1 CORRIGENDUM #1 for Date: Owner : GNGPL Sl. No. Description Volume Page No. Clause / Para / Section Amendment / Addition / Modification / Deletion 1 Last date and time for submission of bid I of II Modification Date and time for submission of bid for subject tender stands modified to: "Upto 1500 hrs. (IST) on " Due Date & Time stated in cut-out slip shall stand modified to the above extent. 2 Date and time of opening of Un-priced Bids at MECON Limited, Delhi I of II Modification Date and time of opening of Un-priced Bids for subject tender stands modified to: "At 1600 hrs. (IST) on " 3 LIST OF VENDORS FOR BOUGHT-OUT ITEMS II of II 126, 127 of 500 VII)A,VII)B,VII)C Modification Vendor list for SS tube, SS tube fittings & SS valves & manifolds is modified to :- 1) M/s Parker (USA)/ M/s Swagelok (USA)/ M/s Hoke/ M/s SSP SS fittings 2) M/s Sandvik, Sweden, M/s Tubacex SS tubes 3) M/s Parker, M/s Swagelok SS valves 4 Reply to Bidder's Queries-I Clarifications Reply to bidder's queries are enclosed herewith as Annexure-I. Note: Any addendum/corrigendum/clarifications shall be integral part of the Bidding Documents and shall be submitted by bidders duly signed & stamped in their bid. Dr. P. K. Sharma DGM (Contracts) MECON, Delhi Page 1 of 1

2 1 Bid Due date Page 4 of 21. Extension of bid due date You are rwquested to please extend the bid due date for one week atleast. Refer Corr. #1. 2 Section IV Page 15 of 500 Size of Skid It is not possible to accommodate the twin stream decomression skid in 3mtr Bidder to submit skid GAD for review / x 2mtr, kinldy confirm approval & shall be dealt during detail engg. 3 Technical Specification of CNG Decompression Skid Page No.16 Online Solar Panel is required for EVC & meter Please confirm local control panel is required for heater & 1 no. of online solar panel is required for EVC & meter. Also provide technical specification of Solar panel. 4 Sli Salient Points Page No. 18 Heater shall hllbe automatically started if temperature Automatic Switch hon & OFF of electric heater will depend don outlet drops below 15 deg C & shall be temperature of the skid or as per the heater vessel temperature. As per our automatically closed if it exceeds beyond 35 deg C understanding the given condition of heater ON/OFF is indicating the temperature of heater vessel.kindly Confirm the philosophy. 5 Salient Points Page No. 18 Outlet temperatures at each stage are to be displayed in the locally mounted control panel. As per our understanding separate controller is required to display the temperature at each stage. Local Control Panel is required for heater. Solar panels as per sizing calculation shall be provided for the instruments available in the skid. Datasheet of solar panel to be submitted by bidder for review / approval. Solar panel system shall be suitable for hazardous area. Min. outlet gas temperature of the skid shall be 15 Deg.C. However Heater shall be automatically started if temperature of gas drops below 15 deg C & shall be automatically stopped if it exceeds beyond 35 deg C. Bidder's understanding is correct. Rest 6 Salient Points Page No. 18 Gas filtration system with 100 % of maximum flow capacity shall be used to remove dust particles less than 25 micron and to remove condensate if any Confirm if Y Strainer can be use in place of filter as it is more cost effective. 7 Piping Material Specification Page No. 42 MOC Of filter & Heater Vessel Please confirm the MOC of filter/strainer or Heater Vessel as it is not given in technical specification 8 Technical Specification of PCV & SSV Page No. 60 Confirguration OF PCV & SSV Please confirm the configuration of regulators at primary & secondary stages, separate SSV is required at both stages or Inbuilt SSV with Active Monitor is acceptable. However Gas filtration system with 100 % of maximum flow capacity shall be used to remove dust particles more than 5 micron and to remove condensate if any. Successful bidder to submit datasheet for review/approval during detail engineering. However filter internal element shall be of SS. PCV & SSV shall be separate at both the stages as indicated in P&ID. PCV with integral SSV is not acceptable. 9 Datasheet of PCV & SSV Page NO.100 Rating of PCV & SSV 2500# PCV & SSV is required at first stage reduction as per datsheet of PCV & SSV but as per general practice 1500# PCV & SSV is sufficient for Ist stage, and it meets technical requirement & well accepted by other CGDs also. 10 Annexure V List Of Vendors Page No. 125 Approved make of RPD Meter Please accept Metreg, Germany as approved make for RPD meter Page 1 of 9

3 11 Annexure V List Of Vendors Page No. 205 Approved make of SS Ball Valve Please accept Hy lok/ssp as approved make for High Pressure SS ball valve (Tube end). Hylok make SS ball valve are not acceptable. SS fittings, SS tubes & SS valves shall be procured from bl below mentioned vendors only : 1) M/s Parker (USA)/ M/s Swagelok (USA)/ M/s Hoke/ M/s SSP SS fittings 2) M/s Sandvik, Sweden, M/s Tubacex SS tubes 3) M/s Parker, M/s Swagelok SS valves Rest, condition Prevails. 12 Annexure V List Of Vendors Page No. 205 Approved make of Ball Valve Please accept Flowchem & Hina as approved make for ball valve. 13 Annexure V List Of Vendors Page No. 205 Approved make of Safety Valve Please accept Leser as approved make for Safety Valve. 14 Volume II of II Page No. 4 Erection, Commissioning, performance testing, on site training to O&M personnal includiong hook up with existing pipelines and all other related works for Please confirm if only supervision is required at site for commissiong, performance testing & hook up with existing pipelines of 450SCMH CNG Decompression Skid in bidders scope commissioning & performance testing of 450SCMH CNG Decompression Skid Technical specifications for PCV & SSV Technical specifications for PCV & SSV 61/500 61/500 The self actuating Pressure regulating valve shall be designed as per EN334 and Pressure Equipment Directive PED 97/23/EC covering the production quality assurance The Slam shut valve shall be designed as per EN14382 and Pressure Equipment Directive PED 97/23/EC covering the production quality assurance. We understand that EN standard is not applicable for 1st stage PCV & SSV as these are valves operating with Pressure upto 250 Barg & EN standard deals with valves operating with pressure upto 100 Barg. Kindly confirm our understanding id correct. Bidder's understanding is correct. Rest TG datasheet 99/500 Process ocessconn:2500# Falnged TG datasheet 99/500 Process Conn: 300# & 150# Flanged Skid inlet connection upto 1t stage regulator is made of high pressure tubing & fittings. Thus flanged thermowell cant be installed. Please confirm acceptance of thermowell of ¾" NPT connection. Line size in 300 & 150# section of skids is only 1" & 2". Thus 1½" flanged thermowell is not suitable. Please confirm acceptance of thermowell of ¾" NPT connection. Will be dealt during detail engg. Will be dealt during detail engg. Page 2 of 9

4 19 EVC comes with inbuilt pressure & temp sensor. Thus external P&ID 112/500 Pressuretransmitter & RTD are shownfor EVC pressuretransmitter & temp elemnt are not required. Kindly confirm same. Confirmed, if EVC is with inbuilt pressure & temperature sensor. Rest, Condition Prevails. 20 P&ID 112/500 Filter is shown at inlet of skid We understand that Filter shown at inlet of skid is high pressure miniature filter. Thus, technical Specification: MEC/TS/05/62/017, Rev 1 is not applicable for such filter. Confirmed. Rest, Condition Prevails. 21 Approved vendor list for Ball valve 130/500 FLOWCHEM/PETRO make ball valves are approved by GAIL, EIL & all CGDs. Kindly accept same for this tender. 22 Approved vendor list for DPG 126/500 Hirlekar DPG are approved in all major CGD like GSPC,GSPL,IGL,Gail etc. Kindly accept the same in this tender 23 Testing & inspection: 6.2 a) 65/ % radiography shall be carried out on all casting Inspection & Testing for Ball Valves a 278/500 We understand that, for 150# Radiography is NIL. For 300# Radiography is required above 16". Kindly confirm our understanding is correct. Refer Technical Specification. Rest, Condition Prevails. Inspection & Testing for Check Valves c 309/ Power supply VOLUME II OF II Kindly confirm availability of 3 phase power supply at site. Page 3 of 9

5 27 Inspection & testing VOLUME II OF II We understand that EN 3.1 Type inspection is applicable for CNG skid. Kindly confirm our understanding is correct. 28 Volume I of II. 3.0 Completion Schedule: Page No. 5 of Completion Schedule: Delivery on FOT (site basis) is to be made within 10(ten) weeks and erection to be completed within 12 (twelve) weeks, from the date of written intimation/ Release order. Kindly accept delivery 16 weeks FOT Site and erection to be completed within 18 (twelve) weeks, from the date of written intimation/ Release order. 29 Volume I of II. 3.0 Completion Schedule: Page No. 26 of Evaluation and Comparison of Bid: We understand that evaluation of the Bid does not include the AMC Evaluation shall be done on overall basis (i.e. for charges to arrive at L1. Please clarify. complete scope of work) and order shall be placed at lowest cost to GNGPL. Evaluation shall include charges for incedental services which includes Maintenance. Refer Clause no of ITB. 30 Volume II of II. Design, detail engineering, manufacturing, assembly, For CNG skidhook up with existing line any site Man power will be Complete manpower required to comply the MATERIAL REQUISITION Item 1a Page No. 4 of 500 provided by purchaser for any site fabrication. Any site civil works is excluded form bidder scope. Please confirm. calibration of instruments, factory testing / inspection, supply of skid mounted 450 SCMH CNG Decompression Skid including packaging, insurance, handling, transportation, loading / unloading at GNGPL Stores / sites, Erection including transportation of CNG Decompression Skid from GNGPL s store to designated site, Hookup with existing pipeline and all related services for Commissioning including commissioning and performance testing as per MR specifications and Special Instructions of GNGPL. scope of work is in bidder's scope. Except civil foundation for skid, all civil works required to comply the scope of work is in bidder's scope. Rest, 31 Volume II of II. Assistance in Maintenance of skid at site on call llbasis we understand dpurchaser will illinformed dfive working day prior for the MATERIAL REQUISITION Item 1c Page No. 4 of 500 within 2 years ARC. The price shall be inclusive of Airfare Boarding, Lodging, Local Transport, Incidental, Traveling etc. & all other expenses. planned visits by purchaser. Also during visit any spares/tools/man power/hydra/crain needed for the maintenance the same shall be in purchaser socpe. Please confirm. Page 4 of 9

6 32 Volume II of II. Page No. 14 of 500 Electrical heating system Electrical /Water Bath/Catalytic Heater (Heat Tracing Option)/ Electrical Water Bath heating/ With Gas FiredHeating System Inter connecting Piping of Regulators and equipments. We understand electrical Gas heater is acceptable. For the same the required power supply of 440 VAC will be make available at skid mounted Heater control panel by Purchaser. Please confirm. Refer Material Requisition (MR). Rest, 33 Volume II of II. Page No. 16 of 500 On line solar panel, Batteries, modem, Inbuilt or field mounted EVC with RPD meter shall be supplied. The system shall be designed in such a way that it should operate through battery. The batteries & charger are to be provided in separate explosion proof junction boxes (along with breather plug) and they are to be mounted on trolley to be fixed at site at an approx. distance of 5 meters. All interconnection cables areinbidder s scope. We understand that interconnecting cables & JB with stand for such connectivity will be supplied loose with the skid. However JB installation at site form 5 meter away form skid & cable laying and JB stand foundation at site will be in purchaser scope. Please confirm. Interconnecting cables & JB with stand is in bidder's scope. Also, all cable laying, installation of JB, JB stand foundation, etc. is in bidder's scope. Rest, condition prevails. 34 Volume II of II. Page No. 16 of 500 Approval of skid design from approving agencies mentioned elsewhere. We understand we need to take skid design approval from Purchaser only during project execution. Any government body approval for the skid installation / startup at site is in purchaser scope.kinldy confirm. 35 Volume II of II. Page No. 18 of Salient Points: 1. Outlet ttemperature of the skid shall hllbe 15 Deg.C. As per P&ID Outlet is mentioned as 15 to 35 Deg.C. We understand skid outlet Temp is required as 15 Deg.C. & We need to size heater accordingly. Please confirm. Min. outlet t gas temperature t of the skid shall be 15 Deg.C. However Heater shall be automatically started if temperature of gas drops below 15 deg C & shall be automatically stopped if it exceeds beyond 35 deg C. Rest, Page 5 of 9

7 36 Volume II of II. Page No. 18 of Inlet Size ¾ SS Tube with plain ends 5. Outlet size 2 NB 150# WNRF. We understand the sizes & Class mentioned in the P&ID & subject clause are fixed & bidder to follow the same. Please confirm. Refer P&ID. Rest, 37 Section X P&ID Pg.No.112 of 500 As per P&ID 2nd stage pressure reduction Regulator & SSV are mentioned seperately. Kindly accept Regulator with Integral Slamshut Model. PCV & SSV shall be separate at both the stages as indicated in P&ID. PCV with integral SSV is not acceptable. 38 Volume II of II. 7. Power supply (230V+ 10%, 1 phase, 50 Hz + 5% ) up to JB is in CLIENT s scope. Bidder has to include suitable voltage conditioning unit, if required. 39 Page No 18 of 500 PCV & SSD PCV Data sheet is same for both 1st stage & 2nd stage regulator. If bidder provide electrical Heater 440 VAC will be available for skid Mounted heater control panel. Please confirm. I think, client is asking to supply SMPS (230VAC to DC convertor as per system requirement). Kindly accept NPT End connection in 1st stage PCV & SSV, For 2nd stage PCV/SSVwith Flanges End Connection. Will be dealt during detail engg. 40 Volume II of II. Page No. 18 of All customer interface connections, gas Inlet & outlet piping connections shall be brought out to approximately 3.0m from the skid edge. Hookup with the customer interface connections, gas inlet and out let piping connections are included in bidder s scope. We understand bidder to provide extra spool(instead of spool we need to mention pipe) / tube length of 3 Mtrs.. Straight length. At skid Inlet & Skid Outlet for the customer interface. Please confirm. Piping shall be done as per site requirement. Rest, 41 Volume II of II. SECTION XII LIST OF VENDORS FOR BOUGHT OUT ITEMS Page No. 125 of 500 PRESSURE REGULATOR AND SLAM SHUT VALVE for First stage Kindly accept Vanaz for first stage regulators & SSV. Page 6 of 9

8 42 Volume II of II. SECTION XII LIST OF VENDORS FOR BOUGHT OUT OUT ITEMS Page No. 130 of 500 Ball valve Kindly accept Petro Valves. 43 Check Valve As per datasheet 5 % RT required and as per spec 600# and above 100% RT required Kindly conform datasheet or tender spec to be followed for RT requirement Refer Technical Specification. Rest, 44 Ball Valve & Globe valve As per datasheet RT not required but as per tender Kindly conform datasheet or tender spec to be followed for RT Refer Technical Specification. Rest, spec 600# and above 100% RT required requirement 45 Ball valve, Globe valve and Check valve As per tender QAP the assembled valve mentioned witness in sampling plan As per tender QAP sampling plane mentioned witness the quantum of check shall be 10% kindly conform Sampling shall be 100%. Rest, 46 Ball valve, Globe valve and As per tender QAP the Contractor and TPI to be As per 3.1 certification either contractor are TPI shall witness kindly Final inspection of all the items shall be done Check valve witnessed conform by TPI as per QAP. Rest, condition prevails. Page 7 of 9

9 47 PSV & CRV As per tender QAP the RT is mentioned but as per tender spec 600# and above 100% RT required Kindly conform for 100% RT requirement we need to follow as per tender spec or tender QAP. Refer Technical Specification. Rest, 48 PCV & SSD As per tender QAP RT not required as per spec RT required 100% 600# and above. Kindly conform for RT requirement. Refer Technical Specification. Rest, 49 Final Dossier To save tree the final dossier shall be two Hardcopy Kindly accept Accepted. Rest, and three soft copy 50 Pg.no.75 of 213 Clause 20. Gautantee operating characteristics of any materials, arises at any time prior to twelve(12) months from the date of the first commercial operation of the Plant for which the materials supplied under the Contract form a part thereof, or twenty four (24) months from the date of last shipment whichever period shall first expire. Kindly Confirm (12) months from the date of the first commercial operation of the Plant for which the materials supplied under the Contract form a part thereof, or twenty four (18) months from the date of last shipment whichever is earlier. Refer clause no. 31 of SCC. conditions prevail. 51 Pg.no.75 of 213 Clause 20. Gautantee Repaired or replaced materials shall be similarly guaranteed by the SELLER for a period of no less than twelve (12) months from the date of replacement/repair. Kindly accept,point no 2.The warranty for the repaired or replaced part will be warrantied for a period of 3 months from the time of repair or replacement to a max of original warranty period. conditions prevail. 52 Pg.no.168 of 213 Clause 31 The CONTRACTOR/ SUPPLIER shall guarantee the Gaurantee Clause in the section is not closed, Please confirm the conditions prevail. DEFECT LIABILITY PERIOD installation/work for a period of 12months from the date of completion of WORK as certified by the ENGINEER IN CHARGE which is indicated in the Gaurantee will stand similar as Clause 20. pg. no. 75 of 213. Page 8 of 9

10 53 Pg.no.81 of 213 Clause 30.4 Arbitration All disputes, controversies, or claims between the parties (except in matters where the decision of the Engineer in Charge is deemed to be final and binding) whichcannotcannot be mutually resolved within a reasonable time shall be referred to Arbitration by a sole arbitrator. Kindly accept, Arbitration panel shall consist of 3 arbitrators each party shall appoint 1 arbitrator and those 2 shall appoint an umpire, if required. conditions prevail. 54 Pg.no.83/84 of 213 Clause 38 Fall Clause The price charged for the materials supplied under the order by the supplier shall in no event exceed the lowest price at which the supplier or his agent/principal/dealer, as the case may be, sells the materials of identical description to any persons/organizations including the Purchaser or any department of the Central Govt. or any Deptt. Of a State Govt. or any Statutory Undertaking of the Central or State Govt. as the case may be, during the currency of the order If at any time during the said period, the supplier or his agent/principal/dealer, as the case may be, reduces the sale price, sells or offers to sell such materials to any Kindly accept "The price charged for the materials supplied under the order by the supplier shall in no event exceed the lowest price at which the supplier sells the materials of identical description,identical scope of work, quantity, currency rate and other terms and conditions, to any person / organizations including the Purchaser or any department of the Central Govt. or any Department of a State Govt. or any Statutory undertaking of the Central or State Govt., as the case may be, in India, during the currency of the Order. persons/organizations including the Purchaser or any Deptt. Of The above stipulation will, however, not apply to : Central Govt. or State Govt. as the case may be, at a price lower than the price chargeable under the order, he shall forthwith notify such reduction or sale or offer of sale to the Purchase Authority who has issued this order and the price payable under the order for the materials supplied after the date of coming into force of such reduction or sale or offer of sale shall stand correspondingly reduced. The above stipulation will, however, not apply to: a) Exports by the Contractor/Supplier or b) Sale of goods as original equipment at prices lower than the prices charged for normal replacement. c) sale of goods such as drugs which have expiry dates. a) Exports by the Contractor/Supplier or b) Sale of goods as original equipment at prices lower than the prices charged for normal replacement conditions prevail. Note: Any addendum/corrigendum/clarifications shall be integral part of the Bidding Documents and shall be submitted by bidders duly signed & stamped in their bid. Page 9 of 9

MAHARASHTRA NATURAL GAS LIMITED

MAHARASHTRA NATURAL GAS LIMITED Replies to Queries of the Bidders Date: 01.12.2018 SUB: Replies to queries of the bidders for Tender for annual rate contract for procurement of SRM for CGD Network of MNGL, Pune REF: Bid Document No.

More information

PRE BID QUERIES FOR CNG & CITY GAS DISTRIBUTION FOR HYDERABAD. Clause No. Description in tender documents Clarifications / Request for change

PRE BID QUERIES FOR CNG & CITY GAS DISTRIBUTION FOR HYDERABAD. Clause No. Description in tender documents Clarifications / Request for change Tender : Bid Document : BGL/100/2010-11 PRE BID QUERIES FOR CNG & CITY GAS DISTRIBUTION FOR HYDERABAD Sl. Clause Description in tender documents Clarifications / 1. ARTICLE 19 :Price If the contractor

More information

Kind Attention: Shri. R.R.Kumar, Addl. General Manager (M.M), PDIL PRE-BID QUERIES. Sl.No Bidder s Query Reference Client / Consultant Reply 1

Kind Attention: Shri. R.R.Kumar, Addl. General Manager (M.M), PDIL PRE-BID QUERIES. Sl.No Bidder s Query Reference Client / Consultant Reply 1 CLIENT M/s GREEN GAS LIMITED, Lucknow CONSULTANT M/s PROJECTS & DEVELOPMENT INDIA LIMITED, Noida TENDER CITY GAS DISTRIBUTION PROJECT AT LUCKNOW GA for GREEN GAS LIMITED TENDER NO. PNMM/EM089/E/111/NCB

More information

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - ISOLATION BALL VALVE

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - ISOLATION BALL VALVE PTS - ISOLATION BALL VALVE 2 30.06.17 Issued for Corrigendum#1 AS ADE GS 1 12.04.17 Issued for Tender AS AD GS 0 06.03.17 Issued for Client s Comments AS AD GS Rev. Date Subject of revision Author Checked

More information

BHAGYANAGAR GAS LIMITED (A JOINT VENTURE OF HPCL & GAIL)

BHAGYANAGAR GAS LIMITED (A JOINT VENTURE OF HPCL & GAIL) (A JOINT VENTURE OF HPCL & GAIL) BID DOCUMENT FOR PROCUREMENT OF METERS AND REGULATORS FOR SUPPLY OF PNG IN HYDERABAD UNDER DOMESTIC COMPETITIVE BIDDING Bid Document No.: BGL/093/2010-11 -II of II BHAGYANAGAR

More information

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar EN - english Instructions for installation and operation Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar Dear customer, Thank you for deciding in favour of the METPOINT

More information

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - APPLIANCE BALL VALVE

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - APPLIANCE BALL VALVE PTS - APPLIANCE BALL VALVE 2 30.06.17 Issued for Tender AS ADE GS 1 12.04.17 Issued for Tender AS AD GS 0 06.03.17 Issued for Client s Comments AS AD GS Rev. Date Subject of revision Author Checked Approved

More information

CSIR-NATIONAL GEOPHYSICAL RESEARCH INSTITUTE (COUNCIL OF SCIENTIFIC & INDUSTRIAL RESEARCH) Uppal Road, Hyderabad (Telangana.

CSIR-NATIONAL GEOPHYSICAL RESEARCH INSTITUTE (COUNCIL OF SCIENTIFIC & INDUSTRIAL RESEARCH) Uppal Road, Hyderabad (Telangana. CSIR-NATIONAL GEOPHYSICAL RESEARCH INSTITUTE (COUNCIL OF SCIENTIFIC & INDUSTRIAL RESEARCH) Uppal Road, Hyderabad - 500 007 (Telangana.) India FAX: +91-40-27012486, 27012533, e-mail: purchase@ngri.res.in

More information

BHEL/Trichy-14 CCDP SYSTEM DESCRIPTION FOR DOME VALVE:

BHEL/Trichy-14 CCDP SYSTEM DESCRIPTION FOR DOME VALVE: BHEL/Trichy-14 CCDP SYSTEM DESCRIPTION FOR DOME VALVE: The Dome Valve is a pressure tight, power operated Valve for application in Material Inlet / Vessel Discharge / Line Change over etc. The Valves should

More information

Ratnagiri Gas & Power Pvt. Ltd. C&M Department. Ref.: RGPPL/C&M/CS-2335/Pre-Bid queries Date: 24/09/2016. Clarifications to bidder

Ratnagiri Gas & Power Pvt. Ltd. C&M Department. Ref.: RGPPL/C&M/CS-2335/Pre-Bid queries Date: 24/09/2016. Clarifications to bidder Ratnagiri Gas & Power Pvt. Ltd. C&M Department Ref.: RGPPL/C&M/CS-2335/Pre-Bid queries Date: 24/09/2016 Clarifications to bidder Sr. No. 1 Clause No. of tender document Pg.12 (section- B) Prequalification

More information

AAVANTIKA GAS LIMITED

AAVANTIKA GAS LIMITED AAVANTIKA GAS LIMITED (A JOINT VENTURE COMPANY OF GAIL & HPCL) CITY GAS DISTRIBUTION PROJECT IN INDORE BID DOCUMENT FOR PROCUREMENT OF ODOURISING UNIT VOL. II OF II TECHNICAL BID DOCUMENT NO.: AGL/ 090

More information

AIRMASTER SERIES RF AUTOMATIC DEWATERING VALVES. For the purging of water from compressed air systems WHERE DO YOU NEED AUTOMATIC DEWATERING VALVES

AIRMASTER SERIES RF AUTOMATIC DEWATERING VALVES. For the purging of water from compressed air systems WHERE DO YOU NEED AUTOMATIC DEWATERING VALVES R SERIES RF AUTMATIC DEWATERING VALVES For the purging of water from compressed air systems The series RF is a high capacity automatic dump valve specifically designed to continuously purge water from

More information

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators Line Pressure Regulators @ - c - e G) t,5 ii:i! 1rlr1t APPLICATION NOTES 1rlr1t A. The Governor regulator is ANSI Z21.80a and ANSI Z21.18 certified for vent limited installations (indoor installations

More information

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators Line Pressure Regulators @ - c - e G) t,5 ii:i! 1rlr1t APPLICATION NOTES 1rlr1t A. The Governor regulator is ANSI Z21.80a and ANSI Z21.18 certified for vent limited installations (indoor installations

More information

Fiji Electricity Authority Transmission Unit 2 Marlow Street, Suva

Fiji Electricity Authority Transmission Unit 2 Marlow Street, Suva TENDER DOCUMENT AND SPECIFICATION MR 333/2017 Preferred Supplier for Double Tail Shock Absorbing Elasticated Webbing Lanyard The Fiji Electricity Authority (FEA) invites bids from reputable suppliers for

More information

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service GUIDELINES Pressure Systems Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service Document Reference: PSG 16 Issue 04 Dated 13/09/16 The Safety Assessment Federation

More information

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information Liquid Level EK-L CSM_EK-L_DS_E 3 Liquid Level That Is Unaffected by the Color of the or Liquid Mount to bypass pipes. Fit a wide range of pipe diameters: 8 to mm or to mm Built-in Amplifiers to save space.

More information

STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL)

STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL) STANDARD SPECIFICATION FOR SPLIT TEES (HOT TAP MATERIAL) TEE (HOT TAPPING MATERIAL) S-04-02-040 Page 1 of 7 1.0 SCOPE This specification covers the basic requirements for the design, manufacture and supply

More information

ADDENDUM NO. 1 Tender for Procurement of Catalyst Testing Pilot Plant for Corporate R & D Centre, Greater Noida

ADDENDUM NO. 1 Tender for Procurement of Catalyst Testing Pilot Plant for Corporate R & D Centre, Greater Noida ADDENDUM NO. 1 Tender for Procurement of Catalyst Testing Pilot Plant for Corporate R & D Centre, Greater Noida CRFQ Number 1000298594 E-Tender System ID: 34790 1.0 SCOPE OF THIS ADDENDUM 1.1 This Addendum

More information

ARAI/TA(4G)/HORIBA/MEXA 584L/ Dated 19 th Jun 2008 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES

ARAI/TA(4G)/HORIBA/MEXA 584L/ Dated 19 th Jun 2008 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s Horiba India Pvt. Ltd. Room 1521, 15 th Floor, Eros Corporate Tower Nehru Place New Delhi 110 019 Cert Annex Drg Tot al 1 6 0 7 pgs Exhaust

More information

BOXING FEDERATION OF INDIA

BOXING FEDERATION OF INDIA BOXING FEDERATION OF INDIA REQUEST FOR PROPOSAL (RFP) FOR PROCUREMENT SPORTS EQUIPMENTS - 1 HOSTING AIBA WOMEN S WORLD BOXING CHAMPIONSHIP, DELHI, 2018 DATE OF ISSUE: September 18, 2018 LAST DATE & TIME

More information

NIT LIMITED NO. NC-105-P-SCS-NOCB CYLINDERS & REGULATORS

NIT LIMITED NO. NC-105-P-SCS-NOCB CYLINDERS & REGULATORS NIT LIMITED NO. CYLINDERS & REGULATORS NATIONAL INSTITUTE OF SCIENCE EDUCATION & RESEARCH JATNI CAMPUS, P.O.: JATNI, Khurdha-752050 Tender Notice No. NIT Limited NO. Sealed Tenders are invited on behalf

More information

DEPARTMENT OF CHEMICAL ENGINEERING INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI , INDIA

DEPARTMENT OF CHEMICAL ENGINEERING INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI , INDIA DEPARTMENT OF CHEMICAL ENGINEERING INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI 600036, INDIA Ref. No. CHE/17-18/CHE/006/GAIM/RAJN Date: 25 APRIL, 2018 Due date: 9 MAY, 2018 Item: High Pressure Gas Hydrate

More information

TENDER FOR THE SUPPLY OF MEDICAL OXYGEN AND NITROUS OXIDE GASES CYLINDERS FOR ONE YEAR.

TENDER FOR THE SUPPLY OF MEDICAL OXYGEN AND NITROUS OXIDE GASES CYLINDERS FOR ONE YEAR. L E S 1 Government of Karnataka BELGAUM INSTITUTE OF MEDICAL SCIENCES, BELGAUM AUTONOMOUS INSTITUTE (Registered Under Societies Registration Act) Dr. B. R. Ambedkar Road, Belgaum 590 001. Phone No: 0831-2420320,

More information

INSTALLATION & MAINTENANCE INSTRUCTIONS

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The QBX series valve uses Proportion-Air closed loop technology for Pressure control. It gives an output pressure proportional to an electrical command signal input. The QB1X

More information

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery

More information

Distribution Connection Forms

Distribution Connection Forms Distribution Connection Forms Form No. DR01 DR02 DR03 DR04 DR05 DR06 DR07 DR08 DR09 DR10 DR11 GDP101 GDP102 GDP105 GDP106 GDP107 GDP108 GDP111 KG-D01 KG-D02 KG-D03 KG-D04 Description Application For Gas

More information

GEMS SENSORS & CONTROLS

GEMS SENSORS & CONTROLS GEMS SENSORS & CONTROLS OPERATING & INSTALLATION INSTRUCTIONS 31XX / 32XX SERIES PLEASE READ CAREFULLY BEFORE INSTALLING Part Number: 560550-0076 Issue: E INTRODUCTION Series 3100/3200 high output pressure

More information

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14 15 Elster GmbH Edition 7.15 Translation from the German 519 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas VG VG 15/1 Contents Solenoid valve for gas

More information

DK48 - DK800. Quick Start. Variable area flowmeter

DK48 - DK800. Quick Start. Variable area flowmeter Quick Start Variable area flowmeter General safety notes You can find the newest and/or additional information in the handbook, the datasheet, special manuals, certificates and the download center at www.krohne.com.

More information

STATUTORY PRESSURE TESTING AND PAINTING OF LPG CYLINDERS

STATUTORY PRESSURE TESTING AND PAINTING OF LPG CYLINDERS TENDER DOCUMENT - CRFQ NO 1000269899 E-tender no : 18984 FOR STATUTORY PRESSURE TESTING AND PAINTING OF LPG CYLINDERS BANGALORE LPG BOTTLING PLANT NH NO. 48,- 47 KM. STONE BANGALORE MANGALORE HIGHWAY,

More information

TRIPURA NATURAL GAS COMPANY LIMITED (A JOINT VENTURE OF GAIL (INDIA) LTD., GOVT. OF TRIPURA & GOVT. OF ASSAM)

TRIPURA NATURAL GAS COMPANY LIMITED (A JOINT VENTURE OF GAIL (INDIA) LTD., GOVT. OF TRIPURA & GOVT. OF ASSAM) TRIPURA NATURAL GAS COMPANY LIMITED (A JOINT VENTURE OF GAIL (INDIA) LTD., GOVT. OF TRIPURA & GOVT. OF ASSAM) PROJECT FOR CNG & CITY GAS DISTRIBUTION FOR E - BID DOCUMENT FOR PROCUREMENT OF CNG CASCADES

More information

Operating Manual. Model BAC-30RT30/BAC-30DC

Operating Manual. Model BAC-30RT30/BAC-30DC Model BAC-30RT30/BAC-30DC Manual No. BAC012 (Rev 1 October 2002) Operating Manual AIR SYSTEMS INTERNATIONAL, INC. 829 Juniper Crescent, Chesapeake, Va., 23320 Telephone (757) 424-3967 Toll Free 1-800-866-8100

More information

Operating Manual. Models AQT-02 & AQT-COO2 Manual No. MON004 (Rev 2 April 2000)

Operating Manual. Models AQT-02 & AQT-COO2 Manual No. MON004 (Rev 2 April 2000) Models AQT-02 & AQT-COO2 Manual No. MON004 (Rev 2 April 2000) Operating Manual AIR SYSTEMS INTERNATIONAL, INC. 829 Juniper Crescent, Chesapeake, Va., 23320 Telephone (757) 424-3967 Toll Free 1-800-866-8100

More information

GAIL GAS LTD (A wholly owned subsidiary of GAIL (India) Limited)

GAIL GAS LTD (A wholly owned subsidiary of GAIL (India) Limited) GAIL GAS LTD (A wholly owned subsidiary of GAIL (India) Limited) CNG AND CITY GAS DISTRIBUTION PROJECT BID DOCUMENT FOR ODORISING UNIT VOLUME II OF II (TECHNICAL) (BID DOCUMENT NO: 110290/WGI/GAIL GAS/12-R1)

More information

Natural Gas Conditioning Skids & Equipments

Natural Gas Conditioning Skids & Equipments Natural Gas Conditioning Skids & Equipments NATURAL GAS CONDITIONING SKIDS NIRMAL has rich experience of supplying complete package of Natural Gas conditioning skids consisting of emergency shut down,

More information

Gas Distribution Connection Forms

Gas Distribution Connection Forms Gas Distribution Connection Forms Updated on: 1 April 18 Gas Distribution Connection Forms S/No. Form No. Description 1 GDP101 Application for Gas Distribution Connection 2 GDP102 Consumer Project Data

More information

Brooks Flow Controllers for Gas and Liquid Service Model FC 8744, Series FC 8800 and 8900

Brooks Flow Controllers for Gas and Liquid Service Model FC 8744, Series FC 8800 and 8900 Data Sheet Flow Controllers for Gas and Liquid Service Brooks Flow Controllers for Gas and Liquid Service Model FC 8744, Series FC 8800 and 8900 Model FC 8800 Flow Controller Model 1350/55 with FC 8900

More information

PRICED BID -PACKAGE II Page 1 of 19 Vendor Seal and Signature. Set 103. Set 23 pulse transmitter and Non return valve for 1.5" ethanol line.

PRICED BID -PACKAGE II Page 1 of 19 Vendor Seal and Signature. Set 103. Set 23 pulse transmitter and Non return valve for 1.5 ethanol line. 1 2 3 Supply of flowmeters 3" line: Supply of Positive displacement type flowmeters, Strainer with DPG, air eliminator, with pulse transmitter for 3" line Erection of Positive displacement type flowmeters,

More information

CAST IRON SAFETY VALVE TYPE 6301

CAST IRON SAFETY VALVE TYPE 6301 CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a

More information

BOXING FEDERATION OF INDIA

BOXING FEDERATION OF INDIA BOXING FEDERATION OF INDIA REQUEST FOR PROPOSAL (RFP) FOR ENGAGING SERVICE PROVIDERS FOR ACCREDITATION SYSTEM AND/OR TICKETING SYSTEM HOSTING AIBA WOMEN S WORLD BOXING CHAMPIONSHIP, DELHI, 2018 DATE OF

More information

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company Installation and Operating Instructions DANGER: DO NOT MIX CHEMICALS! The Acid-Rite ph Adjustment System is designed for use with Axiall

More information

92831 TEL: (714) FAX:

92831 TEL: (714) FAX: Document No. 1800-75 Respiration Test Chamber Copyright 2010 Terra Universal Inc. All rights reserved. Revised September 2010 Terra Universal, Inc. TerraUniversal.com 800 S. Raymond Ave. Fullerton, CA

More information

GasSense NDIR User Manual

GasSense NDIR User Manual INDEX INDEX... 1 1. OVERVIEW... 2 2. TECHNICAL DATA... 3 3. SPECIFICATIONS... 4 4. PRODUCT DESCRIPTION... 5 4.1 Mechanical details... 5 4.2 Piping... 7 4.3 Connections... 7 5. INSTALLATION... 10 6. CALIBRATION

More information

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions VS18/26 with PROFINET and EtherNet/IP Interface ATEX Installation Instructions INDEX 1. INTENDED USAGE 3 2. OPERATING MANUAL ATEX 4 2.1 General conditions 4 2.2 Installation 5 2.3 Operating 5 2.4 Failures

More information

F.No DM(RH)U-16/19/2/ Med. Gases/2003 Dt

F.No DM(RH)U-16/19/2/ Med. Gases/2003 Dt EMPLOYEES STATE INSURANCE HOSPITAL Rohini, Sector-15, New Delhi 110089 ` Website: www.esic.nic.in Fax: 27553098 F.No DM(RH)U-16/19/2/ Med. Gases/2003 Dt. 04.12.2014 To TENDER FOR THE SUPPLY OF MEDICAL

More information

Workhorse 8 Oxygen System Model No 5665, 5673, 5679

Workhorse 8 Oxygen System Model No 5665, 5673, 5679 11436 Sorrento Valley Road, San Diego CA 92121 USA 858-558-0202 Fax 858-558-1915 Workhorse 8 Oxygen System Model No 5665, 5673, 5679 Part Number 1815 Revision B SeQual Technologies San Diego, CA USA Cautions,

More information

NATIONAL INSTITUTE OF ANIMAL BIOTECHNOLOGY (NIAB)

NATIONAL INSTITUTE OF ANIMAL BIOTECHNOLOGY (NIAB) NATIONAL INSTITUTE OF ANIMAL BIOTECHNOLOGY (NIAB) Aryabhata Block, C.R. Rao Advanced Institute of Mathematics, Statistics and Computer Science (AIMSCS), UoH Campus, Gachibowli, Hyderabad-500 046 TENDER

More information

CENTRE OF BIOMEDICAL RESEARCH

CENTRE OF BIOMEDICAL RESEARCH CENTRE OF BIOMEDICAL RESEARCH (Formerly Centre of Biomedical Magnetic Resonance) An Autonomous Centre of Govt. of U.P. Sanjay Gandhi Postgraduate Institute of Medical Sciences Campus, Raebareli Road, Lucknow

More information

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel:

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel: PERMA PURE INSTRUCTION MANUAL FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model 3300 Version 4.06 Perma Pure LLC Tel: 732-244-0010 P.O. Box 2105, 8 Executive Drive Tel: 800-337-3762 (toll free US)

More information

Pressure Vessel Program

Pressure Vessel Program Pressure Vessel Program 1. PURPOSE 1.1 This program provides guidance to University employees that work with or are responsible for pressure vessels. Conformance to this Program aids the University in

More information

VALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44

VALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44 INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44 Pressure Reducing Valve PRV44 - Operation and Installation - 1 - manual PRV44-16-ENG JULY 2016 INDEX PAGE 1 IDENTIFICATION PLATE

More information

453 Series Steam Heated Vaporizing Regulator

453 Series Steam Heated Vaporizing Regulator ADI 0453A Certified ISO 9001:2000 453 Series Steam Heated Vaporizing Regulator INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions Controls Corporation

More information

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information CS-425-01 Controlled Dissolved Gas assembly with optional CS-603-01 Air Aspirator assembly Installation and Operation information Serial # CS-XXX Date of shipment:, 2005 Shipped to: Purchase order #: xxxxxxx

More information

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1 HANDBOOK Ed. 2017 DS-ED 01/2017 - ENG 1 CHAPTER 9 BURSTING DISC DEVICES IN SERIES 3070 SCOPE Use: protection against possible overpressure of the apparatuses listed below, with regard to the operating

More information

INVITATION OF TENDER FOR DUST EXTRACTION SYSTEM, DUST COLLECTORS & SCRUBBERS AND FILTER CLEANING SYSTEM

INVITATION OF TENDER FOR DUST EXTRACTION SYSTEM, DUST COLLECTORS & SCRUBBERS AND FILTER CLEANING SYSTEM INVITATION OF TENDER II FOR DUST EXTRACTION SYSTEM, DUST COLLECTORS & SCRUBBERS AND Tender Document No.- GIA-009 Tender Document Cost Rs. 1000./- RAJASTHAN DRUGS & PHARMACEUTICALS LIMITED Road no. 12,

More information

LPS Product Guide. LPS Series Nitrogen Generators. N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved

LPS Product Guide. LPS Series Nitrogen Generators. N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved LPS Product Guide N2-GEN LPSTM LPS Series Nitrogen Generators N2-GEN LPS TM - Layup Protection System Copyrighted All Rights Reserved - 2014 p 888 526 6284 e info@southteksystems.com w www.southteksystems.com

More information

Operating Instructions Part No

Operating Instructions Part No DIGITAL AUTOMATIC TYRE INFLATOR Operating Instructions Part No. 11.0578 Thank you for selecting this Jamec Pem Automatic Tyre Inflator. Please read this manual before carrying out any installation or service

More information

NIT LIMITED NO. NC-185-SCS-P-NOCB ARGON & NITROGEN CYLINDER WITH REGULATOR

NIT LIMITED NO. NC-185-SCS-P-NOCB ARGON & NITROGEN CYLINDER WITH REGULATOR NIT LIMITED NO. NC-185-SCS-P-NOCB-15-16 ARGON & NITROGEN CYLINDER WITH REGULATOR NATIONAL INSTITUTE OF SCIENCE EDUCATION & RESEARCH JATNI CAMPUS, P.O.: BHIMPUR-PADANPUR, VIA:-JATNI Khurdha-752050 Tender

More information

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers MASS-STREAM TM Instruction Manual D-6200 Analog Mass Flow Meters / Controllers Doc. No.: 9.17.112A Date: 17-03-2017 ATTENTION Before installing and operating the instrument it is strongly recommended that

More information

EMPLOYEES STATE INSURANCE CORPORATION SUPER SPECIALITY HOSPITAL SANATHNAGAR, HYDERABAD LIMITED TENDER For ANNUAL MAINTENANCE CONTRACT

EMPLOYEES STATE INSURANCE CORPORATION SUPER SPECIALITY HOSPITAL SANATHNAGAR, HYDERABAD LIMITED TENDER For ANNUAL MAINTENANCE CONTRACT EMPLOYEES STATE INSURANCE CORPORATION SUPER SPECIALITY HOSPITAL SANATHNAGAR, HYDERABAD-500038 LIMITED TENDER For ANNUAL MAINTENANCE CONTRACT FOR THE MEDICAL GAS PIPELINE SYSTEM Not Transferable Tender

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

Technical Information Conducal CLY421

Technical Information Conducal CLY421 TI00496C/07/EN/01.12 71142150 Products Solutions Services Technical Information Conducal CLY421 Conductivity calibration set for ultrapure water applications Factory calibrated measurement box Certified

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Butterfly Valves C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Butterfly Valves C O N T E N T S SPECIFICATIONS - DETAILED PROVISIONS Section 15103 - Butterfly Valves C O N T E N T S PART 1 - GENERAL... 1 1.01 REQUIREMENT... 1 1.02 VALVE MANUFACTURER... 1 1.03 GUARANTEE... 1 PART 2 - PRODUCT... 1

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

Petrofac Client Doc. No JI-DTS-5002 Page 2 of 8 Rev. TABLE OF CONTENTS

Petrofac Client Doc. No JI-DTS-5002 Page 2 of 8 Rev. TABLE OF CONTENTS M681IDS0003 Petrofac Client Doc.. 100813361JIDTS500 Page of 8 Rev. ALL TABLE OF CONTENTS DESCRIPTION PAGE 1. COVER PAGE 1. TABLE OF CONTENTS 3. 61FCV8006 3 4. 61FCV800 4 5. 61FCV8008 5 6. 61FCV801 6. GENERAL

More information

Oxygen Concentrator. Installation and Operation Manual. ClearWater Tech, LLC. Integrated Ozone Systems

Oxygen Concentrator. Installation and Operation Manual. ClearWater Tech, LLC. Integrated Ozone Systems Oxygen Concentrator Installation and Operation Manual ClearWater Tech, LLC. Integrated Ozone Systems 850-E Capitolio Way, San Luis Obispo, Ca 93401 805-549-9724 Fax: 805-549-0306 E-mail: service@cwtozone.com

More information

SERVICE PROVIDERS FOR GAMES PROMOTION

SERVICE PROVIDERS FOR GAMES PROMOTION BOXING FEDERATION OF INDIA REQUEST FOR PROPOSAL (RFP) FOR ENGAGING SERVICE PROVIDERS FOR GAMES PROMOTION HOSTING AIBA WOMEN S WORLD BOXING CHAMPIONSHIP, DELHI, 2018 DATE OF ISSUE: October 15, 2018 LAST

More information

BS Series Basket Strainer

BS Series Basket Strainer BS Series Basket Strainer Operating, Installation, & Maintenance Manual Corrosion Resistant Fluid and Air Handling Systems. Dated 04-26-12 PRESSURE DROP SIMTECH strainers are engineered to offer the lowest

More information

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC 05 Elster GmbH Edition 0.5 Translation from the German 058 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Linear flow control VFC Linear flow control with actuator IFC Contents

More information

210 Series Transmitter with External Electrochemical Sensor

210 Series Transmitter with External Electrochemical Sensor 210 Series Transmitter with External Electrochemical Sensor INSTRUCTIONS Installation and Operation of the AMC-210 Series Transmitter with External Electrochemical Sensor IMPORTANT: Please read these installation

More information

Supplementary Operator s Manual 42/24-14 EN Rev. 3

Supplementary Operator s Manual 42/24-14 EN Rev. 3 Advance Optima Continuous Gas Analyzers AO2000 Series with Uras26, Magnos206, Caldos25, Caldos27 Designed per Category 3G for Measurement of Flammable Gases ( Safety Concept ) and Non-flammable Gases Supplementary

More information

BOXING FEDERATION OF INDIA REQUEST FOR PROPOSAL (RFP) FOR ENGAGING SERVICE PROVIDERS FOR UNIFORMS FOR

BOXING FEDERATION OF INDIA REQUEST FOR PROPOSAL (RFP) FOR ENGAGING SERVICE PROVIDERS FOR UNIFORMS FOR BOXING FEDERATION OF INDIA REQUEST FOR PROPOSAL (RFP) FOR ENGAGING SERVICE PROVIDERS FOR UNIFORMS FOR HOSTING AIBA WOMEN S WORLD BOXING CHAMPIONSHIP, NEW DELHI, 2018 DATE OF ISSUE: October 08, 2018 LAST

More information

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC 07 Elster GmbH Edition 06.7 Translation from the German 058 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Linear flow control VFC Linear flow control with actuator IFC

More information

OIL INDIA LIMITED (A Government of India Enterprises) 4, India Exchange Place Kolkata -1 INVITATION TO E-BID UNDER COMPOSITE BID SYSTEM

OIL INDIA LIMITED (A Government of India Enterprises) 4, India Exchange Place Kolkata -1 INVITATION TO E-BID UNDER COMPOSITE BID SYSTEM OIL INDIA LIMITED (A Government of India Enterprises) 4, India Exchange Place Kolkata -1 TELEPHONE NO. (033) 222301657 FAX NO: (033) 22302596 Email: oilcalmn@dataone.in;oilcalmn@oilindia.in TENDER NO.

More information

NIT LIMITED NO. RD-NC-40-SPS-PH

NIT LIMITED NO. RD-NC-40-SPS-PH NIT LIMITED NO. RD-NC-40-SPS-PH1302-14-15 ARGON GAS & CO2 with CYLINDER NATIONAL INSTITUTE OF SCIENCE EDUCATION & RESEARCH INSTITUTE OF PHYSICS CAMPUS, P.O.: SAINIK SCHOOL, BHUBANESWAR-751 005 Tender Notice

More information

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS) South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide

More information

COMMERCIAL CORRIGENDUM#1 TO BIDDING DOCUMENT

COMMERCIAL CORRIGENDUM#1 TO BIDDING DOCUMENT COMMERCIAL CORRIGENDUM#1 Dated: 29.06.2018 TO BIDDING DOCUMENT BIDDING DOCUMENT NO. : MEC/23TS/01/51/D2/T05/SU/0004 SUBJECT OF BIDDING DOCUMENT : SUPPLY OF CNG RECIPROCATING COMPRESSORS (ANNUAL RATE CONTRACT

More information

Specification for Medical Gas Pipeline s

Specification for Medical Gas Pipeline s M.S Specification for Medical Gas Pipeline s Supply, installation and commissioning of medical gas pipelines at pediatric emergency and Outborn NICU S. No. Area Beds Gas outlet Oxygen- O2 Flow meter Ward

More information

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Differential Pressure Regulator Type 45-6 Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Edition March 2008 Contents Contents Page 1 Design and principle of operation...................

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.

More information

Columbus Instruments

Columbus Instruments 0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011

More information

The Univentor 1250 Anaesthesia Unit

The Univentor 1250 Anaesthesia Unit THE UNIVENTOR 1200/1250 ANAESTHESIA UNIT The Univentor 1250 Anaesthesia Unit TABLE OF CONTENTS EDITION 1 Section 1 - WARRANTY & SERVICE 1.1. WARRANTY 2 1.2. DAMAGED SHIPMENTS 2 1.3. SERVICE 2 Section 2

More information

THE UNIVENTOR 400 ANAESTHESIA UNIT

THE UNIVENTOR 400 ANAESTHESIA UNIT THE UNIVENTOR 400 ANAESTHESIA UNIT TABLE OF CONTENTS EDITION 3 Section 1 - WARRANTY & SERVICE 1.1. WARRANTY 2 1.2. DAMAGED SHIPMENTS 2 1.3. SERVICE 2 Section 2 - INTRODUCTION 2.1. INTRODUCTION 3 Section

More information

GAIL (India) Limited

GAIL (India) Limited GAIL (India) Limited (A Govt. of India Undertaking) CHAINSA-JHAJJAR-BAMNOULI PIPELINE PROJECT BID DOCUMENT FOR USM AND METERING SKID CORRIGENDUM 1 (BID DOCUMENT NO.: 11/0230/JPK/GAIL/07-R0) LIMITED INTERNATIONAL

More information

FloWash. Industrial Filter Cart

FloWash. Industrial Filter Cart OPERATION AND MAINTENANCE MANUAL FloWash Industrial Filter Cart Read all instructions before installation or operation of equipment. Failure to comply with these instructions could result in bodily injury

More information

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14 2 Elster GmbH Edition. Translation from the German 22 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas G / G Contents Solenoid valve for gas G / G....

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

Bid Document/Request for Proposal. For

Bid Document/Request for Proposal. For Pakistan Telecommunication Company Limited Tender No. RFQ/NW-Ops LHR/Frame Contract/DG-Filters/2018-2019 Bid Document/Request for Proposal For Frame Contract of Unit Based Rates of Different Types of DG

More information

G type DUCTED EXHAUST SAFETY VALVE 2871 AND 288X SERIES. Model/Ref:

G type DUCTED EXHAUST SAFETY VALVE 2871 AND 288X SERIES. Model/Ref: Model/Ref: 28713 www.lauridsenindustri.com CHARACTERISTICS The G type safety valves are dedicated to protect the equipment from potential overpressure. They are automatic and close when the pressure conditions

More information

Instruction Manual. Pressure Vessels

Instruction Manual. Pressure Vessels Instruction Manual Pressure Vessels acc. to DGRL 97 / 23 / EG Edition December 2006 INSTRUCTION MANUAL FOR PRESSURE VESSELS ACCORDING TO DGRL 97/23/EG Production year: * Pressure vessel production number:

More information

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 0700 67 Registered in England and Wales No. 05058855

More information

MAINTENANCE AND SAFETY OF CNG REFUELLING STATIONS

MAINTENANCE AND SAFETY OF CNG REFUELLING STATIONS ISSN 1172-3416 NZ GCP 2 : 1993 NEW ZEALAND GAS CODE OF PRACTICE for MAINTENANCE AND SAFETY OF CNG REFUELLING STATIONS Issued by the Secretary of Commerce in accordance with the Gas Act 1992 THE GAS ACT

More information

CHE Well Testing Package/Service:

CHE Well Testing Package/Service: CHE Well Testing Package/Service: CHE delivers well testing package And services, trailer mounted well testing package and offshore/onshore well testing services with over 10 years experience. Our testing

More information

TENDER SPECIFICATION No: 12/ of SUPERINTENDING ENGINEER (CTI & ENQUIRIES), Dt

TENDER SPECIFICATION No: 12/ of SUPERINTENDING ENGINEER (CTI & ENQUIRIES), Dt 1 TENDER SPECIFICATION No: 12/2018-19 of SUPERINTENDING ENGINEER (CTI & ENQUIRIES), Dt. 08.01.2019 Specification for Supply of Standard Calibration Gas Mixture in the ranges of 5PPM and 100PPM filled in

More information

Natural Gas Connection Policy and Procedures

Natural Gas Connection Policy and Procedures s Updated on: 1 April 18 Table of Contents 1. General Information... 1 1.1 Purpose of this Document... 1 1.2 Singapore Gas Transportation System... 1 1.3 Definitions... 2 1.4 Codes of Practices and Regulatory

More information

SECTION-IV TECHNICAL SPECIFICATIONS OF METERING SKID FOR SHRIKRUPA FOOD INDUSTRIES, AHMEDABAD.

SECTION-IV TECHNICAL SPECIFICATIONS OF METERING SKID FOR SHRIKRUPA FOOD INDUSTRIES, AHMEDABAD. SECTION-IV TECHNICAL SPECIFICATIONS OF METERING SKID FOR SHRIKRUPA FOOD INDUSTRIES, AHMEDABAD. INDEX SL. DESCRIPTION PAGE NO. NO. 1 Technical Specifications (Common and 3 Instrumentation items) for Metering

More information

D10S/D20S Wall/Post Mount Inflator Quick Start Manual

D10S/D20S Wall/Post Mount Inflator Quick Start Manual PART NUMBER SERIAL NUMBER D10S/D20S Wall/Post Mount Inflator Quick Start Manual Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product

More information

PM105 PRESSURE METER USER S MANUAL

PM105 PRESSURE METER USER S MANUAL PM105 PRESSURE METER USER S MANUAL Manual revision: 15 March, 2001 SCSMANP015 Copyrighted 2001 Thank you for purchasing a Tek Know pressure meter. The Tek Know products are manufactured by Scan-Sense AS

More information

Procedure: Pressure equipment safety

Procedure: Pressure equipment safety Procedure: Pressure equipment safety Purpose The purpose of this procedure is to define the method for safe operation and inspection of pressure equipment and the collection and recording of associated

More information