1 IKGAtl Kenneth Grubb Assoiates Ltd BURO HAPPOLD COPPERHOUSE SLUICE GATE DOCUMENT REVISION RECORD Doument Number: Number of Pages: Doument Title: Saved as: C0395/006/DOC 31 REPORT ON THE MECHANICAL SURVEY OF THE COPPERHOUSE SLUICE VERTICAL LIFT GATE K:\Contrats Working\ \C0395B Copper House Sluie\Douments\C0395B_006_DOC Rev A 1.do REV DATE A AUTHOR CHECKED APPROVED C Appleton R Digby K Grubb Refer to the Revision Sheet at the rear of this doument for details of modifiations. Do Ref C0395_006_do Rev A 1 Mehanial Survey of the Vertial
2 :fl!kgali Kenneth Grubb Assoiates Ltd CONTENTS 1. INTRODUCTION SURVEY FINDINGS Review of doumentation SURVEY OF THE GATE STRUCTURE, CIVIL INTERFACES AND LIFTING GEAR Gate Struture Civil Work Interfaes Gate Sealing System Lateral Gate Guiding System Gate Lifting Gear Eletrial Equipment ISSUES AND CONSTRAINTS RECOMMENDATIONS Gate Struture Civil Works Interfaes Gate Sealing System Lateral Gate Guiding System Gate Lifting Gear Eletrial Equipment CONCLUSIONS Do Ref C0395_006_do Rev A 2 Mehanial Survey of the Vertial 1J '0 d G ".l},cj 0: CJ: ; a: le G': II:
3 IKGALI Kenneth Grubb Assoiates Ltd 1. INTRODUCTION At the request of Sura Happold (BH) (the onsultants retained diretly by the Hayle Harbour site developer, lng), Kenneth Grubb Assoiates Ltd (KGAL) has undertaken a mehanial survey of the sited at on Copperhouse Pool and operated by the Environment Ageny Operations Delivery Staff. The survey was of a non-intrusive nature and undertaken during tidal onditions. There is some residual risk that problems relating to the gate were not unovered. Members of the Environment Ageny (EA) staff were on hand to assist the surveyors with information regarding the history of the installation and the site in general. They were also able to provide information with regard to the operation and maintenane of the gates. In addition, Dave Turner of the EA was ontated and provided useful bakground information. The purpose of the survey was to determine the ondition and servieability of the existing gate and drive mehanisms, take measurements of the installation, establish the need for any refurbishment work and ensure that no other problems exist. Also, to onsider the possibility of the gate being apable of being used in a sluiing/souring apaity. As the gate is owned and operated by the Environment Ageny, no attention was given to operational, management or Health and Safety issues, though problems in this regard are obvious on the site. The survey was undertaken between 4th and 6th September Personnel involved: Chris Rose Ken Grubb Chris Appleton (BH) (KGAL) (KGAL) Part- time The purpose of the vertial gate is, primarily, to at as a flood defene mehanism to prevent flooding of the area from tidal water. The seondary purpose of the gate is to regulate the saltwater inundation within the Copperhouse Pool. Note that historially the gate was used as a means of souring sand from the harbour hannels. Sine that time the gate design has been hanged by the EA. There may be some advantage to the potential Hayle harbour development if this funtionality ould be restored. The gate was originally manufatured and installed in 1981 as the diret replaement for a pair of mitre gates. It was originally designed to work as a roller gate. The roller axles are still fitted to the ends of the gate. Do Ref C0395_006_do Rev A 3 Mehanial Survey of the Vertial
4 ' Q IKGALI Kenneth Grubb Assoiates Ltd However, at some time following original installation, the rollers were removed and the gate was modified to run on non-metalli wearing strips mounted on the opposing inner faes of the existing ivil guide setion. Mr. Dave Turner of the Environment Ageny stated that the reason that the gate was onverted to a sliding gate was the high ost of maintenane attributed to the roller bearings whih had ontinually seized. The gate is generally maintained in a position with the lowest edge of the gate approximately 600mm above the ivil sill. No speial problems assoiated with the operation of the equipment had been reported to KGAL prior to the inspetion. Disussions with the EA site staff indiated that the very nature of the gate operation (i.e. either tidal flood defene or undershot gate to relieve upstream flooding) had meant that the gate was very rarely operated. 2. SURVEY FINDINGS 2.1 Review of doumentation There were no drawings of the installation made available to the surveyors. It is understood that drawings are available from the EA. t I f (i; II: e 1:: I Do Ref C0395_006_do Rev A 4 Mehanial Survey of the Vertial & e: e
5 IKGALI Kenneth Grubb Assoiates Ltd 3. SURVEY OF THE GATE STRUCTURE, CIVIL INTERFACES AND LIFTING GEAR 3.1 Gate Struture The survey foused initially on the gate struture. NB: For the purpose of this survey, downstream will be defined as the water in the foreground as shown in Photograph 1 below (i.e. that level open to the sea) and upstream will be defined as water on the other side of the gate as shown in Photograph 1 below (i.e. the impounded Copperhouse Pool). Photograph 1 General view of the gate, lifting frame superstruture, aess footbridge, plant room and ontrol ubile of the vertial lift gate at Do Ref C0395_006_do Rev A 5 Mehanial Survey of the Vertial
6 !KGALI Kenneth Grubb Assoiates Ltd The gate is a steel fabriation onsisting of a retangular skinplate stiffened on the rear fae by a series of steel astellated beam setions and small vertial web plates. ft Photograph 2 General view of the front or downstream fae of the gate showing the retangular skinplate : : e: The upper setion of the skinplate above the tidal marks appears to be in very good on.dition with no evidene of degradation of the painting system. The lower setion of the skinplate below the tidal marks has large areas where the paint has been removed and widespread surfae orrosion of the exposed substrate is evident (see photograph 3). Do Ref C0395_006_do Rev A 6 Mehanial Survey of the Vertial e e: e e: t= 1:
7 IKGALI Kenneth Grubb Assoiates Ltd Photograph 3 General view of the bottom right hand orner of the front or downstream fae of the gate showing the widespread orrosion on the skinplate Loalised measurements were taken and established that "pitting" or indentations up to 2mm deep were ommon. The rear or upstream fae of the gate appeared to be in a very similar ondition to that desribed for the front or downstream fae of the gate in that the areas above the nominal tidal marks were generally in better ondition than those below. Do Ref C0395_006_do Rev A 7 Mehanial Survey of the Vertial
8 IKGALI Kenneth Grubb Assoiates Ltd -f f ' ( e f;: f; g e: Photograph 4. General view of the rear or upstream fae of the gate showing the astellated beam and vertial web plate stiffeners The horizontal astellated beams had aumulated a wide range of debris varying ar from seaweed to timber flotsam. Do Ref C0395 _ 006 _do Rev A 8 Mehanial Survey of the
9 ' " IKGAL,I K_e_nn_e_t_h_G_,.,_u_bb_A_s_so ia_t_es_l-td ; o_p_p_e_rh_o_u_s_e_s_lu_i_e_ Photograph 5 General view of the rear or upstream fae of the gate showing the aumulation of debris on the astellated beams Do Ref C0395_006_do Rev A 9 Mehanial Survey of the Vertial
10 IKGALI Kenneth Grubb Assoiates Ltd There was some very limited surfae "weepage" of orrosion produts around the ( astellated beams where the paint system had been damaged. ( Photograph 6 Loal view of the rear or upstream fae of the gate showing the loalised limited orrosion present on the astellated beams The bottom edge of the gate fabriation has not been designed as a knife-edge and would be unsuitable to at as a sluiing struture without modifiation. This is beause the urrent design of both the struture and sealing system would be prone to vibration. The gate struture has plates losing off the open gate setions at eah end. This original arbon steel end plate has additionally been lad at some time postommissioning with a bolted stainless steel plate over almost its entire length. The roller wheels originally fitted to the gate had also been removed. The roller gate has effetively been onverted to a sliding gate by this modifiation.. However the axles to mount the wheels onto the gate had all been left in plae. Do RefC0395_006_do Rev A 10 Mehanial Survey of the Vertial ( (:.: (; g g @; @:
11 IKGALI Kenneth Grubb Assoiates Ltd Photograph 7 View of the end setion of the gate showing additional "all over" plate with loal ut-outs for original roller axles and two folded guide angles ating as front and rear load bearers The stainless steel plate itself has irular holes ut out of it to permit the original roller axles to protrude through. The lowest setion of original end plate that remained unovered by the stainless steel plate had orroded badly. Do Ref C0395_006_do Rev A 11 Mehanial Survey of the Vertial
12 /KGALI Kenneth Grubb Assoiates Ltd Copperhol.ise Sluie. Photograph 8 View of the end setion of the gate showing extent of additional "all over" stainless steel plate On top of the stainless steel plate at the extreme upstream and downstream edges are two folded and bolted stainless steel "angles". The purpose of these angles is to at as load bearing guides in the absene of the original roller wheels. However, the design of the modifiation does not lend itself to load transferene beause of the use of slotted holes and tapered washers. The strength of the bolted detail is a onern and may not be fit for purpose. The angles bear upon non-metalli bearing strips bolted into the upstream and downstream internal faes of the ivil work guide. A diffiulty with this detail is that a flat sliding fae is srewed to a rowned rail fae with a flexible sealant taking up the neutral voids. It is believed that this ontributes to the damage found at lower setions (see ivil work interfaes). Do Ref C0395_006_do Rev A 12 Mehanial Survey of the Vertial
13 IKGALI Kenneth Grubb Assoiates Ltd Photograph 9 View of the end setion of the gate showing folded stainless steel angles and upstream and downstream bolt-on bearing I sealing faes 3.2 Civil Work Interfaes The non-metalli bearing strips run the full height of the ivil guide slot on both the upstream and downstream faes. The upper setions of the bearing strips appear to be intat and in reasonable ondition. Do Ref C0395_006_doRev A 13 Mehanial Survey of the Vertial
14 ' e: (:.:!KGALI Kenneth Grubb Assoiates Ltd t, t ( ( (: t; Photograph 1 0 General view of the upstream and downstream bolt-on bearing I.. sealing faes However the lower setions of both the upstream and downstream sealing faes are badly damaged and in some ases, missing ompletely. (: f:: (: : f; (: (; = Do Ref C0395_006_do Rev A 14 Mehanial Survey of the Vertial
15 .. '!KGALI Kenneth Grubb Assoiates Ltd Photograph 11 Loalised view of the damage apparent on the lower setion of the downstream bolt-on bearing I sealing faes Do Ref C0395_006_do Rev A 15 Mehanial Survey of the Vertial
16 The very lowest setions of the ivil work guide are the worst affeted, with evidene of extreme souring, loss of material and build up of marine life. t t f ' ( ' (: (: Photograph 12 Loalised view of the erosion damage and build up of marine life on the lowest setion of the ivil work guide slot At the sill, there is a ast in sill beam that ats as the sealing surfae for the seal along the bottom edge of the gate. The surfae of the beam suggests that it is made from stainless steel, although this is unertain, and it appears to be in reasonable ondition. There is loal damage to the harbour walls in the viinity of the gate. No attempt has been made to evaluate this or assess the impat of potential sluiing operations. This should be onsidered by a qualified ivil engineer. Do Ref C0395_006_do Rev A 16 Mehanial Survey of the Vertial {:.: e:.= (: = : : ;
17 /KGAJJ/ Kenneth Grubb Assoiates Ltd Photograph 12 General view of the ast in sill beam Do Ref C0395_006_do Rev A 17 Mehanial Survey of the Vertial
18 w Kenneth Grubb Assoiates Ltd Gate Sealing System The gate sealing system is intended to seal in both diretions. The system onsists of two L shaped or "Hokey Stik" seals bak to bak that at full length down one end of the gate (against a plate mou11ted on the downstream lip of the ivil work guide) aross the ast-in sill beam and up the opposite side of the gate. The L or "Hokey Stik" seal is an ative seal in that it is "ativated" by hydrostati pressure impinging on the leg of the seal. The higher the load, the more the seal is pressed into the mating surfae and in theory, the more effetive the sealing. However, there are gaps between the side seals and their sealing faes. Photograph 13 View of the end setion of the gate showing the bak to bak L shaped or "Hokey Stik" seals and metalli lamp strip The only problem with this is that higher up on the gate (i.e. near to the free surfae of the water when the gate is lowered), there is almost no hydrostati loading on the seal. In these positions, the seal will probably leak slightly. Do Ref C do Rev A 18 Mehanial Survey of the Vertial
19 JKGAI,:_!J --K-en_n_e G_r_ub_b_A ss_o m_re_s Lt_d o_p_p_e_rh_o_u_s_e_s_lu_i_e_ Looking at the lowest orners of the gate, the bak to bak seal turns through goo and travels along the bottom edge of the gate. Photograph 14 View of the bottom orner setion of the gate showing the interfae between the side and bottom bak to bak L shaped. or "Hokey Stik" seals and metalli lamp strips The orner setions between the side and bottom seals have large gaps visible. This means that the seal is not effetive in this position and given the head ating at this point, that water will tend to jet through the gap and impat on the ivil works behind. Over the ourse of time, this ould lead to erosion of the ivil works. 3.4 Lateral Gate Guiding System _ The gate struture is guided laterally by two pairs of guide rollers on eah end of the gate. The rollers at against a plate mounted on the upstream lip of the ivil work guide. Do Ref C0395_006_do Rev A 19 Mehanial Survey of the Vertial
20 IKGALI Kenneth Grubb Assoiates Ltd Photograph 15 View of the end setion of the gate showing one pair of lateral guide rollers and the lateral guide plate that they at against The rollers are thought to be manufatured by Brauer. They are approximately 200mm diameter and 50mm tread width. 3.5 Gate Lifting Gear The gate struture is lifted and lowered using a motor-driven, steel-wire, rope-winh system. The motor drives a grooved drum on whih a stainless steel wire rope (of approx of an inh diameter) is wound. The steel wire rope passes over a series of sheaves and pulleys at both ends of the gate and is terminated at a fixed point on the gate support superstruture at the motor drive end. Thus as the drum turns, the steel wire rope is either paid out or wound onto the drum depending on the diretion of drum rotation. This in tum therefore ats to either lower or raise the gate. Do Ref C0395_006_do Rev A 20 Mehanial Survey of the Vertial e : -: : = = : : : :.-: a: : : a:
21 IKGALI Kenneth Grubb Assoiates Ltd The pulley I sheave onfiguration basially means that the gate is raised or lowered at 25% of the amount of steel wire rope paid out from the drum. Photograph 16 View of the gate atuation mehanism onsisting of an eletri drive motor, drum, steel wire rope and Slak Rope mehanism I swith The steel wire rope leaving the drum is fitted with a Slak Rope mehanism onsisting of a guide pulley and lever frame together with a swith. This devie is fitted to prevent the steel wire rope beoming loose on the drum in the event that the gate was being lowered, beame jammed in its guides and ould not be physially lowered further. The steel wire rope exits through a slot in the roof of the protetive enlosure. The slot is proteted by a moveable guard whih moves as the steel-wire rope pays out from the drum. Do Ref C0395_006_do Rev A 21 Mehanial Survey of the Vertial
22 lkgali Kenneth Grubb Assoiates Ltd Photograph 17 View of the two pulley wheels on one side of the gate Copperhouse Sluie Photograph 17 shows the steel wire rope passing under one pulley, up and over the pulley at the top of the gate support superstruture (not shown), bak down under the other pulley and aross to the orresponding pulley on the opposite side of the gate. The motor and gearbox appeared to be in satisfatory ondition and the operator did not report any problems with the operation or availability of the drive mehanism. The steel wire rope appears to be servieable and generally in good ondition. The pulleys and sheaves have been greased and were all found to rotate without slippage or stiking. There does not appear to be any mehanism for preventing the wire ropes from beoming detahed from the gate pulleys in a slak-rope situation. There is not an obvious method for renewing the wire rope without exposing persons to Health and Safety hazards of working at height. Do Ref C0395_006_do Rev A 22 Mehanial Survey of the Vertial t e.(; e e: g : It e: e: e: e:
23 w Kenneth Grubb Assoiates Ltd , Eletrial Equipment The majority of the eletrial equipment is housed in a.ontrol panel in an adjaent plant room. Aess to the ontrol panel was not available and no reasonable opinion ould be made as to its ondition. Photograph 18 General view within the motorised winh housing showing the eletrial inoming supply and distribution enlosures Additional eletrial equipment is housed within the eletrial enlosure. The interior of the housing appeared to be dry and lean, with no obvious signs of moisture ingress. Eletrial enlosures are mounted diretly on the internal wall of the housing. They were found to be lean and appeared in good order. The enlosures themselves were not opened, so no opinion an be offered regarding the internal ondition of the equipment Do Ref C0395_006_do Rev A 23 Mehanial Survey of the Vertial
24 IKGALI Kenneth Grubb Assoiates Ltd ' The housing was fitted with an Emergeny Stop swith to isolate the inoming power ( supply from the rest of the equipment. ' The housing was fitted with an interloking isolation swith mounted on the door aperture. This ats to isolate power to the equipment within the housing when the door is opened. Photograph 1 9 General view within the motorised winh housing showing the interloking door power isolation swith The gate has a movement limit swith fitted to the front of the gate. Photograph 20 General view of the gate movement limit swith This swith is operated by a striker plate also mounted on the front fae of the gate. Do Ref C0395_006_dei Rev A 24 Mehanial Survey of the Vertial., - ( t (: tt : tt : : ft e: e: fc 11:,-;_
25 /KGALI Kenneth Grubb Assoiates Ltd The position of many of the limit swithes make them diffiult to maintain safely.. I Photograph 21 General view showing the limit swith striker plate with the gate in fully raised position. 4. ISSUES AND CONSTRAINTS There were no issues raised by the EA staff whilst on site with regard to the operation of the gate. It is understood that the EA has some reservations of the use of the gate as a sluie from a number of viewpoints, inluding: 1. The gate is not urrently suitable for sluiing 2. Using the gate as a sluie might ause damage to the adjaent ivil works, whih are listed strutures 3. There may be Health and Safety impliations for the publi Item 1 has been borne out by the survey, but ould be made aeptable by modifiation. Do Ref C0395_006_do Rev A 25 Mehanial Survey of the Vertial
26 .t w Kenneth Grubb Assoiates Ltd Item 2 is a ivil issue and is left to others. Item 3 ould be addressed by management and ontrol modifiations. As it was not possible to obtain opies of the original gate installation drawings prior to the survey, the safety margin for the gate struture against the loads urrently seen is indeterminate. The effet of previously onverting the gate to sliding operation will be to inrease the loads in the winhing system. It is unknown if this was taken into aount. It is aknowledged that in general the gate is only operated under balaned head onditions. Aess to the original drawings would permit alulations to take plae to substantiate the design load ase for the original struture. If no suh drawings are available, it would still be possible to determine the approximate apaity of the existing gate by alulation based on the dimensions reorded during this survey. This work ould be arried out, by agreement, if required. Aspets of the previous gate modifiation to sliding operation are doubtful, however the risks assoiated with this appear to belong to the EA and surrounding properties whih may be at inreased flood risk. It is not lear whether stop logs or other means of establishing dry working onditions around the gate are urrently available. It is thought that there is no suh existing provision. The elapsed time.to remove and modify the gate would take it through at least one monthly tidal-yle, this would expose Copperhouse Pool to some flood risk and would have to be arefully timed and oordinated. The EA may require temporary works to be put in plae during this time. No ost allowane has been inluded in urrent estimates for suh temporary works as they are unknown. Should removal of the gate be required as part of any neessary remedial works, very areful planning will be needed as there are various site onstraints suh as the limited hard standing available within the existing EA site ompound and also the lose proximity of overhead ables. These issues would need to be addressed prior to any plan being made. The gate is too large to be easily removed to another plae for modifiation. It may be possible to plae it diretly onto a barge for removal via the harbour. Alternatively there is suffiient spae in the adjaent ar park to make modifiations diretly. All of the work envisaged to enable the gate to be apable of performing as a sluie ould be undertaken under these onditions. Note that a tented, saffold struture would be required, to ontain painting ontaminants. Do Ref C0395_006_do Rev A 26 Mehanial Survey of the Vertial - t t t G e : g g : : : : = : e: tt : I=
27 IKG.L/ Kenneth Grubb Assoiates Ltd ; 5. RECOMMENDATIONS 5.1 Gate Struture The existing gate struture itself appears to be in reasonable ondition. In order to ontinue to work effetively, some remedial work should be undertaken to urtail the spread of orrosion on the gate struture. This would involve grit - blasting the gate in the areas affeted by orrosion (namely below the tidal line) and re-oating the gate in aordane with the paint manufaturers instrutions. It may be possible to arry out painting works "in-situ", but it would be preferable to lift the gate out of its slot, lay it down somewhere lose at hand and repair as required. By removing the gate and onduting the repairs off site it will aid the prevention of environmental pollution reated by blasting and painting the gate. The gate is not suitable for sluiing in its urrent form and strutural modifiations would be required along the bottom edge. Suh modifiations would require gate removal. 5.2 Civil Works Interlaes The ivil works interfaes generally appear to be in reasonable ondition. The exeption is the two side gate guide slots. In this area, there is signifiant Joss of non-metalli gate bearing strips from both upstream and downstream faes of the side guides on both sides of the gate. This is probably due to the high frition fores developed when trying to move the gate when subjet to hydrostati loading. And, the poor mounting detail. The onventional design for hydrostatially loaded vertial lift gates utilises rollers to allow the gate to move whilst under load without the detrimental effets of high rubbing frition. This obviously results in lower lifting fores, whih will assist in keeping the operating loads applied to the lifting gear to a minimum. This in turn means that the equipment will probably operate reliably for longer as it is not overstressed. It is not lear why the original design aused the rollers to seize, but for long term reliable operation of this gate the reommendation would be to return to the roller system. In the light of the previous problems the axle, bearing and roller design should be onsidered in more detail prior to reinstatement. Do Ref C0395_006_do Rev A 27 Mehanial Survey of the Vertial
28 !KG.L/ Kenneth Grubb Assoiates Ltd In addition to the above, the bottom setion of eah of the side gate guide slots is suffering from exessive erosion of the onrete and also loss of setion of the ast in steel guide. This would need to be repaired in any event. Should the deision be taken to return to a roller design, it would be desirable to hek the ondition of the existing trak faes within the side gate guide slots and make additional repairs (over and above those identified in the previous paragraph) if neessary to ensure a" smooth and ontinuous running fae for the rollers. The real argument for returning to a roller design would be if the future use of the gate involved signifiant amounts of time ating as a sluie gate where the gate was moved regularly against a head differential. The area of ivil works immediately upstream of the ill ould not be safely aessed. Whilst no obvious ivil issue ould be seen there is some element of unknown here. 5.3 Gate Sealing System The gate sealing system appears to be intat with little damage evident. There is, however, a gap within the seals at both bottom orners of the gate (probably exatly as originally installed) whih is obviously a onern as these points are oinident with water at the maximum head. Water spurting through these gaps will therefore travel at relatively high loal veloities and will ause further damage to the built in parts and onrete surround over a period of time. For these reasons, it is reommended that this gap be filled or repaired as required to effet a ontinuous seal. Vulanised orner seals are desirable. The bottom seal detail requires modifiation if the gate is to at as a sluie. 5.4 Lateral Gate Guiding System The lateral gate guide system appears to be working satisfatorily with no operational problems reported by the EA. The rollers and mounting brakets were found to be in very good ondition and do not require any remedial ation. 5.5 Gate Lifting Gear The gate lifting gear appears to be working satisfatorily with no operational problems reported by the EA. The steel wire ropes appeared to have been hanged reently and were in good order. Do Ref C0395_006_do Rev A 28 Mehanial Survey of the Vertial
29 IKGAL/ Kenneth Grubb Assoiates Ltd The motor and gearbox should, as a m1nrmum, be inspeted and subsequently overhauled to ensure that they remain in good working order. Should the equipment be found to be damaged, or irreparable, then replaement units will be required. Wire rope drum bearings should be inspeted and overhauled or replaed as required. 5.6 Eletrial Equipment The eletrial equipment within the motor winh housing appears to be working satisfatorily with no operational problems reported by the EA. A visual external examination of the eletrial equipment revealed no obvious problems and all equipment appeared to be in good order. However, in order to omply with urrent standards, it is strongly reommended that the eletrial installation should be subjeted to a Periodi Inspetion Report (PIR) under the auspies of BS 7671 to ensure the safety of the equipment installed. NB: No information has been made avahable to the surveyors to suggest that a urrent PIR has been issued for this site. This inspetion should be onduted by a ompetent NICEIC registered eletrial inspetor, who will issue a PIR (that remains valid for three years) to the Environment Ageny. The PIR generally assesses whether the installation is satisfatory or not by omparison to the requirements of BS It also reommends work that needs to be arried out to omply with the standard if the installation is deemed to be unsatisfatory Health and Safety Items of a Health and Safety nature were outside the remit of the survey. However, it was noted that a number of issues are present at the site. These are obvious non omplianes with handrail and aess spae requirements. There are also diffiulties in maintaining muh of the equipment by virtue of diffiult aess. 6. CONCLUSIONS The mehanial and eletrial equipment installed at the vertial lifting gate is reported to be operating effetively and reliably by the loal Environment Ageny operations delivery staff. However, it should be remembered that muh of this equipment has not been hanged sine the original installation approximately 25 years ago. Most gate installations would be expeted to have refurbishment intervals of around 25 years, hene it ould be onsidered that refurbishment at this point was timely. Do Ref C0395_006_do Rev A 29 Mehanial Survey of the Vertial
30 IKGALI Kenneth Grubb Assoiates Ltd On this basis alone, it would be wise to plan for the systemati refurbishment of wearing parts within the equipment to ensure long-term reliable future operation. It is reommended that opies of the any existing reord drawings should be soured prior to any refurbishment work on site. Review of manufaturing data always assists in obtaining a better understanding of the aims of the original design. The orrosion protetion system for many parts of the equipment is now in need of refurbishment. In terms of speifi onlusio'ns made for the equipment surveyed, the following notes are listed as appliable: The gate struture itself will require remedial ation to refurbish the existing orrosion protetion system. The use of sarifiial anodes on the gate to help prevent future degradation should be onsidered. The bottom setion of eah of the two side gate guide slots is in urgent need of repair. This will involve repair to the metalli setion of the ast in guides and the loal onrete as required. The use of sarifiial anodes on the metalli setions of the guide to prevent future degradation should be onsidered. The gap in the bottom omers of the seals should be filled or repaired as required to affet a ontinuous seal. Consideration should be given to the future possible usage of the gate. If the gate operation were to hange to inlude sluiing, then there is a strong ase for the re-instatement of the original roller design as this is the onventional design for a vertial lift sluie gate. It will be possible to ahieve this with an improved design that is not prone to seizure. All elements of the eletrial system assoiated with the operation of the gate should be overed separately by a dediated Periodi Inspetion Report for an Eletrial Installation issued in aordane with BS Requirements for Eletrial Installations by an approved ontrator or onforming body enrolled with the National Inspetion Counil for Eletrial Installation Contrating NICEIC). The bottom setion of the gate will require reonstrution to enable sluiing/souring. Do Ref C0395_006_do Rev A 30 Mehanial Survey of the Vertial I..: e
Rules of Hockey5 including explanations
Rules of Hokey5 inluding explanations Effetive from 1 September 2012 Copyright FIH 2012 The International Hokey Federation Rue du Valentin 61 CH 1004, Lausanne Switzerland Telephone: ++41 21 641 0606 Fax:
More informationRules of Hockey5s including explanations
Rules of Hokey5s inluding explanations Effetive from 1 January 2015 (updated 18 May 2015) Copyright FIH 2015 The International Hokey Federation Rue du Valentin 61 CH 1004, Lausanne Switzerland Telephone:
More informationOperating Instructions
Operating life time Normal expeted servie life (expressed in the number of yles over the full adjustment range) is appr. 1 million for the pressure swith. This may be extended to 2.5 million yles max.
More informationBKTA: 3-way change-over ball valve (T) with male thread, PN 40
BKTA: 3-way hange-over ball valve (T) with male thread, PN 40 ow energy effiieny is improved Effiieny means preise hangeover with minimum leakage Features 3-way hange-over ball valve with T-bore for use
More informationMECHANICAL INTEGRITY ASSESSMENT OF A LARGE HORIZONTAL NGL PRESSURE VESSEL: CASE STUDY
Abstrat MECHANICAL INEGRIY ASSESSMEN OF A LARGE HORIZONAL NGL PRESSURE VESSEL: CASE SUDY A methodology for assessing the strutural integrity of a large horizontal NGL (Natural Gas Liquid) vessel has been
More informationRules of Beach Hockey including explanations
Rules of Beah Hokey inluding explanations Effetive from 1 June 2016 (updated 31 May 2016) Copyright FIH 2016 The International Hokey Federation Rue du Valentin 61 CH 1004, Lausanne Switzerland Telephone:
More informationVKR: 2-way regulating ball valve with female thread, PN 40
Produt data sheet 7.1 56.090 VKR: 2-way regulating ball valve with female thread, PN 40 ow energy effiieny is improved Effiieny means preise ontrol and working with minimum leakage Features 2-way regulating
More informationVaccine Storage and Handling Guidelines
Vaine Storage and Handling Guidelines Table of Contents 2 Introdution 3 Definitions 3 The Importane of the Cold Chain 3 Proteting Ontario s Vaine Supply 4 Maintaining Vaine Poteny and Minimizing Wastage
More informationBUL: 3-way unit valve, PN 16
Produt data sheet 55.009 BU: 3-way unit valve, PN 16 Improving energy effiieny inear mixture and no loss through leakage in the ontrol passage for energy-effiient regulation Features Flat-sealing standard
More informationEMPLOYER SAMPLE PROCEDURES FOR HEAT ILLNESS PREVENTION
EMPLOYER SAMPLE PROCEDURES FOR HEAT ILLNESS PREVENTION FEB 2010 California Employers with any outdoor plaes of employment must omply with the Heat Illness Prevention Standard T8 CCR 3395. These proedures
More informationBKR: 3-way regulating ball valve with female thread, PN 40
Produt data sheet 5.1 56.091 BKR: 3-way regulating ball valve with female thread, PN 40 ow energy effiieny is improved Effiieny means preise ontrol and working with minimum leakage Features 3-way regulating
More informationBKR: 3-way ball valve with female thread, PN 40
Regulating valves, ombined with atuator CV5.60 en Produt Data Sheet BKR015...050 BKR: 3-way ball valve with female thread, PN 40 ow energy effiieny is improved Preision ontrol and working without losses
More informationOperating Instructions Single/Dual Bourdon Tube Pressure Switches Type BS/BT/BX
pproval data for Ex i swithes (BT and BX) pproval: II 1 G D Ex ia IIC T6 Ex ia D 20 T0 Operating Instrutions Single/Dual Bourdon Tube Pressure Swithes Type BS/BT/BX Certifiate no.: ISSeP08TEX016X Permissible
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 17.
The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 17. Please refer to the publiation in its entirety for omplete details on this produt inluding
More informationRoboGolf (aka RoboPutting) Robofest 2016 Game
RooGolf (aka RooPutting) Roofest 201 Game 12-2-2015 V1.1 (Kik-off version. Offiial Version will e availale on Jan 8, 201) 4 3 2 1 a A. Game Synopsis Figure 1. RooGolf Playing Field (Jr. Division) There
More informationGeneral Technical Data and Calculations
18 Bosh Rexroth AG R31EN 232 (26.4) General Produt Desription General Tehnial Data and Calulations Fores and load moments In Rexroth the running traks are arranged at a ompression angle of 45. This results
More informationDistribution Restriction Statement Approved for public release; distribution is unlimited.
CCW-PO egulation No. 1165-2-132 Department of the rmy U.S. rmy Corps of ngineers Washington, DC 20314-1000 Water esoures Poliies and uthorities HZDOUS, TOXC ND DOCTV WST (HTW) GUDNC FO CVL WOKS POJCTS
More informationEffect of Pavement/Shoulder Drop-Offs on Highway Safety
Effet of Pavement/Shoulder Drop-Offs on Highway Safety John C. Glennon Transportation Consulting Engineer Overland Park, Kansas Drop-offs at the pavement/shoulder (or shoulder/roadside) edge have been
More information55.109/1. BUT: Three-way unit valve, PN 16. Sauter Components
55.109/1 UT: Three-way unit valve, PN 16 How energy effiieny is improved Linear mixture and no leak losses in the ontrol passage for energy-effiient regulators. reas of appliation Regulating valve for
More information76.111/1. BUD: Flanged three-way valves, PN 6. Sauter Components
76.111/1 BUD: Flanged three-way valves, PN 6 ow energy effiieny is improved urate ontrol with high reliability. reas of appliation Continuous ontrol of old/hot water and air in losed networks 1) and flow
More informationBKR: 3-way ball valve with female thread, PN 40
Regulating valves, ombined with atuator PDS 56.091 en Produt Data Sheet BKR015...050 BKR: 3-way ball valve with female thread, PN 40 ow energy effiieny is improved Preision ontrol and working without losses
More informationWIND TUNNEL MEASUREMENT AND ASSESSMENT ON THE PEDESTRIAN WIND ENVIRONMENT A CASE STUDY OF JINYING HIGH RISE BUILDING IN TAIPEI, TAIWAN
WIND TNNEL MEASREMENT AND ASSESSMENT ON THE PEDESTRIAN WIND ENVIRONMENT A CASE STDY OF JINYING HIGH RISE BILDING IN TAIPEI, TAIWAN Bao-Shi Shiau 1 and Ben-Jue Tsai 2 ABSTRACT In this paper, wind tunnel
More informationHarbour Dues (Pleasure Vessels, House Boats, Large Commercial Yachts and Tall Ships) Regulations 2013
Harbour Dues (Pleasure Vessels, House Boats, Large Commerial Yahts and Tall Ships) Regulations 2013 Index HARBOUR DUES (PLEASURE VESSELS, HOUSE BOATS, LARGE COMMERCIAL YACHTS AND TALL SHIPS) REGULATIONS
More informationHeadwater elevation water surface elevation just. Tailwater elevation water surface elevation just
: Culvert Hydraulis Bob Pitt University of Alabama and Sirley Clark Penn State - Harrisburg Culvert Flow Culvert Systems Culverts typially used in roadway rossings and detention pond outlets. Headwater
More informationRESPIRATORY PROTECTIVE EQUIPMENT
RESPIRATORY PROTECTIVE EQUIPMENT SETTING Correspondene to: Dr R M Howie, 12 Morningside Close, Edinburgh EH10 4DB, UK; robin.howie@ btlik.om T RMHowie Oup Environ Med 2005; 62:423 428. doi: 10.1136/oem.2002.004424
More informationSlow gas expansion in saturated natural porous media by gas injection and partitioning with nonaqueous
MMaster University From the SeletedWorks of Sarah E Dikson 2008 Slow gas expansion in saturated natural porous media by gas injetion and partitioning with nonaqueous phase liquids Kevin G Mumford, Queen's
More informationMeasurement System of Bubbly Flow Using Ultrasonic Velocity Profile Monitor and Video Data Processing Unit, (II)
Journal of Nulear Siene and Tehnology SSN: 22-3131 (Print) 1881-1248 (Online) Journal homepage: http://www.tandfonline.om/loi/tnst2 Measurement System of Bubbly Flow Using Ultrasoni Veloity Profile Monitor
More informationSUPPLEMENTARY REPORT
TO: RGULATORY SRVICS COMMITT TABLD AT 2 5 NOV 214 MTING FROM: TH DIRCTOR OF NVIRONMNTAL AND PLANNING SRVICS MTING DAT: TUSDAY 25 NOVMBR 214 SUPPLMNTARY RPORT I SPA POOL XMPTION RQUST FOR 228 FILLUL STRT,
More informationTrigonometry. terminal ray
terminal ray y Trigonometry Trigonometry is the study of triangles the relationship etween their sides and angles. Oddly enough our study of triangles egins with a irle. r 1 θ osθ P(x,y) s rθ sinθ x initial
More informationSauter Components
55.009/1 U: Unit threeway valve, PN 1 How energy effiieny is improved inear mixing and no losses through leakage for energyeffiient ontrol. reas of appliation Control valve for ontrolling heating zones,
More informationComparison of the South Dakota Road Profiler with Other Rut Measurement Methods
TRANSPORTATION RESEARCH RECORD 1311 Comparison of the South Dakota Road Profiler ith Other Rut Measurement Methods ]AMES B. DuBosE During the fall of 1989, the Illinois Department of Transportation ompleted
More informationOwners Manual Models 4430BF3, 4430BF2 & 4430BF1 Floor Mounted Tri-Level Bottle Filling Tubular Fountain
Owners Manual Models 4430F3, 4430F2 & 4430F1 Floor Mounted Tri-Level ottle Filling Tubular Fountain MODEL 4430F1L MODEL 4430F2UM INSTALLER 4430F Fountains are among the easiest to install Fountains on
More informationHURRICANE SANDY LIMITED REEVALUATION REPORT UNION BEACH, NEW JERSEY DRAFT ENGINEERING APPENDIX SUB APPENDIX E OVERTOPPING & FAILURE ANALYSIS
HURRICANE SANDY LIMITED REEVALUATION REPORT UNION BEACH, NEW JERSEY DRAFT ENGINEERING APPENDIX SUB APPENDIX E OVERTOPPING & FAILURE ANALYSIS Revised 18 Feb 2015 1 OVERTOPPING & FAILURE ANALYSIS 1.0 Introdution
More informationAnalysis of a Twin Screw Expander for ORC Systems using Computational Fluid Dynamics with a Real Gas Model
Purdue University Purdue e-pubs International Compressor Engineering Conferene Shool of Mehanial Engineering 2014 Analysis of a Twin Srew Expander for ORC Systems using Computational Fluid Dynamis with
More informationPhysics 20 Lesson 20 Uniform Circular Motion Vertical Plane
Physis 0 Lesson 0 Uniform Cirular Motion Vertial Plane I. Vertial uniform irular motion Refer to Pearson pages 60 to 64 for a disussion about irular motion. So far we hae onsidered uniform irular motion
More informationTO THE POINT WITHOUT A PINCH: THE RIGHT WAY TO GUARD Safety Guarding Presentation. Presented by: Chris Allen
TO THE POINT WITHOUT A PINCH: THE RIGHT WAY TO GUARD Safety Guarding Presentation Presented by: Chris Allen SAFETY GUARDING PRESENTATION OVERVIEW 1 Let s Get Eduated! 2 Spotting the Problems 3 Let s Remedy
More informationINSTRUCTION HANDBOOK OM2
INSTRUCTION HANDBOOK OM2 Pakaging mahine for sanitary napkins Mahine-No.: 2622668.11.01 Year of onstrution: 2007 Version 1 dated 2007-12-03 Keep for further referene! Manufaturer addresses / Customer servie
More informationGUARDING OF FLOOR-TO-FLOOR WOOL PRESSES
GUARDING OF FLOOR-TO-FLOOR WOOL PRESSES 1 NOTE The technical information in this book was current at the time of printing in 1984. While the guarding principles are still valid, the information does not
More informationi e SD No.2016/0057 HARBOUR DUES (FISHING VESSELS, WORK BOATS AND CONSTRUCTION BARGES) REGULATIONS 2016
i e SD No.2016/0057 HARBOUR DUES (FISHING VESSELS, WORK BOATS AND CONSTRUCTION BARGES) REGULATIONS 2016 Harbour Dues (Fishing Vessels, Work Boats and Constrution Index HARBOUR DUES (FISHING VESSELS, WORK
More informationWind energy potential of Ban village
Available online at www.pelagiaresearhlibrary.om Advanes in Applied Siene Researh, 2013, 4(3):220-225 ISSN: 0976-8610 CODEN (USA): AASRFC Wind energy potential of Ban village Maren. I. Borok 1, Gyang Y.
More informationModelling the decrease in wave height over the shoreface due to slope-induced changes in bottom friction.
Chapter : Modelling the derease in wave height over the shorefae due to slope-indued hanges in bottom frition. Abstrat Wave height-redution on the shorefae is partly indued by frition at the bottom. The
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.
The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 16. Please refer to the publiation in its entirety for omplete details on this produt inluding
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.1.
The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 16.1. Please refer to the publiation in its entirety for omplete details on this produt inluding
More informationAPPENDICES STRANDJACK WEDGES Friction coefficients, micro slip and handling
APPENDICES STRANDJACK WEDGES Frition oeffiients, miro slip and handling Report nr. DCT 2005-78 By: H.G.M.R. van Hoof Idnr : 501326 20 November, 2005 Researh strand jak wedges Appendies By H.G.M.R. van
More informationStabilized Fly Ash Base
8 TRANSPORTATION RESEARCH RECORD 144 Performane Evaluation of a Cement Stabilied Fly Ash Base. H. GRAY, E. TONS, AND T. R. THIRUVENGADAM The performane of a ompated, aggregate-free, ement-stabilied fly
More informationME 425: AERODYNAMICS
ME 45: AERODYNAMICS - Dr. A.B.M. Toufique Hasan Professor Department of Mehanial Engineering, BUET Leture # 3 4 Otober, 6 http://teaher.buet.a.bd/toufiquehasan/ourses.php ME45: Aerodynamis Airfoil Nomenlature
More informationALL TERRAIN CRANE AR-1200M-1
ALL TERRAIN RANE AR-12M JAPANESE SPEIFIATIONS ARRIER MODEL FAUN RTF12-5 SPE. NO. AR-12M-1 AR ontrol No. JA-3-279 - Return to INDEX AR-12M RANE SPEIFIATIONS RANE APAITY 12.2m Boom 12,kg at 2.7m (17part-line)
More informationPeel Viking Longboat Races Order 2012 PEEL VIKING LONGBOAT RACES ORDER 2012
Peel Viking Longboat Raes Order 2012 Index PEEL VIKING LONGBOAT RACES ORDER 2012 Index Artile Page 1 Title... 3 2 Commenement... 3 3 Interpretation... 3 4 Authorisation of use of the longboat area for
More informationTHE RILEY BULDING 219 W. FOURTH STREET, AUSTIN, TX 78701
THE RILEY BULDING SWIMMING POOL AND SPA SHOP DRAWINGS JOB SITE ATION LEGEND LINE TYPES: ELETRIAL - BOND WIRE ELETRIAL ONDUIT POOL WALL (SHOTRETE) STEEL REINFOREMENT (REBAR) POOL SUTION LINES POOL RETURN
More informationBEACH KORFBALL RULES DRAFT RULES NOVEMBER
BEACH KORFBALL RULES DRAFT RULES NOVEMBER 2013 BEACH KORFBALL PLAYING RULES INTRODUCTION Beah korfall is an attrative, highly strenuous and ompetitive korfall variant, espeially when played 3-3 at the
More informationInstant Garage 16' x 12' 3" x 8' 6"
Instant Garage 16' x 12' 3" x 8' 6" Assembly Instructions Door Height 1.8M A B DESRIPTION MODEL # A B IG 1216 Instant Garage 4.9 x 3.7 x 2.6 M - Grey 3503500 16' x 12' 3" x 8' 6" REOMMENDED TOOLS OR Please
More informationJack Blanton, Julie Amft, Peter Verity. Georgia Marine Science Center University System of Georgia Skidaway Island, Georgia
Tehnial Report Series Number94-1 TheMay93 North Edisto Ingress Experiment (NED1) Jak Blanton, Julie Amft, Peter Verity 31 31 Georgia Marine Siene Center University System of Georgia Skidaway Island, Georgia
More informationIV. Environmental Impact Analysis K. Traffic, Access, and Parking
IV. Environmental Impat Analysis K. Traffi, Aess, and Parking 1. Introdution This setion analyzes the potential projet impats assoiated with traffi, aess, and parking. The analyses in this setion are based
More informationCONTROLLED MARINE AREA (SEISMIC SURVEY WORKS) REGULATIONS 2016
Controlled Marine Area (Seismi Survey Works) Regulations 2016 Statutory Doument No. 2016/0362 Marine Infrastruture Management At 2016 CONTROLLED MARINE AREA (SEISMIC SURVEY WORKS) REGULATIONS 2016 Laid
More informationTranslation of the original Operating Instructions for HKS rubber compensators
Because of their flexible elements and mechanisms, HKS rubber compensators are susceptible to damage of all types and adverse loads in operation. For reliable operation of a compensator and, thus, the
More informationm. ANmYSIS OF RESULTS
Aordingly, the U. S. Government retains a nonexlusive, royaltyfree liense to publish Effets of Vertial Aperture on Beam Lifetime at the Advaned Photon Soure ( A P S ) Storage Ring* Hana M. Bizek Advaned
More informationTECH TIPS: ROPE DEFECTS
Hoist Ropes: Why must they be inspected? A hoist rope is not made to last forever. This is a useful fact, as the kinds of wear that appear on a rope can indicate areas of problems within an installation
More informationStick insect locomotion in a complex environment: climbing over large gaps
The Journal of Experimental Biology 7, 7-86 Published by The Company of Biologists doi:./jeb.888 7 Stik inset loomotion in a omplex environment: limbing over large gaps Bettina Blaesing* and Holk Cruse
More informationTHEORETICAL BACKGROUND OF "LEAK-BEFORE-BREAK" AS A CONCEPT IN PRESSURE VESSELS DESIGN. Šárka Pacholková a Howard Taylor b
METAL 00 14. 16. 5. 00, Hrade nad Moravií THEORETICAL BACGROUND OF "LEA-BEFORE-BREA" AS A CONCEPT IN PRESSURE VESSELS DESIGN Šárka Paholková a Howard Taylor b a VÚ- NOVÁ HUŤ, a.s., Vratimovská 689, 707
More informationmanual h/p/cosmos discovery 4.0 Instruction- & Service manual Manufacturer h/p/cosmos sports & medical gmbh h/p/cosmos discovery 4.
manual h/p/osmos disovery 4.0 Instrution- & Servie manual Manufaturer h/p/osmos disovery 4.0 h/p/osmos sports & medial gmbh Firmware version 3.01.3 Am Sportplatz 8 DE 83365 ussdorf-traunstein Germany phone
More informationIncident report of accidental drowning Saturday, August 11 Tutukaka, Northland, Nz
Inident report of aidental drowning Saturday, August 11 Tutukaka, Northland, Nz John Park 1967-2018 Author: Tim Eves John s Paddle Launh 1444hrs John launhed from Te wai Parore Bay and headed soueast Turn
More information11/ This paper not to be cited without prior reference to the author. I'
/ 11/ This paper not to be ited without prior referene to the author. I' International Counil for the Exploration of the Sea C. M. 197 2/H : 3 0 Pelagi Fish (N) Committee THE EFFECTS OF REGULATIONS OF
More informationCLIENT NAME: LOCATION: CALM BUOY INSPECTION:
INSPECTOR REVIEWED INSPECTION OF CALM BUOY OVERALL PHOTO REVISION DESCRIPTION: Preliminary / Final Page: 1 TABLE OF CONTENT 1. MANAGEMENT SUMMARY... 3 1.1. SCOPE OF WORK:... 3 1.2. CORRECTIVE ACTIONS...
More informationStatistical Mechanics of the Frequency Modulation of Sea Waves
Statistial Mehanis of the Frequeny Modulation of Sea Waves Hiroshi Tomita and Takafumi Kawamura Ship Researh Institute, Shinkawa 6-8-, Mitaka, Tokyo 8-, Japan tomita@srimot.go.jp Abstrat. The longtime
More informationAbsorption Equilibrium and Kinetics for Ethylene-Ethane Separation with a Novel Solvent Introduction Experimental
Absorption Equilibrium and Kinetis for Ethylene-Ethane Separation with a Novel Solvent Travis A. Reine, R. Brue Eldridge 2004 The University of Texas at Austin Prepared for Presentation at 2004 Annual
More informationOverspeed governors (113 OG Моment 250 MR, 114 OG Moment 250 A3, 115 OG Moment 250 MRL, 119 OG Moment 250 MRL/1)
Overspeed governors (113 OG Моment 250 MR, 114 OG Moment 250 A3, 115 OG Moment 250 MRL, 119 OG Moment 250 MRL/1) Instructions for installation and operation 113 OG Моment 250 MR 115 OG Moment 250 MRL Overspeed
More informationExperimental Study on the Limits of Flow Regimes for Different Configurations of Stepped Spillway
Civil and Environmental Researh Experimental Study on the Limits of Flow Regimes for Different Configurations of Stepped Spillway Najm Obaid Salim Alghazali 1*, Salam M. Jasim 2 1. Asst. Prof. Dotor, Civil
More informationImplementing Actuated Signal-Controlled Intersection Capacity Analysis with Pedestrians
Ipleenting Atuated Signal-Controlled Intersetion Capaity Analysis with Pedestrians DingXin Cheng, Zong Z. Tian, and Honghao Liu For an atuated signalized intersetion, pedestrian alls are likely to affet
More informationANSWERS TO COMMONLY ASKED QUESTIONS
NSWERS TO COMMONLY SKE QUESTIONS Should we onentrate on passing or dribbling at Uw6? The game at the U-6 level is haraterized by awkward, rudimentary attempts at dribbling mixed with enthusiasti kiking
More informationdolphins National Aquarium building protected ocean home for retired Their Own Space ln The Ocean
National quarium building proteted oean home for retired dolphins y ssoiated Press, adapted by Newsela staff 06.22.16 MlMl, Fla. Eight dolphins will soon be retired from the National - quarium in altimore,
More informationEffectiveness of a law to reduce alcohol-impaired driving in Japan
1 Takemi Program, Department of International Health, Harvard Shool of Publi Health, Boston, MA, USA; 2 Department of Emergeny Mediine, St Mary s Hospital, Kurume, Japan; 3 Division of Pharmaoepidemiology
More informationMODEL FOR PREDICTING BATHYMETRIC AND GRAIN SIZE CHANGES BASED ON BAGNOLD S CONCEPT AND EQUILIBRIUM SLOPE CORRESPONDING TO GRAIN SIZE COMPOSITION
MODEL FOR PREDICTING BATHYMETRIC AND GRAIN SIZE CHANGES BASED ON BAGNOLD S CONCEPT AND EQUILIBRIUM SLOPE CORRESPONDING TO GRAIN SIZE COMPOSITION Yasuhito Noshi, Takaaki Uda 2, Masumi Serizawa 3, Takayuki
More informationFull scale measurements of pressure equalization on air permeable façade elements
Full sale measurements of pressure equalization on air permeable façade elements Carine van Bentum, Chris Geurts Department of Strutural Dynamis, TNO, Delft, The Netherlands email: arine.vanbentum@tno.nl,
More informationME 425: Aerodynamics
ME 45: Aeroynamis Dr. A.B.M. Toufique Hasan Professor Department of Mehanial Engineering Banglaesh University of Engineering & Tehnology BUET, Dhaka Leture-6 /5/8 teaher.buet.a.b/toufiquehasan/ toufiquehasan@me.buet.a.b
More informationImpact of Using Freeway Shoulders as Travel Lanes on Fuel Consumption
Transportation Researh Reord 901 l Impat of Using reeway Shoulders as Travel Lanes on uel Consumption WILLIM R. MCSLN general proedure, based on data derived from the merian ssoiation of State Highway
More informationAN EXPERIMENTAL STUDY ON NONLINEAR WAVE DYNAMICS: ROUGE WAVE GENERATION AND WAVE BLOCKING
AN EXPERIMENTAL STUDY ON NONLINEAR WAVE DYNAMICS: ROUGE WAVE GENERATION AND WAVE BLOCKING Wen-Yang Hsu, Igor Shugan, Wen-Son Chiang, Ray-Yeng Yang, Hwung-Hweng Hwung 2, Sergey Kuznetsov 3 and Yana Saprykina
More informationAllspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)
Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk SOFT LINE CUTTER SL55 PRODUCT CODE No. 980504 INSTRUCTIONS FOR INSTALLATION,
More informationSpecialists in HTM Medical Gas Pipeline Equipment AVSU/Module Operating and Maintenance Instructions
The Area Value Service Units and Module format (AVSU) provide a local gas isolation facility for use during normal installation and maintenance or in the event of an emergency. They are built in accordance
More informationEffect of the concentration distribution on the gaseous deflagration propagation in the case of hydrogen/oxygen mixture
Effet of the onentration distribution on the gaseous deflagration propagation in the ase of hydrogen/oxygen mixture Isabelle Sohet, Philippe Gillard, Florent Guelon To ite this version: Isabelle Sohet,
More informationOriginal Application Packet
MARN WOODS Attahment A: Original Appliation Paket City of Oak Harbor Development Servies Department 865 SE Barrington Drive, Oak Harbor, WA 98277 http:/lwww.oakharbor.org Phone: 36-279-451 Fax: 36-279-4519
More informationOperating instruction
Operating instruction MV, XV, HG, HP, RKO, D2G, TV, BV, WB & SLV 1 Introduction 2 2 Stafsjö s knife gate valves 2 3 Technical information 2 3.1 Pressure test 2 3.2 Labelling 2 4 Storage 3 5 Transportation
More informationHYDRAULIC MOBILE LIFTING TABLE
HYDRAULIC MOBILE LIFTING TABLE MODEL NO: HTL300 & HTL500 PART NO: 7610148 & 76210152 OPERATION & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS GC1116 INTRODUCTION Thank you for purchasing this CLARKE
More informationCongruence Axioms. Data Required for Solving Oblique Triangles. 1 of 8 8/6/ THE LAW OF SINES
1 of 8 8/6/2004 8.1 THE LAW OF SINES 8.1 THE LAW OF SINES Congrueny and Olique Triangles Derivation of the Law of Sines Appliations Amiguous Case Area of a Triangle Until now, our work with triangles has
More informationManual winch MANISTOR 100 and 200
Manual wall winch Manual winch MANISTOR 100 and 200 Instruction manual UK 173-192.10-3 PRODUCT DEVELOPED AND MANUFACTURED ACCORDING TO NF EN 13157 STANDARD REGISTERED DESIGN To ensure the constant improvement
More informationEngineering Data Sheet
Page 1 of 6 CE MARKING AND THE PRESSURE EQUIPMENT DIRECTIVE 97/23/EC Valves must be installed into a well designed system and it is recommended that the system be inspected in accordance with the appropriate
More informationThe Optimal Control of a Periodic Adsorber:
., Natural Convetion in nonnewtonian Fluids Heated from Below, paper presented at First Paifi Chem. Eng. Congr. (1972). Samuels, M. R., Stability of a Fluid in a Long Horizontal, Retangular Cylinder Heated
More informationFREE-SURFACE AND SEEPAGE BUBBLY FLOWS ON A GABION STEPPED SPILLWAY WEIR: EXPERIMENTAL OBSERVATIONS
E-proeedings of the 36 th IAHR World Congress FREE-SURFACE AND SEEPAGE BUBBLY FLOWS ON A GABION STEPPED SPILLWAY WEIR: EXPERIMENTAL OBSERATIONS GANGFU ZHANG (1), & HUBERT CHANSON (2) (1) The University
More informationHORNE T109A/306A/307A THERMOSTATIC SHOWER VALVE FOR SURFACE MOUNTING WITH TIMED FLOW CONTROL INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
Horne Engineering Ltd PO Box 7, Rankine Street Johnstone, PA5 8BD Tel: +44 (0)1505 321455 Fax: +44 (0)1505 336287 Email: Technical@horne.co.uk Web: www.horne.co.uk HORNE T109A/306A/307A THERMOSTATI SHOWER
More informationLIQUIP DRYBREAK COUPLER. API800 Series MAINTENANCE INSTRUCTIONS
LIQUIP DRYBREAK COUPLER API800 Series MAINTENANCE INSTRUCTIONS API LOADING COUPLER TO API RP1004 June 2015 Issue: F M:\Product-Info\API8xx\6-Service-Maintenance\API800 MAINTENANCE INSTRUCTIONS 40183.doc
More informationarxiv:cond-mat/ v1 [cond-mat.stat-mech] 28 Nov 1997
Coeffiient of normal restitution of visous partiles and ooling arxiv:ond-mat/9733v [ond-mat.stat-meh] 8 Nov 997 rate of granular gases Thomas Shwager and Thorsten Pöshel Humboldt-Universität zu Berlin,
More informationDriver Decision Making at Traffic Signals
TRANSPORTATION RESEARCH RECORD 1172 93 Driver Deision Making at Traffi Signals RICHARD VAN DER HORST The driving task at signalized road intersetions is simplified substantially over that at nonsignalized
More informationApollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual
I854000.D Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual Introduction This manual presents guidelines for the Installation, Operation and
More informationCAISSON SHAFT SYSTEM
CAISSON SHAFT SYSTEM Installation Guide INSTALLATION GUIDE FOR DN2000 TO DN3660 UNITS PLATE JOINTING SYSTEM This guide is to be used for the Installation of CPM Group Ltd caisson shaft units which use
More informationEffective Date: July 2018 Void After: July Product: Plumbing Fixture Fittings File No. 4155
IAPMO Researh and Testing, In. is a produt ertifiation body whih tests and inspets samples taken from the supplier's stok or from the market or a ombination of both to verify ompliane to the requirements
More informationRB70 Automatic Diluent Valve Maintenance Manual. Version 1.1 November 2006 Written by Tino de Rijk. Page 1 of 23
RB70 Automatic Diluent Valve Maintenance Manual Version 1.1 November 2006 Written by Tino de Rijk Page 1 of 23 Table of Contents 1. Introduction... 3 2. ADV diagram and parts list (Pre June 2006)... 4
More informationpdf WATER RETICULATION STANDARD VENTILATION LOUVRE BOXES SINGLE AND DOUBLE DUCT SYSTEMS
Drawing Index Name Doc.No Document Description 2001979.061H.pdf 2001979.061 WATER RETICULATION STANDARD SCOUR VALVE CHAMBER WITH CIRCULAR COVER AND FRAME SHEET NO1 OF 2 2001979.062F.pdf 2001979.062 WATER
More informationPF30 Inspection & Maintenance Manual
PF30 Inspection & Maintenance Manual Version 1.4 (September 2011) 1 Contents 1. Warning!!!!!!!!!! 3 2. Terminology! Figure 1: POWERFAN PF30 and Drope!!!! 4! Figure 2: POWERFAN PF30 with belt guard retracted!!
More informationCONTENTS ORIGINAL MANUAL Page General warning 3 Technical data 3. Description of equipment. Rigging arrangements 3. Installing the wire rope 5. Releas
0086086.03-0/95 operating and maintenance instructions equipment in accordance with CE directives tirfor lifting and pulling machines models TU : TU-8 TU-6 TU-3 T-500D : T-508D T-56D T-53D CONTENTS ORIGINAL
More informationCFD Simulations of Contaminant Transport between two Breathing Persons Bjørn, Erik; Nielsen, Peter Vilhelm
Aalborg Universitet CFD Simulations of Contaminant Transport between two Breathing Persons Bjørn, Erik; Nielsen, Peter Vilhelm Publiation date: 1998 Doument Version Publisher's PDF, also known as Version
More informationSERIES 2 RAMP OWNER S MANUAL TOOLS REQUIRED: BEFORE YOU BEGIN... Read and understand these instructions before beginning a ramp setup.
SERIES 2 RAMP OWNER S MANUAL BEFORE YOU BEGIN... Read and understand these instructions before beginning a ramp setup. Use caution and care for your back when lifting, pushing, pulling, folding or unfolding
More information