1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing.

Size: px
Start display at page:

Download "1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing."

Transcription

1 EVALUATION OF FRAMED WALL CONSTRUCTION SECTIONS UTILIZING SOPREMA S SOPRASEAL STICK 1100T SELF-ADHERED AIR BARRIER SYSTEM IN ACCORDANCE WITH CAN/ULC S Report to: Soprema 1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9 Attention: Mr. Marc-Etienne Mathieu,ing. Telephone: (819) ext.3327 Cell: (819) memathieu@soprema.ca Report No.: M Pages, 6 Appendices Proposal No.: Date: July 25, 2015

2 Evaluation of Soprema SOPRASEAL STICK 1100T Table of Contents TABLE OF CONTENTS Page No. 1.0 INTRODUCTION PROCEDURE Test-Wall Construction Air Leakage Testing Wind Pressure Conditioning Deflection Test Dates General Test Specimen Setup Photographs RESULTS Detailed Exova Specimen No M Detailed Exova Specimen No M CONCLUSION REPORT REVISION SUMMARY 19 APPENDICES APPENDIX A: APPENDIX B: APPENDIX C: APPENDIX D: APPENDIX E: APPENDIX F: Logarithmic Air Leakage Graphs (Exova Specimen No.: M0146-1) Logarithmic Air Leakage Graphs (Exova Specimen No.: M0146-2) Application Photographs (Exova Specimen No.: M0146-1) Application Photographs (Exova Specimen No.: M0146-2) Air Barrier Application Notes Wall Assembly Detail Drawings

3 Page 1 of INTRODUCTION At the request of Soprema, Exova was retained to evaluate various wall section configurations using the Soprema Sopraseal Stick 1100T self-adhered membrane applied to exterior sheathing utilizing a framed construction configuration. The testing was conducted in accordance with CAN/ULC S referencing ASTM E as outlined in Proposal Number: Upon receipt, the specimens were assigned the following Exova Specimen Numbers: Client Specimen Description Exova Specimen No. Primary Air Barrier Material: Soprema Sopraseal Stick 1100T M Wall Specimen Description Opaque Wall Frame Construction: 3-5/8" Steel Studs, 18 ga. Installed 16" (406 mm) O/C Exterior Sheathing: Georgia Pacific 1/2" (13 mm) thick DensGlass Gold Exterior Sheathing Referencing ASTM E , Specimen 1 - Section A , Client Specimen Description Exova Specimen No. Primary Air Barrier Material: Soprema Sopraseal Stick 1100T M Wall Specimen Description Continuity at Penetrations Wall Frame Construction: 3-5/8" Steel Studs, 18 ga. Installed 16" (406 mm) O/C Exterior Sheathing: Georgia Pacific 1/2" (13 mm) thick DensGlass Gold Exterior Sheathing Referencing ASTM E , Specimen Section A A Brick Ties: Block-LOK 607 Note: Photographs documenting the air barrier installation for each respective wall assembly are located in Appendices C & D. Detail drawings for both wall sections (Exova Specimens M & 2) are located in Appendix E. 2.0 PROCEDURE Test Method Section (a), ASTM E , Section 9.1 Section Section Section (a), ASTM E , Section 9.1 Note: SI Units are the primary units of measure. Test Description Air Leakage Wind Pressure Loading Deflection Post Conditioning Air Permeance 2.1 Test Wall Construction Specimens M & 2 (Opaque & Penetrated Foundation Interface Wall Sections): The 10' x 10' test wall sections were constructed using commercially purchased steel studs (3-5/8" Steel Studs, 18 ga / 16 O/C. deep,) and built as per the construction details located in Figures A1.1 & A1.2 + A1.3 of ASTM E on June 17 18, 2015 The air barrier system was applied on the exterior side of the wall system with Soprema Sopraseal Stick 1100T at Exova s Systems Laboratory by representatives from Soprema on June 22-23, The air barrier application was also witnessed by representatives of Exova s Building Systems Laboratory staff.

4 Page 2 of Air Leakage Testing Testing was conducted in both exfiltration (-) and infiltration (+) cases. Upon mounting the wall system on the wall test apparatus, a sheet of 6 mil poly was draped over and sealed against the exterior face of the specimen s test frame utilizing sheathing tape and double-sided gasket material for extraneous air leakage measurement purposes. Using the procedure outlined in ASTM E , Section 9.1.2, the wall section was subjected to positive and negative pressures of: 25, 50, 75, 100, 150, 250, 300 Pa. Upon completion of the extraneous air leakage, the 6 mil poly was carefully removed and the actual specimen air leakage testing was conducted. As per ASTM E , Section logarithmic graphs for each air leakage test (infiltration/exfiltration) displaying the linear regression (r 2 > 0.95) values are located in Appendices A & B. The air leakage testing as described above was also conducted upon completion of the Wind Pressure Loading & Deflection portion as outlined in the standard. 2.3 Wind Pressure Conditioning The following wind pressure loading schedule was applied to the wall system using the loads prescribed for a sustained 1 in 50 hourly wind pressure difference of 650 Pa at a building height 12 meters above grade: Sustained Loads: Deformation Test (Sustained Pressure, P 1) The wall system was subject to increasing pressure in increasing stages for a minimum period of 10 seconds at each stage, up to a maximum pressure of 650 Pa which was maintained for 1-hour. Deformation Test (Sustained Pressure, P 1) The wall system was subjected to increasing pressure in increasing stages for a minimum period of 10 seconds at each stage, up to a maximum pressure of -650 Pa which was maintained for 1-hour. The deformation measurements were taken continuously during pressurisation. Note: As per CAN/ULC S742-11, Section , P1 air pressure differences are to be applied in 100 Pa increments. However, as testing was also conducted in conjunction with ASTM E , the loading increments used were 160 Pa stepping followed by the 650 Pa pressure hold (which exceeds the standard requirement of 550 Pa to match ASTM E ). This is considered a more severe stepping increment and is representative of the procedure outlined in CAN 07272, in which the CAN/ULC S742 standard is based. Cyclic Loads P 2 & P 2: Repeated Positive and Negative Pressure Test (Cyclic Pressure, P 2 & P 2) The wall system was subject to 2,000 cycles of pressure. The first 1000 cycles were from 0 to +950 Pa and was followed by 1,000 cycles from 0 to 950 Pa. The deformation measurements were taken continuously during cycling.

5 Page 3 of 19 Gust Loads, P 3 & P 3: 2.4 Deflection The wall system was then subjected to a Gust Wind pressure of Pa followed by a repeat Gust Wind pressure of 1410 Pa. These pressures were held for a minimum of 3 seconds. The maximum deformation readings were taken after each gust pressure. Upon completing the wind pressure conditioning sub-section, the wall specimens were subjected to wind pressure loading of ±1440 Pa for 10 seconds (exceeding the P2 and P'2 values as per CAN/ULC S742-11, Section 6.3.4) to match ASTM E , Table 2 Q10 > 0.40 kpa / 1440 Pa values. After completing the deflection loads above, air leakage testing was again conducted at ambient conditions at an exterior temperature of -20 C and the interior temperature of 20 C as per CAN/ULC S742-11, Section in both exfiltration (-) and infiltration (+) cases. 2.5 Test Dates Specimen Number Test Criteria Testing Date M Air Leakage (Exfiltration)-Prior June 25, 2015 Air Leakage (Infiltration)-Prior June 25, 2015 Wind Load Conditioning June 26, 2015 Wind Load Durability June 26, 2015 Air Leakage (Infiltration) Ambient June 27, 2015 Air Leakage (Exfiltration) Ambient June 27, 2015 Air Leakage (Infiltration) Cold June 29, 2015 Air Leakage (Exfiltration) Cold June 29, 2015 Specimen Number Test Criteria Testing Date M Air Leakage (Exfiltration)-Prior June 30, 2015 Air Leakage (Infiltration)-Prior June 30, 2015 Wind Load Conditioning June 30, 2015 Wind Load Durability June 30, 2015 Air Leakage (Infiltration) Ambient July 1, 2015 Air Leakage (Exfiltration) Ambient July 1, 2015 Air Leakage (Infiltration) Cold July 2, 2015 Air Leakage (Exfiltration) Cold July 2, 2015

6 Page 4 of General Test Specimen Setup Photographs Figure 1 Hygrothermal Chamber Prior to Specimen Installation Displaying Location of Air Seal Figure 2 General Specimen Installation between Warm Side GHB and Hygrothermal Chamber

7 Page 5 of RESULTS Table 1 - Summarized Air Leakage Results at 75 Pa in Accordance with CAN/ULC S742-11, Section (a), referencing ASTM E Section 9.1, Air Leakage Testing Optional Ambient Cold Exova Specimen No.: Airflow Direction Calculated Air Leakage at 75 Pa Prior to Wind Pressure Conditioning (L/s m 2 ) Calculated Air Leakage at 75 Pa After Wind Pressure Conditioning (L/s m 2 ) Calculated Air Leakage at 75 Pa After Wind Pressure Conditioning (L/s m 2 ) Air Leakage Rate Classification (2) M (Opaque Wall) M (Penetrated Wall in Combination with a Foundation Interface) (1) A1 Notes: '-' denotes exfiltration airflow direction (simulated negative wind loading) '+' denotes infiltration airflow direction (simulated positive wind loading) (1) Highest measured air leakage rate at 75 Pa (2) As per CAN/ULC S742-11, an air barrier in compliance with this standard shall be classified as one of the types listed in clause to clause according to its reference air leakage rate: A1 The reference air leakage rate shall not exceed 0.05 L/(s m 2 ) at a pressure difference of 75 Pa A2 The reference air leakage rate shall not exceed 0.10 L/(s m 2 ) at a pressure difference of 75 Pa A3 The reference air leakage rate shall not exceed 0.15 L/(s m 2 ) at a pressure difference of 75 Pa A4 The reference air leakage rate shall not exceed 0.20 L/(s m 2 ) at a pressure difference of 75 Pa A5 The reference air leakage rate shall not exceed 0.50 L/(s m 2 ) at a pressure difference of 75 Pa. The reference air leakage rate is the highest air leakage rate of those recorded among all specimens when tested in accordance with CAN/ULC S742-11, Section 6.

8 Page 6 of DETAILED EXOVA SPECIMEN NO M RESULTS Table 2 - Summarized Air Leakage Results in Accordance with ASTM E Section 9.1, Air Leakage Testing Exova Specimen No.: M (Exfiltration '-') Optional Ambient Cold (-20 C) Differential Pressure (Pa) Calculated Air Leakage Prior to Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning (L/s m 2 ) (L/s m 2 ) (L/s m 2 ) Table 3 - Summarized Air Leakage Results in Accordance with ASTM E Section 9.1, Air Leakage Testing Exova Specimen No.: M (Infiltration '+') Optional Ambient Cold (-20 C) Differential Pressure (Pa) Calculated Air Leakage Prior to Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning (L/s m 2 ) (L/s m 2 ) (L/s m 2 ) * As per ASTM E , logarithmic graphs for each air leakage test (infiltration/exfiltration) displaying the linear regression (r 2 ) value are located in Appendix A.

9 Page 7 of 19 Figure 3 Exova Specimen No.: M Exfiltration Air Leakage Prior to Wind Conditioning Figure 4 Exova Specimen No.: M Infiltration Air Leakage Prior to Wind Conditioning

10 Page 8 of 19 Figure 5 Exova Specimen No.: M Exfiltration Air Leakage After Wind Conditioning (Ambient) Figure 6 Exova Specimen No.: M Infiltration Air Leakage After Wind Conditioning (Ambient)

11 Page 9 of 19 Figure 7 - Exova Specimen No.: M Exfiltration Air Leakage After Wind Conditioning (Cold) Figure 8 Exova Specimen No.: M Infiltration Air Leakage After Wind Conditioning (Cold)

12 Page 10 of 19 Table 4 Wind Pressure Loading Deflection Results in Accordance with CAN/ULC S742-11, Section Exova Specimen No.: M Cycle Pressure (Pa) Q 10 > 0.20 kpa Gauge Numbers (Locations) & Maximum Deflections (mm) Sustained Loads 650 (P 1) (P 1') Cyclic Loads Gust Loads 0 to 950 (P 2) to -950 (P 2') to 1410 (P 3) to (P 3') Table 5 Deflection Results in Accordance with CAN/ULC S742-11, Section (Increased Pressure to Match ASTM E ) Exova Specimen No.: M Cycle Pressure (Pa) Q 10 > 0.40 kpa / D 0.60 Gauge Numbers (Locations) & Deflections (mm) Wind Loading 0 to to Note: The locations for each gauge number are located on the following page in Figure 9.

13 Page 11 of 19 Wall Section Observations During Structural Wind Loading During the wind loading schedule as shown in Tables 4 and 5, there were no visible signs of Exova Specimen No M tearing, cracking or peeling from the sheathed wall section. Figure 9 Exova Specimen M Gauge Locations

14 Page 12 of DETAILED EXOVA SPECIMEN NO M RESULTS Table 6 - Summarized Air Leakage Results in Accordance with ASTM E Section 9.1, Air Leakage Testing Exova Specimen No.: M (Exfiltration '-') Optional Ambient Cold (-20 C) Differential Pressure (Pa) Calculated Air Leakage Prior to Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning (L/s m 2 ) (L/s m 2 ) (L/s m 2 ) Table 7 - Summarized Air Leakage Results in Accordance with ASTM E Section 9.1, Air Leakage Testing Exova Specimen No.: M (Infiltration '+') Optional Ambient Cold (-20 C) Differential Pressure (Pa) Calculated Air Leakage Prior to Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning Calculated Air Leakage After Wind Pressure Conditioning (L/s m 2 ) (L/s m 2 ) (L/s m 2 ) * As per ASTM E , logarithmic graphs for each air leakage test (infiltration/exfiltration) displaying the linear regression (r 2 ) value are located in Appendix B.

15 Page 13 of 19 Figure 10 Exova Specimen No.: M Exfiltration Air Leakage Prior to Wind Conditioning Figure 11 Exova Specimen No.: M Infiltration Air Leakage Prior to Wind Conditioning

16 Page 14 of 19 Figure 12 Exova Specimen No.: M Exfiltration Air Leakage After Wind Conditioning (Ambient) Figure 13 Exova Specimen No.: M Infiltration Air Leakage After Wind Conditioning (Ambient)

17 Page 15 of 19 Figure 14 - Exova Specimen No.: M Exfiltration Air Leakage After Wind Conditioning (Cold) Figure 15 Exova Specimen No.: M Infiltration Air Leakage After Wind Conditioning (Cold)

18 Page 16 of 19 Table 8 Wind Pressure Loading Deflection Results in Accordance with CAN/ULC S742-11, Section Exova Specimen No.: M Cycle Pressure (Pa) Q 10 > 0.20 kpa Gauge Numbers (Locations) & Maximum Deflections (mm) Sustained Loads 650 (P 1) (P 1') Cyclic Loads Gust Loads 0 to 950 (P 2) to -950 (P 2') to 1410 (P 3) to (P 3') Table 9 Deflection Results in Accordance with CAN/ULC S742-11, Section (Increased Pressure to Match ASTM E ) Exova Specimen No.: M Cycle Pressure (Pa) Q 10 > 0.40 kpa / D 0.60 Gauge Numbers (Locations) & Deflections (mm) Wind Loading 0 to to Note: The locations for each gauge number are located on the following page in Figure 16.

19 Page 17 of 19 Wall Section Observations During Structural Wind Loading During the wind loading schedule as shown in Tables 8 and 9, there were no visible signs of Exova Specimen No M tearing, peeling or cracking away from the sheathed wall section. Figure 16 Exova Specimen M Gauge Locations

20 Page 18 of CONCLUSION The Soprema Sopraseal Stick 1100T self-adhered membrane encompassed in Exova Specimens: M & 2, comply with the air leakage requirements of CAN/ULC S utilizing various wall section configurations and achieved an A1 air leakage rate classification at a 1 in 50 hourly wind pressure difference of 650 Pa, 12 meters above grade. The summarized test results are located in the table below: Table 10 - Summarized Air Leakage Results at 75 Pa in Accordance with CAN/ULC S742-11, Section (a), Referencing ASTM E Section 9.1, Air Leakage Testing Optional Ambient Cold Exova Specimen No.: Airflow Direction Calculated Air Leakage at 75 Pa Prior to Wind Pressure Conditioning (L/s m 2 ) Calculated Air Leakage at 75 Pa After Wind Pressure Conditioning (L/s m 2 ) Calculated Air Leakage at 75 Pa After Wind Pressure Conditioning (L/s m 2 ) Air Leakage Rate Classification (2) M (Opaque Wall) M (Penetrated Wall in Combination with a Foundation Interface) A1 Notes: '-' denotes exfiltration airflow direction (simulated negative wind loading) '+' denotes infiltration airflow direction (simulated positive wind loading)

21 Page 19 of REPORT REVISION SUMMARY Revision No.: Date (yyyy-mm-dd): Description of Revisions: Original Document Original Document This report and service are covered under Exova Canada Inc s. Standard Terms and Conditions of Contract which may be found on our company s website or by calling

22 Appendix A APPENDIX A Logarithmic Air Leakage Graphs Exova Specimen No.: M (Opaque Wall Section) (3 Pages)

23 Appendix A, Page 1 of 3 Figure A1 Exova Specimen M Exfiltration Log/Log Graph Prior to Wind Conditioning Figure A2 Exova Specimen M Infiltration Log/Log Graph Prior to Wind Conditioning

24 Appendix A, Page 2 of 3 Figure A3 Exova Specimen M Exfiltration Log/Log Graph After Wind Conditioning Figure A4 Exova Specimen M Infiltration Log/Log Graph After Wind Conditioning

25 Appendix A, Page 3 of 3 Figure A5 Exova Specimen M Exfiltration Log/Log Graph After Wind Conditioning (-20 C) Figure A6 Exova Specimen M Infiltration Log/Log Graph After Wind Conditioning (-20 C)

26 Appendix B APPENDIX B Logarithmic Air Leakage Graphs Exova Specimen No.: M (Continuity at Penetrations & Foundation Interface Wall Section) (3 Pages)

27 Appendix B Page 1 of 3 Figure B1 Exova Specimen M Exfiltration Log/Log Graph Prior to Wind Conditioning Figure B2 Exova Specimen M Infiltration Log/Log Graph Prior to Wind Conditioning

28 Appendix B Page 2 of 3 Figure B3 Exova Specimen M Exfiltration Log/Log Graph After Wind Conditioning Figure B4 Exova Specimen M Infiltration Log/Log Graph After Wind Conditioning

29 Appendix B Page 3 of 3 Figure B5 Exova Specimen M Exfiltration Log/Log Graph After Wind Conditioning (-20 C) Figure B6 Exova Specimen M Infiltration Log/Log Graph After Wind Conditioning (-20 C)

30 Appendix C APPENDIX C Application Photographs Exova Specimen No.: M (Opaque Wall Section) (3 Pages)

31 Appendix C, Page 1 of 3 Figure C1 Opaque Wall Section Prior to Air Barrier Installation Figure C2 Application of Soprema Sopraseal Stick 1100T over Mammouth Sopraseal Stick Primer 37782

32 Appendix C, Page 2 of 3 Figure C3 Mammouth Sopraseal Stick Primer Figure C4 Application of BASF TM MasterSeal NP1 around the perimeter of Air Barrier Installation

33 Appendix C, Page 3 of 3 Figure C5 Completed Wall Assembly

34 Appendix D APPENDIX D Application Photographs Exova Specimen No.: M (Continuity at Penetrations + Foundation Interface Wall Section) (6 Pages)

35 Appendix D Page 1 of 6 Figure D1 Wall Section Prior to Air Barrier Application Figure D2 Application of Mammouth Sopraseal Stick Primer throughout Densglass Substrate

36 Appendix D Page 2 of 6 Figure D3 Application of Soprema Sopraseal Stick 1100T around Window Rough Opening Figure D4 Application of Soprema Sopraseal Stick 1100T around around Duct and Junction Boxes

37 Appendix D Page 3 of 6 Figure D4 Application of BASF MasterSeal NP1 Sealant around Duct, Brick ties and PVC Pipe

38 Appendix D Page 4 of 6 Figure D5 Application of BASF MasterSeal NP1 Sealant around Brick Ties Figure D6 Application of BASF MasterSeal NP1 Sealant around Electrical Conduit and Junction Box

39 Appendix D Page 5 of 6 Figure D7 Application of BASF MasterSeal NP1 Sealant around Hexagonal Junction Box Figure D8 - Application of BASF MasterSeal NP1 around the perimeter of Air Barrier Installation

40 Appendix D Page 6 of 6 Figure D9 Sealing of Duct, Conduits, Junction Boxes, and Brick-Ties

41 Appendix D Page 7 of 6 Figure D11 Window Installed Figure D12 Completed Wall Assembly

42 Appendix E APPENDIX E Air Barrier Application Notes (2 Pages)

43 Appendix E, Page 1 of 2

44 Appendix E, Page 2 of 2

45 Appendix F APPENDIX F General Wall Construction Detail Drawings (2 Pages)

46 Appendix F, Page 1 of 2

47 Appendix F, Page 2 of 2

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA EVALUATION OF FRAMED WALL CONSTRUCTION SECTIONS UTILIZING LATICRETE INTERNATIONAL S LATICRETE BUILDING ENVELOPE SYSTEM AIR BARRIER SYSTEM IN ACCORDANCE WITH CAN/ULC S742-11 Report to: LATICRETE International

More information

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS Architectural Testing PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E 2357 Rendered to: BAUTEX SYSTEMS SERIES/MODEL: AMB 20-WN PRODUCT TYPE: Air Barrier System Report

More information

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144 ASTM E1886 and ASTM E1996 TEST REPORT Report No.: E6587.01 201 44 Rendered to: 3M COMPANY St. Paul, Minnesota 55144 PRODUCT TYPE: Safety and Security Window Film SERIES/MODEL: 3M Safety and Security Film

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO:

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO: AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA/WDMA/CSA 101/I.S.2/A440-08 STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO: ALL SEASONS DOOR & WINDOW, INC. 28 EDGE ROAD EAST BRUNSWICK, NJ 08816 MODEL/ A-200

More information

CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window

CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window Report No.: Test Dates: 07/30/07 Through: 08/03/07 Report Date: 08/20/07 Expiration Date:

More information

Laboratory Report H

Laboratory Report H Air Permeance Testing of in accordance with ASTM E2178 Prepared for: 6797 Thoreau Lane Baltimore, OH 43105 Date of Issuance: January 16, 2013 Page 2 of 5 CLIENT INFORMATION: TRINITY ERD PROJECT: 6797 Thoreau

More information

TESTING APPLICATION STANDARD (TAS)

TESTING APPLICATION STANDARD (TAS) TESTING APPLICATION STANDARD (TAS) No. 00(A)-9 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE AND/OR INCREASED WINDSPEED RESISTANCE OF SOFFIT VENTILATION STRIP AND CONTINUOUS OR INTERMITTENT VENTILATION

More information

Test Report. Test Report Smart Systems Limited Incorporating Smart Extrusions. Page 1 of 78

Test Report. Test Report Smart Systems Limited Incorporating Smart Extrusions. Page 1 of 78 Test Report 8365614. Smart Systems Limited Incorporating Smart Extrusions Page 1 of 78 Introduction. This report has been prepared by Adam Pearce and relates to the activity detailed below: Job/Registration

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4124.02-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Sun Tunnel Skylight SERIES/MODEL: TCC 022 SPECIFICATION(S): Occupational Safety and Health

More information

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7 Page 2 of 22 CONTENTS 1. INTRODUCTION...3 2. DESCRIPTION OF TEST SAMPLE...4 3. TEST RIG GENERAL ARRANGEMENT...6 4. TEST SEQUENCE...7 5. SUMMARY AND CLASSIFICATION OF TEST RESULTS...8 6. WATERTIGHTNESS

More information

Technical Report. Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for The Window Glass Company Limited

Technical Report. Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for The Window Glass Company Limited Technical Report Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for Limited Report No: N950-3-670 Report number N950-3-670 CONTENTS INTRODUCTION...4 2 SUMMARY

More information

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any

More information

Bomb Blast Mitigation Test

Bomb Blast Mitigation Test 7 June 2005 Bomb Blast Mitigation Test In this time and day of increased natural disasters and terrorist activities, windows have not been put to the test more. With the cries for safety film getting louder

More information

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Series Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Series Smoke Seals in Accordance with BS 476: Part 31, Section 31. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of

More information

APPENDIX B TESTING PROTOCOLS. Method A: Straight Test Method B: Angular Deflection Test. Method C: Shear Load Test

APPENDIX B TESTING PROTOCOLS. Method A: Straight Test Method B: Angular Deflection Test. Method C: Shear Load Test APPENDIX B TESTING PROTOCOLS Method A: Straight Test Method B: Angular Deflection Test Method C: Shear Load Test B.1 METHOD A. STRAIGHT PIPE JOINT TEST In order to simulate the straight pipe-joint condition

More information

NSAI Agrément Approval Scheme for. Certified Air Tightness Tester Scheme Master Document

NSAI Agrément Approval Scheme for. Certified Air Tightness Tester Scheme Master Document NSAI Agrément Document Title Air Tightness Tester Page Page 1 of 10 Scheme NSAI Agrément Approval Scheme for Certified Master Document to I.S. EN ISO 9972:2015 - Thermal Performance of Buildings - Determination

More information

NIOSH Task Number 18388

NIOSH Task Number 18388 National Personal Protective Technology Laboratory Technology Evaluation Branch Certified Product Investigation Program Report of Self-Contained Breathing Apparatus Second Stage Regulators Submitted by

More information

Technical Report. Product testing of 6 mm Graniti Fiandre Maximum panels with support system and fabrication by Telling Architectural

Technical Report. Product testing of 6 mm Graniti Fiandre Maximum panels with support system and fabrication by Telling Architectural Technical Report Title: Product testing of 6 mm panels with support system and fabrication by Telling Architectural Report No: N950-14-16799 CONTENTS 1 INTRODUCTION...4 2 CLASSIFICATION OF TEST RESULTS...5

More information

AIRTIGHTNESS OF BUILDING PENETRATIONS: AIR SEALING SOLUTIONS, DURABILITY EFFECTS AND MEASUREMENT UNCERTAINTY

AIRTIGHTNESS OF BUILDING PENETRATIONS: AIR SEALING SOLUTIONS, DURABILITY EFFECTS AND MEASUREMENT UNCERTAINTY AIRTIGHTNESS OF BUILDING PENETRATIONS: AIR SEALING SOLUTIONS, DURABILITY EFFECTS AND MEASUREMENT UNCERTAINTY Wolf Bracke *1, Nathan Van Den Bossche 1, Arnold Janssens 1 1 Ghent University Jozef Plateaustraat

More information

QUANEX BUILDING PRODUCTS TEST REPORT

QUANEX BUILDING PRODUCTS TEST REPORT QUANEX BUILDING PRODUCTS TEST REPORT SCOPE OF WORK DUAL PANE INSULATING GLASS UNIT PERFORMANCE & GAS EVALUATION REPORT NUMBER H1690.01-119-28 R0 TEST DATE(S) 05/24/17-09/28/17 ISSUE DATE 10/18/17 RECORD

More information

Smart Water Application Technologies (SWAT) TM

Smart Water Application Technologies (SWAT) TM Smart Water Application Technologies (SWAT) TM Equipment Functionality Test Protocol Version 2.3 June 2014 SWAT Committee 8280 Willow Oaks Corporate Drive Suite 400 Fairfax, VA 22031 www.irrigation.org

More information

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Yunlong (Jason) Liu, PhD, PE HNTB Corporation Sean Cassady, FPE HNTB Corporation Abstract Extraction

More information

CERTIFICATE OF APPROVAL No ME 5088

CERTIFICATE OF APPROVAL No ME 5088 CERTIFICATE OF APPROVAL No ME 5088 1 Unit C, Alexander Bell Centre, Hopkinson Way, West Portway Business Park, Andover, Hampshire, SP10 3UR Tel: 01264 333305 Have been assessed against the requirements

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1003 - REVISED: 2009 Water Pressure Reducing Valves for Domestic Water Distribution Systems MANUFACTURER: CONTACT

More information

SUMMARY STEPS TO CERTIFY ACOUSTIC DUCT SILENCER PERFORMANCE UNDER AMCA INTERNATIONAL S CERTIFIED RATINGS PROGRAM

SUMMARY STEPS TO CERTIFY ACOUSTIC DUCT SILENCER PERFORMANCE UNDER AMCA INTERNATIONAL S CERTIFIED RATINGS PROGRAM AMCA International Member Logo cannot be used in catalogs containing performance data. AMCA International Corporate Identity Logo can only be used by AMCA International, Inc. SUMMARY STEPS TO CERTIFY ACOUSTIC

More information

Specific Accreditation Criteria Calibration ISO IEC Annex. Mass and related quantities

Specific Accreditation Criteria Calibration ISO IEC Annex. Mass and related quantities Specific Accreditation Criteria Calibration ISO IEC 17025 Annex Mass and related quantities January 2018 Copyright National Association of Testing Authorities, Australia 2014 This publication is protected

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1048 - REVISED: 2009 Double Check Detector Fire Protection Backflow Prevention Assemblies Separate, complete laboratory

More information

Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers

Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers Presented to the IAPMO Standards Review Committee on October 15, 2018 General: The changes

More information

REPORT HOLDER: FRAMECAD LICENSING LTD. POST OFFICE BOX 1292 AUCKLAND 1140 NEW ZEALAND EVALUATION SUBJECT: COLD FORMED STEEL C SHAPES AND TRACKS

REPORT HOLDER: FRAMECAD LICENSING LTD. POST OFFICE BOX 1292 AUCKLAND 1140 NEW ZEALAND EVALUATION SUBJECT: COLD FORMED STEEL C SHAPES AND TRACKS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2361 Reissued 05/2017 This report is subject to renewal 05/2019. DIVISION: 05 00

More information

SUMMARY STEPS TO CERTIFY AIRFLOW MEASUREMENT PERFORMANCE UNDER AMCA INTERNATIONAL S CERTIFIED RATINGS PROGRAM

SUMMARY STEPS TO CERTIFY AIRFLOW MEASUREMENT PERFORMANCE UNDER AMCA INTERNATIONAL S CERTIFIED RATINGS PROGRAM AMCA International Member Logo cannot be used in catalogs containing performance data. AMCA International Corporate Identity Logo can only be used by AMCA International, Inc. SUMMARY STEPS TO CERTIFY AIRFLOW

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: NORTH EAST WINDOWS, USA, INC. SERIES/MODEL: DH990 Double Hung Report Number: Original Report Date: Revised

More information

Installation / Operation / Maintenance Manual KLINGER Reflex Level Gauge Type R 25

Installation / Operation / Maintenance Manual KLINGER Reflex Level Gauge Type R 25 Klinger Italy S.r.l Via De Gasperi, 88 20017 Rho, Mi - Italy Tel. +39 02 93333.1 Fax +39 02 93901312/3 www.klinger.it Telephone: +61 (08) 9350 1100 Facsimile: +61 (08) 9358 6200 ABN 95 008 679 838 Installation

More information

SUPPORTING NOTES FOR THE EVALUATION OF UNBOUND ROAD BASE AND SUB-BASE AGGREGATES

SUPPORTING NOTES FOR THE EVALUATION OF UNBOUND ROAD BASE AND SUB-BASE AGGREGATES SUPPORTING NOTES FOR THE EVALUATION OF UNBOUND ROAD BASE AND SUB-BASE AGGREGATES (These notes are guidelines only and must not be included in the Contract Documents). 1. SCOPE These Notes are guidelines

More information

Intertek Testing Services Building Products. Enterdoor AB ubv

Intertek Testing Services Building Products. Enterdoor AB ubv TEST REPORT EN 14351-1:2006 + A1:2010 Windows and doors Product standard, performance characteristics- Part 1: Windows and external pedestrian doorsets without resistance to fire and/or smoke leakage characteristics

More information

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE TEST REPORT Report Number 0602 Report Date 21 / 02 / 2006 Client Specimen description ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR 190 18 MAGOULA ATTIKIS Curtain Wall Specimen With three

More information

CTG Certification Protocol -- Version 3.0 SUMMARY

CTG Certification Protocol -- Version 3.0 SUMMARY Date of Test: Test Report Number: SUMMARY Date of Prior Certification: Certified by: Re-certification Due Date: Unit Description: Make : Model: Serial Number: Location: CERTIFIER INFORMATION Name: Client

More information

Team Insert Valve Sample Specification The Insert Valve shall conform to the following:

Team Insert Valve Sample Specification The Insert Valve shall conform to the following: Team Insert Valve Sample Specification The Insert Valve shall conform to the following: The Ductile Iron 250 p.s.i.g. Insert Valve shall be a Resilient Wedge Gate Valve designed for use in potable water,

More information

Evidence of Performance. Class 4. Class 5A. Class C5 / B5. Test Report No PR01. ift Rosenheim

Evidence of Performance. Class 4. Class 5A. Class C5 / B5. Test Report No PR01. ift Rosenheim Evidence of Performance Test Report No 16-002359-PR01 (PB-A01-02-en-01) Client Product Designation Performance-relevant product details Overall dimensions (W x H) Special features - / - SUNCE Marinkovic

More information

IECEx Certificate of Conformity Annexe

IECEx Certificate of Conformity Annexe for Certificate No.: IECEx TSA 09.004X Issue No.: 1 Equipment description pertaining to Issue 0 of this Certificate: A range of electrical power distribution, control, protection and monitoring equipment

More information

ASSE International Product (Seal) Listing Program. ASSE Performance Requirements for Air Valve and Vent Inflow Preventer

ASSE International Product (Seal) Listing Program. ASSE Performance Requirements for Air Valve and Vent Inflow Preventer ASSE International Product (Seal) Listing Program ASSE 1063-2016 Performance Requirements for Air Valve and Vent Inflow Preventer Manufacturer: Contact Person: E-mail: Address: Laboratory: Laboratory File

More information

Standard Recommended Practice. Field Measurement of Surface Profile of Abrasive Blast-Cleaned Steel Surfaces Using a Replica Tape

Standard Recommended Practice. Field Measurement of Surface Profile of Abrasive Blast-Cleaned Steel Surfaces Using a Replica Tape NACE Standard RP0287-2002 Item No. 21035 Standard Recommended Practice Field Measurement of Surface Profile of Abrasive Blast-Cleaned Steel Surfaces Using a Replica Tape This NACE International standard

More information

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and Bulletin 68-7-11 Swimming pool, hot tub and spa installations Rules 68-000, 68-056, 68-058, 68-064, 68-068, 68-302 and 68-404 Scope (1) Swimming pools - general (2) Grounding & bonding (a) Bonding for

More information

SECTION PRESSURE TESTING OF PIPING

SECTION PRESSURE TESTING OF PIPING SECTION 15044 PRESSURE TESTING OF PIPING PART 1 - GENERAL 1.01 DESCRIPTION A. Scope of Work: This section specifies the leakage and pressure testing of piping. B. Testing Records: PART 2 - PRODUCTS 2.01

More information

Water Management Residential Podium Construction BSC Experts Session Overview. Overview

Water Management Residential Podium Construction BSC Experts Session Overview. Overview Building Science Experts' Seminar Water Management Residential Podium December 11-12, 2013 Peter Baker, P.Eng. Water Management Residential Podium BSC Experts Session 2013 Overview Building Enclosure Commissioning

More information

6.0 ENGINEERING. Build Anything Better. REPRINTED 2017

6.0 ENGINEERING. Build Anything Better.  REPRINTED 2017 6.0 ENGINEERING TABLE OF CONTENTS 6.1 U.S. ENGINEERING ANALYSIS REPORT... P. 6-3 BELOW-GRADE WALL REINFORCEMENT TABLES... P. 6-5 ABOVE-GRADE WALL REINFORCEMENT TABLES.. P. 6-21 LINTEL REINFORCEMENT TABLES...P.

More information

Discussion and guidance on the definition and qualification of porous loads

Discussion and guidance on the definition and qualification of porous loads SUMMARY Porous Loads requiring Sterilisation are often a Critical Control Point for the manufacture of Sterile products. Particularly Aseptically filled products. Regulatory guidance in this area is not

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To nformation Whereas the Parliament of ndia has set out to provide a practical regime of right to information for citizens to secure access to information

More information

WSC Performance Standard and Recommended Installation Procedures for Sanitary Water Well. Pitless Adapters, Pitless Units, And Well Caps

WSC Performance Standard and Recommended Installation Procedures for Sanitary Water Well. Pitless Adapters, Pitless Units, And Well Caps WSC Performance Standard and Recommended Installation Procedures for Sanitary Water Well Pitless Adapters, Pitless Units, And Well Caps History of the WSC PAS Standard he Water Systems Council (WSC) has

More information

Containment Structure Performance as Controlled by Penetrations and Extensions

Containment Structure Performance as Controlled by Penetrations and Extensions Containment Structure Performance as Controlled by Penetrations and Extensions Julia Milman 1) and Tarek S. Aziz 1) 1) CANDU Services Civil Engineering, Atomic Energy of Canada Limited, Mississauga, ON,

More information

Airfix D-E-B Installation and operating instructions

Airfix D-E-B Installation and operating instructions www.flamco.nt-rt.ru Airfix D-E-B Installation and operating instructions Dear Customer, With the Airfix D-E-B membrane expansion vessel you have acquired a Flamco quality product. This expansion vessel

More information

TEST FOR STABILOMETER VALUE OF BITUMINOUS MIXTURES

TEST FOR STABILOMETER VALUE OF BITUMINOUS MIXTURES Test Procedure for TEST FOR STABILOMETER VALUE OF BITUMINOUS MIXTURES TxDOT Designation: Tex-208-F Effective Date: February 2005 1. SCOPE 1.1 Use this test method to determine the Hveem stability value

More information

Gilson Aqua-Check Moisture Tester MA-26X

Gilson Aqua-Check Moisture Tester MA-26X OPERATING MANUAL Gilson Aqua-Check Moisture Tester MA-26X Rev: 01/2019 PHONE: 800-444-1508 P.O. Box 200, Lewis Center, Ohio 43035-0200 740-548-7298 E-mail: customerservice@gilsonco.com Product Web Page:

More information

Triaxial automated systems

Triaxial automated systems Triaxial automated systems Pressure ranges: 0-1MPa (0-10 bar) 0-2MPa (0-20 bar) 0-3MPa (0-30 bar) 0-4MPa (0-40 bar) 0-5MPa (0-50 bar) Volume capacity: 230cc Interface: Touchscreen / USB connection (other

More information

Section GATE VALVES

Section GATE VALVES Section 02521 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of gate valves for isolation and dead-end service as shown on Plans and as specified herein. 1.02 MEASUREMENT

More information

Freeze-Thaw Effects and Gas Permeability of Utility Line Backfill

Freeze-Thaw Effects and Gas Permeability of Utility Line Backfill 1 Fred P. Hooper, 1 W. Allen Marr, 2 Ryan B. Drefus, 3 and Khalid Farrag 4 Freeze-Thaw Effects and Gas Permeability of Utility Line Backfill ABSTRACT: Backfill materials used in utility trenches must maintain

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

SEMATECH Provisional Test Method for Pressure Cycle Testing Filter Cartridges Used in UPW Distribution Systems

SEMATECH Provisional Test Method for Pressure Cycle Testing Filter Cartridges Used in UPW Distribution Systems Provisional Test Method for Pressure Cycle Testing Filter Cartridges Used in UPW Distribution Systems Technology Transfer 92010941B-STD and the logo are registered service marks of, Inc. 1996, Inc. Provisional

More information

Presented to the IAPMO Standards Review Committee on March 7, 2016

Presented to the IAPMO Standards Review Committee on March 7, 2016 Summary of Substantive Changes between the 2015 edition of ASSE 1070/ASME A112.1070/CSA B125.70, Water Temperature Limiting Devices, the 2004 edition of ASSE 1070, Water Temperature Limiting Devices, and

More information

STANDARD METHOD OF IMPACT TEST AND PERFORMANCE REQUIREMENTS FOR FOOTBALL FACEGUARDS. NOCSAE DOC ND087-17m17c

STANDARD METHOD OF IMPACT TEST AND PERFORMANCE REQUIREMENTS FOR FOOTBALL FACEGUARDS. NOCSAE DOC ND087-17m17c STANDARD METHOD OF IMPACT TEST AND PERFORMANCE REQUIREMENTS FOR FOOTBALL FACEGUARDS NOCSAE DOC ND087-17m17c Prepared by NATIONAL OPERATING COMMITTEE ON STANDARDS FOR ATHLETIC EQUIPMENT Revised: January

More information

TEST REPORT. Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass.

TEST REPORT. Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass. TEST REPORT Solamatrix Inc. GLASS-GARD GGL1200 Multi-ply Window Film and Wetglaze Anchoring System on Single 6mm (1/4 ) Annealed Glass. Class 3B US General Services Administration Explosion Resistant Standard

More information

AFRL-RH-WP-TR

AFRL-RH-WP-TR AFRL-RH-WP-TR-2016-0040 C-130J BREATHING RESISTANCE STUDY George W. Miller Air Force Research Laboratory Wright-Patterson Air Force Base, OH 45433 May 2016 Final Report STINFO COPY AIR FORCE RESEARCH LABORATORY

More information

Vehicle-mounted meters, pump supplied

Vehicle-mounted meters, pump supplied Purpose This inspection procedure outline (IPO) defines the minimum tests which must be performed to ensure that basic volumetric measuring devices comply with the legislation. Application Vehicle-mounted

More information

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010

REPORT NUMBER: G COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 TEST REPORT REPORT NUMBER: G100017878COQ-004 rev 1 ORIGINAL ISSUE DATE: May 18, 2010 REVISION DATE: June 7, 2010 EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C.

More information

Product Test Report F.A. Lennon Drive December 2015 Solon, Ohio U.S.A. Page 1 of 7. Valve Series Description Test Pressure Test Qty.

Product Test Report F.A. Lennon Drive December 2015 Solon, Ohio U.S.A. Page 1 of 7. Valve Series Description Test Pressure Test Qty. Product Report Solon, Ohio 44139 U.S.A. Page 1 of 7 TITLE Fugitive and Seat Leakage Performance Type of Swagelok VB05 Block and Bleed Process Interface Valves Witnessed by a Third Party PRODUCT TESTED

More information

European Technical Standard Order (ETSO)

European Technical Standard Order (ETSO) Date: 28/11/2008 European Aviation Safety Agency European Technical Standard Order (ETSO) Subject: CREWMEMBER OXYGEN MASK 1 - Applicability This ETSO gives the requirements which the crewmember constant

More information

Vehicle- or rack-mounted liquefied gas meters, pump supplied

Vehicle- or rack-mounted liquefied gas meters, pump supplied Purpose This inspection procedure outline (IPO) defines the minimum tests which must be performed to ensure that basic volumetric measuring devices comply with the legislation. Application Rack/fixed metering

More information

PEAK ALUMINUM FENCING AQUATINE Review for compliance with 2015 International Swimming Pool and Spa Code

PEAK ALUMINUM FENCING AQUATINE Review for compliance with 2015 International Swimming Pool and Spa Code PEAK ALUMINUM FENCING AQUATINE Review for compliance with 2015 International Swimming Pool and Spa Code Peak Products USA Corporation December 21, 2015 RJC No. VAN.106169.0012 Prepared for: Peak Products

More information

PERFORMANCE SPECIFICATION SHEET MICROPHONE ASSEMBLY, M-169A/AIC

PERFORMANCE SPECIFICATION SHEET MICROPHONE ASSEMBLY, M-169A/AIC PERFORMANCE SPECIFICATION SHEET INCH-POUND MIL-PRF-26542/12C 12 September 2012 SUPERSEDING MIL-PRF-26542/12B 11 February 1999 MICROPHONE ASSEMBLY, M-169A/AIC This specification sheet is approved for use

More information

EVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HVAC DUCTS AND CASINGS.

EVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HVAC DUCTS AND CASINGS. ICC-ES Report PMG-1171 Reissued 11/2018 This report is subject to renewal 11/2019 EVALUATION SUBJECT: UNDERGROUND SINGLE WALL & DOUBLE WALL INSULATED DUCT FOR HVAC DIRECT BURIAL APPLICATIONS AND UNDERGROUND

More information

Performance Evaluation of Proprietary Drainage Components and Sheathing Membranes when Subjected to Climate Loads

Performance Evaluation of Proprietary Drainage Components and Sheathing Membranes when Subjected to Climate Loads CONSTRUCTION Performance Evaluation of Proprietary Drainage Components and Sheathing Membranes when Subjected to Climate Loads Task 4 Characterization of Air flow Within Drainage Cavities and Drainage

More information

Product Specification Spring Finger

Product Specification Spring Finger Product Specification 108-115008-3 Spring Finger Restricted to Sony Ericsson Mobile Communications 1. SCOPE 1.1. Content This specification covers the requirements for product performance test methods

More information

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC 157-20067 1 PURPOSE 1.1 The purpose of this standard is to establish an acceptable standard

More information

CHAPTER 3 RESULTS AND DISCUSSION

CHAPTER 3 RESULTS AND DISCUSSION CHAPTER 3 RESULTS AND DISCUSSION The research included the development and verification of the earlier apparatus, and the collection and validation of moisture diffusion data under both isothermal and

More information

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE March 22, 2013 RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE Regulators: Symptom: Pressure Drop Cause: External leaks detected at pigtail hose MPT fitting connection(s) to regulator body

More information

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE TEST REPORT Report Number 0601 Report Date 10 / 02 / 2006 Client Specimen description ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR 190 18 MAGOULA ATTIKIS Curtain Wall Specimen With four

More information

A F LCON PANEL PRODUCTS LTD

A F LCON PANEL PRODUCTS LTD FA LCON PANEL PRODUCTS LTD If the doorset design is required to provide for a smoke control function to comply with Building Regulations, in the absence of a suitable pressurisation system, the doorset

More information

Heat Engine. Reading: Appropriate sections for first, second law of thermodynamics, and PV diagrams.

Heat Engine. Reading: Appropriate sections for first, second law of thermodynamics, and PV diagrams. Heat Engine Equipment: Capstone, 2 large glass beakers (one for ice water, the other for boiling water), temperature sensor, pressure sensor, rotary motion sensor, meter stick, calipers, set of weights,

More information

VACUUM TESTING PRECAST CONCRETE MANHOLES

VACUUM TESTING PRECAST CONCRETE MANHOLES 1 OF 5 testing is a quick, safe and practical way to validate manhole system integrity. Manhole sections can be tested at the precast concrete plant prior to delivery or on site prior to backfilling. Here

More information

PTB Ex PT Scheme. Procedure Instruction of program Explosion Pressure - Test Round 2017

PTB Ex PT Scheme. Procedure Instruction of program Explosion Pressure - Test Round 2017 Procedure Instruction of program Explosion Pressure - Test Round 2017 Content 1 General Performance... 2 2 Measurand / Characteristic of interest... 2 3 Test Item and Configurations... 2 3.1 Components...

More information

SECTION BUTTERFLY VALVES

SECTION BUTTERFLY VALVES SECTION 15112 BUTTERFLY VALVES PART 1 GENERAL 1.01 SUMMARY A. All butterfly valves shall be of the tight closing, rubber seated type and fully comply with the latest revision of AWWA Standard C504, Class

More information

TEST REPORT TS EN : TS EN A1 Windows and doors - Product standard. Testing Reference. : BM 72 Gizli Kanat Pencere (Hidden Vent Window)

TEST REPORT TS EN : TS EN A1 Windows and doors - Product standard. Testing Reference. : BM 72 Gizli Kanat Pencere (Hidden Vent Window) TEST REPORT TS EN 12153 Testing Reference : TS EN 14351-1 +A1 Windows and doors - Product standard Product / Project : BM 72 Gizli Kanat Pencere (Hidden Vent Window) Prepared by : Nilay BULUT Accreditation

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR WATER HEATER SUPPLY SHUTOFF VALVE WITH A / THERMAL EXPANSION CONTROL VALVE IGC 128-2006a8 1. PURPOSE 1.1 The purpose

More information

Testing Procedures of Watertight Compartments

Testing Procedures of Watertight Compartments (1996) (Rev.1 Feb 2001) (Rev.2 May 2001) (Rev.3 May 2010) (Rev.4 Aug 2012) Testing Procedures of Watertight Compartments.1 Application Revision 4 of this UR is to be complied with in respect of the testing

More information

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Tel: +44 (0) Fax: +44 (0)

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Tel: +44 (0) Fax: +44 (0) 56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM Email: testing@inspec-international.com Website: www.inspec-international.com Tel: +44 (0)16 1737 0699 Fax: +44 (0)16 1736 0101 Test

More information

A REVIEW OF THE 2000 REVISIONS TO ANSI 2530/API MPMS 14.3/AGA REPORT NO. 3 - PART2 Paul J. LaNasa CPL & Associates

A REVIEW OF THE 2000 REVISIONS TO ANSI 2530/API MPMS 14.3/AGA REPORT NO. 3 - PART2 Paul J. LaNasa CPL & Associates A REVIEW OF THE 2000 REVISIONS TO ANSI 2530/API MPMS 143/AGA REPORT NO 3 - PART2 Paul J LaNasa CPL & Associates PO Box 801304, Houston, TX 77280-1304 ABSTRACT Periodically, natural gas measurement standards

More information

Evaluation of n-situ easurement ethods for ir ermeability of indows

Evaluation of n-situ easurement ethods for ir ermeability of indows Evaluation of n-situ easurement ethods for ir ermeability of indows Christoph Geyer, Andreas Müller, Barbara Wehle, Martin Greiner, Pascal Urech Research and Development; Architecture, Wood and Civil Engineering

More information

Shut-Off Valves and Valve Boxes

Shut-Off Valves and Valve Boxes Installation and Maintenance Manual V1.2 Shut-Off Valves and Valve Boxes Alert-1 w w w. a m i c o. c o m Table of Contents Introduction 3 Medical Facility Responsibility 3 Precautions 3 Installation of

More information

SEI Certification Program Manual

SEI Certification Program Manual Schedule of Initial s- Footwear Label Content (Structural) Label Content (Proximity) 5.1 & 5.2; Specific content and height. English. 5.1 & 5.3; Specific content and height. English. Checklist $35 1 copy

More information

1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General...

1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General... American Petroleum Institute Contents Page 1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General... 7 Apparatus and Materials... 8 High-temperature/high-pressure

More information

WATER INFILTRATION THROUGH OPENINGS IN A VERTICAL PLANE UNDER STATIC AND DYNAMIC PRESSURE CONDITIONS

WATER INFILTRATION THROUGH OPENINGS IN A VERTICAL PLANE UNDER STATIC AND DYNAMIC PRESSURE CONDITIONS WATER INFILTRATION THROUGH OPENINGS IN A VERTICAL PLANE UNDER STATIC AND DYNAMIC PRESSURE CONDITIONS Michael A. Lacasse 1, Nathan Van Den Bossche 2 and Travis Moore 3 ABSTRACT Moisture is the cause of

More information

JAR-23 Normal, Utility, Aerobatic, and Commuter Category Aeroplanes \ Issued 11 March 1994 \ Section 1- Requirements \ Subpart C - Structure \ General

JAR-23 Normal, Utility, Aerobatic, and Commuter Category Aeroplanes \ Issued 11 March 1994 \ Section 1- Requirements \ Subpart C - Structure \ General JAR 23.301 Loads \ JAR 23.301 Loads (a) Strength requirements are specified in terms of limit loads (the maximum loads to be expected in service) and ultimate loads (limit loads multiplied by prescribed

More information

Health and Safety at Work (Hazardous Substances Reduced Secondary Containment for Certain Above Ground Stationary Tanks) Safe Work Instrument 2017

Health and Safety at Work (Hazardous Substances Reduced Secondary Containment for Certain Above Ground Stationary Tanks) Safe Work Instrument 2017 Health and Safety at Work (Hazardous Substances Reduced Secondary Containment for Certain Above Ground Stationary Tanks) Safe Work Instrument 2017 This safe work instrument is approved under section 227

More information

SUBPART C - STRUCTURE

SUBPART C - STRUCTURE SUBPART C - STRUCTURE GENERAL CS 23.301 Loads (a) Strength requirements are specified in terms of limit loads (the maximum loads to be expected in service) and ultimate loads (limit loads multiplied by

More information

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6 Sub Section INDEX Page Number 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6 6. INSTALLATION AND OPERATION 6 7. MAINTENANCE 8 8. REPAIR 9 9. ASSEMBLY 10 10.

More information

Air Leakage Detailing & Awareness Services

Air Leakage Detailing & Awareness Services Tel: 08456 808048 Mob: 07866 948200 www.aldas.co.uk Info@aldas.co.uk Report on the Repeat Air Permeability Testing of the Passivhaus Refurbishment of: 57 Portfield Street, Hereford 16 th July 2010 Address:

More information

SPECIFICATION FOR REPEATED LOAD TRIAXIAL (RLT) TESTING FOR PAVEMENT MATERIALS

SPECIFICATION FOR REPEATED LOAD TRIAXIAL (RLT) TESTING FOR PAVEMENT MATERIALS SPECIFICATION FOR REPEATED LOAD TRIAXIAL (RLT) TESTING FOR PAVEMENT MATERIALS 1. SCOPE This specification details the six (6) stage permanent strain Repeated Load Triaxial (RLT) test for unbound and modified

More information

Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices

Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices Status as of 2014-01 Principles of testing Insulating hose assemblies on cable cutting devices

More information

Coda cx1 Thermal Cycle Test Procedure

Coda cx1 Thermal Cycle Test Procedure Coda cx1 Thermal Cycle Test Procedure CDL 1-TP07-0200:0209 MIT Ref. 85-01050.04 Revision 2.0 8 th June 2004 CDL 1-TP07-0200:0209 Contents 1 Introduction... 1 1.1 Activity Description... 1 2 Requirements...

More information

World Area Differences Technical Information

World Area Differences Technical Information World Area Differences Technical Information DMISC2047X02 This document is to give more information about the following: Porting & Threads Cleaning Procedures Conversion Tables PORTING & THREADS NPT (National

More information

SOLAR ENERGY. solutions. adhesives, sealants, and Potting encapsulants For solar energy applications

SOLAR ENERGY. solutions. adhesives, sealants, and Potting encapsulants For solar energy applications SOLAR ENERGY solutions adhesives, sealants, and Potting encapsulants For solar energy applications Micro-inverters charge controllers J-Box Potting Batteries Bonding / sealing EPIC RESINS quality SolutIoNS

More information