1: Using a screw driver, unscrew the valve plug as shown OR Later Model Earlier Model Step 2: OR Unplug as shown Current Model Earlier Model Copyright 43 of 46 2/10/2014

44 Step 3: Unscrew the bracket by removing the 2 screws as shown. Earlier Model OR Current Model Step 4: Hold the fitting back and pull tube out to separate from filter housing Hold fitting back Pull tube out Copyright 44 of 46 2/10/2014

45 Step 5: Undo filter housing by turning anti-clockwise Step 6: Remove filter housing & ensure O ring is in good condition. Replace O ring if needed Part No. SC Copyright 45 of 46 2/10/2014

46 Step 7: Remove filter by turning anti-clockwise. Replace filter if needed Part No. SC Step 8: Clean filter housing cap if required. Note: Reverse step 7 to step 1 to re-assemble. Copyright 46 of 46 2/10/2014

INSTRUCTION MANUAL DRY PRESSURE TRANSDUCER MODELS WL3100/WL3100A

INSTRUCTION MANUAL DRY PRESSURE TRANSDUCER MODELS WL3100/WL3100A INSTRUCTION MANUAL DRY PRESSURE TRANSDUCER MODELS WL3100/WL3100A QUALITY SYSTEM ISO:9001 CERTIFIED HYQUEST SOLUTIONS PTY LTD PO BOX 332, LIVERPOOL B.C NSW 1871, AUSTRALIA Phone:(Int.) 612 9601 2022 Fax:

More information

SDI mA Pressure Transducer (Submersible + Dry) Model WL2100 Operating Manual

SDI mA Pressure Transducer (Submersible + Dry) Model WL2100 Operating Manual SDI-12 + 4-20mA Pressure Transducer (Submersible + Dry) Model WL2100 Operating Manual (Submersible) WL2100W (Dry) WL2100D QUALITY SYSTEM ISO: 9001 CERTIFIED HYQUEST SOLUTIONS PTY LTD 48-50 Scrivener St,

More information

Installation and Operation Manual. Advanced Bubbler System

Installation and Operation Manual. Advanced Bubbler System Installation and Operation Manual Advanced Bubbler System Models: HS40 Compact (HS40AFC) HS40/2100 Compact (HS40AFC/2100) HS40/3100 Compact (HS40AFC/3100) HS40/3100A Compact (HS40AFC/3100A) plus /DO and

More information

HS Bubbler Technology. HyQuest Solutions New Zealand User Group August 2017

HS Bubbler Technology. HyQuest Solutions New Zealand User Group August 2017 HS Bubbler Technology HyQuest Solutions New Zealand User Group August 2017 Origins of Gas Purge Technology 1940 s - Developed By Dutch Engineer Late 1940 s 1954 - Adopted by State of Illinois Water Group

More information

Hyquest Solutions Pty Ltd

Hyquest Solutions Pty Ltd INSTRUCTION MANUAL BUBBLERS MODELS HS23SL / HS23DL / HS23DO QUALITY SYSTEM ISO: 9001 CERTIFIED HYQUEST SOLUTIONS PTY LTD PO BOX 332, LIVERPOOL B.C NSW 1871, AUSTRALIA Phone:(Int.) 612 9601 2022 Fax: :(Int.)

More information

Installation and Operation Manual. Advanced Bubbler System. Models : HS40 Series II HS40/3100 Series II HS40/3100A Series II and Dual Orifice

Installation and Operation Manual. Advanced Bubbler System. Models : HS40 Series II HS40/3100 Series II HS40/3100A Series II and Dual Orifice Installation and Operation Manual Advanced Bubbler System Models : HS40 Series II HS40/3100 Series II HS40/3100A Series II and Dual Orifice Series II QUALITY SYSTEM ISO: 9001 CERTIFIED HYQUEST SOLUTIONS

More information

Hydrological Services Pty Ltd 2012

Hydrological Services Pty Ltd 2012 INSTRUCTION MANUAL DRY BUBBLE UNIT MODEL HS23SL/HS23DO HYDROLOGICAL SERVICES PTY LTD PO BOX 332, LIVERPOOL B.C NSW 1871, AUSTRALIA Phone: (Int.) 612 9601 2022 Fax:(Int.) 612 9602 6971 Phone: (Nat.) (02)

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler. Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure

More information

HyQuest Solutions Pty. Ltd.

HyQuest Solutions Pty. Ltd. INSTRUCTION MANUAL L GAS PURGE COMPRESSOR MODEL HS55V / HS55VDO/HS55VB Gas Purge Compressor- Model HS-55/DO/D DB HS-55 100-1 Issue 2: 30/5/2014 CONTENTS Contents HS 55 & HS 55DO & HS 55DB GAS PURGE COMPRESSOR...

More information

DPC-30 DPC-100. Reference Manual

DPC-30 DPC-100. Reference Manual DPC-30 DPC-100 Reference Manual 1. Introduction 1.1 Description The Martel DPC Digital Pneumatic Calibrator improves upon traditional dial gauge pneumatic calibrators. The Martel DPC improves accuracy,

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

Appendix D: SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor. Description and Principle of Operation

Appendix D: SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor. Description and Principle of Operation Page 1 of 19 : SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor Description and Principle of Operation The photoacoustic multi-gas monitor (INNOVA 1412, Innova AirTech Instruments, Denmark) is a highly

More information

Air Bubbler Depth Gauge DG2200 Installation and Reference Manual

Air Bubbler Depth Gauge DG2200 Installation and Reference Manual Air Bubbler Depth Gauge DG2200 Installation and Reference Manual Rev. 3.2.2 06/2011 Installation and Reference Manual Page 2 Contents Chapter 1: Installation and Overview... 3 1.1 DG2200 Location Diagram...

More information

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

256 Pneumatic Pressure Indicator

256 Pneumatic Pressure Indicator 256 Pneumatic Pressure Indicator 51425699 Copyright 2002 Slope Indicator Company. All Rights Reserved. This equipment should be installed, maintained, and operated by technically qualified personnel. Any

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Healthcare and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

WL16 WATER LEVEL LOGGERS Submersible pressure transducer and USB datalogger combination

WL16 WATER LEVEL LOGGERS Submersible pressure transducer and USB datalogger combination WL16 WATER LEVEL LOGGERS Submersible pressure transducer and USB datalogger combination Warning: Non-vented water level loggers may have readings with errors of up to 250mm due to barometric pressure changes.

More information

Pneumatic high-pressure controller Model CPC7000

Pneumatic high-pressure controller Model CPC7000 Calibration technology Pneumatic high-pressure controller Model CPC7000 WIKA data sheet CT 27.63 Applications Automotive and avionics industry Industry (laboratory, workshop and production) Transmitter

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

Model PDT Dewpoint Transmitter

Model PDT Dewpoint Transmitter Model PDT Dewpoint Transmitter Instruction Manual Alpha Moisture Systems Alpha House 96 City Road Bradford BD8 8ES England Tel: +44 1274 733100 Fax: +44 1274 733200 email: mail@amsytems.co.uk web: www.amsystems.co.uk

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

BS2000 MOTOR ELECTRONICS, INC. PROTECTION INSTRUCTION MANUAL. (407) Phone: Website:

BS2000 MOTOR ELECTRONICS, INC. PROTECTION INSTRUCTION MANUAL. (407) Phone: Website: BS2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Revision Date: 6-23-14 RECOMMENDED REPLACEMENT

More information

Additel 761 Automated Pressure Calibrators

Additel 761 Automated Pressure Calibrators Automated Calibrators UPDATED Fully automated pressure calibrator with built-in pressure generator / controller to as high as 600 psi (40 bar) or as low as 0.01 Pa (0.00004 inh 2 O) accuracy Dual pressure

More information

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments Pegas 4000 MF Gas Mixer InstructionManual Contents I Table of Contents Foreword Part I Introduction 1 2 1 System overview... 2 2 Specifications... 3 Part II Installation 4 1 Rear panel connections...

More information

Instructions for Assembly, Installation, and Operation of the Gas Addition Kit Accessory with the CEM Discover Systems

Instructions for Assembly, Installation, and Operation of the Gas Addition Kit Accessory with the CEM Discover Systems Corporation Issued: 5/09 P/N: 600104 Rev. 2 Instructions for Assembly, Installation, and Operation of the Gas Addition Kit Accessory with the CEM Discover Systems The Gas Addition Accessory permits the

More information

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet:

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet: OXY Integral INTERCON ENTERPRISES INC Tel: 800 665 6655 Fax: 604 946 5340 E-Mail: sales@intercononline.com Internet: www.intercononline.com Manual Integral 2006 1 INDEX 2-3 PREFACE 4 INTRODUCTION 5 Principle

More information

Additel 761 Automated Pressure Calibrators Selection Guide

Additel 761 Automated Pressure Calibrators Selection Guide Automated Calibrators Selection Guide Model Features Range 761-LLP 761-D 761-L 761-LA 761-M 761-MA 761-H 761-HA 761-BP 0.05 to 8 bar.a -0.90 to 25 bar (1.2 to 115 psi.a) (-13 to 375 psi) 0.1 to 26 bar.a

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring

More information

Manual Weighingblock VB2 series and Uniscale

Manual Weighingblock VB2 series and Uniscale Manual Weighingblock VB2 series and Uniscale Note: At page 8 in this manual you will find a short form instruction. Normally the only instruction shipped together with the Scale. Overview different ranges.

More information

C-Flow Coriolis Mass Flow Meters

C-Flow Coriolis Mass Flow Meters Coriolis Mass Flow Meters Ready for Take Off The New Compact C-Flow Küppers Elektromechanik GmbH The C-Flow The C-Flow Coriolis Mass Meters consist of two components: KCE Transmitter KCM Transducer 2 KEM

More information

Bubble Tube Installations

Bubble Tube Installations Instruction MI 020-328 September 2013 Bubble Tube Installations For Liquid Level, Density, and Interface Level Measurements 2 Contents Introduction... 5 Abbreviations... 5 Principle of Operation... 5 Alternative

More information

Columbus Instruments

Columbus Instruments 0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011

More information

Cover Page for Lab Report Group Portion. Pump Performance

Cover Page for Lab Report Group Portion. Pump Performance Cover Page for Lab Report Group Portion Pump Performance Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 March 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section number:

More information

SonoMeter 30 Energy Meters

SonoMeter 30 Energy Meters Data Sheet SonoMeter 30 Energy Meters Description The Danfoss SonoMeter 30 is a range of ultrasonic, compact energy meters intended for measuring energy consumption in heating and cooling applications

More information

Instructions for Use

Instructions for Use Select-380 T-Auto T-Auto Contents Page Instructions for Use Ref: 3.0 IFU 380 T-Auto Mar 18 2 Schematic layout of the doser 3 Quick-fit instructions 4 Description/Installation/Operation Pump tubes & Water

More information

Additel 761 Automated Pressure Calibrators

Additel 761 Automated Pressure Calibrators Additel 761 Fully automated pressure calibrator with built-in pressure generator / controller to as high as 600 psi (40 bar) or as low as 0.01 Pa (0.00004 inh 2 O) accuracy Dual pressure modules Built-in

More information

CDS-2000 CO 2 Sensor Verification, Calibration, and Troubleshooting Bulletin

CDS-2000 CO 2 Sensor Verification, Calibration, and Troubleshooting Bulletin Electronic Control Manual 216 Sensors and Stats Section S Technical Bulletin CDS-2000 Issue Date 0393 CDS-2000 CO 2 Sensor Verification, Calibration, and Troubleshooting Bulletin Introduction 3 Pre-Verification

More information

Additel 761 Automated Pressure Calibrators Selection Guide

Additel 761 Automated Pressure Calibrators Selection Guide / Process Calibration Equipment Automated Calibrators Selection Guide Model Features Range Module 1 761-LLP 761-D 761-L 761-LA 761-M 761-MA 761-H 761-HA 761-BP -2.5 to 2.5 mbar (-1 to 1 inh 2 O) -0.95

More information

BAPI Pressure Line of Products - FAQs

BAPI Pressure Line of Products - FAQs Table of Contents 1. Several manufacturers produce pressure transmitters, why should I purchase from BAPI?... p. 2 2. BAPI makes several styles of pressure transmitters. What are the features of each?...

More information

Pressure Automated Calibration Equipment

Pressure Automated Calibration Equipment GE Measurement & control Pressure Automated Calibration Equipment Safety Instructions and User Guide - K0447 PACE5000 PACE6000 K0447 Issue No. 9 1 10 1 PACE5000 1 2 3 4 5 PACE6000 2 6 7 8 3 4 5 6 7 8 9

More information

HumiSys HF High Flow RH Generator

HumiSys HF High Flow RH Generator HumiSys HF High Flow RH Generator Designed, built, and supported by InstruQuest Inc. Versatile Relative Humidity Generation and Multi-Sensor System The HumiSys HF is a high flow version of the previously

More information

Cover Page for Lab Report Group Portion. Head Losses in Pipes

Cover Page for Lab Report Group Portion. Head Losses in Pipes Cover Page for Lab Report Group Portion Head Losses in Pipes Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 February 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section

More information

Instruction Manual VCG-6

Instruction Manual VCG-6 Specifications Amps / Volts requirements 400 ma @ 24 VDC Propane pressure (VCG-6LP) 11 WC / 2.8 kpa Natural Gas pressure (VCG-6NG) 4.5 WC / 1.15 kpa Cu ft per hour / CO2 3-6 SCFH BTU Rating (Variable)

More information

Additel 761 Automated Pressure Calibrators

Additel 761 Automated Pressure Calibrators Automated Calibrators UPDATED Fully automated pressure calibrator with built-in pressure generator / controller to as high as 600 psi (40 bar) or as low as 0.01 Pa (0.00004 inh 2 O) accuracy Dual pressure

More information

The HumiSys. RH Generator. Operation. Applications. Designed, built, and supported by InstruQuest Inc.

The HumiSys. RH Generator. Operation. Applications. Designed, built, and supported by InstruQuest Inc. The HumiSys RH Generator Designed, built, and supported by InstruQuest Inc. Versatile Relative Humidity Generation and Multi-Sensor System The new HumiSys with single or dual RH probes capabilities is

More information

PTG100 Precision Test Gauge

PTG100 Precision Test Gauge PTG100 Precision Test Gauge User Manual PD1007 Rev B 03/28/2014 Palmer Instruments Inc. 234 Old Weaverville Road Asheville, NC 28804 Toll Free: 800-421-2853 Phone: 828-658-3131 Fax: 828-658-0728 Email:

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

PRODUCT MANUAL. Diver-DCX

PRODUCT MANUAL. Diver-DCX PRODUCT MANUAL Diver-DCX Contents 1 Introduction... 1 1.1 SDI-12... 1 1.2 Independent Data Recording... 2 1.3 Additional Information... 2 2 Installation... 3 3 Sensor Parameters... 3 3.1 Default Settings...

More information

Inert Air (N2) Systems Manual

Inert Air (N2) Systems Manual INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing

More information

NTF-230 OPERATION MANUAL

NTF-230 OPERATION MANUAL NTF-230 OPERATION MANUAL MAHLE Aftermarket Inc., Service Solutions 10 Innovation Drive York, Pennsylvania 17402 USA Phone: 717-840-0678 Toll Free: 800-468-2321 Web-site: www.servicesolutions.mahle.com

More information

Squeegee Unit for MRS Multi-Recovery System

Squeegee Unit for MRS Multi-Recovery System En Operating Instructions Squeegee Unit for MRS Multi-Recovery System Translation of the original operating instructions Squeegee - MRS Table of Contents Safety Recommendations Technical Data - MRS Booth

More information

AutoChanger Installation & User Guide Issue 2

AutoChanger Installation & User Guide Issue 2 1 INDEX Page 1. Introduction... 3 2. AutoChanger Components Guide 4 3. Installation. 5-11 a) Installation Guidelines.. 5 b) Installation Retrofit... 6-11 c) Installation New... 11 4. AutoChanger User Guide

More information

6900 Maintenance Instruction System Flush

6900 Maintenance Instruction System Flush Equipment Required FA74005 Damper Drain Tube FA16005 Cover Removal Tool FA900005 Beaker 0.25 Litre FA900003 Solvent Cleaning Bottle FA940021 Syringe Polypropylene 50 ml as required FA999045 Gloves Latex

More information

Instruction Manual. Pipe Friction Training Panel

Instruction Manual. Pipe Friction Training Panel Instruction Manual HL 102 Pipe Friction Training Panel 100 90 80 70 60 50 40 30 20 10 HL 102 Instruction Manual This manual must be kept by the unit. Before operating the unit: - Read this manual. - All

More information

Hand-held pressure calibrator with integrated pump Model CPH6600

Hand-held pressure calibrator with integrated pump Model CPH6600 Calibration technology Hand-held pressure calibrator with integrated pump Model CPH6600 WIKA data sheet CT 16.01 Applications Calibration service companies and service industry Measurement and control

More information

TEL/jlRE" Introduction. Display Features and Modes. Startup Procedure. Power-Up Procedure. Adjustment Modes

TEL/jlRE Introduction. Display Features and Modes. Startup Procedure. Power-Up Procedure. Adjustment Modes TEL/jlRE" Introduction The Telaire 7001 CO 2 /T emperature monitor (shown in Fi gt u e 1 below) is an easy to use hand-held instnunent, which provides stable and highly accurate readings due to Telaire

More information

SCOPE OF THIS GUIDE STARTING-UP. 1 Check mini CORI-FLOW functional properties

SCOPE OF THIS GUIDE STARTING-UP. 1 Check mini CORI-FLOW functional properties Quick Installation Guide Doc nr.: 9.17.052H Date: 10-12-2015 SCOPE OF THIS GUIDE mini CORI-FLOW instruments are highly accurate instruments for measuring and controlling the mass flow rate of liquids and/or

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

Gas Pressure Probe. Information Sheet. Total Dissolved Gas

Gas Pressure Probe. Information Sheet. Total Dissolved Gas Total Dissolved Gas Information Sheet T900 Total Dissolved Gas Pressure Probe Description The In-Situ Inc. T900 probe is a specially adapted submersible pressure transducer designed to monitor Total Dissolved

More information

Met One E-BAM Particulate Monitor

Met One E-BAM Particulate Monitor STANDARD OPERATING PROCEDURES Met One E-BAM Particulate Monitor AMBIENT AIR MONITORING PROGRAM for the 130 LIBERTY STREET DECONSTRUCTION PROJECT LOWER MANHATTAN DEVELOPMENT CORPORATION 1 Liberty Plaza

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

RC 195 Receiver-Controller

RC 195 Receiver-Controller Document No. 129-082 RC 195 Receiver-Controller Product Description The POWERS RC 195 Receiver-Controller is a pneumatic instrument that receives one, two or three pneumatic inputs. It produces a pneumatic

More information

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications Outstanding performance in extremely low pressure and low pressure ranges from 0.003 to. Realizing high performance, energy saving, and compact size. Realize precise pressure control in a pressure range

More information

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05 IDL0 Battery Powered Precision Digital Gauge for Leak Testing Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger

More information

RD(H)20/25 Pressure-Reducing Regulator User Manual

RD(H)20/25 Pressure-Reducing Regulator User Manual RD(H)20/25 Pressure-Reducing Regulator User Manual Read the complete manual before installing and using the regulator. 2 Safe Product Selection When selecting a product, the total system design must be

More information

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels 12.09 product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels Introduction: This manual covers the installation and operation of Humboldt FlexPanels for Triaxial and Permeability

More information

HPICAL Operation & Data Logging Procedures. Click spacebar to advance through slides 1

HPICAL Operation & Data Logging Procedures. Click spacebar to advance through slides 1 HPICAL-15000 Operation & Data Logging Procedures Click spacebar to advance through slides 1 WARNING Always wear proper safety equipment when using high pressure equipment. Do not exceed 125 psi air pressure.

More information

Installation and Operation Manual

Installation and Operation Manual Manual Static pressure transducer with controller Differential static pressure transducer with analog output and optional PI control mode Large diaphragm element with differential transformer Transducer

More information

Halsey Taylor Owners Manual STOP!

Halsey Taylor Owners Manual STOP! Halsey Taylor Owners Manual 4710 Freeze Resistant Floor Mounted Steel Fountain STOP! PLEASE READ THE FOLLOWING INFORMATION. ITALLATION ITRUCTIO FOR THE 4710FR FTN. WITH 97243C SINGLE VALVE CONTROL ASSEMBLY

More information

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER Features ±0.01% FS Measurement & Control Accuracy ±0.001% /ºC Thermal Stability Pressure Ranges from ±1 psid to 1200 psia Applications Barometric Measurement

More information

Built-in Purge Control Functions

Built-in Purge Control Functions Built-in Purge Control Functions Why clean a sensor? As the velocity sensor was calibrated clean, operating it clean also preserves the best calibration. Any build up of material on a thermal sensor tends

More information

ATOC Meteorological Tower (6 meter-4 level) Guide

ATOC Meteorological Tower (6 meter-4 level) Guide ATOC Meteorological Tower (6 meter-4 level) Guide SETUP Outline 1. Siting 2. Components 3. Transportation 4. The Tower 5. The Cables and Data Logger Siting Selecting an appropriate site for the weather

More information

LEAK TROUBLESHOOTING

LEAK TROUBLESHOOTING LEAK TROUBLESHOOTING If you suspect that your TMC isolation system is leaking (most often evidenced by going through air/nitrogen tanks too quickly), this guide will help you to find and fix the problem.

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

SPECIFICATIONS APCEPH1

SPECIFICATIONS APCEPH1 APCEPH1 ph CONTROLLER SPECIFICATIONS APCEPH1 Input voltage 120 Volts AC Maximum amperage 14.5 amps @ 120 VAC ph Accuracy +/- 0.2 ph ph Control range Adjustable 4.5 8.5 ph Weight < 1 lbs Dimensions 3" x

More information

User Manual. Quantos Automated Dosing Liquid Module

User Manual. Quantos Automated Dosing Liquid Module User Manual Liquid Module 1 Safety Information 1.1 Definition of warnings and symbols Signal Words WARNING for a hazardous situation with medium risk, possibly resulting in severe injuries or death if

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

Quick Installation Guide Doc nr.: C Date:

Quick Installation Guide Doc nr.: C Date: Quick Installation Guide Doc nr.: 9.17.093C Date: 13-05-2016 SCOPE OF THIS GUIDE mini CORI-FLOW instruments are highly accurate instruments for measuring and controlling the mass flow rate of liquids and/or

More information

Operating Instructions Part No

Operating Instructions Part No DIGITAL AUTOMATIC TYRE INFLATOR Operating Instructions Part No. 11.0545 Thank you for selecting this Jamec Pem Automatic Tyre Inflator. Please read this manual before carrying out any installation or service

More information

Ventam 85 Installation & Commissioning Instructions

Ventam 85 Installation & Commissioning Instructions Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoeburyness Essex SS3 9QY Phone 01702 382 307 Fax 01702 382 340 Ventam 85 Installation & Commissioning Instructions 1 General The Ventam

More information

Precision digital pressure gauge Model CPG1000

Precision digital pressure gauge Model CPG1000 Calibration technology Precision digital pressure gauge Model CPG1000 WIKA data sheet CT 10.01 Applications Oil and gas industry Maintenance and service facilities Calibration service companies and service

More information

The Ins and Outs of I/P Transducers

The Ins and Outs of I/P Transducers The Ins and Outs of I/P Transducers By Mark B. Levine, ControlAir Inc. General description I/P transducers are versatile instruments that use an electrical control signal to proportionally regulate gas

More information

Superconducting Susceptometer (MPMS-5S) Quantum Design Room 296 (MPMS)

Superconducting Susceptometer (MPMS-5S) Quantum Design Room 296 (MPMS) Superconducting Susceptometer (MPMS-5S) Quantum Design Room 296 (MPMS) Sensitivity: 1x10 11 A m 2 Applied DC fields: 0 T to 5 T Applied AC fields: 0 G to 3 G (zero-to-peak), 0.01 Hz to 1000 Hz Temperatures

More information

Precision pressure sensor Basic version Model CPT6020

Precision pressure sensor Basic version Model CPT6020 Calibration Precision pressure sensor Basic version Model CPT6020 WIKA data sheet CT 25.13 Applications Calibration technology High-accuracy pressure monitoring Pressure sensing in critical applications

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

The HumiPyc - Model 1 - Gas Pycnometer; Density, Moisture, Permeation Analyzer; RH sensor Calibrator

The HumiPyc - Model 1 - Gas Pycnometer; Density, Moisture, Permeation Analyzer; RH sensor Calibrator The HumiPyc - Model 1 - Gas Pycnometer; Density, Moisture, Permeation Analyzer; RH sensor Calibrator Designed, built, and supported by InstruQuest Inc. Temperature controlled, multi-technique volumetric

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Micro-S / Micro-S Digital Wall Hung Unit Please fulfil all listed requirements prior to and during

More information

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation. Quality Products at Competitive Prices Gas Check Automatic testing of the down-stream installation to check that all valves are closed and that pipework and fittings are gas tight before each system start-up.

More information

High-performance submersible pressure transmitter For level measurement Model LH-10

High-performance submersible pressure transmitter For level measurement Model LH-10 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-10 WIKA data sheet PE 81.09 Applications Level measurement in rivers and lakes Deep well

More information

Instruction Manual Dräger MSI P7 and MSI P7 plus

Instruction Manual Dräger MSI P7 and MSI P7 plus Dräger MSI GmbH Rohrstraße 32 58093 Hagen Tel.: +49-2331 / 9584-0 Fax: +49-2331 / 9584-29 e-mail: info@draeger-msi.de D 923; Edition 2011-01-01 Content 1. General Hints Page 4 2. The Instrument 2.1 Front

More information

Lab 1: Pressure and surface tension. Bubblers, gravity and the mighty paper clip.

Lab 1: Pressure and surface tension. Bubblers, gravity and the mighty paper clip. Lab 1: Pressure and surface tension. Bubblers, gravity and the mighty paper clip. CEE 3310 - Summer 2012 SAFETY The major safety hazard in this laboratory is a shock hazard. Given that you will be working

More information

ADT 761 Automated Pressure Calibrator

ADT 761 Automated Pressure Calibrator 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com With a built-in high performance electronic pump and precision pressure controller,

More information